Note: 1. The E53-E8Q Voltage Output Unit or the E53-E8C Current
Output Unit can be used with the E5ZE. The E53-E8Q Voltage Output Unit and the E53-E8C Current Output Unit are
sold separately.
2. The heater burnout and SSR failure detection function of the
E5ZE will be invalid if the heating side control output of the
E5ZE is current output.
3. The E54-E8CT CT Input Unit is required for the heater burnout and SSR failure detection. The E54-E8CT CT Input Unit
is sold separately.
4. The E53-E01 Communications Unit for RS-232C communication or the E53-E04 Communications Unit for RS-422 and
RS-485 communication can be used with the E5ZE. The
E53-E01 Communications Unit and the E53-E04 Communications Unit are sold separately.
8-point (SPST-NO x 8) relay output with NPN DC coil (+ common)G7TC-OC08
16-point (SPST-NO x 16) relay output with NPN DC coil (+ common)G7TC-OC16
16-point (SPST-NO x 16) relay output with NPN DC coil (+ common)G7VC-OC16
16-point (SPST-NO x 16) SSR AC output with NPN DC coil (+ common)G7VC-OA16
16-point (SPST-NO x 16) SSR DC output with NPN DC coil (+ common)G7VC-OD16
Note: 1. The Setting Display Unit is originally for use with the E5ZD . Be careful when using the Setting Display Unit with the E5ZE as some of the
E5ZE’s functions cannot be used with the Setting Display Unit.
2. Each model available as a 100-to-240-VAC type or 24-VDC type. (Exception: The E5ZD-SDLM is available only as a 24-VDC type).
Multipoint Temperature Controller E5ZE3
Specifications
■Ratings
Supply voltage24 VDC
Operating voltage range85% to 110% of rated supply voltage
Power consumption15 W + 20% max. at rated supply voltage
InputInput typeThermocouple: K, J, R, S, T, E, B, N, L, U, W, PL-II
Input impedanceThermocouple: 1 M
Rated platinum resistance
thermometer current
Control outputsVoltage output (with short-circuit protecting function)
Alarm outputsTemperature alarm:The total output of all control points (alarm 1 NPN open collector output and
No. of input c ontrol points8 input and 8 control points
Setting methodVia communication
Control methodON/OFF control
Platinum resistance thermometer: Pt100, JPt100
Ω min.
1 mA
ON:12
OFF:0.5 VDC max.
Max. load current: 30 mA DC per point
Current output
Rated output range: 4 to 20 mA DC
Current output range: 0 to 22 mA DC
With an output value of 0%: 4
With an output value of 100%:20
Max. load resistance: 600
Open collector output (NPN) (cooling side only)
Max. applied voltage: 30 VDC
Max. load current:50 mA DC per point
ON residual voltage: 2 VDC max.
OFF leakage current: 1 mA DC max.
HB alarm (heater burnout detection): Total output of all control points (1-point NPN open collector
HS alarm (SSR failure detection):Total output of all control points (1-point NPN open collector
Temperature controller error output (memory, set value, or hardware error):
1-point NPN open collector output
Max. applied voltage: 30 VDC
Max. load current:50 mA DC per point
Hybrid of 2-PID control and fuzzy control
Manual operation
± 1.2 VDC
+0
/
mA DC
–0.6
+2
/–0 mA DC
Ω per point
alarm 2 NPN open collector output)
output)
output)
4Multipoint Temperature Controller E5ZE
■Input Ranges
Thermocouple
Input (switch
selectable)
(see note 1)
Range
Setting no.01/82/34/9567AB
Min. setting unit 1
°C−200 to
°F−300 to
K (CA)
Chromel vs.
alumel (see
note 2)
1,300
2,300
°C or 0.1°C
J (IC)/L
Iron vs.
constantan
−100 to 850 0 to 1,700−200 to 400 0 to 600100 to 1,800 0 to 1,3000 to 2,3000 to 1,300
−100 to
1,500
R/S
Platinum
vs. Plati-
num rhod-
ium 10%
0 to 3,000−300 to 700 0 to 1,100300 to 3,000 0 to 2,30032 to 4,100 0 to 2,300
T (CC)/U
Copper vs.
constantan
E (CRC)
Chromel vs.
constantan
B
Platinum
rhodium
30% vs.
platinum
rhodium 6%
N
Nichrosil
vs. nisil
W
(see note 3)
PL-II
(Platinum)
Platinum Resistance Thermometer
Input (switch
selectable)
(see note 1)
Range
Setting no.01
Min. setting unit 1
Note: 1. The setting selector set to 0 (K) or 0 (Pt 100) before shipping.
°C−100.0 to 500.0−100.0 to 500.0
°F−100.0 to 900.0−100.0 to 900.0
2. A temperature range is factory-set to a range of –200
3. Thermocouple W is W/Re5-26 (tungsten rhenium 5, tungsten rhenium 26).
Pt 100JPt 100
°C or 0.1°C
° to 1,300°C (K(CA)) or −100.0° to 500.0°C (Pt 100).
Multipoint Temperature Controller E5ZE5
■Characteristics
Measurement accuracy (see note)Thermocouple:
±0.3% of the process value or ±2°C, whichever greater) ±1 digit max.
(
(
±0.3% of the process value or ±3.6°F, whichever greater) ±1 digit max.
Platinum resistance thermometer:
(
±0.3% of the process value or ±0.8°C, whichever greater) ±1 digit max.
(
±0.3% of the process value or ±1.5°F, whichever greater) ±1 digit max.
Hysteresis0.0
°C/°F to 99.9°C/°F for ON/OFF control only (in units of 0.1°C/°F)
Cooling coefficient0.0 to 10.0 (in units of 0.1)
Proportional band0.0
°C/°F to 999.9°C/°F (in units of 0.1°C/°F)
Cooling side: Cooling coefficient x Proportional band
Integral (reset) time0 to 3,999 s (in units of 1 s) (for both heating and cooling)
Derivative (rate) time0 to 3,999 s (in units of 1 s) (for both heating and cooling)
Control periodHeating side:1 to 99 s (in units of 1 s)
Cooling side: 1 to 99 s (in units of 1 s)
Sampling periodApprox. 200 ms for 8 control points
Dead band/overlap ba nd
Alarm output setting range
−999°C/°F to 999°C/°F (in units of 1°C/°F)
−999°C/°F to 9999°C/°F, 0 to 9999°C/°F (upper- and lower-limit alarm) (in units of 1°C/°F)
−999.9°C/°F to 9999.9°C/°F, 0.0 to 9999.9°C/°F (upper- and lower-limit alarm) (in units of 0.1°C/°F)
Fuzzy strength0% to 99% (in units of 1%)
Fuzzy scale 10.2
Fuzzy scale 20.02
°C/°F to 999.9°C/°F (in units of 0.1°C/°F)
°C/s or °F/s to 99.99°C/s or °F/s (in units of 0.01°C/s or °F/s)
Set value backupLithium battery
Set value backup period10 years min. at room temperature
Insulation resistance20 M
Ω min. between the FG terminal and all analog input terminals (at 500 VDC)
Dielectric strengthA leakage current of 1 mA A C max. with 500 V AC f or 1 minutes between the FG terminal and all analog
input terminals
Vibration resistance
Malfunction: 10 to 55 Hz, 10 m/s
Destruction: 10 to 55 Hz, 20 m/s
Shock resistance
Malfunction: 150 m/s
Destruction: 200 m/s
Ambient temperatureO perating:
Storage:
2
(15.3G), 3 times each in 6 directions
2
(20.4G), 3 times each in 6 directions
−10°C to 55°C (with no icing or condensation)
−25°C to 65°C (with no icing or condensation)
2
(1G) for 10 min each in X, Y , and Z directions
2
(2G) for 2 hrs each in X, Y, and Z directions
Ambient humidityOperating:35% to 85%
Storage:35% to 95%
DimensionsWithout casing: 169.5 x 192 x 58 mm max.
With casing: 173.5 x 200 x 65 mm max.
Degree of protectionIP00
WeightWithout casing: 900 g max.
Approved standardsConforms to EN50081-2, EN50082-2 (see note 3)
Note: 1. The measurement accuracy of the E5ZE used with a thermocouple B at 400°C or 750°F max. is not guaranteed. The following
measurement accuracy values are applied to the E5ZE.
K and T at
K and T at
R, S, and W at 200
R, S, and W at 400
2. The measurement accuracy of the E5ZE used with any thermoc ouple is 1
temperature ranges to increase the measurement accuracy to as high as 0.1
K thermocouple:0.0
T or U thermocouple: 0.0
N thermocouple: 400.0
−100°C max. and U:±3°C ±1 digit max.
−100°F max. and U:±5.4°F ±1 digit max.
°C max., and B at 1,000°C max.: ±4°C ±1 digit max.
°F max., and B at 1,800°F m a x.:±7.2°F ±1 digit max.
°C/°F. The thermocouple can be used under the following
°C/°F.
°C to 1,300.0 °C, 0.0 °F to 2,300.0 °F
°C to 400.0 °C, 0.0 °F to 700.0 °F
°C to 1,300.0 °C, 700.0 °F to 2,300.0 °F
J, E, L, or PLII thermocouple: Any temperature
3. To ensure EMC conformance, refer to Wiring for Conformance to the EMC Directives on page 16.
6Multipoint Temperature Controller E5ZE