Parr Instrument 4848B User Manual

4848B
Reactor Controller
Operating Instruction Manual
575M
Table of Contents
Preface
Scope — 4
Applications — 4
Explanation of Symbols — 5
Safety Information — 5
Intended Usage — 5
Cleaning & Maintenance — 5
General Specifi cations — 6
Environmental Conditions — 6
Provisions for Lifting and Carrying — 6
4848B Reactor Controller Specifi cations — 6
User’s Responsibility — 7
Unpack Carefully — 7
Installation
General Instructions — 8
Connections — 8
Component Summary
Switches and Indicators — 9
Protective Fuses and Relays — 10
High Limit Reset— 11 Access to the Controller Cabinet— 11 Fuses— 11
4848B Factory Defaults
Navigating the Menu System/Factory Default Settings — 22
Primary Temperature Module — 22
TDM / MCM Module — 23
Pressure Module — 23
HTM/ETLM Module — 24
MTM Module — 25
Appendix A: Controller Parameters
Initial Setting Mode — 26
Operation Mode — 27
Regulation Mode — 28
Parts List
Fuses — 29
Communication — 29
Cooling Solenoids — 29
Primary Temperature Module — 30
Pressure Display Module (PDM) — 30
Tachometer Module (TDM) — 31
or Motor Control Module (MCM) — 31
Hi-Temp Cut-Off Module (HTM) — 31
or External Temperature Limit Module (ETLM) — 31
Instructions for the 4848B Reactor Controller
Temperature Control Module — 12
Temperature Control— 12 High Temperature Alarm Setpoint— 12 PID groups— 12 Autotuning— 13 Temperature Profi les - Ramp and Soak— 13 Engaging a Program— 14 Adjustments To Speed Control Board— 19
Solenoid Valve Module — 19
Communication with PC — 20
Quick Start Instructions for Connecting with PC— 20 Datalogging and Charting— 21 Converting a Chart File to TXT— 21
Visit our website to fi nd our Controller FAQ
http://www.parrinst.com/support/48484838-controller-support/controller-faq/
www.parrinst.com
1
4848B Reactor Controller

Preface

Related Instructions

The following Parr publications are also included to further your understanding of this instrument and its component parts:
No. Description
201M Limited Warranty
576M 4848B Controller CD

Scope

These instructions cover the installation, opera­tion and maintenance of Parr Model 4848B Reactor Controller as used with Parr laboratory reactors and pressure vessels. They cover the basic functions provided in each of these controllers and describe the several optional control modules which can be added to these expandable units. The users should study the instructions carefully before using any of these controllers so that they will fully understand the capabilities and limitations of this equipment and the safety precautions to be observed in its operation.

Applications

Each 4848B Reactor Controller consists of a pack­aged temperature control unit completely wired and assembled with appropriate power and safety relays, switches and pilot lights.
These units are designed specifi cally for use with Parr reactors and pressure vessels and are to be used only with Parr equipment.
Controllers furnished with Parr reactors equipped with variable speed, DC motors have a motor switch and a speed control knob on the front panel. Con­trollers to be used with AC equipment or an air mo­tor do not have a speed control knob.

Customer Service

Questions concerning the installation or operation of this instrument
can be answered by the Parr Customer Service Department:
1-309-762-7716 • 1-800-872-7720 • Fax: 1-309-762-9453
E-mail: parr@parrinst.com • http://www.parrinst.com
2
Parr Instrument Company

Explanation of Symbols

II On position, full power heater switch
I On position, half power heater switch
O Off Position
~ Alternating Current (AC)
4848B Reactor Controller
This CAUTION symbol may be present on the Product Instrumentation and literature. If present on the product, the user must consult the ap­propriate part of the accompanying product literature for more infor­mation.
Protective Earth (PE) terminal. Provided for connection of the protec­tive earth (green or green/yellow) supply system conductor.

Safety Information

To avoid electrical shock, always:
1. Use a properly grounded electrical outlet of cor­rect voltage and current handling capability.
2. Ensure that the equipment is connected to elec­trical service according to local national electri­cal codes. Failure to properly connect may create a fi re or shock hazard.
3. For continued protection against possible haz­ard, replace fuses with same type and rating of fuse.
4. Disconnect from the power supply before main­tenance or servicing.
To avoid personal injury:
5. Do not use in the presence of fl ammable or com­bustible materials; fi re or explosion may result. This device contains components which may ignite such material.
6. Refer servicing to qualifi ed personnel.

Intended Usage

Cleaning & Maintenance

Periodic cleaning may be performed on the exterior surfaces of the controller with a lightly dampened cloth containing mild soap solution. All power should be disconnected and the power cord should be unplugged when cleaning the 4848B Controller.
There are no user serviceable parts inside the prod­uct other than what is specifi cally called out and discussed in this manual. Advanced troubleshooting instructions beyond the scope of this manual can be obtained by calling Parr Instrument Company in order to determine which part(s) may be replaced or serviced.
Ensure that any hot surfaces have had ad­equate time to cool before cleaning or main­taining the reactor and/or its components.
This controller has been designed for use with Parr pressure vessels and reactors. It has been de­signed, built, and tested to strict physical and electri­cal standards. However, it is the user’s responsibil­ity to install and operate it in conformance with local pressure and electrical codes.
If the instrument is used in a manner not specifi ed by Parr Instrument Company, the protection provid­ed by the equipment may be impaired.
www.parrinst.com
3
4848B Reactor Controller
General Specifi cations
Electrical Ratings
115VAC, 15.0 Amps, 50/60 Hz
230VAC, 15.0 Amps, 50/60 Hz
Before connecting a controller to an electrical outlet, the user must be certain that the electrical outlet has an earth ground connection and that the line, load and other characteristics of the installation do not exceed the following limits:
Voltage: Fluctuations in the line voltage should not exceed 10% of the rated nominal voltage shown on the data plate.
Frequency: Controllers can be operated from either a 50 or 60 Hertz power supply without affecting their operation or calibration.
Current: The total current drawn should not exceed the rating shown on the data plate on the controller by more than 10 percent.
Thermocouple: Unless otherwise specifi ed, all 4848B Controllers operate with a Type-J (Iron-Con­stantan) thermocouple. The total resistance of the thermocouple and the lead wires should not exceed 100 ohms. If the resistance of the thermocouple circuit is higher, it will not function properly.

Environmental Conditions

This instrument is intended to be used indoors.
Operating: 15 ºC to 35 ºC; maximum relative humid­ity of 80% non-condensing. Installation Category II (over voltage) in accordance with IEC 664. Pollution degree 2 in accordance with IEC 664.

Provisions for Lifting and Carrying

Before moving the instrument, disconnect all con­nections from the rear of the apparatus. Lift the instrument by grabbing underneath each corner.
Caution! Do not use in hazardous atmospheres.
4848B Reactor Controller Specifi cations
Input Thermocouple type
Operating Range 0-800 °C Readout and Setpoint
Resolution System Accuracy +/-2 °C Control action three-term PID plus limit
Control output 1 115VAC or 230VAC Control output 2 .2 amp max
Operating voltages 115VAC or 230 VAC
Heater Loop
Proportional Band: 12 C Integral time: 375 sec Derivative: 93 C/sec Cycle time: 20 sec
Cooling Loop
Proportional Band: 5 C Cycle time: 5 sec
Type-J
1 °C
control
115VAC or 230VAC
Altitude Limit: 2,000 meters.
Storage: -25 ºC and 65 ºC; 10% to 85% relative hu-
midity.
4
Parr Instrument Company
4848B Reactor Controller

