• Safety notes are marked with
WARNING or CAUTION,
depending on the severity of possible
consequences that may result when the
instructions are not followed exactly as
stated.
Proper installation is important for your
safety and proper functioning of the units.
Thoroughly read the following safety
precautions prior to installation.
After reading this manual, pass the manual on to the end
user to retain for future reference.
The users should keep this manual for future reference and
refer to it as necessary. This manual should be made
available to those who repair or relocate the units. Make
sure that the manual is passed on to any future air
condition system users.
• Thoroughly read the following safety precautions prior to installation.
• Observe these precautions carefully to ensure safety.
WARNING
CAUTION
• After reading this manual, pass the manual on to the end user to retain for future reference.
• The users should keep this manual for future reference and refer to it as necessary. This manual should be made available to those
who repair or relocate the units. Make sure that the manual is passed on to any future air condition system users.
Electric work must be performed by an authorized technician.
Indicates a risk of death or serious injury.
Indicates a risk of injury or structural damage.
WARNING
Installation
To reduce the risk of fire and electric shock, do not install
the units where they can get wet.
To reduce the risk of electric shock, fire, and malfunction,
do not install the unit in a steamy or condensing
environments.
Properly dispose of the packing materials.
Plastic bags can pose suffocation and choking hazards. Keep
out of the reach of children. Tear the plastics bags before
disposing of them.
Wire installation
Properly install the unit on a stable, load-bearing surface.
Unit installed on an unstable surface may fall and cause injury.
Units must be properly installed by your dealer or
authorized technician according to the instructions in the
Installation Manual.
Improper installation may result in electric shock or fire.
Properly secure the cables with clamps so that the weight
of the cables will not strain the connectors.
Improperly connected cables may break, produce heat, and
cause smoke or fire.
Electric work must be performed by an authorized
technician according to the local regulations and the
instructions detailed in this manual. Always use a
dedicated circuit.
Capacity shortage to the power supply circuit or improper
installation may result in electric shock, smoke, or fire.
Install all required covers.
Infiltration of dust or water may cause electric shock, smoke,
or fire.
Take appropriate measures against electrical noise
interference when installing the air conditioners in
hospitals or radio communication facilities.
• Inverter, power generators, or radio communication
equipment may interfere with the normal operation of the
unit.
• Subsequently, the device may also affect medical treatment,
image broadcasting by creating frequency noise.
Make sure that there is a main power switch and residual
current circuit breaker (RCCB) for each unit.
A ready accessible breaker for power source line helps reduce
the risk of electric shock. Installation of a breaker is mandatory
in some area.
To reduce the risk of electric leak, overheating, and fire,
only use standard cables with the proper current carrying
capacity.
Use properly rated breakers (residual current circuit
breaker (RCCB), main switch + fuse, circuit breaker).
The use of improperly rated breakers may result in
malfunctions or fire.
To reduce the risk of electric shock and malfunctions,
keep wire pieces and sheath shavings out of the terminal
block.
This appliance must be earthed.
Do not connect the protective earth cable to a gas pipe, water
pipe, lightning rod, or telephone earthing cable.
If the unit is not properly earthed, the unit may malfunction due
to electrical noise interference. It also poses a risk of electric
shock, smoke, or fire.
- 2 -
Page 3
General caution
Do not install the unit in environments where large
amounts of oil (including machine) or acidic/alkaline
chemical sprays are present. These types of substances
may cause device performance to be reduced and cause
electrical shock, malfunction, smoke, or fire.
To reduce the risk of electric shock, fire, or malfunction,
do not wash the unit with water or other types of liquids.
Relocating/Repairing units
Consult your dealer or an authorized technician when the
unit needs to be relocated or repaired.
Do not disassemble the unit or make any modifications/
alterations to the unit.
Improper repair, modification, or alteration may cause injury,
electric shock, or fire.
Transporting units/Unit installation
Do not install the unit where there is a risk of leaking
flammable gas.
If flammable gas accumulates around the unit, it may ignite
and cause a fire or explosion.
Wear protective gloves.
A high voltage is applied to the terminals. To reduce the risk of
electric shock, wear protective gloves before touching the
electrical parts on the unit.
CAUTION
Take appropriate safety measures against earthquakes to
prevent the unit from toppling over.
Unit installed on an unstable surface may fall and cause injury.
Electric work
Do not touch switches or other electrical parts with wet
hands.
Doing so poses a risk of fire or electric shock.
General caution
To reduce the risk of electric shock, turn off the power
before performing electric work.
When replacing fuses, only use fuses with adequate
breaking capacity.
The use of improperly rated fuses or a substitution of fuses
with steel or copper wire may result in fire.
To avoid deformation and malfunction, do not install the
remote controller in direct sunlight or where the ambient
temperature exceeds 55°C (131°F) or drops below -10°C
(14°F).
Always use adequate tools for repair.
The use of unsuitable tools may result in failure to complete
the job properly and cause unit damage or injury.
To reduce the risk of injury, do not touch the edges of
parts.
To reduce the risk of injury from accidentally dropped
tools, check the surroundings before performing
installation, inspection, and repairs, and keep children
away from the site.
Important
To avoid malfunctions, do not bundle the power cable and
signal transmission lines together, or put them in the
same conduit.
To avoid fire, malfunction, and damage, do not connect
the power cable to terminal block for signal cables.
When connecting to the Internet, manage the security of
the Internet.
To prevent unauthorized access, always use a security device
such as a VPN router when connecting to the Internet.
