Mitsubishi PLFY-P32VKM-A.UK, PLFY-P40VKM-A.UK, PLFY-P50VKM-A.UK, PLFY-P63VKM-A.UK Service Manual

5 (1)

SPLIT-TYPE,HEAT PUMP AIR CONDITIONERS

No. OC259

TECHNICAL & SERVICE MANUAL

Series PLFY

Ceiling Cassettes R407C R22

Indoor unit

 

[Model names]

[Service Ref.]

PLFY-P32VKM-A

PLFY-P40VKM-A

PLFY-P50VKM-A

PLFY-P63VKM-A

PLFY-P32VKM-A.UK PLFY-P40VKM-A.UK PLFY-P50VKM-A.UK PLFY-P63VKM-A.UK

CONTENTS

 

1. SAFETY PRECAUTION···········

 

2. PART NAMES AND FUNCTIONS ······

 

3. SPECIFICATION ··············

 

4. OUTLINES AND DIMENSIONS·······

 

5. WIRING DIAGRAM·············

 

6. REFRIGERANT SYSTEM DIAGRAM······

 

7. TROUBLE SHOOTING···········

 

8. DISASSEMBLY PROCEDURE········

 

9. PARTS LIST················

INDOOR UNIT

10. OPTIONAL PARTS ·············

1 SAFETY PRECAUTION

Cautions for using with the outdoor unit which adopts R407C refrigerant.

· Do not use the existing refrigerant piping.

-The old refrigerant and lubricant in the existing piping contains a large amount of chlorine which may cause the lubricant of the new unit to deteriorate.

· Use “low residual oil piping”.

-If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the lubricant will result.

·Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)

-If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.

·Use ESTR , ETHER or HAB as the lubricant to coat flares and flange connection parts.

Use liquid refrigerant to seal the system.

-If gas refrigerant is used to seal the system, the composition of the refrigerant in the cylinder will change and performance may drop.

· Do not use a refrigerant other than R407C.

-If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the lubricant to deteriorate.

· Use a vacuum pump with a reverse flow check valve.

-The vacuum pump oil may flow back into the refrigerant cycle and cause the lubricant to deteriorate.

3

[1] Service tools

Use the below service tools as exclusive tools for R407C refrigerant.

No.

Tool name

Specifications

1

Gauge manifold

·Only for R407C.

 

 

 

 

 

·Use the existing fitting SPECIFICATIONS. (UNF7/16)

 

 

 

 

 

·Use high-tension side pressure of 3.43MPa·G or over.

 

 

 

2

Charge hose

·Only for R407C.

 

 

 

 

 

·Use pressure performance of 5.10MPa·G or over.

3Electronic scale

4

Gas leak detector

·Use the detector for R134a or R407C.

 

 

 

5

Adapter for reverse flow check.

·Attach on vacuum pump.

6Refrigerant charge base.

7 Refrigerant cylinder.

·For R407C

·Top of cylinder (Brown)

 

·Cylinder with syphon

8Refrigerant recovery equipment.

[2]Notice on repair service

·After recovering the all refrigerant in the unit, proceed to working. ·Do not release refrigerant in the air.

·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.

[3] Refrigerant recharging

(1) Refrigerant recharging process

1Direct charging from the cylinder.

·R407C cylinder are available on the market has a syphon pipe. ·Leave the syphon pipe cylinder standing and recharge it.

(By liquid refrigerant)

Unit

Gravimeter

(2) Recharge in refrigerant leakage case

·After recovering the all refrigerant in the unit, proceed to working. ·Do not release the refrigerant in the air.

·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.

4

Mitsubishi PLFY-P32VKM-A.UK, PLFY-P40VKM-A.UK, PLFY-P50VKM-A.UK, PLFY-P63VKM-A.UK Service Manual

2 PART NAMES AND FUNCTIONS

Indoor (Main) Unit

Filters

 

Remove dust and pollutants

 

from return air

Horizontal Air Outlet

 

Sets airflow horizontal automatically

 

during cooling or dehumidifying.

 

Grille

Auto Air Swing Vane

Disperses airflow up and down and adjusts the angle of airflow direction.

Air Intake

Returns air from room.

Remote controller

[PAR-20MAA]

 

● Once the controls are set, the same operation mode can

 

be repeated by simply pressing the ON/OFF button.

Operation buttons

 

TEMP. ADJUSTMENT button

TIME SETTING button

AIR SPEED button

This sets the room temperature. The

This sets the current time, start time

This sets the ventilation fan speed.

temperature setting can be performed

and stop time.

 

 

 

 

 

in 1: units

 

 

 

 

 

Setting range

 

 

 

 

 

Cooler 19: to 30:

 

 

 

 

ON/OFF button

Heater 17: to 28:

 

 

 

 

 

 

 

 

 

This switches between the operation

 

 

 

 

 

and stop modes each time it is pressed.