User’s Responsibility

All Parr Reactors and Pressure Vessels are designed and manufactured with great care to assure safe operation when used within their prescribed tem­perature and pressure limits.
But… the basic responsibility for safety when us­ing this equipment rests entirely with the user; who must:
1. Select a reactor or pressure vessel that has the capability, pressure rating, corrosion resistance, and design features that are suitable for its intended use. Parr engineers will be glad to dis­cuss available equipment and material options with prospective users, but the fi nal responsi­bility for selecting a reactor or pressure vessel that will perform to the user’s satisfaction in any particular reaction or test must rest with the user
- not with Parr.
2. In exercising the responsibility for the selection of pressure equipment, the prospective user is often faced with the choice between over or under-designed equipment. The hazards intro­duced by under-designed pressure vessels are readily apparent, but the penalties that must be paid for over-designed apparatus are often over­looked. Recognizing these criteria, Parr reac­tors and pressure vessels are offered in several different styles, each designed for convenient use in daily operation within certain temperature and pressure limits, using gaskets, closures, and other elements carefully selected for safe opera­tion within the limits specifi ed for that design. But in order to preserve the validity of these de­signs, all temperature and pressure limits must be observed, and no attempt should be made to increase these limits by making alterations or by substituting components which are not recom­mended by Parr Instrument Company.
3. Install and operate the equipment within a
suitable barricade, if required, with appropriate safety accessories and in full compliance with local safety codes and rules.
All standard Parr pressure vessels are provided
with either suitable relief device or a means to attach one (typically in the form of a plugged opening). When a pressure vessel is delivered without a pressure venting device, it is the cus­tomer’s responsibility to provide pressure relief in order to protect the operator and the equip­ment from destructive high pressures. If you need more information or need help in selecting a proper relief device, please contact Parr Instru­ment Company.
4. Establish training procedures to ensure that any
person handling the equipment knows how to use it properly.
5. Maintain the equipment in good condition and
establish procedures for periodic testing to be sure the vessel remains structurally sound.

Unpack Carefully

Unpack the equipment carefully and check all the parts against the packing list. If shipping damage is discovered, report it immediately to the deliver­ing carriers. Examine the components closely for any loose parts or shipping damage and be sure to check all layers of packing materials thoroughly so as not to overlook any parts which might otherwise be discarded.
www.parrinst.com
5
4848B Reactor Controller

Installation

General Instructions

Set the controller on a sturdy bench or table where there is convenient access to an electrical outlet with the appropriate supply voltage and current rat­ings in accordance with national and local electrical code requirements. Leave a space of at least twelve inches between the controller and the heater of the reactor so that the controller will not be affected by radiant heat.

Connections

Labeled connections are provided on the rear panel of the controller.
Parr Cooling Only:
The Temperature Input connection is for the Tem- perature Module or ETLM sensor input.
The Pressure Input connection is for the Pressure Module sensor input.
The RPM Input connection is for the RPM Module sensor input.
The Comm connector is for Communication output.
The Auxiliary 1 and Auxiliary 2 input connections are for additional connections and may be used on a number of devices. The 4848B Reactor Controller can be purchased with Auxiliary 1 and/or 2 confi g­ured as a Temperature Module Input or a Pressure Module Input.
The cooling output connector is to be used only with Parr Instrument Company cooling solenoid valve assemblies supplied with the appropriate cooling power cord.
Parr Heating Only:
The heating output connector is to be used only with Parr Instrument Company heater assemblies supplied with the appropriate heater power cord.
Motor: Secure the clamp on motor cord to the con­troller with the provided screw next to the motor socket for safety purposes.
The motor output connector is to be used only with Parr Instrument Company motor assemblies sup­plied with the appropriate motor power cord. Other appropriate connectors are provided on the rear panel of the controller.
4848B Rear Panel 115V
The Primary Temp Input connection is for the Pri- mary Temperature Module sensor input.
6
Parr Instrument Company
4848B Rear Panel 230V

Component Summary

Switches and Indicators

4848B Reactor Controller
Front Side
4848B Reactor Controller
The Heater Switch is a manual, three-position, illu-
minated switch which controls the amount of power sent to the heater. In the HIGH (II) position, full power is developed by the heater. In the middle (0) position the heater is off. In the LOW (I) position, a diode is switched into the system to allow only one­half of the rated voltage to be supplied to the heater. This low setting will be most useful when operating the reactor at temperatures below 175 °C. Power for the heater is supplied through a solid state relay controlled by the temperature control module. The light in the heater switch will glow only when cur­rent is fl owing to the heater.
The high limit indicator light will glow if the control­ler receives an indication from any of its sensors that a high temperature or high pressure limit has been reached and the High Limit Reset has opened. When the light comes on, the user must fi nd the source of the problem, correct it, and then manually reset the system using the high limit reset button on the front of the controller.
The Motor Controls consist of an on-off switch and a speed control knob. The speed control knob should be turned down to a minimum setting before turning on the motor switch to minimize electri­cal surges within the speed control unit. A speed control know is not included when the reactor is equipped with an air motor for stirring or when the controller is created for use with a non-stirred ves­sel.
If equipped with a motor control module, there will also be a remote/local switch. When the remote/ local switch is in local mode, the speed control knob will adjust the motor stirring speed. When the remote/local switch is in remote mode, the RPM module will adjust the motor stirring speed. If there is no motor control module installed, the remote/lo­cal port will be plugged and the speed control knob is the sole control for the stirring speed.
The Main Power Switch will cut off power to the controller. Take care to position the controller such that the main power switch may be accessed easily
when the controller needs to be disconnected.
www.parrinst.com
7
4848B Reactor Controller
Back Side
4848B Reactor Controller

Protective Fuses and Relays

An instrument fuse is mounted on the back panel. This is a Fast-acting, 250VAC, 1.0 amp fuse, intended to protect the temperature control module and any installed display modules.
The motor reset/motor fuse provides overload protection for 0-90VDC motors. This is a re-settable breaker designed to protect the motor if it becomes overloaded. The breaker will have a rating selected to match the motor on the apparatus.
A lighted fuse holder provides protection for 0-180 VDC motors. A light will come on if the motor be­comes overloaded and the fuse burns out. The fuse rating will be selected to match the motor on the apparatus.
A load fuse is mounted on the back panel on 115V systems. This fast-acting, 250VAC, 20 amp fuse is in­tended to protect the controller and prevent electric shock hazard from fault from occurring.
Two load fuses are mounted on the back panel on 230V systems. These are fast-acting, 20 Amps, 250VAC and are intended to protect the controller and to prevent electric shock hazard from fault from occurring.
Caution! Unplug unit before servicing. For continued protection against possible hazard, replace fuses with same type and rating of fuse.
8
Parr Instrument Company
4848B Reactor Controller
Thermocouple burnout protection is included in each of these controllers. If the thermocouple should burn out, or if there is a break in the thermo­couple circuit, power to the heater will be shut off. In most cases this will cause the controller to show a “NO CONT” reading. A similar high reading will be displayed if the controller is turned on without an attached thermocouple. In either of these situations, the high limit reset will activate. The thermocouple break must then be corrected and the High Limit Re­set must be reset in order to activate the system.

High Limit Reset

Each Series 4848B Controller has a high tempera­ture limit control which will trip the High Limit Relay and shut off the heater if the temperature reaches a preset level. If tripped, the lockout relay will pop out, thereby preventing the system from heating the reaction when the temperature falls back below the limit setting. This must be manually reset before heating can occur again.
On Model 4848B Controllers the high tempera­ture limit is preset at the factory to 375 °C for most systems. On these controllers an alarm condition is indicated by an illuminated red indicator labeled as "ALM". If the temperature exceeds the limit, the controller alarm condition will appear, the High Limit Reset will be tripped, and power to the heater will be shut off.

Access to the Controller Cabinet

To open the controller cabinet, unplug the power cord and remove the two screws in the upper corners of the back panel. Then lift the top plate upwards, allowing the hinged top and front panel to swing forward, providing full access to all internal components.
Caution! Inside of controller cabinet should be ac­cessed by qualifi ed personnel only.