- 3 -
Page 4
Important
The PAC-YG50ECA expansion controller and the type of controllers that connect to the expansion controller via the LAN (e.g.,
AG-150A) each have a DB No. This 2-digit number is indicated on the package box and the controller. ([DB No.: ∗∗])
The DB number of the expansion controller can also be verified on its 7-segment controller.
Controllers with different DB No. cannot be connected to each other. Be sure to check the DB No. of each controller to be connected.
Connection of two or more controllers that have different DB No. requires a controller software version update. Consult your dealer
for how to update the software.
<Location of the DB No. (expansion controller)>
Package box
Label
Label
Label content
The DB No. is indicated here in two digits.
Controller
<Bringing up the DB No. on the 7-segment LED on the expansion controller>
On the switch board, set SW601 to “All OFF”, SW606 to “2,” and SW607 to “5.” (Refer to page 16 for the location of each switch.)
The DB No. will appear on the 7-segment LED on the expansion controller.
Refer to for details.
For instructions for how to verify the DB No. of the controllers (AG-150A etc.) that connect to the expansion controller via the
10 7-segment LED
LAN, refer to the Installation/Instructions Manuals that came with the controller.
- 4 -
Page 5
1Specifications
1-1. Product Specifications
ItemsSpecifications
Power source
Interface
Ambient
conditions
Dimensions
Weight2.6kg [5-
Installation conditionsInside the control panel (indoor)
1-2. External dimensions
97.2 (3-7/8)
Rated input100-240VAC ±10% 0.4-0.3A 50/60Hz
Fuse250VAC 3.15A Time-delay Type (IEC127-2.S.S.5)
Rated output of the power supply
to M-NET transmission lines
22-30VDC
External input/output12VDC or 24VDC (requires an external power supply)
LAN100BASE-TX/10BASE-T
Temperature
Operating
temperature range
Storage
temperature range
-10~55°C [14~131°F]
-20~60°C [-4~140°F]
Humidity30 ~ 90%RH (Non-condensing)
217 (H) × 250 (W) × 97.2 (D) mm
[8-9/
(H) × 9-7/8 (W) × 3-7/8 (D) in.]
16
3
/4 lbs.]
250 (9-
155 (6-
7
/8)
1
/8)
)
16
/
3
Unit: mm (in.)
M-NET Terminal
block (M3.5)
LAN
Power source 100-240VAC
Terminal block (M3.5)
)5 (
)
16
/
16
/
1
9
217 (8-
204.5 (8-
- 5 -
Page 6
1-3. Supplying power to the M-NET transmission lines
PAC-YG50ECA has a built-in function to supply power to the M-NET transmission line. (power supply coefficient: 6)
When power is supplied from PAC-YG50ECA , the types of system controllers listed in the table below are connectable.
Table 1 Power consumption coefficient of the controller
System controllerM-NET remote controller
System remote controller
ON/OFF remote controller
10.50.25
Table 2 No. of connectable units
System controllerM-NET remote controller
ON/OFF remote controller
6 units12 units24 units
Table 3 No. of connectable units in systems with various combinations of remote controllersV: connectable
Total number of system remote controllers,
schedule timers, and group remote
controllers combined.
Schedule timer
Group remote controller
System remote controller
Schedule timer
Group remote controller
0VVVVVVV
1VVVVVV
2VVVVVV
3VVVVV
4VVVVV
5VVVV
6VVVV
7VVV
8VVV
9VV
10VV
11V
12V
ME remote controller
LOSSNAY remote controller
ME remote controller
LOSSNAY remote controller
Total number of ON/OFF remote controllers
0123456
Note When PAC-YG50ECA is connected to M-NET system, AG-150A/G(B)-50A cannot be connected to the same
M-NET system.
- 6 -
Page 7
2System configuration
The figure below only shows the transmission line connections. Power supply lines are omitted.
Do not connect directly to the Internet. When
connecting to the Internet through the AG-150A
etc., use a security device such as a VPN router.
PC for centralized control
(TG-2000A)
HUB
HUB
LAN
LAN
Each unit can control up to a total of 2000 indoor, LOSSNAY, and other units.
LAN
LAN
M-NET
24VDC
Each AG-150A unit can control up to a total of 150 indoor, LOSSNAY, and other units (when used with three
expansion controllers).
24VDC
AG-150A
M-NET
PAC-YG50ECA
PAC-SC51KUA
Outdoor unit
ME remote controller
M-NET
Indoor unit
M-NET
LOSSNAY
unit
HUB
AG-150A
Outdoor unit
ME remote controller
M-NET
PAC-YG50ECA
Outdoor unit
ME remote controller
M-NET
PAC-YG50ECA
Each AG-150A unit can control up to a total of 50 indoor, LOSSNAY, and other units (without the use of
expansion controllers).
LOSSNAY
unit
LOSSNAY
unit
M-NET
Outdoor unit
24VDC
ME remote controller
M-NET
M-NET
M-NET
Indoor unit
Indoor unit
LOSSNAY
unit
Indoor unit
LOSSNAY
unit
LOSSNAY
unit
LOSSNAY
unit
LOSSNAY
unit
PAC-SC51KUA
- 7 -
Page 8
Address setting for various devices:The same address cannot be used more than once within the same system of the expansion
controller (PAC-YG50ECA). (K-control units and K-control remote control addresses are excluded.)
Address setting method
Indoor unit
Outdoor unit
Auxiliary outdoor unit
(BC controller etc.)
