Omron E5ZN-DRT DATASHEET

DeviceNet Communications Unit
E5ZN-DRT
Connect the E5ZN Modular Temperature Controller to DeviceNet
• The I/O link function allows setting and monitoring (e.g., of present values) for the E5ZN Modular Temperature Controller to be performed without communications programming.
• Up to 16 E5ZN Modular Temperature Controllers can be con­nected to one Unit.
• All the parameters for the E5ZN can be uploaded or download­ed in one operation using DeviceNet Configurator.
Ordering Information
List of Models
Name External input power
DeviceNet Communications Unit
Note: A DeviceNet Communications Unit and Terminal Unit are required to connect to DeviceNet. (For details on the Terminal Unit, refer to
page 148 or to the E5ZN Catalog (H116-E1-02).) Two End Plates are provided with E5ZN-SCT24S Terminal Units. When mounting to a DIN track, be sure to mount End Plates on both sides.
supply voltage
24 VDC E5ZN E5ZN-DRT
Applicable Temperature
Controller
Model
Specifications
Ratings
Power supply voltage DeviceNet 24 VDC (for internal circuits)
External input power supply
Allowable voltage range
Power consumption (See note.)
Connectable Temperature Controllers E5ZN Series Maximum number of connectable Temperature
Controllers Ambient operating temperature 10 to 55°C (with no icing or condensation) Ambient operating humidity 25% to 85% Ambient storage temperature 25 to 65°C (with no icing or condensation)
Note: The power consumption for the Temperature Controllers is not included.
DeviceNet 11 to 25 VDC External input power
supply DeviceNet Approx. 1.1 W (for a current of 45 mA at 24 VDC) External input power
supply
24 VDC (for RS-485 communications circuits and Temperature Controllers)
20.4 to 26.4 VDC
Approx. 0.5 W (for a current of 20 mA at 24 VDC)
16
Controller
Temperature
DeviceNet Communications Unit E5ZN-DRT I-145
Characteristics
Insulation resistance 20 M min. (at 100 VDC) Dielectric strength 500 VAC, 50/60 Hz for 1 min between the DIN track and all DeviceNet connector terminals and between the DIN track
and all terminal socket terminals
Vibration resistance Shock resistance
10 to 55 Hz, 10 m/s
2
150 m/s
, 3 times each in ±X, ±Y, and ±Z directions
2
for 2 hrs each in ±X, ±Y, and ±Z directions
Weight 100 g max. Safety standards cULus508
EMS: Electrostatic Discharge (ESD) EN61006-2, EN61000-4-2 (4 kV/contact, 8 kV/air)
Radiated Electromagnetic Fields EN61006-2, EN61000-4-3 (10 V/m) Electrical Fast transients/BURST EN61006-2, EN61000-4-4 (2 kV/DC power-line, 1 kV/Signal-line) Surge Transients EN61006-2, EN61000-4-5 (line to ground : 1 kV/DC power-line)
: 2 kV/Signal-line
line to line : 0.5 kV/DC power-line)
Conducted Disturbances EN61006-2, EN61000-4-6 (10 V)
EMI: Radiated Emissions (electric field) EN50081-2 Class A
Communications (for Temperature Controller Expansion)
Transmission line
RS-485 multipoint
connection method Communications method RS-485 (2-wire, half-duplex) Synchronization
Start-stop synchronization
method Baud rate 38,400 bps Transmission code ASCII Data bit length 7 bits Stop bit length 2 bits Error detection Vertical parity (even)
BCC (block check character)
Flow control None Number of Units that can
16 Units max. (32 channels)
be connected in parallel
Connections
Terminal Arrangement
E5ZN-DRT E5ZN-SCT24S
×10
Color
Red
Communications power, positive (+V)
Communications signal, high (CAN H)
White
---
Shield
Communications signal, low (CAN L)
Blue
Black
Communications power, negative (–V)
Signal
NODE ADR
×1
UP/DN
COPY
MS
NS
ON
TS
External input power supply (24VDC)
Setting Display Unit communications
Communications for Temperature Controller expansion
(TOP VIEW)
+
B (+)
A (−)
B (+)
A (−)
19
13
20 14
21 15
22 16 10
23 17 11
24 18 12
71
82
93
4
5
6
I-146 DeviceNet Communications Unit E5ZN-DRT
Not used with the DeviceNet Communications Unit