Fuses

The 4848B Controller has a number of fuses which are intended to be fi eld serviceable.
Fuse Rating Part No.
Instrument Fuse
Cooling Fuse Fast acting, .25 Amp,
Line Fuse(s) Fast acting, 20 Amp,
Motor Board Fuse (A+)
Motor Board Fuse (L)
Fast acting, 1 Amp, 250VAC
250VAC
250VAC
Very Fast acting, 8 Amp, 250VAC
Fast acting, 10 Amp, 250VAC
139E6
139E10
2074E
959E5
185E2
Motor fuse/ reset
Check back panel for specifi cations
Caution! Unplug unit before servicing. For continued protection against possible hazard, replace fuses with same type and rating of fuse.
Check part list
www.parrinst.com
9
4848B Reactor Controller

Instructions for the 4848B Reactor Controller

Caution! Check that controller settings are set to factory defaults before operating for the fi rst time. The default settings are listed at the back of this manual.
Note: Controller parameters can be found in Appendix A on page 24 of this manual.

Temperature Control Module

PRIMARY
TEMPERATURE
The 4848B Reactor Controllers are available with a microprocessor based control module that provides full three-term PID control with adjustable tuning parameters. The temperature control interface is labeled as Primary Temperature on front panel.
been reached, the High Limit Reset will trip, cutting power to the heater, and the ALM light will illumi­nate indicating a High Limit was activated.

Temperature Control

The easiest way to control temperature with the 4848B Controller is to use setpoint control. With set­point control, the controller will attempt to bring the temperature to the value of the setpoint by adjust­ing the heater output.
The setpoint may be adjusted by doing the following:
1. Press the up or down arrow until the lower display shows the desired setpoint. The lower display will blink, showing the value has not been set yet.
2. Press the set button. The lower display will stop blinking, showing the new value has been set.

High Temperature Alarm Setpoint

The 4848B Reactor Controller also has a High Tem­perature Alarm built into it. When the temperature exceeds this limit, it will pop the High Limit Reset, preventing power from going to the heater. The High Temperature Alarm setpoint may be adjusted by doing the following:
1. Press the circular arrow key three times. The up­per display will read AL1H and the lower display will read the High Temperature Alarm setpoint (usually 375C).
2. Use the up or down arrow to adjust this to the desired setpoint.
To facilitate start up with reasonably good PID con­trol, parameters for both heating and cooling are pre programmed at the factory.
Output 1 on these controllers drives the heater. Output 2 can be used to activate a cooling system. The control parameters can be set independently for each of these outputs.
Two lines of information, labeled PV and SV, are shown on the display during normal operations. The upper line (PV) shows the actual temperature as read by the control thermocouple. The lower line (SV) shows the set point. When the controller is heating, the Out1 light will illuminate or blink. When the controller is cooling, the Out2 light will illuminate or blink. When an alarm condition has
10
Parr Instrument Company
3. Press the up or down arrow until the lower display shows the desired setpoint. The lower display will blink, showing the value has not been set yet.
4. Press the set button. The lower display will stop blinking, showing the new value has been set.
5. Pressing the set button again will return the dis­play to the main screen.

PID groups

a. The primary temperature controller contains
4 groups of PID parameters (PID0, PID1, PID2 and PID3), which can be used to store up to four different sets of PID parameters. Each group is identifi ed by the SV used during the autotuning cycle.
4848B Reactor Controller
b. The parameter displayed is the group in use
with exception of PID4. When PID4 is set, the PID parameters will automatically switch between PID groups 0, 1, 2 and PID group 3, depending on which group’s SV best matches the current temperature (PV).
c. All of PID parameters in the group can be ob-
tained from auto-tuning or they can be set manually. When manually entering PID values into a particular group, the SV for that group can be manually entered as well.

Autotuning

1. Fill the vessel with an amount of liquid which well represents the intended process.
Caution! Refer to Manual 230M for safety information on the heating of liquids in Parr Reactors and Pressure Vessels.
2. If you wish to autotune at different temperatures using the four available PID groups proceed with step 3, otherwise skip to step 4.
3. Press the set key once followed by the return key (circular arrow) twice. [
PID0
] will be displayed on the screen in the top display. Use the up and down arrow keys to change between PID groups 0, 1, 2 and 3. Press the set key to solidify the change. Press the set key again to return to the main screen.
4. Heat the system to the desired temperature us­ing set point control on the primary temperature controller. Let the temperature come to steady state which will typically occur 15 to 30 minutes after reaching the desired set point depending on the size of the reactor.
5. On the main screen of the controller, press the set key. The screen will show [AT] on the top display and [
OFF
] on the bottom display. Press the up arrow to change the lower display to [ON]. The display will blink, press set to solidify the change. Press set again to return to the main screen.
6. As the Autotune starts, the LED indicator under AT will blink, and Out 1 will fully engage at­tempting to heat the reactor 100% power. This will continue for a while, and the controller will go through a few cycles where it turns the
power on at 100% and turns it off to see how the temperature responds.
7. A typical Autotune time is half an hour for liquid water systems, but it may take longer depending on the process. When the process is complete, the AT light will stop fl ashing, and the tempera­ture will settle on the set point.
Temperature Profi les - Ramp and Soak
The 4848 Controller has a programming feature which allows more fl exibility when compared to set point control. Rather than controlling temperature to a single set point, a ramp and soak program may be entered to control various soak times, ramp rates and set points. Within the programming mode there are eight patterns available with each pattern hav­ing up to eight steps which can be programmed. Patterns can be set to repeat and they can be linked to other patterns (or the same pattern which allows for infi nite program cycles). This allows for up to 64 unique steps and thousands of possible program confi gurations.
To input a ramp and soak:
1. First set the controller’s Run/Stop [ rameter to Stop [
STOP
]. This will prevent the
R-S
] pa-
program from automatically starting after the program has been entered. You can do this by pressing the return key once and use the arrow keys to change the setting to “stop” and press the set key to solidify the change.
2. To enable the ramp and soak control mode, hold the set key for approximately three seconds. The upper display will change to indicate the Input
INPT
[
] parameter, and the lower display will
indicate the temperature sensor type.
3. Press the return key until the upper display indicates the control mode parameter [
CRTL
] and the lower display indicates the control method (default is PID [ to change this value to the program [
PID
]). Use the arrows
PROG
] setting. The display will blink, and pressing the set key will solidify the change.
4. Press the return key once. The upper display will indicate the pattern [
PATN
] parameter and the lower display will show the pattern number. The pattern parameter defi nes which pattern param­eters are being viewed in steps 5 - 10. Setting the pattern parameter to off [
OFF
] allows you to
skip the proceeding ramp/soak parameters. Use
www.parrinst.com
11
4848B Reactor Controller
the arrow keys to change the pattern number and press the set key to solidify the change.
5. Press the return key once. The upper display will
SP00
read [
], where the “00” represents the pattern and step number, respectively. The lower display will indicate the set point for indicated step. The set point can be adjusted using the arrow keys then press the set key to solidify the change.
Note: The fi rst SP_O used must be a higher temperature than the current temperature (PV) or the program will not execute properly.
6. Press the return key once. The upper display will
TI00
read [
], where the “00” represents the pattern number and the step number, respec­tively. The lower display will show the time to execute the current set point in “hh:mm” format. The time setting can be changed by using the arrow keys then press the set key to solidify the change.
7. Repeat steps 4 and 5 for “SP01” through “SP07” and “tI01” through “tI07” as required. Once you have entered all the steps you want, you can leave the remaining “SP” and “tI” variables at zero and press the return key to advance.
8. Press the return key to display [
PSY0
] on the upper display, where “0” represents the current pattern number. This parameter determines the last step to execute in the pattern. For example, if PSy0 has a value of 3, Steps SP00 through SP03 will execute. Use the arrow keys to change the setting and press the set key to solidify the change.
9. Press the return key to display [
CYC0
], where “0” represents the pattern number. This pa­rameter defi nes how many times you want the indicated pattern to repeat. If you would like the pattern to only execute once, set this value to zero. Use the arrow keys to change the setting and press the set key to solidify the change.
10. Press the return key to display [
LIN0
], where “0” represents the pattern number. This pa­rameter allows you to link the indicated pat­tern another. If you would like more than seven separate steps in the process, set this to the next pattern number you wish to link to. Use the ar-
row keys to change the setting and press the set key to solidify the change.
11. Press set to return to the main screen. Note that the lower display of the main screen has changed to show the program step.
Note: The program will attempt to hold the temperature at the set point determined by the last step executed. So, if you wish for the reactor cool to room temperature once the program has fi nished, the last executed step must have a set point consistent with room temperature and the time for the last step can be set to 00:00.