OA processing unit/
LOSSNAY
Mr.Slim outdoor unit
M-NET remote controller
MA remote controller
Sub system controller
DIDO controller
(PAC-YG66DCA)
PI controller
(PAC-YG60MCA)
AI controller
(PAC-YG63MCA)
K-control indoor unit
K-control remote
controller
K-transmission converterAssign an address that equals the lowest K-control indoor unit address plus 200.201 ~ 250
Assign the lowest address to the main indoor unit in the group, and assign sequential
addresses to the rest of the indoor units in the same group.
Assign an address that equals the lowest indoor unit address in the same refrigerant
group plus 50.
Assign an address that equals the address of the outdoor unit in the same refrigerant
system plus 1.
Assign an arbitrary but unused address to each of these units after assigning an
address to all indoor units.
Make the settings in the same way as with the indoor units. Requires an M-NET
adapter (sold separately).
Assign an address that equals the address of the main indoor unit with the lowest
address in the group plus 100.
Add 150 in stead of 100 to set the address for a sub remote controller.
Address setting is not required.
Connection of two remote controllers requires the main/sub setting for each
controller to be made.
Assign an address that equals the group number of the smallest controlled group
plus 200.
Assign an arbitrary but unused address to the controller after completing the address
setting for the units with an address between 1 and 50.
The number of controllable units changes with the number of channels used.
Assign an arbitrary but unused address to the controller after completing the address
setting for the units with an address between 1 and 50.
Assign an arbitrary but unused address to the controller after completing the address
setting for the units with an address between 1 and 50.
Assign an address to all indoor units connected to the M-NET lines (incl. LOSSNAY
units) first, and then assign addresses to the K-control indoor units, starting with the
address after the last address.
Assign an address as the lowest address of the K-control indoor units in the same
group.
M-NET
address
1 ~ 50
51 ~ 100
52 ~ 100
1 ~ 50
1 ~ 50
101 ~ 200
–
201 ~ 250
1 ~ 50
1 ~ 50
1 ~ 50
1 ~ 50
1 ~ 50
Important Check that the setting for the central control switch SW2-1 on the M-NET outdoor unit is set to “ON.”
(Refer to the outdoor unit Installation Manual for the detailed information about dip switch settings.)
Note the following when using a K-transmission converter (model: PAC-SC25KAA) to control the K-control units.
Refer to the K-transmission converter Installation Manual for details.
1 Be sure to set the PAC-YG50ECA address to “000.”
2 Set the “K-transmission converter connection setting” (to be set from a Main controller) to ON (with a
connection to K-transmission converter).
When this setting is set to ON, an address field will appear. Enter the K-transmission converter address in the
field.
3 Assign addresses to the K-control air conditioners so that they are larger than the addresses that are
assigned to the M-control indoor units.
4 Make the group settings for K-control units so that the group number equals the lowest address of the indoor
units within the group.
5 If the K-control Y series units and other types of units (K-control Mr. Slim) are used in combination, a relay
board is required. The K-control Y series of units and other types of units cannot be connected to the same
transmission line.
6 A relay board may be required, depending on the number of K-control units and the length of transmission
lines. Refer to the System Design Manual (control version) for details.
7 LOSSNAY units that are connected to the general K-control kit cannot be connected.
8 Remote controller addresses is not required in the group setting for the K-control models.
NoteA-control jet burner models cannot be controlled.
Some models cannot be controlled.Main system controllers, such as the AG-150A, cannot be connected to a M-NET system that is controlled by the
expansion controller.
- 8 -
Page 9
* Main and Sub system controllers (M-NET)
PAC-YG50ECA can be used only as the Main controller, not as a Sub controller.
Main system controller (Main SC)
Main SC refers to a controller that controls all other system controllers including the units they control. If a given system
has only one system controller, that controller becomes a Main controller. Group settings and interlock settings can be
made only from a Main controller.
Sub system controller (Sub SC)
Sub controller refers to a system controller that is controlled (including the units it controls) by a Main system controller.
PAC-YG50ECA
Main SC’s control range (M-NET)
Sub SC’s control
range
GroupGroup
Group
PAC-YG50ECA is exclusively for use as a Main SC. It cannot be used as a Sub
SC or controlled from a Main SC.
Note Groups that are not under the control of a Main controller cannot be controlled from a Sub controller.
Main SCSub SC
GroupGroupGroup
Each group cannot be placed under the control of two or more Main controllers.
Main SC 1Main SC 2
GroupGroupGroup
Sub controllers cannot be placed under the control of two or more Main controllers.
Main SC 1Sub SCMain SC 2
GroupGroupGroupGroup
- 9 -
Page 10
3Installation
3-1. Field-supplied parts
The following parts are required to install the unit.
Required partsSpecification
Power cable/
protective earth cable
M-NET transmission line
Ring terminal (with a
sleeve)
ScrewHave four M4 screws ready to install the unit.
LAN cableCategory 5 or above straight cable (Maximum 100m (328 ft))
HUBSwitching HUB (communication speed: 100 Mbps or faster is recommended.)
Power supply cable of appliances shall not be lighter than design 245 IEC 57 or 227 IEC 57.
Cable size: 0.75mm² to 2mm²
Shielded cable
• CPEVS: φ1.2mm to φ1.6mm
• CVVS:1.25mm² to 2mm²
M3.5 terminal (used with the power cable (L/L1, N/L2), M-NET transmission line (A, B, S))
M4 ring terminal (used with the protective earth cable)
Overcurrent breaker and
Residual Current Circuit
Breaker (RCCB)
Overcurrent breakerResidual Current Circuit
FuseCircuit breaker
Rated current: 3A
*1 Use a Circuit breaker and a Residual current circuit breaker (RCCB) of bipolar type (2P2E).
Use a breaker with the minimum contact distance of 3 mm (
*2 When using a fuse, use it in combination with a main switch (Rated current: 3A).