 

 

 

 

 

The lamp on this button lights during

TIMER button

 

CENTRALLY CONTROLLED

1Hr.

operation.

 

 

 

This switches between continuous

 

 

ON OFF

˚C

 

 

CHECK

CLOCK

FILTER

 

operation and the timer operation.

 

˚C

 

CHECK MODE

AIR DIRECTION button

DEFROST

 

TEST RUN

 

 

 

NOT AVAILABLE FUNCTION

 

STAND BY

 

ERROR CODE

 

 

 

 

 

 

 

 

 

TEMP.

 

ON/OFF

This adjusts the vertical angle of the

 

 

 

 

 

 

 

 

 

 

ventilation.

 

 

 

 

FILTER

 

OPERATION SWITCH button

 

 

 

CHECK TEST

 

 

 

 

 

 

Press this button to switch the cooler,

PAR-20MAA

TIMER SET

 

FILTER button

electronic dry (dehumidify), automatic

 

 

 

 

 

and heater modes.

 

 

 

 

This resets the filter service indication

 

 

 

 

 

display

LOUVER button

 

 

 

CHECK-TEST RUN button

This switch the horizontal fan motion

 

 

Only press this button to perform an

ON and OFF.

 

 

 

inspection check or test operation.

 

 

 

 

Do not use it for normal operation.

(Not available for this model.)

 

 

 

 

 

5

Display

CENTRALLY CONTROLLED display

This indicates when the unit is controlled by optional features such as central control type remote controller.

CLOCK display

The current time , start time and stop time can be displayed in ten second intervals by pressing the time switch button. The start time or stop time is always displayed during the timer operation.

In this display example on the bottom left, a condition where all display lamps light is shown for explanation purposes although this differs from actual operation.

TIMER display

This indicates when the continuous operation and time operation modes are set.

It also display the time for the timer operation at the same time as when it is set.

OPERATION MODE display

This indicates the operation mode.

STANDBY display

The [STANDBY] symbol is only displayed from the time the heating operation starts unit the heated air begins to blow.

DEFROST display

This indicates when the defrost operation is performed.

AIR DIRECTION display

This displays the air direction.

 

CENTRALLY CONTROLLED

1Hr.

 

 

 

ON OFF

 

˚C

 

CHECK

CLOCK

 

 

 

 

 

 

 

 

 

 

FILTER

 

˚C

 

 

CHECK MODE

STAND BY

ERROR CODE

 

TEST RUN

 

NOT AVAILABLE

FUNCTION

DEFROST

 

 

 

 

TEMP.

 

 

ON/OFF

FILTER

CHECK TEST

PAR-20MAA

TIMER SET

AIR SPEED display

The selected fan speed is displayed.

ROOM TEMPERATURE display

The temperature of the suction air is displayed during operation. The display range is 8°C to 39°C. The display flashes 8°C when the actual temperature is less than 8°C and flashes 39°C when the actual temperature is greater than 39°C.

Operation lamp

This lamp lights during operation, goes off when the unit stops and flashes when a malfunction occurs.

CHECK MODE

display

TEST RUN

This display lights in the check mode or when a test operation is performed.

CHECK display

 

 

 

 

 

 

SET TEMPERATURE display

 

POWER display

This indicates when a malfunction

 

 

 

 

 

has occurred in the unit which should

 

This displays the selected setting

 

This lamp lights when electricity is

be checked.

 

 

 

temperature.

 

supplied to the unit.

 

 

 

 

 

 

 

 

Caution

FILTER display

This lamp lights when the filter need to be cleaned.

Only the Power display lights when the unit is stopped and power supplied to the unit.

When the central control remote control unit, which is sold separately, is used the ON-OFF button, operation switch button and TEMP. adjustment button do not operate.

“NOT AVAILABLE” is displayed when the Air speed button are pressed.This indicates that this room unit is not equipped with the fan direction adjustment function and the louver function.

When power is turned ON for the first time, it is normal that “H0” is displayed on the room temperature indication (For max. 2minutes). Please wait until this “H0” indication disappear then start the operation.

6

3 SPECIFICATION

3-1. Specification

Item

PLFY-P32VKM-A.UK

PLFY-P40VKM-A.UK

PLFY-P50VKM-A.UK

PLFY-P63VKM-A.UK

 

 

 

 

 

 

 

Power

[,V,Hz

Cooling capacity

kW

Heating capacity

kW

characteristic

 

Input

 

Cooling

kW

 

 

 

 

 

 

 

 

Heating

 

 

 

 

 

kW

Electric

 

Current

 

Cooling

A

 

 

Heating

A

 

 

 

 

 

 

 

 

 

 

 

 

 

Exterior

(munsell symbol)

 

 

 

 

Height

mm

Dimensions

 

Width

mm

 

 

 

 

Depth

mm

Heat exchanger

 

 

Fan No

 

 

F

 

Air flow W3

k/min

a

 

 

External

 

n

 

Pa

 

static pressure

 

 

Fan motor

kW

 

 

output

 

 

Insulator

 

 

Air filter

 

 

 

 

sideGas

[mm(in.)

 

Pipe

 

dimensions

Liquidside [mm(in.)

Cond. drain pipe size

[mm

Noise level W3

dB

Product weight

kg

 

 

Single phase , 220-230-240V , 50Hz

 

 

3.6

 

4.5

 

5.6

 

7.1

 

 

 

4.0

 

5.0

 

6.3

 

8.0

0.13

 

0.13

 

0.14

 

0.15

0.13

 

0.13

 

0.14

 

0.15

0.60

 

0.60

 

0.64

 

0.68

0.60

 

0.60

 

0.64

 

0.68

Unit : Galvanized sheets · Standard grills : ABS resin acrylic coating

Munsell<0.70Y 8.59/0.97>

 

 

 

298<30>

 

 

 

 

 

660<760>

 

 

 

 

 

660<760>

 

 

 

 

 

Cross fin

 

 

 

 

 

Turbo fan 1

 

 

15-14.5-14-13

 

 

 

 

 

 

 

16-15-14-13

 

17-16-15-14

 

 

 

0

 

 

 

 

 

0.030

 

 

 

 

 

Polyethylene sheet

 

 

 

 

 

PP honey comb

 

 

12.7(1/2")

 

 

 

 

15.88(5/8")

6.35(1/4")

 

 

9.52(3/8")

 

 

 

 

 

 

 

O.D.32 (PVC pipe VP-25 connectable)

35-34-32.5-31

37-35.5-34-32

39-38-36.5-35

19<3.7>

 

20<3.7>

 

 

 

Note 1.

Rating conditions(JIS B 8616)

 

 

Cooling :

Indoor :

D.B. 27°C

W.B. 19.0°C

 

 

outdoor :

D.B. 35°C

 

 

Heating :

Indoor :

D.B. 20°C

 

 

 

outdoor :

D.B. 7°C

W.B. 6°C

Note 2.

The number indicated in < > is just for the grill.

W 3.

Air flow and the noise level are indicated as High-Middium 1-Middium 2-Low.

7

3-2. Electrical parts specifications

Model

 

 

 

 

 

 

Parts

Symbol

PLFY-P32VKM-A.UK

PLFY-P40VKM-A.UK

PLFY-P50VKM-A.UK

PLFY-P63VKM-A.UK

 

 

 

 

 

 

name

 

 

 

 

 

 

Room temperature

TH21

Resistance 0:/15k', 10:/9.6k', 20:/6.3k', 25:/5.2k', 30:/4.3k', 40:/3.0k'

thermistor

 

 

 

 

 

 

Liquid pipe thermistor

TH22

Resistance 0:/15k', 10:/9.6k', 20:/6.3k', 25:/5.2k', 30:/4.3k', 40:/3.0k'

Gas pipe thermistor

TH23

Resistance 0:/15k', 10:/9.6k', 20:/6.3k', 25:/5.2k', 30:/4.3k', 40:/3.0k'

Fuse

FUSE

 

 

250V 6.3A

 

(Indoor controller board)

 

 

 

 

 

 

 

 

 

 

6-pole OUTPUT 30W

 

Fan motor

 

 

 

PA1-V30F

 

MF

 

 

 

 

 

(with Inner-thermostat)

 

 

 

 

 

 

 

 

OFF 125:±5:

 

 

 

Inner-thermostat

 

 

 

 

 

ON 85:±20:

 

Fan motor capacitor

C

 

 

2.5+ x 400V

 

Vane motor

MV

 

 

MC8 200V-240V

 

 

 

2.5/2W 5/6R.P.M

 

(with limit switch)

 

 

 

 

 

 

 

 

 

 

Drain-up mechanism

DP

 

 

PJV-1002

 

 

 

INPUT 8/7.5W 24R/Hr

 

 

 

 

 

 

Drain sensor

DS

Heater resistance 0:/6k', 10:/3.9k', 20:/2.6k', 25:/2.2k', 30:/1.8k', 40:/1.3k'

 

 

 

 

DC12V Stepping motor drive port

 

Linear expansion valve

LEV

 

 

dimension 3.2 ' (0~2000pulse)

 

 

 

 

 

EDM-402ME

 

Electric heater

H2

 

 

240V 28.8W

 

(Condensation proof)

 

 

 

 

 

 

Power supply terminal

TB2

 

 

(L,N,;) 330V 30A

 

block

 

 

 

 

 

 

 

 

 

Transmission terminal

TB5

 

 

(M1,M2,S) 250V 20A

 

block

 

 

 

 

 

 

 

 

 

MA remote controller

TB15

 

 

(1,2) 250V 10A

 

terminal block

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 