Engaging a Program

1. From the main screen, press the return key two
times to display [
PTRN
] on the upper display. The lower display will indicate the pattern at which you wish to execute.
2. Press the return key until the run/stop parameter
R-S
[
] is on the upper display. The lower display will indicate the setting of the run/stop parameter. Change this value to [
RUN
] in order to start the program determined in step 1. Press set to return to the main screen.
If you wish to stop the program completely, you may change this value to [
STOP
]. Changing the run/stop mode back to stop will restart the program from the beginning.
If you wish to stop the program and continue con­trolling the temperature at the current set point, you may change this value to program stop [
PSTP
]. Changing back to run mode from a program stop will restart the program from the beginning.
If you wish to hold the program at the current temperature, you may change this to program hold
PHOD
[
]. Changing back to run mode from a pro­gram hold will continue the program from its cur­rent step.
3. The main screen will now show the current set point on the lower display. Pressing the arrows will allow you to change between: [ the current pattern and step, [
P-ST
R-TC
] to display
] to display the remaining time in the current pattern step, or [SP] to display the set point for the current pattern step. Press set will solidify this display change.
12
Parr Instrument Company
4848B Reactor Controller

Appendix: sample programs

A sample program to ramp from 25 °C to 250 °C in 2-hrs:
Variable Value Meaning
ptrn 00 Pattern 0
SP00 25 Setpoint of 25 ºC (first step is a
soak by default)
tI00 00:01 Hold for 1-min
SP01 250 Setpoint of 250 °C
tI01 02:00 Ramp to setpoint in 2 hrs
SP02 250 Setpoint of 250 °C
tI02 00:40 Ramp to setpoint in 40-min*
SP03 25 Setpoint of 250 °C
tI03 00:00 Ramp to setpoint immediately**
SP04 25 Setpoint of 25 °C
tI04 00:00
SP05 25 Setpoint of 25 °C
tI05 00:00
SP06 25 Setpoint of 25 °C
tI06 00:00
SP07 25 Setpoint of 25 °C
tI07 00:00
PSy0 3 Execute steps 0-3 only***
CyC0 0 Do not re-cycle program
Lin0 off Do not execute another program
upon completion
* The beginning and fi nal setpoint are equal, making this a soak step.
** The time is zero, making this a step function in­stead of a ramp.
*** Steps 4-7 are not executed here.
**** The SP_0 vaue must be higher than the initial temperature (PV) of the reactor or the program will not initiate correctly.
A sample program to heat to 200 °C as fast a pos­sible, hold for 2-hrs, and come back down as quickly as possible:
Variable Value Meaning
ptrn 00 Pattern 0
SP00 200 Setpoint of 200 °C (first step is
a soak by default)
tI00 00:00 Move setpoint to 200 °C im-
mediately
SP01 200 Setpoint of 200 °C
tI01 01:00 Ramp from 200°C to 200 °C
over 1-hrs *
SP02 200 Setpoint of 200 °C
tI02 02:00 Ramp from 200C to 200 °C over
2-hrs **
SP03 25 Setpoint of 25 °C
tI03 00:00 Ramp to setpoint immediate-
ly***
SP04 25 Setpoint of 25 °C
tI04 00:00
SP05 25 Setpoint of 25 °C
tI05 00:00
SP06 25 Setpoint of 25 °C
tI06 00:00
SP07 25 Setpoint of 25 °C
tI07 00:00
PSy0 3 Execute steps 0-3 only****
CyC0 0 Do not re-cycle program
Lin0 off Do not execute another pro-
gram upon completion of this program
* The physical system will take some time to go from room temp to 200 °C. Step 01 is presented as a “heat up” step. The time value in this step should be ad­justed after the fi rst run is complete and the operator knows the expected heat up time.
** It is useful to keep this step 02 separate from step 01 so you can adjust step 01 to match the heat up time.
*** The time is zero, making this a step function in­stead of a ramp.
**** Steps 4-7 are not executed here.
www.parrinst.com
13
4848B Reactor Controller

Pressure Display Module (PDM)

PRESSURE
2. Press the set button. The lower display will stop
blinking, showing the new value has been set.
When ordering a pressure display module sepa­rately or installed in any Parr controller, always specify the reactor on which the transducer will be installed so that the proper mounting hardware can be furnished.
When this optional module is present, the left dis­play in red shows the pressure, and the right hand display in green shows the Pressure Alarm setpoint. If the reactor pressure exceeds this setpoint, the pressure module will trip the High Limit Alarm, cut­ting power to the heater.
This module provides a digital read out for continu­ously monitoring the pressure within the reactor, plus a backup safety feature which will terminate power to the heater if a preset maximum is reached. Pressure is displayed with a 1 psi resolution and a 1% FS accuracy. The safety cut-out feature offers excellent protection against accidental over-pressure by allowing the user to set a maximum pressure which, if reached, will activate the high limit relay and turn off the heater immediately.
The signal for the pressure display is generated by a transducer in a stainless steel housing mounted on the reactor. The transducer must not be heated above 120 °C; an elevated temperature can caused the accuracy of the transducer to suffer. A water cooling sleeve attached to the transducer mounting body can be used to keep the transducer below this limit when operating the reactor at higher tempera­tures.
For applications involving reactants corrosive to stainless steel, the transducer body can be replaced with an isolator of special alloys which will keep the reactants away from the transducer. Users should consult with the Parr Technical Support before pur­chasing one of these.
The Pressure Alarm setpoint may be adjusted by do­ing the following:
Note: if the pressure transducer is not attached to the 4848B Controller, the High Limit Reset may trip or show a fi xed but incorrect value. We recommend always operating with the transducer attached.

Tachometer Display Module (TDM)

RPM
This optional feature can be included in any 4848B Controller to provide a means for continuously monitoring the stirring speed in a Parr reactor. It consists of an optical sensor installed in the overarm drive on the reactor which is then connected to the 4848B Controller.
The connecting cable has a plug which fi ts the marked socket on the back panel of the controller. The digital display will show the stirring speed over a range of 0-2200 rpm with a 1 rpm resolution and +/- 10 rpm accuracy.
Note: The SV display serves no function on a TDM
Users wishing to control the stirring speed remotely with setpoint control ought to consider the Motor Control Module (MCM) in lieu of the TDM.
1. Press the up or down arrow until the lower display shows the desired setpoint. The lower display will blink, showing the value has not been set yet.
14
Parr Instrument Company
4848B Reactor Controller

Motor Control Module (MCM)

RPM
When this optional module is present, the left dis­play in red shows the stirring speed, and the right hand display in green shows the rpm setpoint. The 4848B Controller is designed to run in either Local or Remote stirring mode. The local/remote switch on the front panel will toggle between these two modes.
In Local mode, the stirring speed is controlled by turning the speed control knob on the front panel. The rpm setpoint has no bearing on the stirring speed.
In Remote mode, the motor will stir at the rpm set­point using closed loop PI control. The speed con­trol knob has no bearing on the stirring speed. The RPM setpoint may be adjusted by doing the fol­lowing:
1. Press the up or down arrow until the lower display shows the desired setpoint. The lower display will blink, showing the value has not been set yet
2. Press the set button. The lower display will stop blinking, showing the new value has been set.

Motor Torque Module (MTM)

This module provides a means for continuously monitoring the motor output percent to the stirrer motor. When used with a Motor Control Module (MCM), the motor speed control will provide a con­stant stirring speed at a given setting. Changes in the power required by the motor will correspond to changes in the viscosity of the fl uids in the vessel. This will be a useful option for users who want to monitor the progress of a polymerization reaction in which there are viscosity changes as the reaction proceeds.

High-Temp Cut-Off Module (HTM)

TEMPERATURE
This module provides a redundant high tempera­ture safety cut-off which will shut down the reactor heater if an unusual malfunction should develop in the primary control system. It is a completely inde­pendent safety backup system, operating in addition to the high-limit control built into each Parr tempera­ture controller. It has its own thermocouple, digital display and wiring, and can be preset to shut down the heater at any desired temperature.
If the secondary temperature (PV) exceeds the alarm setpoint (SV), the alarm indicator on this display will illuminate and the High Limit breaker will trip, inter­rupting power to the heater.
The High Temp Cut-Off Alarm setpoint may be ad­justed by doing the following:
1. Press the up or down arrow until the lower display shows the desired setpoint. The lower display will blink, showing the value has not been set yet.
2. Press the set button. The lower display will stop blinking, showing the new value has been set.
This secondary temperature module does not con­trol the heater. It is used as an alarm only. When ordering this option separately or installed in the 4848B Parr Controller, always specify the reactor with which it will be used so that a thermocouple of the proper style and length can be furnished.
www.parrinst.com
15
4848B Reactor Controller

External Heater Temperature Limit Control Module (ETLM)

TEMPERATURE
ETLM
This module should be considered in systems with large thermal lags or long dead times such as gas phase reactions or other systems where tempera­ture control is diffi cult.
This confi guration is similar to the High Tempera­ture Cut Off Module (HTM), but the display will now turn off the heater if it exceeds a pre-set adjustable setpoint. This non-latching setpoint will establish a maximum wall temperature, and combined with the main temperature control module will help suppress overshoot in diffi cult to control processes.
As an added safety feature, there is also a second­ary alarm which will trip the High Limit Reset when breached. This secondary alarm provides a redun­dant high temperature safety cut-off which will shut down the reactor heater if an unusual malfunction should develop in the primary control system. It is a completely independent safety backup system, operating in addition to the high limit control built into each Parr temperature controller. It has its own thermocouple, digital display and wiring, and can be preset to shut down the heater at any desired tem­perature.
To set the primary (non-latching) temperature limit, press the up or down arrow on the display. The set­point value on the right will fl ash. Press the set but­ton to solidify this display and complete the change.
To set the secondary (latching) temperature limit, press the circular arrow key three times. The left­hand display will read ALIH and the right-hand display will read the secondary temperature limit setpoint (usually 375 °C). Press the up or down ar­row on the display. The setpoint value on the right will fl ash. Press the set button to solidify this dis­play and complete the change.
When ordering this option separately or installed in the 4848B Parr Controller, always specify the reactor with which it will be used so that a thermocouple of the proper style and length can be furnished.

Motor Speed Control

Parr 4848B Controllers are equipped with a solid state speed control module for use with the variable speed, DC motors installed on Parr stirred reactors. The module itself (approximately 4 inches square) is mounted inside the chassis on the bottom plate. A motor switch and a speed adjustment potentiometer are mounted on the front panel. Each module also requires a resistor matched to the horsepower of the motor with which it will be used, as listed in the following table:
Motor Rating
1/17 HP 90 VDC 0.25 ohm 876E6
1/8 HP 90 VDC 0.10 ohm 876E3
1/4 HP 90 VDC 0.05 ohm 876E
1/4 HP 180 VDC 0.10 ohm 876E3
1/2 HP 90 VDC 0.025 ohm 876E2
1/2 HP 180 VDC 0.05 ohm 876E
3/4 HP 180 VDC 0.035 ohm 876E5
Motor Voltage
Resistor Required
Parr Part Number
If the heater temperature exceeds the ETLM setpoint (non-latching), the output to the heater will be inter­rupted. This will not trip the High Limit Reset, and when the heater temperature falls back below the primary setpoint, it will allow power to fl ow to the heater again.
16
Parr Instrument Company
4848B Reactor Controller
4848B Controllers furnished as a part of a complete Parr stirred reactor system will have the proper resistor installed at the factory. Any controller sold separately will require a motor specifi cation so that the proper resistor may be provided.
Always turn the speed control knob fully counter­clockwise to the off position before turning on the motor switch, then advance the knob clockwise slowly to develop the desired speed. Do not over­load the motor. Any high speed or high viscosity load which trips the circuit breaker (90 VDC motors) is too heavy. Reduce the speed to avoid overload­ing and use the reset button on the rear panel to restart the motor.

Adjustments To Speed Control Board

There are fi ve trimpots in the speed control module that can be used to adjust the performance of the motor. These are set at the factory for optimum performance and should not be disturbed unless customized settings are required to match a par­ticular set of operating conditions. The instructions below should be followed carefully if these controls are to be readjusted.
The CL, current limiting/torque adjustment is set at the factory to 1.5 times the motor rating. It is intend­ed to protect both the module and the motor against overloads and heavy surge currents during startup. It can also serve as a torque limiting device by re­ducing the maximum power output of the system.
The IR, compensation adjustment is used to im­prove motor control under varying load conditions. If the loads do not fl uctuate, this control can remain at approximately one-fourth of full setting. But if the motor speed drops more than 2% under load, this adjustment should be increased. If it is set too high, the motor speed will fl uctuate in a cyclical manner. The MAX, maximum speed adjustment controls the maximum speed of the motor. To increase the mo­tor speed, turn the control knob on the front panel to its maximum setting, then use the MAX trimpot to raise the speed to the desired level. Note, how­ever, that the motor may become dangerous if the speed is raised above the motor's rated rpm.
The MIN, minimum speed adjustment can be used to raise the minimum motor speed. To change this setting, turn the control knob on the front panel to its minimum setting, then adjust the MIN trimpot to obtain the desired minimum speed, this adjust­ment will also affect the maximum setting, making it necessary to adjust both MAX and MIN trimpots to obtain the desired spread.
The ACCEL, acceleration adjustment is normally set to provide controlled acceleration from zero to full speed in 2 seconds. It can be adjusted to higher or lower acceleration times anywhere between 0.5 and 4 seconds, but changing this setting will affect the MAX speed and IR compensation which will have to be readjusted. If the acceleration time is reduced to
0.5 seconds (6 o'clock trimpot position), increase the
IR trimpot one quarter turn clockwise and decrease the MAX trimpot one fi fth turn counterclockwise. If the acceleration time is increased to the maximum time of 4 seconds (full rotation), the IR trimpot must be decreased and the MAX increased in the same rotation amounts mentioned above.

Solenoid Valve Module

This module provides a solenoid valve, a metering valve and all parts needed to assemble an automatic cooling system for any reactor. It usually is installed in a cold water line with a fl ow connection to the cooling coil and an electrical connection to the cooling socket on the back of the 4848B Controller. Coolant will then be admitted to the coil whenever cooling is called for by the controller, thereby mini­mizing any temperature overshoot. This system is particularly advantageous when holding fi xed tem­peratures below 150 °C or for controlling exothermic reactions. Compressed air can be used as a coolant if the amount of heat to be removed is not large.
www.parrinst.com
17
4848B Reactor Controller

Communication with PC

The 4848B Controller is provided with RS-485 port (labeled comm) and may be connected to a USB port on a PC with optional A1925E4 communication cable.