*2
Rated current: 3A
*1
Breaker (RCCB)
Rated current: 3A
Rated sensitivity current: 30mA
Maximum operation time:
0.1 sec or less
1
/8 in.).
*1
- 10 -
Page 11
3-2. M-NET transmission line length
• Connect the PAC-YG50ECA to the transmission line for centralized control (TB7 on the outdoor unit).
• There should only be one power supply source within a single transmission circuit. The factory setting is to supply power
from PAC-YG50ECA.
•
Provide an earth for the indoor-outdoor transmission lines at one single outdoor unit.
• Maximum line distance500 m (1640 ft)
• Maximum power supply distance200 m (656 ft)
Maximum power supply distance is the distance in which a power supply unit (or an outdoor unit designated as a power
supply unit) is capable of supplying power to other units on the receiving end, such as remote controllers and indoor
units.
*1
*1
Wiring example
LAN
Expansion
Controller
(PAC-YG50ECA)
M-NET transmission line
(Transmission line for
centralized control)
M-NET transmission line
(indoor-outdoor
transmission line)
(3) Power supply distance for the centralized control transmission lines
1 L1 + L2 200m (656 ft)
2 L1 + L3 200m (656 ft)
CAUTION
*1 The ME remote controller wiring length ( 3, 8) should be 10 m (32 ft) or less.
The length that exceeds 10 m (32 ft) needs to be included in the maximum distance to the farthest unit (500 m (1640 ft)) and
in the maximum power supply distance (200 m (656 ft)).
*2 If the ME remote controller wiring length ( 3, 8) is 10 m (32 ft) or less, it does not need to be included in the maximum
distance to the farthest unit.
- 11 -
Page 12
3-3. Installation
• Leave enough space around the unit as shown in the figure below to allow for an installation/uninstalltaion of the cover and
wiring.
• Screw down the cover with M4 screws as shown in the figure below.
Be sure to screw down the four corners to prevent it from falling.
• Install on the control panel whose effective depth is 105 mm (4-
20 (13/16)20 (13/16)
3
/16 in.) or more.
/16)
13
20 (
50 (2)
* Refer to section for the product dimensions and weight.
Properly install the unit on a stable, load-bearing surface.
1Specifications
Important :
Unit installed on an unstable surface may fall and cause injury.PAC-YG50ECA is not water-proof.
Be sure to install it inside the control panel.
Be sure to install it inside the control panel. Be sure to
install in an area where there is no possibility of dew
condensation.
Unit: mm (in.)
- 12 -
Page 13
4Wiring connections
WARNING• Electric work must be performed by an authorized technician. Improper wiring work may result in electric
shock or fire.
• Turn off the power supply before performing wiring work.
CAUTION• To avoid damage to the terminal block, do not connect an AC power supply (100-240VAC) to the M-NET
transmission terminal block.
4-1. Installing and uninstalling the cover
Unscrew the two screws on the cover to remove it as shown in the figure below.
Reinstall the cover using the two screws that were unscrewed.
4-2. Connecting the power cable and protective earth cable
To prevent overheating and fire, properly fix the cables in place so that the weight of the cables will not strain the
connectors.
Improperly connected cables may break, produce heat, and cause smoke or fire.
• Connect the power cable and the protective earth cable as shown in the figure below.
• Use an M3.5 ring terminal to the power cable and an M4 ring terminal to the protective earth cable before connecting them to
their corresponding terminals (power supply terminal block or protective earth terminal).
• Secure cables with cable clamps.
• Install an overcurrent breaker and a residual current circuit breaker for the power cable. Use a bipolar breaker (2P2E) with a
minimum contact distance of 3 mm (
Power supply
100-240VAC
50Hz/60Hz
B
B Residual current circuit breaker
A Overcurrent breaker*1
*1 When using a fuse, use it in combination with a main switch (Rated current: 3A).
1
A
Earth
/8 in.).
Power cable
Protective earth cable
TB1
L/L1 N/L2
Power cable
Protective
earth
terminal
Protective
earth cable
Cable
clamps
- 13 -
Page 14
4-3. Connecting the M-NET transmission line
CN41
CN40
OFF
CN41
OFF
CN41
CAUTION • In an air conditioner system has more than 1 Outdoor units, System controller receiving transmission power
through TB7 on one of the Outdoor unit would have a risk that the connected Outdoor units failure would stop
power supply to System controller, and disrupt the whole system.
(1) To supply power to the M-NET transmission line from the expansion controller (PAC-YG50ECA)
Connect the M-NET transmission lines as shown in the figure below.
Outdoor unit
Expansion controller
(PAC-YG50ECA)
OFF
OFF
ONONON
TB3
ABS
CN41
CN40
CN40
M-NET
TB7TB3
CN40CN41
CN41
CAUTION• Connect the power jumper of PAC-YG50ECA to
CN40 (supplies power).
Connect the power jumper of the outdoor unit
to CN41 (does not supply power).
• Use specified transmission lines, and connect
them to the appropriate terminals. Secure the
cables to keep undue force from being applied.
Improper connections or failure to properly secure
cables may result in overheating and fire.
*1 Insulate the cables with vinyl tape, except the part
that connects to the ring terminal.
(2) To supply power to the M-NET transmission line from the power supply unit (PAC-SC51KUA, etc.)
Connect the M-NET transmission lines as shown in the figure below.
Power supply unit
(PAC-SC51KUA, etc.)
Outdoor unit
Expansion controller
(PAC-YG50ECA)
M-NET
TB7TB3
CN40CN41
CAUTION• Connect the power jumper of the PAC-
TB3
OFF
OFF
ONONON
CN41
CN41
CN40
YG50ECA to CN41 (does not supply power).
Connect the power jumper of the outdoor unit
to CN41 (does not supply power).
• Use specified transmission lines, and connect
them to the appropriate terminals. Secure the
cables to keep undue force from being applied.
Improper connections or failure to properly secure
cables may result in overheating and fire.
ABS
CN41
- 14 -
*1 Insulate the cables with vinyl tape, except the part
that connects to the ring terminal.
Page 15
4-4. Connecting the LAN cable
Connect the LAN cable to the LAN connector on the PAC-YG50ECA.
• Connect the PAC-YG50ECA and AG-150A via a HUB.
• The maximum distance between the HUB and PAC-YG50ECA is 100 m (328 ft).
• The LAN cable is field-supplied. Use a category 5 or above cable (straight cable).
• Use the switching HUB.
• Do not connect more than four devices (gateway, router, layer 3 switch, HUB, and etc.) in series between AG-150A and
PAC-YG50ECA. (Transmission delay time must not exceed 2 seconds.)
LAN
HUB
LANLAN
Expansion controller
(PAC-YG50ECA)
CAUTION • Install the LAN cable before installing the unit, and route the cable in the same way as the M-NET transmission
lines.
• Leave enough space around the LAN port on the PAC-YG50ECA to allow for the connection of the connector
and the cables. Refer to section .
3Installation
AG-150A
- 15 -
Page 16
5Initial settings
Introduction
Controllers with different DB numbers cannot be connected to each other.
Be sure to check the DB numbers of each controller to be connected.
Refer to “Important” (page 4) and to check the DB No..
Initial setting procedures
StepsSetting items
IP address of the expansion controller/Network
Default settings:
1
IP address 192.168.1.211
Subnet mask255.255.255.0
Gateway address0.0.0.0
2IP address for the AG-150A etc. and network
3Input IP address of expansion controller
M-NET address setting for the expansion controller
4
Default: 00
Normally requires no setting changes.
Functions
5
(Operation prohibit range setting, external input
mode etc.)
6Group
7Interlocked ventilation
Test run
8
* Refer to the AG-150A Instructions Manual, Technical Manual, and other related manuals for the detailed information about the
initial settings and operation methods.
10 7-segment LED
Controllers: Settable
Expansion controller
(PAC-YG50ECA)
Refer to section 5-1 “IP address and
network settings.”
*2
Refer to section
9
Detail setting switch setting method
*2
Refer to section 6-1 “Batch operation/
Stop (error reset) switches.”
AG-150A etc.
*1
*1
*1
*1
*1: To be set from the main AG-150A or other controllers.
*2: It is recommended that this item be set from the AG-150A or other controllers.
Internal layout of the expansion controller
7-segment LED
MAIN Board
Switch Board
TB1
SW601
Detail setting switch
(Use to select items)
SW605
Detail setting switch
(Use to save the settings)
SW606, SW607
Detail setting switch
TB3
M-NET Board
(Use to select values and items to be displayed on the LED)
USB
SW604
SW604
Function setting switch
SW603
Function setting switch
SW602
Quick IP address setting switch
- 16 -
Page 17
5-1. IP address and network settings
5-1-1. Quick IP address setting switch
IP address can be easily set to an address between 192.168.1.211 and 192.168.1.225 with dipswitch SW602. Set this
dipswitch before turning on the power.
Use the detail setting switch to set the IP address, subnet mask, and gateway address.
255.255.255.00.0.0.0
Note If fifteen or fewer expansion controllers are connected to a dedicated network, it is recommended that the IP
address be set with SW602 on the PAC-YG50ECA.
Turn all SW602 to OFF before setting the IP addresses with the detail setting switch (refer to section 5-1-2).
5-1-2. Setting the M-NET address, IP address, or network settings with the detail setting switches
M-NET address, IP address, subnet mask, or gateway address can be set with dipswitch SW601, rotary switches SW606 and
607, and push switch SW605. Quick IP address setting switches (SW602) should be set to “ALL OFF” to make these settings.
Consult the network administrator for how to set the IP address, subnet mask, and gateway address when connecting the
expansion controller to an existing LAN.
Refer to section for how to set the switches.
9Detail setting switch setting method
- 17 -
Page 18
5-1-3. IP address and network setting examples
1 Connecting to a dedicated LAN system
If fifteen or fewer expansion controllers are connected to a dedicated network, it is recommended that the IP address be
set with SW602 on the PAC-YG50ECA.
IP address:192.168.1.1
Subnet mask: 255.255.255.0
Gateway:0.0.0.0
2 Connecting to an existing LAN system
Consult the network administrator for how to set the IP address, subnet mask, and gateway address
when connecting the expansion controller to an existing LAN.
IP address:192.168.1.211
Subnet mask: 255.255.255.0
Gateway:0.0.0.0
Backbone LAN
IP address:192.168.1.212
Subnet mask: 255.255.255.0
Gateway:0.0.0.0
IP address:192.168.1.213
Subnet mask: 255.255.255.0
Gateway:0.0.0.0
IP address:10.1.1.1
Subnet mask: 255.255.255.0
Gateway:10.1.1.250
IP address:10.1.1.101
Subnet mask: 255.255.255.0
Gateway:10.1.1.250
IP address:10.1.2.41
Subnet mask: 255.255.255.0
Gateway:10.1.2.250
IP address:10.1.2.51
Subnet mask: 255.255.255.0
Gateway:10.1.2.250
Important Install the LAN cable before installing the unit, and route the cable in the same way as the M-NET
transmission lines.