Quick Start Instructions for Connecting with PC

1. Put the 576M CD into the CD-ROM.
2. Connect the A1925E4 communication cable be­tween the comm port on the back of the 4848B Controller and an open USB slot on the PC.
3. The PC should open an "Install Hardware" wizard automatically when the cable is connected to the USB slot. If it does not, go to the Control Panel and select "Add Hardware" to start the wizard.
4. When prompted, check the box to search remov­able media for the proper driver. The wizard should fi nd the driver on the 576M CD and install the USB driver. It may prompt that the driver has not been validated; select "continue anyway" to continue the installation. After this it may repeat the installation process for the RS-485 converter.
5. Copy the controller software to the PC. The soft­ware is located on the CD at: "software\ParrCom. exe”.
6. Once copied to the PC, open the ParrCom.exe fi le. No installation is necessary.
7. At the main ParrCom program screen, select "protocol >> set PC". Ensure that the following values are set:
Baud: 9600 Data length: 8 Parity: even Stop bit: 1 ASCII: RTU
Click OK to return to the main screen.
8. At the main screen, select "Program >> Monitor". The Monitor screen will come up. There will be a generic icon on the left, and four mini screens on the right. Each mini screen can be used to connect to a different module on the 4848B Con­troller.
9. In the fi rst mini screen, select 1 for the Ad­dress, and click Connect. It should connect to the Primary Temperature module on the 4848B Controller, and the bottom half of the screen should show parameters for the controller. These may be modifi ed here. Of most interest will be the "Input >> SV" value, which is the setpoint for temperature. Also, the "Alarm >> Alarm 3" value will show the High Limit alarm for this module.
10. Any other modules on the 4848B Controller may be accessed through the remaining avail­able mini screens. The modules have addresses numbered 1-4 starting from the left most module on the 4848B Controller.
18
Parr Instrument Company
4848B Reactor Controller

Datalogging and Charting

The 4848B Controller comes equipped with a chart­ing and datalogging program. This program cannot be run simultaneously with the control program, but once the user is satisfi ed that the controller is set, the control program may be closed, allowing the charting and datalogging program to run. The mod­ules on the 4848B may still be modifi ed manually at the physical panel during datalogging and charting.
1. Open the ParrCom.exe fi le. No installation is necessary.
2. At the main program screen, select "protocol >> set PC" (if you have already done previously, you may skip this step). Ensure that the following values are set:
Baud: 9600 Data length: 8 Parity: even Stop bit: 1 ASCII: RTU
Click OK to return to the main screen.
3. At the main screen, select "Program >> Record­er". The Recorder screen will come up.
4. Select the proper address for the Devices you wish to chart. The primary temperature has ad­dress 1, and each additional module would have an address numbered 2-4 going from left to right on the physical 4848B Controller.
7. The chart will show the process values of each module represented. As the values change, the chart will automatically scale to show the values.
8. When you wish to stop recording, click the stop button. The chart has already been saved in the REC fi le created in step 5. You may view the chart by clicking the recorder button.
9. You can convert the fi le to a TXT fi le for export to a spreadsheet as well.

Converting a Chart File to TXT

Once a chart REC fi le has been created, you can con­vert it to a TXT fi le for export into a spreadsheet.
1. Insert the 576M CD into the CD-ROM. Locate the conversion fi le at “ \software\convert.exe”. Copy it to the PC.
2. Open the convert.exe fi le. No installation is necessary.
3. Click the "CONVERT" button. Locate the REC fi le to be converted, and click "Open".
4. The conversion program will create a new TXT fi le in the same location as the REC fi le with the name "CONVFILE.TXT".
5. Click the Save button and save a REC fi le to an appropriate place on the PC. When the chart is generated, it will write to this fi le.
6. When you return to the main Record­er screen, notice that the Save button is depressed. Hit the Start button to begin recording.
www.parrinst.com
19
4848B Reactor Controller

4848B Factory Defaults

Navigating the Menu System/Factory Default Settings

There are three broad categories of functions in the 4848B Controller modules. They are Regulation, Op­eration, and Initial Settings. From the main screen, Regulation mode is accessed by pressing the set button. The Initial Setting mode is accessed by holding the set button for three seconds. Operation mode is accessed by pressing the circular arrow.
In each mode, you can cycle through the variables by pressing the circular arrow. To change a value, use the up or down arrow, which causes the value to fl ash. Then press the set button to solidify the choice. Return to the main screen by pressing set again.
Keys command:
1. Press “SET” to select
2. Press return key move to next operation mode
3. Up/Down arrow keys to adjust value or select type

Primary Temperature Module

Press and hold down “SET” for 5-sec
Operation Mode
InPt J** Input type
tPUn C Temperature unit
tP-H 800** Upper-limit range
tP-L 0 Lower-limit temperature range
CTRL PID Control mode (ON/OFF, MANU-
S-HC H1C2 Output 1 is Heating and output
ALA1 6 Absolute upper limit alarm op-
ALA2 0 Alarm 2 is disabled
SALA OFF System alarm
CoSH ON Communication write function
C-Sl RTU Format type
C-no * Communication address
bPS 9600 Communication baud rate
Len 8 Data length setting
PrtY Even Parity bit setting
StoP 1 Stop bit setting
Select type/value
Comment
AL, PID and PID PROG)
2 is Cooling
erates when PV value is higher than AL1H setting
that able to use set point from software
Press return key and release
Operation Mode
r-S Run Run/Stop
SP 0** Decimal point position
AL1H 375 Upper alarm setting
LoC OFF Lock mode (lock all keys or
Out1 - (read-only) Heater output %
Out2 - (read-only) Cooling output %
Select type/value
Comment
only up/down arrow able to use)
** If using a type-J or type-K thermocouple, SP = 0 If using an RTD, SP = 1
* See note on address at end of Factory Defaults ** If using a type-J thermocouple, InPt = J, tP-H = 800 If using a type-K thermocouple, InPt = K, tP-H = 800 If using an RTD, InPt = Pt, tP-H = 600
Press “SET” and release
Operation Mode
At OFF Auto Tuning ON/OFF
PID0 0 The 0th PID Parameter
SV 0 The 0th SV
P0 11. 8 Proportional control
I0 375 Integral control
D0 93 Derivative control
IoF0 0 Integral value offset
HtPd 5 Heat cycle control
HcPd 5 Cool cycle control
CoEF 1 1 & 2 value output group dur-
dEAd 0 Dead band
tPoF * PV Offset
Select type/value
Comment
ing dual loop output control
20
* Set at factory
Parr Instrument Company
4848B Reactor Controller

TDM / MCM Module

Press return key and release
Operation Mode
r-S Run Run/Stop
SP 0 Decimal point position
LoC OFF Lock mode (lock all keys or
Out1 - (read-only) Motor output %
Select type/value
Comment
only up/down arrow able to use)
Press and hold down “SET” for 5-sec
Operation Mode
InPt v5 Input type (v5 = 0-5V, v10 =
tP-H 2206 Upper-limit range
tP-L 0 Lower-limit temperature range
CTRL PID Control mode (ON/OFF, MAN-
S-HC Heat Heat/Cool control
ALA1 0 Alarm 1 is disabled
SALA OFF System alarm
CoSH ON Communication write func-
C-Sl RTU Format type
C-no * Communication address
bPS 9600 Communication baud rate
Len 8 Data length setting
PrtY Even Parity bit setting
StoP 1 Stop bit setting
Select type/value
Comment
0-10V, nA0 = 0-20mA, nA4 = 4-20mA, nV =0-50mV)
UAL, PID and PID PROG)
tion that able to use set point from software
* See note on address at end of Factory Defaults
Press “SET” and release
Operation Mode
At OFF Auto Tuning ON/OFF
PID0 0 The 0th PID Parameter
SV 0 The 0th SV
P0 170 Proportional control
C0 1 Integral control
D0 0 Derivative control
CoF0 0 Integral value
HtPd .5 Heat/Cool cycle control
tPoF * PV Offset
CrHI 0 Analog output high
CrLo 0 Analog output low
Select type/value
Comment

Pressure Module

Press return key and release
Operation Mode
r-S Run Run/Stop
SP To be deter-
AL1H 0 Upper-limit alarm 1
LoC OFF Lock mode (lock all keys or
Select type/value
mined**
Comment
Decimal point position
only up/down arrow able to use)
** If units are psi, SP = 0 If units are Bar, SP = 1 If units are MPa, SP = 2
Press and hold down “SET” for 5-sec
Operation Mode
InPt V5 Input type (V5 = 0-5V, V10 =
tP-H Determined
tP-L 0
CTRL ON/OFF Control mode (ON/OFF,
S-HC Heat Heat/Cool control
ALA1 2 Alarm operates when PV
SALA OFF System alarm
CoSH ON Communication write func-
C-Sl RTU Format type
C-no * Communication address
bPS 9600 Communication baud rate
Len 8 Data length setting
PrtY Even Parity bit setting
StoP 1 Stop bit setting
Select type/value
by transduc­er**
[-14.7 if com­pound psi]
[-1.0 if com­pound bar]
[-0.1 if com­pound mPa]
Comment
0-10V, nA0 = 0-20mA, nA4 = 4-20mA, nV =0-50mV)
Upper-limit pressure range
Lower-limit pressure range
MANUAL, PID and PID­PROG)
value is higher than SV Value + ALH setting
tion that able to use set point from software
* See note on address at end of Factory Defaults
* Set at factory
www.parrinst.com
21
4848B Reactor Controller
** Set according to the following:
Transducer range - psi
200 200 13.79 1.38
500 500 34.47 3.45
300 (compound)
1000 1000 68.95 6.89
2000 2000 137.9 13.79
3000 3000 206.8 20.68
5000 5000 344.7 34.47
7500 7500 517.1 51.71
tP-H for psi
300 20.68 2.07
tP-H for Bar
tP-H for MPa
Press “SET” and release
Operation Mode
HtS 0 Heating hysteresis setting
tPoF * PV Offset
Select type/value
Comment
* Set at factory

HTM/ETLM Module

Press return key and release
Operation Mode
r-S Run Run/Stop
SP 0** Decimal point position
AL1H 375*** Upper-limit alarm 1
LoC OFF Lock mode (lock all keys or
Out1 - (read-only) Heater Output %
Select type/value
Comment
only up/down arrow able to use)
** If using a type-J or type-K thermocouple, SP = 0 If using an RTD, SP = 1
*** If using an HTM, AL1H = 0 If using an ETLM, AL1H = 375
Press and hold down “SET” for 5-sec
Operation Mode
InPt J** Input type
tPUn C Temperature unit
tP-H 800** Upper-limit temperature
tP-L 0 Lower-limit temperature
CTRL ON/OFF Control mode (ON/OFF,
S-HC Heat Heat/Cool control
ALA1 6*** Alarm operates when PV
SALA OFF System alarm
CoSH ON Communication write func-
C-Sl RTU Format type
C-no * Communication address
bPS 9600 Communication baud rate
LEn 8 Data length setting
PrtY Even Parity bit setting
StoP 1 Stop bit setting
Select type/value
Comment
range
range
MANUAL, PID and PID PROG)
value is higher than AL1H value
tion that able to use set point from software
* See note on address at end of Factory Defaults
** If using a type-J thermocouple, InPt = J, tP-H = 800 If using a type-K thermocouple, InPt = K, tP-H = 800 If using an RTD, InPt = Pt, tP-H = 600
*** If using an HTM, ALA1 = 2 If using an ETLM, ALA1 = 6
Press “SET” and release
Operation Mode
HtS 0 Heating hysteresis setting
tPoF * PV Offset
Select type/value
Comment
* Set at factory
22
Parr Instrument Company

MTM Module

4848B Reactor Controller
Press return key and release
Operation Mode
r-S Run Run/Stop
SP 1 Decimal point position
LoC OFF Lock mode (lock all keys or
Select type/value
Comment
only up/down arrow able to use)
Press and hold down “SET” for 5-sec
Operation Mode
InPt v10 Input type (v5 = 0-5V, v10 =
tP-H To be deter-
tP-L 0 Lower-limit temperature
CTRL ON/OFF Control mode (ON/OFF,
S-HC Heat Heat/Cool control
ALA1 0 Alarm mode
SALA OFF System alarm
CoSH ON Communication write func-
C-Sl RTU Format type
C-no * Communication address
bPS 9600 Communication baud rate
Len 8 Data length setting
PrtY Even Parity bit setting
StoP 1 Stop bit setting
Select type/value
mined**
Comment
0-10V, nA0 = 0-20mA, nA4 = 4-20mA, nV =0-50mV)
Upper-limit range
range
MANUAL, PID and PID PROG)
tion that able to use set point from software
Press “SET” and release
Operation Mode
HtS 0 Hysteresis
TPoF 0 PV Offset
CrHI 0 Analog output high
CrLo 0 Analog output low
Select type/value
Comment
* Alternate C-no Defaults for 4848B The C-no Address in a 4848B takes special con­sideration. Each module must have a unique c-no address to properly communication with a PC. For the 4848B assign the c-no address according to the following diagram.
C-no=2 C-no=3 C-no=4
C-no=1
C-no=5 C-no=6 C-no=7
* See note on address at end of Factory Defaults
** For 90VDC motor, 115VAC, tP-H = 142.9 For 180VDC motor, 230VAC, tP-H = 120.4 For 90VDC motor, 230VAC, tP-H = 153.2
www.parrinst.com
23
4848B Reactor Controller

Appendix A: Controller Parameters

Initial Setting Mode

Press to advance
Set input type
Set temperature unit (Does not display when analog input)
Set upper-limit of temperature range
Set lower-limit of temperature range
Select control mode
Select heating/cooling control or dual loop output control
Alarm 1 mode setting
Alarm 2 mode setting (Only available on Primary Temperature Controller)
Alarm 3 mode setting (Only available on Primary Temperature Controller)
Set system alarm
Communication write function enable/disable
ASCII, RTU communication format selection
Communication address setting
Communication baud rate setting
Data length setting
Parity bit setting
Stop bit setting
24
Parr Instrument Company

Operation Mode

Press to advance
Use key to set temperature set point
Control setting RUN or STOP
Start pattern setting (PID program control and
Decimal point position selection (except for B, S, R type inputs, all the other types can be set)
Upper-limit alarm 1 (This parameter is available only when ALA1 function is enabled)
Lower-limit alarm 1 (This parameter is available only when ALA1 function is enabled)
Upper-limit alarm 2 (This parameter is available only when ALA2 function is enabled)
Lower-limit alarm 2 (This parameter is available only when ALA2 function is enabled)
Upper-limit alarm 3 (This parameter is available only when ALA3 function is enabled)
Lower-limit alarm 3 (This parameter is available only when ALA3 function is enabled)
4848B Reactor Controller
Time setting)
Setting lock mode
Display output value of 1st output group
Display output value of 2nd output group
www.parrinst.com
25
4848B Reactor Controller

Regulation Mode

Press to advance
Auto-tuning (Available in PID control and RUN mode)
4 groups PID modes (n=0~3). When n=4, PID control is auto regulated.
PD control offset setting (Available when PID control is ON and Ti=0, set the value of PdoF)
Heating hystereisis setting (Available in ON/OFF control mode)
Cooling hystereisis setting (Available in ON/OFF control mode)
or
Heating and Cooling control cycle (Available in PID control mode)
Control cycle setting of 2nd output group (Available in PID control and Dual Loop output control mode)
P value of 1st & 2nd output group during dual loop output control
P value of 2nd output group = (P value of 1st output group) x
Dead Band (Available in Dual Loop output control mode)
Regulate temperature deviation value
Regulate upper-limit of analog output value (Display when equipped with an analog output)
Regulate lower-limit of analog output value (Display when equipped with an analog output)
26
Parr Instrument Company

Parts List

4848B Reactor Controller

Fuses

Fuse Rating Part Number
Instrument Fuse Fast acting, 1 Amp, 250VAC 139E6 Cooling Fuse Fast acting, .25 Amp, 250VAC 139E10 Line Fuse(s) Fast acting, 20 Amp, 250VAC 2074E
Motor Board Fuse (A+) Very Fast acting, 8 Amp, 250VAC 959E5 Motor Board Fuse (L) Fast acting, 10 Amp, 250VAC 185E2
Motor breaker / fuse
1/2 hp, 180VDC Slo-blo, 2.5 Amp, 250VAC 139E8 1/4 hp, 180VDC Slo-blo, 1.5 Amp, 250VAC 139E19 3/4 hp, 180VDC Slo-blo, 4.0 Amp, 250VAC 139E20 1/12 hp, 90VDC Circuit breaker, 1.0 Amp 801E 1/17 hp, 90VDC Circuit breaker, 1.0 Amp 801E 1/8 hp, 90VDC Circuit breaker, 1.5 Amp 801E3 1/4 hp, 90VDC Circuit breaker, 2.5 Amp 801E2 1/2 hp, 90VDC Circuit breaker, 5.0 Amp 801E4
Caution: For continued protection against possible hazard, replace fuses with same type and rating of fuse.

Communication

Part Number Description
A1925E4 RS-485 to USB Conversion Cable

Cooling Solenoids

Part Number Description
A160HW3EB Solenoid Valve Pkg 115V A160HW3EE Solenoid Valve Pkg 230V A160HW7EB Solenoid Valve Pkg 115V 10FT A160HW7EE Solenoid Valve Pkg 230V 10FT A160HW8EB Solenoid Valve Pkg 115V 20FT A160HW8EE Solenoid Valve Pkg 230V 20FT A160HW9EB Solenoid Valve Pkg 115V 30FT A160HW9EE Solenoid Valve Pkg 230V 30FT
www.parrinst.com
27
4848B Reactor Controller

Primary Temperature Module

Part No. Description
A470E2 Thermocouple extension wire,
type-J, 5-ft
A470E4 Thermocouple extension wire,
type-J, 10-ft
A470E7 Thermocouple extension wire,
type-J, 15-ft
A470E5 Thermocouple extension wire,
type-J, 20-ft
A470E8 Thermocouple extension wire,
type-J, 25-ft
A470E6 Thermocouple extension wire,
type-J, 30-ft
A470E9 Thermocouple extension wire,
type-J, 35-ft
A470E10 Thermocouple extension wire,
type-J, 40-ft
A472E4 Thermocouple, type-J, 5-1/2" length A472E2 Thermocouple, type-J, 9-1/2" length A472E3 Thermocouple, type-J, 11-1/2" length A472E Thermocouple, type-J, 7-1/2" length A472E5 Thermocouple, type-J, 21-1/2" length A472E6 Thermocouple, type-J, 15-1/2" length A490E4 Dual T/C, type-J, 5-1/2" length A490E Dual T/C, type-J, 7-1/2" length A490E2 Dual T/C, type-J, 9-1/2" length A490E3 Dual T/C, type-J, 11-1/2" length A490E6 Dual T/C, type-J, 15-1/2" length A490E2 Dual T/C, type-J, 21-1/2” length A511E2 Heater thermocouple, type-J,
bayonet style
A511E4 Heater thermocouple, dual, type-J,
bayonet style

Pressure Display Module (PDM)

Part No. Description
A1905E5 Pressure harness, 5-ft, covered A1905E Pressure harness, 10-ft, covered A1905E8 Pressure harness, 15-ft, covered A1905E3 Pressure harness, 20-ft, covered A1905E9 Pressure harness, 25-ft, covered A1905E7 Pressure harness, 30-ft, covered A1905E10 Pressure harness, 35-ft, covered A1905E11 Pressure harness, 40-ft, covered
A1906EP02 Transducer, 200 psi A1906EP05 Transducer, 500 psi A1906EP10 Transducer, 1000 psi A1906EP20 Transducer, 2000 psi A1906EP30 Transducer, 3000 psi A1906EP50 Transducer, 5000 psi
A2599HC2 Transducer cooling body assembly A2685HC Cooling sleeve assembly 2083HC Cooling sleeve for A2599HC2 827HC O-rings for cooling sleeve 2714HC Hose nipple
Note: Additional Pressure Ranges are available upon request.
28
Parr Instrument Company
4848B Reactor Controller

Tachometer Module (TDM) or Motor Control Module (MCM)

Part No. Description
A10 01E Optical sensor for cart reactor A1001E2 Optical sensor for bench reactor A1001E3 Optical sensor for gear box drives A1001E4 Optical sensor for 4553/54/77/78 A1001E6 Optical sensor for 5100 reactor A1001E8 Optical sensor for 3:1 gear box drive A1001E9 Optical sensor for 4555 reactor A10 01E10 Optical sensor for 10:1 gear box drive A1831E Optical sensor for 5500 Compact Lab
Reactor
1564HC Slotted wheel for cart, bench, and low
pressure (1:1) reactors
1564HC2 Slotted wheel for low pressure (2:1)
reactors
3056HC Slotted wheel for 5500 Compact Lab
Reactor
A1177E8 Tachometer harness, 5-ft A1177E Tachometer harness, 10-ft A1177E4 Tachometer harness, 15-ft A1177E2 Tachometer harness, 20-ft A1177E5 Tachometer harness, 25-ft A1177E3 Tachometer harness, 30-ft A1177E6 Tachometer harness, 35-ft A1177E7 Tachometer harness, 40-ft

Hi-Temp Cut-Off Module (HTM) or External Temperature Limit Module (ETLM)

Part No. Description
A470E2 Thermocouple extension wire, 5-ft A470E4 Thermocouple extension wire, 10-ft A470E7 Thermocouple extension wire, 15-ft A470E5 Thermocouple extension wire, 20-ft A470E8 Thermocouple extension wire, 25-ft A470E6 Thermocouple extension wire, 30-ft A470E9 Thermocouple extension wire, 35-ft A470E10 Thermocouple extension wire, 40-ft
A472E Thermocouple, type-J, 7-1/2" length A472E2 Thermocouple, type-J, 9-1/2" length A472E3 Thermocouple, type-J, 11-1/2" length A472E4 Thermocouple, type-J, 5-1/2" length A472E5 Thermocouple, type-J, 21-1/2" length A472E6 Thermocouple, type-J, 15-1/2" length
A490E Dual T/C, type-J, 7-1/2" length A490E2 Dual T/C, type-J, 9-1/2" length A490E3 Dual T/C, type-J, 11-1/2" length A490E4 Dual T/C, type-J, 5-1/2" length A490E5 Dual T/C, type-J, 21-1/2" length A490E6 Dual T/C, type-J, 15-1/2" length
A511E2 Heater thermocouple, type-J, bayonet
style
A511E4 Heater thermocouple, dual, type-J,
bayonet style
www.parrinst.com
29
Revision 04/03/13
Loading...