Consult the network administrator for how to set the IP address, subnet mask, and gateway address when
connecting the expansion controller to an existing LAN. Use a router etc. between the existing LAN and the
MITSUBISHI products so that they are not connected directly.
Use the switching HUB.Do not connect more than four devices (gateway, router, layer 3 switch, HUB, and etc.) in series between
AG-150A and PAC-YG50ECA.
- 18 -
Page 19
5-2. Function setting
5-2-1. Operation prohibit range setting (To be set from the AG-150A or other controllers)
Set this switch to prohibit operation from both the Sub system controller and remote controller OR only from the remote
controller.
SettingFunction
SC·RC
(Factory setting)
RC OnlyOperation only from the remote controller will be prohibited.
Operation from both the Sub controller and remote controller will be prohibited.
* Normally, this setting should be selected.
5-2-2. External input mode (To be set from the AG-150A or other controllers)
Set the external input mode.
Refer to section .
SettingFunction
Do not use
(Factory setting)
Emergency Stop
(Level signal)
ON/OFF (Level signal)Run/Stop (level signal)
ON/OFF/Prohibit/Permit
(Pulse signal)
8External input/output
External input signal will not be used.
Emergency stop/ Normal (level signal)
Run/Stop, Prohibit/Permit (pulse signal)
5-2-3. Prohibiting connection of AG-150A and other controllers (SW603-4)
Set SW603-4 to ON to disallow connection of AG-150A etc. and other controllers. Set the switch after the completion of a test
run.
Accidental connection of AG-150A etc. that should be connected to other systems can be prevented by making the setting that
disallows the connection of additional controllers, thus preventing negative impact on the operation of the air conditioners
(unintended operation, abnormal stop etc.)
SW603-4Function
OFF
(Factory setting)
ON
(At the completion of a test run)
Allows connection of AG-150A and other controllers
Disallows connection of AG-150A and other controllers
- 19 -
Page 20
6Test run
6-1. Batch operation/Stop (error reset) switches
• Before performing a test run, check that the group setting and interlock settings from the AG-150A and other controllers have
been properly made.
• The batch operation function on the PAC-YG50ECA cannot be used to change the operation mode of the connected indoor units
(including the test run mode). Units will be operated in the mode they are set to operate in. The PAC-YG50ECA does not have
the function to automatically stop the test run in two hours as the remote controllers do.
<Setting procedures>
1 Turn on all units and the PAC-YG50ECA.
2 Set the switches as follows. SW601: All set to OFF; SW606: “0”; SW607: “0”
3 Check that LD5 on PAC-YG50ECA is unlit (SW601: All set to OFF; SW606: “0”; SW607 “0”).
LD5 will be lit if the group setting and interlock setting from the AG-150A and other controllers have not been completed.
LD5 will blink while M-NET is starting up (takes approx. 10 minutes to complete).
Turn SW603-1 from the OFF position to the ON position. The operation signal will be sent to the groups that are registered.
4
5 LD3 (SW601: All set to OFF; SW606: “0”; SW607 “0”) will be lit when the units are in operation.
6 Check each unit for proper operation (e.g., supply air comes out of the indoor unit outlet.).
7 Turn SW603-2 from the OFF position to the ON position to bring the units to stop.
8 Turn SW603-1 and SW603-2 to OFF at the completion of the test run.
SW603Function setting
1
2
Transmission of operation run signal to the registered groups (when turned ON from the OFF position)
Transmission of operation stop signal to the registered groups (when turned ON from the OFF position)
*1 The equipment connected to DIDO controller cannot be operated. Refer to the appropriate manual for details.
6-2. Service LED display
PAC-YG50ECA has service LEDs to display the operation status.
LED No.ItemStatusNotes
LANLANLINKLitLinking
ACTUnlitNot linked
BlinkTransmitting
M-NETM-NETLitPowered
UnlitNot powered
BlinkM-NET transmission in progress
ErrorError statusBlink
7-
LD1CPU statusLitNormal
segment
LED
LD2(Not assigned)
LD3Operation statusLitAt least one air conditioning unit is in
LD4Error statusLit
LD5M-NET startup statusLitGroup information not available
LD6(Not assigned)
LD7Number of connected
AG-150A and other
LD8
controllers
*1 Error LED and LD4 will not be lit/blink when the AG-150A or other controllers are in error.
Number of connected AG-150A and other
controllers (Numerical display)
At least one air conditioning unit is in error*1
UnlitNormal
UnlitError
operation.
UnlitAll units are stopped.
At least one air conditioning unit is in error*1
UnlitAll units are normal.
UnlitComplete
BlinkStarting up
SW601: All set to off
SW606: [0]
SW607: [0]
(Refer to section 10
10 7-segment LED
information on how other settings
are displayed.)
*1
*1
for
*1
7-segment LED
LD2
LD1
LD3
LD4LD5
- 20 -
LD6LD7LD8
Page 21
7M-NET system setting example
1 Connecting multiple M-NET system controllers
LAN
AG-150A
etc.
HUB
Make the initial group and interlock settings from the AG-150A or other controllers.Designate a system controller within the system as the only controller from which operation prohibit setting can be made.
PAC-YG50ECA
“000”
(Main system controller)
ON/OFF remote
controller
“201”
(Sub system controller)
M-NET
50 indoor units
Group 1 - Group 20
2 Controlling the K-control models
LAN
AG-150A
etc.
HUB
Set the PAC-YG50ECA address to “000” when connecting a K-transmission converter.When making the group setting for K-control units, make the setting only for the indoor units that belong to a given group.The group number given to a group of K-control units should be the same as the lowest address of the indoor units that belong to
the group.
If the K-control Y series units and other types of units (K-control Mr. Slim) are used in combination, a relay board is required.
The K- control Y series units cannot be connected to the same transmission lines as the other types of units.
Depending on the number of K-control units and transmission line length, a relay board may be required. Refer to the System
Design/Manual (control version) for details.
LOSSNAY units cannot be connected if they are connected to the K-control kit.Remote controller addresses do not need to be included in the group setting for a group of K-control units.
PAC-YG50ECA
“000”
(Main system controller)
M-NET
“221”
K-transmission converter
(Model: PAC-SC25KAA)
20 indoor units
Group 1 - Group 20
20 K-control indoor units
Group 21 - Group 38
- 21 -
Page 22
8External input/output
8-1. External signal input function
* To use the external signal input, a separately-sold external input/output adapter (PAC-YG10HA) is required.
External input/output terminal (CN5)
8-1-1. External input signal function setting (to be set from the AG-150A or other controllers)
External contact signal (12VDC or 24VDC) can be used to send signals indicating the following status of all air conditioning
units that are controlled by the controller: Emergency stop/Normal, Run/Stop, and local remote controller operation Prohibit/
Permit.
No.External input signal function Notes
External input signal will not be used.
1
(factory setting)
While the units are stopped due to an error, the Run/Stop mode cannot be
2
Emergency stop/Normal (level signal)
3
Run/Stop (level signal)
4
Run/Stop, Prohibit/Permit (pulse signal)The pulse width (contact ON) should be between 0.5 and 1 second.
changed from the local remote controller, and the Run/Stop mode and
Prohibit/Permit settings cannot be changed from the PAC-YG50ECA. Timer
setting will be ignored.
The Run/Stop mode cannot be changed from the local remote controller,
and the Run/Stop mode and Prohibit/Permit settings cannot be changed
from the PAC-YG50ECA. Timer setting will be ignored.
1 If “Emergency stop/Normal operation signal” is selected, the unit will come to an emergency stop when the contact
turns on, and the unit will resume normal operation when the contact turns off. When emergency stop is reset, all units
will remain stopped, including the ones that were operating before the emergency stop signal input was received. To
return to the previous operation status, these units need to be manually restarted.
2 If “Run/Stop signal input” is selected, the unit will go into operation when external input signal contact turns ON, and the
unit will stop when the contact signal turns OFF.
Emergency stop/Normal
(level signal)
signal input
Run/Stop
(level signal)
Run/Stop signal inputOperation signal input
prohibit signal input
permit signal input
0.5 - 1 second
0.5 - 1 second
Emergency stop
StopStop
Run/Stop, Prohibit/Permit
(pulse signal)
- 22 -
Page 23
(B) Pulse signals
1 If pulse signals to operate the units are received while the units are in operation, the units will continue their operation
(same with the Stop, Prohibit, and Permit signals).
2 When operation from the local remote controllers is prohibited, Run/Stop mode, operation mode, temperature setting,
and filter reset settings cannot be changed from the local remote controller.
3 The pulse width (contact ON) should be between 0.5 and 1 second.
8-1-4. Recommended circuit
(A) Level signals
9
8
7
6
5
1
Red
Orange
Maximum
10m(32ft)
X1
Run/Stop or Emergency stop
Power supply
X1
(12VDC or 24VDC)
(*1)
Use relays that meet the following specifications for X1, X2, Y1, and Y2.
Contact rating
Rated voltage: 12VDC or above
Rated current: 0.1 A or above
CN5
PAC-YG50ECA
(B) Pulse signals
Minimum applied load: DC 1 mA or below
CN5
9
8
7
6
5
1
PAC-YG50ECA
Red
Gray
Blue
Yel lo w
Orange
Maximum
10m(32ft)
Power supply
Y2
Y1
X2
X1
(*1)
(12VDC or 24VDC)
X1
Run Stop Prohibit Permit
Y2
Y1
X2
1 Relays, DC power supplies, and extension cables are field supplied.
2 The maximum length of extension cable is 10 m (32 ft). (Use a cable with a diameter of at least 0.3 mm2.)
3 Cut the excess cable near the connector, and insulate the exposed cable end with tape.
8-2. External signal output function
* A separately sold external input/output adapter (PAC-YG10HA) is required to use the external signal output.
8-2-1. External output
Operation signal is output when one or more units are in operation, and error signal is output when one or more units are in
(*1)
error
*1: Error signal is not output when the AG-150A or other controllers are in error.
.
8-2-2. External output specification
CN5
No. 1GreenCommon GND for external output (external DC, power supply GND)
No. 2BlackRun/Stop
No. 3BrownError/Normal
1 Operation signal is output during an error.
Lead wire
(PAC-YG10HA)
8-2-3. Recommended circuit
With relays
CN5
9
(*2)
4
Brown
3
Black
2
Green
1
Maximum
PAC -YG5 0EC A
10m(32ft)
1 Each element turns on during operation and error.
2 The maximum length of extension cable is 10 m (32 ft).
3 Relays, lamps, diodes, and extension cables are field supplied.
Diode
Z1
Power supply
(*1)
Z1L1
Z2
Z2L2
L1 : Operation indicator
L2 : Error indicator
Terminal type
Use relays that meet the following specifications for Z1 and Z2.
Operation coil
Rated voltage: 12VDC or 24VDC
Power consumption: 0.9 W or less
(*1) Use a power supply suitable for the type of relays used.
(12VDC or 24VDC)
(*2) Use a diode at both ends of the relay coils.
- 23 -
Page 24
9Detail setting switch setting method
IP address and other settings can be made with the detail setting switches on the PAC-YG50ECA.
SW601
NO
160 0 0 1 0 0 0 0 IP address a192
170 0 0 1 0 0 0 1b168
180 0 0 1 0 0 1 0c1
190 0 0 1 0 0 1 1d211
200 0 0 1 0 1 0 0 Subnet maska255
210 0 0 1 0 1 0 1b255
220 0 0 1 0 1 1 0c255
230 0 0 1 0 1 1 1d0
240 0 0 1 1 0 0 0 Gatewaya0
250 0 0 1 1 0 0 1b0
260 0 0 1 1 0 1 0c0
270 0 0 1 1 0 1 1d0
650 1 0 0 0 0 0 1
250 1 1 1 1 1 0 1 0
251 1 1 1 1 1 0 1 1
[0: OFF, 1: ON]
1 2 3 4 5 6 7 8
Setting items
M-NET
address
Initial setting
data
Copy to USB
memory
Initial setting
data
Read from
USB memory
Factory
setting
00
–
–
IP address
a.b.c.d
(Factory setting: 192.168.1.211)
M-NET address
00, 201 to 250
(Factory setting: 00)
Set to SW606: “0”; SW607: “0”
Copy the setting data to the \[“EC_” +
Serial Number]\ folder in the root folder
of the USB memory.
Set to SW606: “0”; SW607: “0”
Read the setting data from USB memory.
Create [“SetupData_” + IP address]*
folder in the root folder of the USB
memory using PC. Save the setting data
in the folder.
*1: When the IP address of PACYG50ECA is “192.168.1.211”, the folder
name will be
[SetupData_192_168_1_211].
ExplanationNotes
Set all SW602
to OFF.
Reset the power
after all settings
have been
made.
Reset the power
after all settings
have been
made.
1
Reset the power
after all settings
have been
made.
Note: The following types of USB memory are recommended. (As of Apr. 2009)
a: Manufacturer: SandiskModel: SDCZ6-2048-J65RB Memory size: 2G
b: Manufacturer: KingstonModel: DT400/2GBFEMemory size: 2G
c: Manufacturer: I-O DATAModel: TB-BH2/2G/*Memory size: 2G
d: Manufacturer: BUFFALO Model: RUF-C2GS-**/U2Memory size: 2G
e: Manufacturer:adataModel: C702Memory size: 2G
(* or ** in the models of c and d indicates color.)
- 24 -
Page 25
9-1. Switch setting
How to set the switches is explained below, using an example of how to set No. 16 “IP address a” to “197 (C5 in hexadecimal
notation).”
Use hexadecimal notation to set the values using switches SW606 (upper digit) and SW607 (lower digit).
The LED display is in decimal notation.
StepsSetting itemSetting method7-segment LED display
Select the item No. Set SW601 to [0001 0000].[ _ 016] will appear for one second, and the
1
Enter a value.Set SW606 (upper digit) to “C”, and SW607
2
Save the setting.Press and hold SW605 for three seconds.[ End] will appears after [ 197] blinks.
3
(lower digit) to “5”.
Important Refer to section 10-1 “7-segment LED display and switch settings,” and check that the switches are set
correctly.
SW606 and SW607 preset values will
appear.
[ 197]
Reset the setting when [ Err_ ] is displayed.
TB3
Switch Board
M-NET Board
7-segment LED
MAIN Board
TB1
SW601
Detail setting switch
(Use to select items)
SW605
Detail setting switch
(Use to save the settings)
SW606, SW607
Detail setting switch
(Use to select values and items to be displayed on the LED)
USB
SW604
SW604
Function setting switch
SW603
Function setting switch
SW602
Quick IP address setting switch
- 25 -
Page 26
10 7-segment LED
The settings for switches SW601, SW606, and SW607 on the PAC-YG50ECA can be verified on the 7-segment LED.
Numerical display
(Example: 18.8)
Flag display
(Example: LD1, LD2, LD5, and LD7 are on.)
7-segment LED
SW601
Detail setting switch
(Use to select items)
SW605
Detail setting switch
(Use to save the settings)
SW606, SW607
Detail setting switch
(Use to select values and items to be displayed on the LED)
LD1
LD2
LD4LD5
LD3
SW604
Function setting switch
SW603
Function setting switch
SW602
Quick IP address setting switch
LD6LD7LD8
<Bringing up the DB No. on the 7-segment LED on the expansion controller>
On the switch board, set SW601 to “All OFF”, SW606 to “2,” and SW607 to “5.”
The DB No. will appear on the 7-segment LED on the expansion controller.
Refer to the following pages for other displays and switch settings.
- 26 -
Page 27
10-1. 7-segment LED display and switch settings
SW601
1234 5678
0000 0000
0: OFF
1: ON
SW606 SW607
00
01
Expansion controller statusCPU
Error detection[Error code] and [Error source address] appear alternately. The latest error appears if multiple
*1 ECL error: Error between the AG-150A etc. and expansion controller (PAC-YG50ECA)
NOTE:
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to
Part 15 of the FCC Rules. These limits are designed to provide resonable protection against harmful
interference in a residential installation. This equipment generates, uses and can radiate radio frequency
energy and, if not installed and used in accordance with the instructions, may cause harmful interference to
radio communications.
However, there is no guarantee that interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception, which can be determined
by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more
of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio / TV technician for help.
- 33 -
Page 34
Page 35
Page 36
This product is designed and intended for use in the residential,
commercial and light-industrial environment.
The product at hand is
based on the following
EU regulations: