MELDAS is a registered trademark of Mitsubishi Electric Corporation.
Other company and product names that appear in this manual are trademarks or registered
trademarks of their respective companies.
Introduction
Thank you for selecting the Mitsubishi numerical control unit.
This instruction manual describes the handling and caution points for using this AC
servo/spindle.
Incorrect handling may lead to unforeseen accidents, so always read this instruction
manual thoroughly to ensure correct usage.
Make sure that this instruction manual is delivered to the end user.
Always store this manual in a safe place.
In order to confirm if all function specifications described in this manual are applicable,
refer to the specifications for each CNC.
Notes on Reading This Manual
(1) Since the description of this specification manual deals with NC in general, for the
specifications of individual machine tools, refer to the manuals issued by the
respective machine manufacturers. The "restrictions" and "available functions"
described in the manuals issued by the machine manufacturers have precedence
to those in this manual.
(2) This manual describes as many special operations as possible, but it should be
kept in mind that items not mentioned in this manual cannot be performed.
Precautions for safety
Please read this manual and auxiliary documents before starting installation, operation,
maintenance or inspection to ensure correct usage. Thoroughly understand the device, safety
information and precautions before starting operation.
The safety precautions in this instruction manual are ranked as "WARNING" and "CAUTION".
Note that some items described as
the situation. In any case, important information that must be observed is described.
The signs indicating prohibited and mandatory matters are explained below.
DANGER
WARNING
CAUTION
When there is a potential risk of fatal or serious injuries if
handling is mistaken.
When a dangerous situation, or fatal or serious injuries may
occur if handling is mistaken.
When a dangerous situation may occur if handling is mistaken
leading to medium or minor injuries, or physical damage.
CAUTION
may lead to major results depending on
Indicates a prohibited matter. For example, "Fire Prohibited"
is indicated as .
Indicates a mandatory matter. For example, grounding is
indicated as
.
After reading this specifications and instructions manual, store it where the user can access it
easily for reference.
The numeric control unit is configured of the control unit, operation board, servo drive unit,
spindle drive unit, power supply, servomotor and spindle motor, etc.
In this section "Precautions for safety", the following items are generically called the "motor".
• Servomotor
• Linear servomotor
• Spindle motor
In this section "Precautions for safety", the following items are generically called the "unit".
• Servo drive unit
• Spindle drive unit
• Power supply unit
• Scale interface unit
• Magnetic pole detection unit
POINT
Important matters that should be understood for operation of this machine
are indicated as a POINT in this manual.
1. Electric shock prevention
Do not open the front cover while the power is ON or during operation. Failure to observe this
could lead to electric shocks.
Do not operate the unit with the front cover removed. The high voltage terminals and charged
sections will be exposed, and can cause electric shocks.
Do not remove the front cover and connector even when the power is OFF unless carrying
out wiring work or periodic inspections. The inside of the units is charged, and can cause
electric shocks.
Since the high voltage is supplied to the main circuit connector while the power is ON or
during operation, do not touch the main circuit connector with an adjustment screwdriver o r
the pen tip. Failure to observe this could lead to electric shocks.
Wait at least 15 minutes after turning the power OFF, confirm that the CHARGE lamp has
gone out, and check the voltage between P and N terminals with a tester, etc., before starting
wiring, maintenance or inspections. Failure to observe this could lead to electric shocks.
Ground the unit and motor following the standards set forth by each country.
Wiring, maintenance and inspection work must be done by a qualified technician.
Wire the servo drive unit and servomotor after installation. Failure to observe this could lead to
electric shocks.
Do not touch the switches with wet hands. Failure to observe this could lead to electric shocks.
Do not damage, apply forcible stress, place heavy items on the cables or get them caught.
Failure to observe this could lead to electric shocks.
WARNING
2. Injury prevention
The linear servomotor uses a powerful magnet on the secondary side, and could adversely
affect pacemakers, etc.
During installation and operation of the machine, do not place portable items that could
malfunction or fail due to the influence of the linear servomotor's magnetic force.
Take special care not to pinch fingers, etc., when installing (and unpacking) the linear
servomotor.
In the system where the optical communication with CNC is executed, do not see directly the
light generated from CN1A/CN1B connector of drive unit or the end of cable. When the light
gets into eye, you may feel something is wrong for eye.
(The light source of optical communication corresponds to class1 defined in JIS C68 02 or
IEC60825-1.)
1. Fire prevention
Install the units, motors and regenerative resistor on non-combustible material. Direct
installation on combustible material or near combustible materials could lead to fires.
Always install a no-fuse breaker and contactor on the servo drive unit power input as explained
in this manual. Refer to this manual and select the correct no-fuse breaker and contactor. An
incorrect selection could result in fire.
Shut off the power on the unit side if a fault occurs in the units. Fires could be caused if a large
current continues to flow.
When using a regenerative resistor, provide a sequence that shuts off the power with the
regenerative resistor's error signal. The regenerative resistor could abnormally overheat and
cause a fire due to a fault in the regenerative transistor, etc.
The battery unit could heat up, ignite or rupture if submerged in water, or if the poles are
incorrectly wired.
Cut off the main circuit power with the contactor when an alarm or emergency stop occurs.
2. Injury prevention
Do not apply a voltage other than that specified in this manual, on each terminal. Failure to
observe this item could lead to ruptures or damage, etc.
CAUTION
Do not mistake the terminal connections. Failure to observe this item could lead to ruptures or
damage, etc.
Do not mistake the polarity (
damage, etc.
Do not touch the radiation fin on unit back face, regenerative resistor or motor, etc., or place
parts (cables, etc.) while the power is turned ON or immediately after turning the power OFF.
These parts may reach high temperatures, and can cause burns or part damage.
Structure the cooling fan on the unit back face, etc., etc so that it cannot be touched after
installation. Touching the cooling fan during operation could lead to injuries.
+
,
). Failure to observe this item could lead to ruptures or
CAUTION
3. Various precautions
Observe the following precautions. Incorrect handling of the unit could lead to faults, injuries and
electric shocks, etc.
(1) Transportation and installation
Correctly transport the product according to its weight.
Use the motor's hanging bolts only when transporting the motor. Do not transport the
machine when the motor is installed on the machine.
Do not stack the products above the tolerable number.
Follow this manual and install the unit or motor in a place where the weight can be borne.
Do not get on top of or place heavy objects on the unit.
Do not hold the cables, axis or detector when transporting the motor.
Do not hold the connected wires or cables when transporting the units.
Do not hold the front cover when transporting the unit. The unit could drop.
Always observe the installation directions of the units or motors.
Secure the specified distance between the units and control panel, or between the servo drive
unit and other devices.
Do not install or run a unit or motor that is damaged or missing parts.
Do not block the intake or exhaust ports of the motor provided with a cooling fan.
Do not let foreign objects enter the units or motors. In particular, if conductive objects such as
screws or metal chips, etc., or combustible materials such as oil enter, rupture or breakage
could occur.
The units and motors are precision devices, so do not drop them or apply strong impacts to
them.
CAUTION
Store and use the units under the following environment conditions.
Environment
Ambient
temperature
Ambient
humidity
Atmosphere
Altitude
Vibration/impact
(Note 1) For details, confirm each unit or motor specifications in addition.
(Note 2) -15°C to 55°C for linear servomotor.
Operation: 0 to 55°C (with no freezing),
Storage / Transportation: -15°C to 70°C
Operation: 90%RH or less
(with no dew condensation)
Storage / Transportation: 90%RH or less
(with no dew condensation)
With no corrosive gas, inflammable gas, oil mist, dust or conductive fine particles
Operation/Storage: 1000 meters or less above
Transportation: 13000 meters or less above sea
Unit Motor
(with no freezing)
sea level,
level
According to each unit or motor specification
Operation: 0 to 40°C (with no freezing),
Storage: -15°C to 70°C
Operation: 80%RH or less
(with no dew condensation),
Storage: 90%RH or less
(with no dew condensation)
Indoors (no direct sunlight)
Operation: 1000 meters or less above sea level,
Storage: 10000 meters or less above sea level
(Note 2)
(with no freezing)
Securely fix the servomotor to the machine. Insufficient fixing could lead to the servomotor
slipping off during operation.
Always install the servomotor with reduction gear in the designated direction. Failure to do so
could lead to oil leaks.
Structure the rotary sections of the motor so that it can never be touched during operation.
Install a cover, etc., on the shaft.
When installing a coupling to a servomotor shaft end, do not apply an impact by hammering,
etc. The detector could be damaged.
Do not apply a load exceeding the tolerable load onto the servomotor shaft. The shaft could
break.
Store the motor in the package box.
When inserting the shaft into the built-in IPM motor, do not heat the rotor higher than 130°C.
The magnet could be demagnetized, and the specifications characteristics will not be
ensured.
Always use a nonmagnetic tool (explosion-proof beryllium copper alloy safety tool: NGK
Insulators, etc.) when installing the linear servomotor.
Always provide a mechanical stopper on the end of the linear servomotor's travel path.
If the unit has been stored for a long time, always check the operation before starting actual
operation. Please contact the Service Center, Service Station, Sales Office or delayer.
(2) Wiring
CAUTION
Correctly and securely perform the wiring. Failure to do so could lead to abnormal operation of
the motor.
Do not install a condensing capacitor, surge absorber or radio noise filter on the output side of
the drive unit.
Correctly connect the output side of the drive unit (terminals U, V, W). Failure to do so could
lead to abnormal operation of the motor.
When using a power regenerative power supply unit, always install an AC reactor for each
power supply unit.
In the main circuit power supply side of the unit, always install an appropriate no-fuse breaker
or contactor for each unit. No-fuse breaker or contactor cannot be shared by several units.
Always connect the motor to the drive unit's output terminals (U, V, W).
Do not directly connect a commercial power supply to the servomotor. Failure to observe this
could result in a fault.
When using an inductive load such as a relay, always connect a diode as a noise measure
parallel to the load.
When using a capacitance load such as a lamp, always connect a protective resistor as a noise
measure serial to the load.
Do not reverse the direction of a diode
which connect to a DC relay for the
control output signals such as
Servodrive unit
COM
(24VDC)
Servodrive unit
COM
(24VDC)
contractor and motor brake output, etc.
to suppress a surge. Connecting it
backwards could cause the drive unit to
malfunction so that signals are not
Controloutput
signal
RA
Control output
signal
output, and emergency stop and other
safety circuits are inoperable.
RA
Do not connect/disconnect the cables connected between the units while the power is ON.
Securely tighten the cable connector fixing screw or fixing mechanism. An insecure fixing could
cause the cable to fall off while the power is ON.
When using a shielded cable instructed in the instruction manual, always ground the cable with
a cable clamp, etc.
Always separate the signals wires from the drive wire and power line.
Use wires and cables that have a wire diameter, heat resistance and flexibility that conforms to
the system.
(3) Trial operation and adjustment
Check and adjust each program and parameter before starting operation. Failure to do so could
lead to unforeseen operation of the machine.
Do not make remarkable adjustments and changes of paramete r a s the ope ration could
become unstable.
The usable motor and unit combination is predetermined. Always check the models before
starting trial operation.
If the axis is unbalanced due to gravity, etc., balance the axis using a counterbalance, etc.
The linear servomotor does not have a stopping device such as magnetic brakes. Install a
stopping device on the machine side.
(4) Usage methods
In abnormal state, install an external emergency stop circuit so that the operation can be
stopped and power shut off immediately.
Turn the power OFF immediately if smoke, abnormal noise or odors are generated from the unit
or motor.
CAUTION
Do not disassemble or repair this product.
Never make modifications.
When an alarm occurs, the machine will start suddenly if an alarm reset (RST) is carried out
while an operation start signal (ST) is being input. Always confirm that the operation signal is
OFF before carrying out an alarm reset. Failure to do so could lead to accidents or injuries.
Reduce magnetic damage by installing a noise filter. The electronic devices used near the
unit could be affected by magnetic noise. Install a line noise filter, etc., if there is a risk of
magnetic noise.
Use the unit, motor and regenerative resistor with the designated combination. Failure to do so
could lead to fires or trouble.
The brake (magnetic brake) of the servomotor are for holding, and must not be used for normal
braking.
There may be cases when holding is not possible due to the magnetic brake's life, the machine
construction (when ball screw and servomotor are coupled via a timing belt, etc.) or the
magnetic brake’s failure. Install a stop device to ensure safety on the machine side.
After changing the programs/parameters or after maintenance and inspection, always test the
operation before starting actual operation.
Do not enter the movable range of the machine during automatic operation. Never place body
parts near or touch the spindle during rotation.
Follow the power supply specification conditions given in each specification for the power (input
voltage, input frequency, tolerable sudden power failure time, etc.).
Set all bits to "0" if they are indicated as not used or empty in the explanation on the bits.
Do not use the dynamic brakes except during the emergency stop. Continued use of the
dynamic brakes could result in brake damage.
If a no-fuse breaker for the main circuit power supply is shared by several units, the no-fuse
breaker may not activate when a short-circuit fault occurs in a small capacity unit. This is
dangerous, so never share the no-fuse breakers.
(5) Troubleshooting
If a hazardous situation is predicted during power failure or product trouble, use a servomotor
with magnetic brakes or install an external brake mechanism.
Use a double circuit configuration
that allows the operation circuit for
the magnetic brakes to be operated
even by the external emergency
stop signal.
CAUTION
Shut off with the servomotor
brake control output.
Servomotor
Magnetic
brake
Shut off with NC brake
control PLC output.
MBR
EMG
24VDC
Always turn the input power OFF when an alarm occurs.
If an alarm occurs, remove the cause, and secure the safety before resetting the alarm.
Never go near the machine after restoring the power after a power failure, as the machine
could start suddenly. (Design the machine so that personal safety can be ensured even if the
machine starts suddenly.)
(6) Maintenance, inspection and part replacement
Always backup the programs and parameters before starting maintenance or i nspections.
The capacity of the electrolytic capacitor will drop over time due to self-discharging, etc. To
prevent secondary disasters due to failures, replacing this part every five years when used
under a normal environment is recommended. Contact the Service Center, Service Station,
Sales Office or delayer for repairs or part replacement.
Do not perform a megger test (insulation resistance measurement) during inspections.
If the battery low warning is issued, back up the machining programs, tool data and
parameters with an input/output unit, and then replace the battery.
Do not short circuit, charge, overheat, incinerate or disassemble the battery.
The heat radiating fin used in some units contains substitute Freon as the refrigerant.Ta ke
care not to damage the heat radiating fin during maintenance and replacement work.
(7) Disposal
Do not dispose of this type of unit as general industrial waste. Always contact the Service
Center, Service Station, Sales Office or delayer for repairs or part replacement.
Do not disassemble the unit or motor.
Dispose of the battery according to local laws.
Always return the secondary side (magnet side) of the linear servomotor to the Service
Center or Service Station.
When incinerating optical communication cable, hydrogen fluoride gas or hydrogen chloride
gas which is corrosive and harmful may be generated. For disposal of optical communication
cable, request for specialized industrial waste disposal services that has incineration facility
for disposing hydrogen fluoride gas or hydrogen chloride gas.
CAUTION
(8) Transportation
The unit and motor are precision parts and must be handled carefully.
According to a United Nations Advisory, the battery unit and battery must be transported
according to the rules set forth by the International Civil Aviation Organization (ICAO),
International Air Transportation Association (IATA), International Maritime Organization
(IMO), and United States Department of Transportation (DOT), etc.
(9) General precautions
The drawings given in this manual show the covers and safety partitions, etc., removed to provide a
clearer explanation. Always return the covers or partitions to their respective places before starting
operation, and always follow the instructions given in this manual.
{ Treatment of waste {
The following two laws will apply when disposing of this product. Considerations must be made to each
law. The following laws are in effect in Japan. Thus, when using this product overseas, the local laws will
have a priority. If necessary, indicate or notify these laws to the final user of the product.
1. Requirements for "Law for Promotion of Effective Utilization of Resources"
(1) Recycle as much of this product as possible when finished with use.
(2) When recycling, often parts are sorted into steel scraps and electric parts, etc., and sold to scrap
contractors. Mitsubishi recommends sorting the product and selling the members to appropriate
contractors.
2. Requirements for "Law for Treatment of Waste and Cleaning"
(1) Mitsubishi recommends recycling and selling the product when no longer needed according to
item (1) above. The user should make an effort to reduce waste in this manner.
(2) When disposing a product that cannot be resold, it shall be treat ed as a waste product.
(3) The treatment of industrial waste must be commissioned to a licensed industrial waste treatment
contractor, and appropriate measures, including a manifest control, must be taken.
(4) Batteries correspond to "primary batteries", and must be dispos ed of according to local disposal
laws.
CONTENTS
1. Introduction
1-1 Servo/spindle drive system configuration..................................................................................... 1-2
1-1-1 System configuration ............................................................................................................ 1-2
1-2 Explanation of type....................................................................................................................... 1-3
1-1 Servo/spindle drive system configuration ..........................................................................................1-2
1-1-1 System configuration...................................................................................................................1-2
1-2 Explanation of type............................................................................................................................. 1-3
2-3-4 D/A output specifications for servo drive unit..............................................................................2-8
2-3-5 D/A output specifications for spindle drive unit .........................................................................2-11
2-3-6 Explanation of each part............................................................................................................2-14
2 - 1
2. Specifications
2-1 Servomotor
2-1-1 Specifications list
HF Series
Servomotor type
HF75 HF105HF54 HF104 HF154 HF204 HF354
Compatible servo drive
unit type
Rated output [kW] 0.75 1.0 0.5 1.0 1.5 2.0 3.5
Continuous
characteristics
Rated rotation speed [r/min] 4000 3000
Maximum rotation speed [r/min] 5000 4000 3500
Maximum current [A] 14.0 15.5 16.8 29.0 52.0 52.0 64.0
Maximum torque [N·m] 8.0 11.0 13.0 23.3 42.0 42.0 65.0
Power rate at continuous
rated torque
Motor inertia [kg·cm2] 2.6 5.1 6.1 11.9 17.8 38.3 75.0
Motor inertia with brake [kg·cm2] 2.8 5.3 8.3 14.1 20.0 48.0 84.7
Maximum motor shaft conversion load
inertia ratio
Motor side detector
Structure
Environment
Weight
Without / with brake
Armature insulation class Class F
(Note 1) The above characteristics values are representative values. The maximum current and maximum torque are the values
(Note 2) Use the HF motor in combination with the MDS-D-SVJ3 Series drive unit compatible with the 200VAC input.
(Note 3) The shaft-through portion is excluded.
when combined with the drive unit.
This motor is not compatible with the conventional MDS-B/C1/CH Series.
MDS-D-SVJ3- 07 07 07 10 20 20 35
[A] 2.8 3.6 1.8 3.6 5.8 6.8 13.8
[kW/s] 12.3 11.2 4.1 8.4 12.7 10.6 16.5
High-speed, high-accuracy machine : 3 times or less of motor inertia
General machine tool (interpolation axis) : 5 times or less of motor inertia
General machine (non-interpolation axis) : 7 times or less of motor inertia
Weight [kg] 15 20 25 30 49 60 70
Insulation Class F
(Note 1)
Continuous rating
[kW]
Short time rated output
[kW]
Input voltage
Maximum power
consumption
Ambient
temperature
Ambient humidity Operation: 90%RH or less (with no dew condensation), Storage: 90%RH or less (with no dew condensation)
Atmosphere Indoors (no direct sunlight); no corrosive gas, inflammable gas, oil mist, or dust
Altitude
The rated output is guaranteed at the rated input voltage (200/220/230VAC) to the drive unit.
If the input voltage fluctuates and drops below 200VAC, the rated output may not be attained.
The 50%ED rating applies for a 10-minute cycle time consisting of ON for five minutes and OFF for five minutes.
(Note 2)
The tolerable radial load is the value calculated at the center of output shaft.
Earth leakage current [mA] 1 (Max. 2)
Main circuit method
Control method
Braking
External analog output
Structure
Cooling method
Weight
Heat radiated at rated
output
Noise
Ambient temperature Operation: 0 to 55°C (with no freezing), Storage / Transportation: -15°C to 70°C (with no freezing)
Ambient humidity
Atmosphere
Altitude Operation/Storage: 1000 meters or less above sea level, Transportation: 13000 meters or less above sea level
Vibration/impact 4.9m/s
With no corrosive gas, inflammable gas, oil mist, dust or conductive fine particles
MDS-D-SVJ3-03 04 07 10 20 35
Rated voltage [V] 200AC (50Hz) /200 to 230AC (60Hz)
Frequency [Hz] 50/60 Frequency fluctuation within ±5%
Rated current [A] 1.5 2.9 3.8 5.0 10.5 16.0
Rated voltage [V] AC155
Rated current [A] 1.5 3.2 5.8 6.0 11.0 17.0
Voltage
Frequency [Hz] 50/60 Frequency fluctuation within ±5%
Current
Rush current [A] Max.30
Operation: 90%RH or less (with no dew condensation)
Storage / Transportation: 90%RH or less (with no dew condensation)
Indoors (no direct sunlight)
2
(0.5G) / 49m/s2 (5G)
Servo drive unit MDS-D-SVJ3 Series
Power fluctuation rate within +10%, -15%
Power fluctuation rate within +10%, -15%
Converter with resistor regeneration circuit
Sine wave PWM control method
Regenerative braking and dynamic brakes
0 to +5V, 2ch (data for various adjustments)
Less than 55dB
2 - 6
2-3-3 Spindle drive unit
Spindle drive
unit type
Rated output
Power facility capacity
Input
Output
Control
power
Earth leakage current
Main circuit method
Control method
Braking
External analog output
Structure
Cooling method
Weight
Heat radiated at
continuous rated output
Noise
MDS-D-SPJ3-075 22 37 55 75 110
Rated voltage [V] 200AC (50Hz) / 200 to 230AC (60Hz)Power fluctuation rate within +10%, -15%
Frequency
Rated current [A] 2.6 9.0 10.5 16.0 26.0 35.4
Rated voltage [V] 270 to 311DC
Rated current [A] 4.5 10.0 11.0 18.0 26.0 36.0
Voltage
Frequency
Current
Rush current [A] Max.30
2-3-4 D/A output specifications for servo drive unit
(1) D/A output specifications
Item Explanation
2ch
Output cycle
Output precision
Output voltage range
Output magnification
setting
Output pin
(CN9 connector)
0.8ms (min. value)
10bit
0V to 2.5V (zero) to +5V
-32768% to +32767% (1% scale)
MO1 = Pin 4
MO2 = Pin 14
GND = Pins 1, 11
CN9 connector
Pin
1
2
3
4
5
6
7
8
10
Name
LG
MO1
9
Pin
11
12
13
14
15
16
17
18
19
20
Name
LG
MO2
MDS-D-SVJ3
When the output data is 0, the offset voltage is 2.5V.
If there is an offset voltage, adjust the zero level position in the measuring instrument side.
Memory
+5 [V]
Speed FB
+2.5 [V]
0 [V]
+5 [V]
Current FB
+2.5 [V]
Scroll
2 - 8
0 [V]
Example of D/A output waveform
2. Specifications
(2) Output data settings
<Standard output>
No. Abbrev. Parameter name Explanation
SV061 DA1NO D/A output channel 1 data No. Input the No. of the data to be output to each D/A output channel.
SV062 DA2NO D/A output channel 2 data No.
No. Output data
0
Commanded rotation speed
1
Motor rotation speed
2
Torque command
3
Torque feedback
8
Machine vibration frequency
30
Collision detection estimated torque
*1 The estimated load inertia ratio (unit: 100%) is applied for the rotary motor, and the moving sections gross weight (unit: 100kg) for
Collision detection disturbance estimated
31
torque
Estimated load inertia ratio
*1
32
or moving sections gross weight
Position droop
50
Position command
51
Position feedback
52
53 Position F⊿T
Deviation from ideal position
54
(considering servo tracking delay)
Position droop
60
Position command
61
Position feedback
62
63 Position F⊿T
Deviation from ideal position
64
(considering servo tracking delay)
Position droop
70
Position command
71
Position feedback
72
73 Position F⊿T
Deviation from ideal position
74
(considering servo tracking delay)
126
Saw tooth wave
127
2.5V test data
the linear motor.
Standard output unit
Linear axisRotary axis
1000(r/min)/V 0.8ms
1000(r/min)/V 0.8ms
100%/V 0.8ms
100%/V 0.8ms
500Hz/V 0.8ms
100% 0.8ms
100% 0.8ms
100% or 100kg 0.8ms
1µm/V
1µm/V
1µm/V
1µm/s/V
1µm/V
1mm/V
1mm/V
1mm/V
1mm/s/V
1mm/V
1m/V
1m/V
1m/V
1m/s/V
1m/V
1/1000°/V
1/1000°/V
1/1000°/V
1/1000°/s/V
1/1000°/V
1°/V
1°/V
1°/V
1°/s/V
1°/V
1000°/V
1000°/V
1000°/V
1000°/s/V
1000°/V
0V to 5V 0.8ms
2.5V 0.8ms
Output cycle
0.8ms
0.8ms
0.8ms
0.8ms
0.8ms
0.8ms
0.8ms
0.8ms
0.8ms
0.8ms
0.8ms
0.8ms
0.8ms
0.8ms
0.8ms
2 - 9
2. Specifications
< Servo control signal >
Servo control input (NC to SVJ3) Servo control output (SVJ3 to NC)
No. Details No.Details
16384
16385
16391
16409
16410
16411
16416
Servo control input 1-0 READY ON command
Servo control input 1-1 Servo ON command
Servo control input 1-7 Alarm reset command
Servo control input 2-9 Speed monitor command valid
Servo control input 2-A In door closed (controller)
Servo control input 2-B In door closed (all drive units)
Servo control input 3-0 Control axis detachment
command
16480
Servo control output 1-0 In READY ON
16481
Servo control output 1-1 In servo ON
16487
Servo control output 1-7 In alarm
16492
Servo control output 1-C In in-position
16493
Servo control output 1-D In current limit
16494
Servo control output 1-E In absolute position data loss
16495
Servo control output 1-F In warning
16496
Servo control output 2-0 Z phase passed
16499
Servo control output 2-3 In zero speed
16503
Servo control output 2-7 In external emergency stop
16505
Servo control output 2-9 In speed monitor
16506
Servo control output 2-A In door closed (controller)
16507
Servo control output 2-B In door closed
(self drive unit)
16512
Servo control output 3-0 In control axis detachment
2 - 10
2. Specifications
2-3-5 D/A output specifications for spindle drive unit
(1) D/A output specifications
Item Explanation
Output cycle
Output precision
Output voltage range
Output magnification
setting
Output pin
(CN9 connector)
2ch
0.8ms (min. value)
10bit
0V to 2.5V (zero) to +5V
±32768
MO1 = Pin 4
MO2 = Pin 14
GND = Pins 1, 11
CN9 connector
Pin
Name
LG
1
2
3
4
MO1
5
6
7
8
10
Name
Pin
LG
11
12
13
9
14
15
16
17
18
19
20
MO2
When the output data is 0, the offset voltage is 2.5V.
If there is an offset voltage, adjust the zero level
position in the measuring instrument side.
Speed FB
Current FB
MDS-D-SPJ3
Memory
Scroll
+5 [V]
+2.5 [V]
0 [V]
+5 [V]
+2.5 [V]
0 [V]
Example of D/A output waveform
2 - 11
2. Specifications
(2) Setting the output data
<Standard output>
No. Abbrev. Parameter name Explanation
SP125 DA1NO
SP126 DA2NO
No. Output data
0 Commanded motor rotation speed
1 Motor rotation speed
2 Torque current command
3 Torque current feedback
50 Position droop
60 Position droop
127
2.5V test data output
D/A output channel 1 data No.
D/A output channel 2 data No.
Input the No. of the data to be output to each D/A output channel.
Output unit
for standard setting
1000(r/min)/V 0.8ms
1000(r/min)/V 0.8ms
100%/V 0.8ms
100%/V 0.8ms
1/1000°/V 0.8ms
1°/V 0.8ms
2.5V 0.8ms
Output cycle
2 - 12
2. Specifications
< Spindle control signal>
Spindle control input (NC to SPJ3) Spindle control output (SPJ3 to NC)
No. Details No.Details
16384
Spindle control input 1-0 READY ON command
16385
Spindle control input 1-1 Servo ON command
16391
Spindle control input 1-7 Alarm reset command
16392
Spindle control input 1-8 Torque limit 1 selection
16393
Spindle control input 1-9 Torque limit 2 selection
16394
Spindle control input 1-A Torque limit 3 selection
16409
Spindle control input 2-9 Speed monitor command
16410
Spindle control input 2-A In door closed (controller)
16411
Spindle control input 2-B In door closed
16432
Spindle control input 4-0 Spindle control mode
16433
Spindle control input 4-1 Spindle control mode
16434
Spindle control input 4-2 Spindle control mode
16437
Spindle control input 4-5 Gear selection command 1
16438
Spindle control input 4-6 Gear selection command 2
16444
Spindle control input 4-C M coil selection command
16445
Spindle control input 4-D L coil selection command
16446
Spindle control input 4-E Sub-motor selection
16462
Spindle control input 5-E Spindle holding force up
command
command
command
valid
(all drive units)
selection command 1
selection command 2
selection command 3
command
16480
Spindle control output 1-0 In ready ON
16481
Spindle control output 1-1 In servo ON
16487
Spindle control output 1-7 In alarm
16488
Spindle control output 1-8 In torque limit 1 selection
16489
Spindle control output 1-9 In torque limit 2 selection
16490
Spindle control output 1-A In torque limit 3 selection
16492
Spindle control output 1-C In in-position
16493
Spindle control output 1-D In torque limit
16495
Spindle control output 1-F In warning
16496
Spindle control output 2-0 Z phase passed
16499
Spindle control output 2-3 In zero speed
16503
Spindle control output 2-7 In external emergency stop
16505
Spindle control output 2-9 In speed monitor
16506
Spindle control output 2-A In door closed (controller)
16507
Spindle control output 2-B In door closed
(self drive unit)
16528
Spindle control output 4-0 In spindle control mode
16529
Spindle control output 4-1 In spindle control mode
16530
Spindle control output 4-2 In spindle control mode
16533
Spindle control output 4-5 In gear selection 1
16534
Spindle control output 4-6 In gear selection 2
16540
Spindle control output 4-C In M coil selection
16541
Spindle control output 4-D In L coil selection
16542
Spindle control output 4-E In sub-motor selection
16544
Spindle control output 5-0 Current detection
16545
Spindle control output 5-1 Speed detection
16550
Spindle control output 5-6 In coil changeover
16552
Spindle control output 5-8 In 1 drive unit 2 motor
16553
Spindle control output 5-9 2nd speed detection
16558
Spindle control output 5-E In spindle holding force up
16559
Spindle control output 5-F In 2nd in-position
selection 1
selection 2
selection 3
changeover
2 - 13
2-3-6 Explanation of each part
(1) Explanation of each servo drive unit part
(1)
2. Specifications
(2)
(3)
(10)
(11)
(12)
(13)
MDS-D-SVJ3-03/04/07
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(12)
(11)
MDS-D-SVJ3-10/20/35
The connector and terminal block layout may differ according to the unit being used. Refer to each unit
outline drawing for details.
Each part name
(1) LED --- Unit status indication LED --(2) SW1 --- Axis No. setting switch --(3) SW2 --- For machine tool builder adjustment (Always ON) --(4) CN9 --- DI/O or maintenance connector --(5) CN1A --- NC or master axis optical communication connector --(6) CN1B --- Slave axis optical communication connector --(7) CN2 --- Motor side detector connection connector ---
Control circuit
(8) CN3 --- Machine side detector connection connector --(9)
(10) CNP1
(11) CNP2
(12)
Main circuit
CNP3 U, V, W Motor power output terminal (3-phase AC output) ---
Name Description Screw size
BAT --- Battery connection connector ---
L1,L2,L3
N,P1,P2
P,C,D
L11,L21
L1,L2,L3: 3-phase AC power input
N,P1,P2: not used (short-circuit between the P1 and P2.)
Regenerative resistor connection terminal
Control power input terminal (single-phase AC input)
---
---
(13)
PE
Grounding terminal M4 x 10
2 - 14
2. Specifications
(2) Explanation of each spindle drive unit (0.75 to 3.7kW) part
(1)(2)
(9)
(10)
(11)
(12)
MDS-D-SPJ3-075/22/37
(3)
(4)
(5)
(6)
(7)
(8)
The connector and terminal block layout may differ according to the unit being used. Refer to each unit
outline drawing for details.
Each part name
(1) LED --- Unit status indication LED --(2) SW1 --- Axis No. setting switch --(3) SW2 --- For machine tool builder adjustment (always ON) --(4) CN9 --- DI/O or maintenance connector --(5) CN1A --- NC or master axis optical communication connector --(6) CN1B --- Slave axis optical communication connector ---
Control circuit
(7) CN2 --- Motor side detector connection connector --(8)
(9) CNP1
(10) CNP2
(11)
CN3 --- Machine side detector connection connector ---
Main circuit
CNP3 U, V, W Motor power output terminal (3-phase AC output) ---
Name Description Screw size
L1,L2,L3
N,P1,P2
P,C,D
L11,L21
L1,L2,L3: 3-phase AC power input
N,P1,P2: Not used (short-circuit between the P1 and P2.)
Regenerative resistor connection terminal
Control power input terminal (single-phase AC input)
---
---
(12)
PE
Grounding terminal M4 x 10
2 - 15
2. Specifications
(3) Explanation of each spindle drive unit (5.5 to 11kW) part
(1)
(9)
(10)
(11)
MDS-D-SPJ3-55/75
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(10)
(11)
MDS-D-SPJ3-110
The connector and terminal block layout may differ according to the unit being used. Refer to each unit
outline drawing for details.
Ambient temperature
Ambient humidity
Atmosphere
Altitude
Vibration X: 19.6m/s2 (2G) Y: 19.6m/s2 (2G)
3-1-2 Quakeproof level
Motor type
3. Characteristics
Operation: 0 to 40°C (with no freezing),
Storage: -15°C to 70°C (with no freezing)
Operation: 80%RH or less (with no dew condensation),
Storage: 90%RH or less (with no dew condensation)
Indoors (no direct sunlight);
no corrosive gas, inflammable gas, oil mist, or dust
Operation: 1000 meters or less above sea level,
Storage: 10000 meters or less above sea level
Acceleration direction
Axis direction (X) Direction at right angle to axis (Y)
HF75, HF105
X: 9.8m/s
HF54, HF104, HF154
HF204, HF354
X: 19.6m/s
The vibration conditions are as shown below.
200
100
80
60
50
40
30
Vibration amplitude
(double-sway width) (µm)
20
1000200030000
Speed (r/min)
2
(1G) or less Y: 24.5m/s2 (2.5G) or less
2
(2G) or less Y: 49m/s2 (5G) or less
cceleration
Servomotor
3 - 2
3. Characteristics
3-1-3 Shaft characteristics
There is a limit to the load that can be applied on the motor shaft. Make sure that the load applied on the
radial direction and thrust direction, when mounted on the machine, is below the tolerable values given
below. These loads may affect the motor output torque, so consider them when designing the machine.
Note: The symbol L in the table refers to the value of L below.
L
L : Length from flange installation surface to center of load weight [mm]
CAUTION
Radial load
Thrust load
1. Use a flexible coupling when connecting with a ball screw, etc., and keep the
shaft core deviation to below the tolerable radial load of the shaft.
2. When directly installing the gear on the motor shaft, the radial load increases
as the diameter of the gear decreases. This should be carefully considered
when designing the machine.
3. When directly installing the pulley on the motor shaft, carefully consider so
that the radial load (double the tension) generated from the timing belt tension
is less than the values shown in the table above.
4. In machines where thrust loads such as a worm gear are applied, carefully
consider providing separate bearings, etc., on the machine side so that loads
exceeding the tolerable thrust loads are not applied to the motor.
5. Do not use a rigid coupling as an excessive bending load will be applied on
the shaft and could cause the shaft to break.
3 - 3
3-1-4 Oil / water standards
3. Characteristics
(1) The motor protective format uses the IP type, which complies
with IEC Standard. (Refer to the section "2-1-1 Specifications
Oil or water
list".) However, these Standards are short-term performance
specifications. They do not guarantee continuous
environmental protection characteristics. Measures such as
covers, etc., must be taken if there is any possibility that oil or
water will fall on the motor, and the motor will be constantly wet
and permeated by water. Note that the motor’s IP-type is not
indicated as corrosion-resistant.
Servomotor
(2) When a gear box is installed on the servomotor, make sure that the oil level height from the
center of the shaft is higher than the values given below. Open a breathing hole on the gear
box so that the inner pressure does not rise.
(3) When installing the servomotor horizontally, set the power cable and detector cable to face
downward. When installing vertically or on an inclination, provide a cable trap.
Cable trap
1. The servomotors, including those having IP67 specifications, do not have a
completely waterproof (oil-proof) structure. Do not allow oil or water to
constantly contact the motor, enter the motor, or accumulate on the motor. Oil
can also enter the motor through cutting chip accumulation, so be careful of
CAUTION
this also.
2. When the motor is installed facing upwards, take measures on the machine
side so that gear oil, etc., does not flow onto the motor shaft.
3. Do not remove the detector from the motor. (The detector installation screw is
treated for sealing.)
3 - 4
3-1-5 Magnetic brake
1. The axis will not be mechanically held even when the dynamic brakes are
used. If the machine could drop when the power fails, use a servomotor with
magnetic brakes or provide an external brake mechanism as holding means
to prevent dropping.
2. The magnetic brakes are used for holding, and must not be used for normal
braking. There may be cases when holding is not possible due to the life or
machine structure (when ball screw and servomotor are coupled with a timing
CAUTION
belt, etc.). Provide a stop device on the machine side to ensure safety.
3. When operating the brakes, always turn the servo OFF (or ready OFF). When
releasing the brakes, always confirm that the servo is ON first. Sequence
control considering this condition is possible by using the brake contact
connection terminal (CN20) on the servo drive unit.
4. When the vertical axis drop prevention function is used, the drop of the
vertical axis during an emergency stop can be suppressed to the minimum.
(1) Motor with magnetic brake
(a) Types
The motor with a magnetic brake is set for each motor. The "B" following the standard motor
model stands for the motor with a brake.
(b) Applications
When this type of motor is used for the vertical feed axis in a machining center, etc., slipping
and dropping of the spindle head can be prevented even when the hydraulic balancer's
hydraulic pressure reaches zero when the power turns OFF. When used with a robot, deviation
of the posture when the power is turned OFF can be prevented.
When used for the feed axis of a grinding machine, a double safety measures is formed with
the deceleration stop (dynamic brake stop) during emergency stop, and the risks of colliding
with the grinding stone and scattering can be prevented.
This motor cannot be used for the purposes other than holding and braking during a power
failure (emergency stop). (This cannot be used for normal deceleration, etc.)
(c) Features
1) The magnetic brakes use a DC excitation method, thus:
• The brake mechanism is simple and the reliability is high.
• There is no need to change the brake tap between 50Hz and 60Hz.
• There is no rush current when the excitation occurs, and shock does not occur.
• The brake section is not larger than the motor section.
2) The magnetic brake is built into the motor, and the installation dimensions are the same as
the motor without brake.
(d) Considerations to safety
1) Using a timing belt
Connecting the motor with magnetic brakes and the load (ball screw, etc.) with a timing
belt as shown on the left below could pose a hazard if the belt snaps. Even if the belt's
safety coefficient is increased, the belt could snap if the tension is too high or if cutting
chips get imbedded. Safety can be maintained by using the method shown on the right
below.
3. Characteristics
Dangerous!
Motor
Brake
Timing belt
Top
Load
Bottom
Ball screw
3 - 5
Safe!
Motor
(No brakes)
Timing belt
Load
Bottom
Ball screw
Brake
Top
3. Characteristics
(2) Magnetic brake characteristics
Motor type
Item
Type (Note 1)
Rated voltage 24VDC
Rated current at 20°C (A) 0.38 0.8 1.4
Capacity (W) 9 19 34
Static friction torque (N•m) 2.4 8.3 43.1
Inertia (Note 2)
Release delay time (Note 3) (s) 0.03 0.04 0.1
Braking delay time (DC OFF)
(Note 3)
Tolerable
braking work
amount
Brake play at motor axis (degree) 0.1 to 0.9 0.2 to 0.6 0.2 to 0.6
Brake life
(Note 1) There is no manual release mechanism. If handling is required such as duri ng the machine core alignment work,
(Note 2) These are the values added to the servomotor without a brake.
(Note 3) This is the representative value for the initial attraction gap at 20°C.
(Note 4) The brake gap will widen through brake lining wear caused by braking. However, the gap cannot be adjusted. Thus,
(Note 5) A leakage flux will be generated at the shaft end of the servomotor with a magnetic brake.
(Note 6) When operating in low speed regions, the sound of loose brake lining may be heard. However, this is not a problem in
Per braking (J) 64 400 4,500
Per hour (J) 640 4,000 4,5000
No. of braking
(Note 4)
operations
Work amount
per braking
prepare a separate 24VDC power supply, and electrically release a brake.
the brake life is considered to be reached when adjustments are required.
terms of function.
2
(kg•cm
)
(s) 0.03 0.03 0.03
(times) 20,000 20,000 20,000
(J) 32 200 1,000
HF75B
HF105B
Spring closed non-exciting operation magnetic brakes
(for maintenance and emergency braking)
0.2 2.2 9.7
HF54B
HF104B
HF154B
HF204B
HF354B
3 - 6
(3) Magnetic brake power supply
1. Always install a surge absorber on the brake terminal when using DC OFF.
CAUTION
2. Do not pull out the cannon plug while the brake power is ON. The cannon
plug pins could be damaged by sparks.
(a) Brake excitation power supply
1) Prepare a brake excitation power supply that can accurately ensure the attraction current
in consideration of the voltage fluctuation and excitation coil temperature.
2) The brake terminal polarity is random. Make sure not to mistake the terminals with other
circuits.
(b) Brake excitation circuit
1) When turning OFF the brake excitation power supply (to apply the brake), DC OFF is used
to shorten the braking delay time. A surge absorber will be required. Pay attention to the
relay cut off capacity.
<Cautions>
• Provide sufficient DC cut off capacity at the contact.
• Always use a surge absorber.
• When using the cannon plug type, the surge absorber will be further away, so use
shielded wires between the motor and surge absorber.
3. Characteristics
100VAC or
200VAC
PS
ZD1, ZD2
VAR1, VAR2
24VDC
SW1
ZD1
PS
VAR1
ZD2
(b) Example of DC OFF
: 24VDC stabilized power supply
: Zener diode for power supply protection (1W, 24V)
: Surge absorber
Magnetic brake circuits
SW2
VAR2
Magnetic brake 1
Magnetic brake 2
3 - 7
3. Characteristics
3-1-6 Dynamic brake characteristics
If a servo alarm that cannot control the motor occurs, the dynamic brakes will function to stop the
servomotor regardless of the parameter settings.
(1) Deceleration torque
The dynamic brake uses the motor as a generator, and obtains the deceleration torque by
consuming that energy with the dynamic brake resistance. The characteristics of this deceleration
torque have a maximum deceleration torque (Tdp) regarding the motor speed as shown in the
following drawing. The torque for each motor is shown in the following table.
Deceleration
torque
Tdp
0
Deceleration torque characteristics of a dynamic brake
There is a limit to the load that can be applied on the motor shaft. Make sure that the load applied on the
radial direction, when mounted on the machine, is below the tolerable values given below. These loads
may affect the motor output torque, so consider them when designing the machine.
Spindle motor Tolerable radial load
Operation: 0 to 40°C (with no freezing),
Storage: -20°C to 65°C (with no freezing)
Operation: 90%RH or less (with no dew condensation),
Storage: 90%RH or less (with no dew condensation)
Indoors (no direct sunlight);
no corrosive gas, inflammable gas, oil mist, or dust
Operation: 1000 meters or less above sea level,
Storage: 1000 meters or less above sea level,
Transportation: 10000 meters or less above sea level
SJ-VL0.75-01E, SJ-VL1.5-01E 490N
SJ-V2.2-01E, SJ-V3.7-01E 980N
SJ-V5.5-01E 1470N
SJ-V7.5-01E, SJ-V11-01E 1960N
Radial load
(Note) The load point is at the one-half of the shaft length.
3 - 10
3-3 Drive unit characteristics
3-3-1 Environmental conditions
Environment Conditions
Ambient temperature
Ambient humidity
Atmosphere
Altitude
Vibration/impact 4.9m/s2 (0.5G) / 49m/s2 (5G)
(Note) When installing the machine at 1,000m or more above sea level, the heat dissipation characteristics will drop as the
altitude increases. The upper limit of the ambient temperature drops 1°C with every 100m increase in altitude. (The
ambient temperature at an altitude of 2,000m is between 0 and 45°C.)
Storage / Transportation: 90%RH or less (with no dew condensation)
With no corrosive gas, inflammable gas, oil mist, dust or conductive fine particles
3. Characteristics
Operation: 0 to 55°C (with no freezing),
Storage / Transportation: -15°C to 70°C (with no freezing)
Operation: 90%RH or less (with no dew condensation)
Indoors (no direct sunlight)
Operation/Storage: 1000 meters or less above sea level,
Transportation: 13000 meters or less above sea level
3 - 11
3. Characteristics
3-3-2 Heating value
Each heating value is calculated with the following values.
The values for the servo drive unit apply at the stall output. The values for the spindle drive unit apply for
the continuous rated output.
Servo drive unit Spindle drive unit
Type
MDS-D-SVJ3-
03
04
07
10
20
35
Heating value
[W]
Inside panel
25
35
50
90
130
195
Type
MDS-D-SPJ3-
075
22
37
55
75
110
Design the panel's heating value taking the actual axis operation (load rate) into
consideration. The following table shows a load rate in a general machine tool.
POINT
Servo drive unit 50%
Spindle drive unit 100%
Unit Load rate
Heating value
[W]
Inside panel
50
90
130
150
200
300
3 - 12
3. Characteristics
3-3-3 Overload protection characteristics
The servo drive unit has an electronic thermal relay to protect the servomotor and servo drive unit from
overloads. The operation characteristics of the electronic thermal relay are shown below when standard
parameters (SV021=60, SV022=150) are set.
If overload operation over the electronic thermal relay protection curve shown below is carried out,
overload 1 (alarm 50) will occur. If the maximum torque is commanded continuously for one second or
more due to a machine collision, etc., overload 2 (alarm 51) will occur.
4-5-2 List of cables and connectors.................................................................................................... 4-25
4-5-3 Optical communication cable specifications .............................................................................4-29
4 - 1
4. Dedicated Options
4-1 Servo options
The option units are required depending on the servo system configuration. Check the option units to be
required referring the following items.
(1) Corresponding machine side detector
For MDS-D-SVJ3 series, various linear scales and rotary encoders can be used as machine side
detectors.
Note that, however, resolutions that can be used are limited.
Axis type Detector resolution that can be used
Linear scale (For linear axis) 1nm or more
Rotary encoder (For rotary axis)
36,000,000pulse/rev or less
1/100,000°)or more
(
POINT
Contact MITSUBISHI for resolutions exceeding the limits.
4 - 2
4. Dedicated Options
(2) System establishment in the full closed loop control
Refer to the table below to confirm the interface unit (I/F) and battery option required for the full
closed loop control.
Absolute position detector is not required for the motor side detector when using absolute position
scale.
Machine side detector
to be used
OSA105-ET2
Relative position linear scale
(Various types)
Relative position rotary
encoder (Various types)
Relative position linear scale
SR33 (SONY)
Relative position linear scale
LS186, LS486, etc.
(HEIDENHAIN)
Relative position linear scale
(Various types)
Relative position rotary
encoder (Various types)
Relative position linear scale
SH13 (SONY)
Relative position linear scale
LS186, LS486, etc.
(HEIDENHAIN)
Relative position rotary
encoder
ERM280 1024/1200/2048,
etc.
(HEIDENHAIN)
Absolute position linear scale
AT342, AT343, AT543
(Mitutoyo)
Absolute position linear scale
LC191M, LC491M
(HEIDENHAIN)
Absolute position rotary
encoder
RCN223, RCN723
(HEIDENHAIN)
Absolute position rotary
encoder
MPRZ series (MME)
Detector
signal output
Serial
communication
Oblong wave
signal output
-
Analog
1Vp-p
SIN wave
signal output
Analog
1Vp-p
SIN wave
signal output
Analog
1Vp-p
SIN wave
signal output
Analog
1Vp-p
SIN wave
signal output
Analog
1Vp-p
SIN wave
signal output
Serial
communication
Serial
communication
Serial
communication
-
Required
interface unit (I/F)
- -
- - Incremental
CN33
(SONY)
IBV series
(HEIDENHAIN)
MDS-B-HR-11
MJ831
(SONY)
APE391M A0
(HEIDENHAIN)
APE391M C0
series
APE391M C2
series
(HEIDENHAIN)
- -
- -
- -
ADB-20J71
(MME)
I/F signal
output
Oblong wave
signal output
Oblong wave
signal output
Serial
communication
Serial
communication
Serial
communication
Serial
communication
Serial
communication
Servo system
specifications
Absolute
position
Incremental
Incremental
Incremental
Incremental
Incremental
Incremental
Absolute
position
Absolute
position
Absolute
position
Absolute
position
Remarks
Requires battery option
ER6V-C119B, etc.
Contact: Each machine
side detector
manufacturer
Contact:
Sony Manufacturing
Contact:
HEIDENHAIN
Contact: Each machine
side detector
manufacturer
Contact:
Sony Manufacturing
Contact:
HEIDENHAIN
Contact:
HEIDENHAIN
Contact:
Mitutoyo
Contact:
HEIDENHAIN
Contact:
HEIDENHAIN
Contact:
MME Corporation
4 - 3
4. Dedicated Options
Contact information about machine side detector
Mitutoyo Corporation http://www.mitutoyo.co.jp/
Sony Manufacturing Systems Corporation http://www.sonysms.co.jp/
HEIDENHAIN CORPORATION http://www.heidenhain.co.jp/
MHI MACHINE TOOL ENGINEERING CO., LTD http://www.mme-e.co.jp/
The absolute position system cannot be established in combination with the
POINT
relative position (incremental) machine side detector and absolute position
motor side detector.
4 - 4
4. Dedicated Options
4-1-1 Battery option (MR-J3BAT)
This battery option may be required to establish absolute position system. Refer to the section "4-1
Servo option" and use the following battery option depending on the servo system.
Type MR-J3BAT
Installation
type
Hazard classNot applicable
Number of
connectable
axes
Battery
change
Appearance
Drive unit with battery holder type
1 axis
Possible
(1)
(1) Cell battery (MR-J3BAT)
< Specifications >
Battery option type
Lithium battery series ER6V
Nominal voltage 3.6V
Nominal capacity 2000mAh
Battery
safety
Number of connectable axes 1 axis
Battery continuous backup time Approx. 20000 hours
Battery useful life
(From date of unit manufacture)
Data save time in battery
replacement
Back up time from battery
warning to alarm occurrence
(Note2)
Weight 20g
(Note1) MR-J3BAT is a battery built in a servo drive unit. Install this battery only in the servo drive unit that executes absolute
position control.
(Note2) This time is a guideline, so does not guarantee the back up time. Replace the battery with a new battery as soon as a battery
alarm occurs.
The absolute position may be lost before the battery alarm occurs. Change the battery periodically.
Hazard class
Battery shape
Number of
batteries used
Lithium alloy
content
Mercury content
HF series: approx. 20 hours at time of delivery, approx. 10 hours after 5 years
Cell battery
MR-J3BAT
Approx. 100 hours
(Note1)
-
Single battery
ER6V×1
0.7g
1g or less
7 years
4 - 5
< Installing the cell battery >
4. Dedicated Options
Insert the connector into CN4.
1. On January 1, 2003, new United Nations requirements, "United Nations
Dangerous Goods Regulations Article 12", became effective regarding the
transportation of lithium batteries. The lithium batteries are classified as
hazardous materials (Class 9) depending on the unit. (Refer to Appendix 4.)
2. The lithium battery must be transported according to the rules set forth by the
International Civil Aviation Organization (ICAO), International Air
Transportation Association (IATA), International Maritime Organization
(IMO), and United States Department of Transportation (DOT), etc. The
packaging methods, correct transportation methods, and special regulations
are specified according to the quantity of lithium alloys. The battery unit
CAUTION
exported from Mitsubishi is packaged in a container (UN approved part)
satisfying the standards set forth in this UN Advisory.
3. To protect the absolute value, do not shut off the servo drive unit control
power supply if the battery voltage becomes low (warning 9F).
4. Contact the Service Center when replacing the battery.
5. The battery life (backup time) is greatly affected by the working ambient
temperature. The above data is the theoretical value for when the battery is
used 8 hours a day/240 days a year at an ambient temperature of 25°C.
Generally, if the ambient temperature increases, the backup time and useful
life will both decrease.
4 - 6
4. Dedicated Options
4-1-2 Ball screw side detector (OSA105-ET2)
(1) Specifications
Detector type
Electrical
characteristics
Mechanical
characteristics
for rotation
Mechanical
configuration
Working
environment
(Note) If the tolerable rotation speed at power off is exceeded, position deviation will occur.
Detector resolution 1,000,000pulse/rev
Detection method
Tolerable rotation speed at power off
The machine side detectors are all special order parts, and must be prepared by the user.
(1) Relative position detector
Depending on the output signal specifications, select a machine side relative position detector with
which the following (a), (b) or (c) is applied.
(a) Serial signal type (serial conversion unit made by each manufacture )
The following serial conversion unit converts the detector output signal and transmits the signal
to the drive unit in serial communication.
For details on the specifications of each conversion unit scale and for purchase, contact each
corresponding manufacture directly.
(Note1) The combination of speed / rotation speed in the table depends on the following calculation formula.
For linear scale:
Maximum speed (m/min) = scale analog signal cycle (m) x maximum input frequency (Hz) x 60
For rotary encoder:
Maximum rotary speed (r/min) = maximum input frequency (Hz) / numbers of encoder scale (1/rev) x 60
An actual Maximum speed/ rotary speed is limited by the mechanical specifications and electrical specifications, etc. of
the connected scale, so contact the manufacture of the purchased scale.
(Note2) The combination resolution in the table depends on the following calculation formula.
In use of linear scale: Minimum resolution (m) = Scale analog signal frequency (m) / division number
In use of rotary encoder: Minimum resolution (pulse/rev) = numbers of encoder scale (1/rev) x division number
HEIDENHAIN 400kHz 4096
input
frequency
Division
number
Rotary encoder can
be combined
ERM 1024 23,437r/min
ERM 1200 20,000r/min
ERM 2048 11,718r/min
Combination
maximum
rotation
speed (Note1)
Combination
resolution
(Note2)
4,194,304
pulse/rev
4,915,200
pulse/rev
8,388,608
pulse/rev
CAUTION
The above value does not guarantee the accuracy of the system.
4 - 9
4. Dedicated Options
(b) SIN wave output (using MDS-B-HR)
When using a relative position detector that the signal is the SIN wave output, the detector
output signal is converted in the detector conversion unit (MDS-B-HR), and then the signal is
transmitted to the drive unit in the serial communication. Select a relative position detector with
A/B phase SIN wave signal that satisfies the following conditions. For details on the
specifications of MDS-B-HR, refer to the section “4-4-1”.
(Detector output signal)
• 2.5V reference 1Vp-p analog A-phase, B-phase, Z-phase differential output
• Output signal frequency 200kHz or less
Voltage [V]
2.5
A phase B phase
3
2
Time
A/B phase output signal waveform during forward run
• Combination speed / rotation speed
In use of linear scale:
Maximum speed (m/min) = scale analog signal frequency (m) x 200,000 x 60
In use of rotary encoder:
Maximum rotation speed (r/min) = 200,000 / numbers of encoder scale (1/rev) x 60
An actual Maximum speed/ rotary speed is limited by the mechanical specifications and
electrical specifications, etc. of the connected scale, so contact the manufacture of the
purchased scale.
• Division number 512 divisions per 1 cycle of signal
In use of linear scale:
Minimum resolution (m) = scale analog signal frequency (m) / 512
In use of rotary encoder:
Minimum resolution (pulse/rev) = numbers of encoder scale (1/rev) x 512
CAUTION
The above value does not guarantee the accuracy of the system.
4 - 10
A
O
A
A
4. Dedicated Options
(c) Oblong wave output
Select a relative position detector with an A/B phase difference and Z-phase width at the
maximum feedrate that satisfies the following conditions.
Use an A, B, Z-phase signal type with differential output (RS-422 standard product) for the
output signal.
utput circuit
, B, Z-phase
, B, Z-phase
Phase difference
-phase
B-phase
0.1µs or more
Z-phase
For a scale having multiple Z phases, select the neighboring Z
phases whose distance is an integral mm.
0.1µs or
more
Integer mm
(Note) The above value is minimum value that can be received normally in the servo drive unit
side.
In an actual selection, ensure margin of 20% or more in consideration of degradation of
electrical wave and speed overshoot.
<Example of scale specifications >
The example of using representative oblong save scale is shown below.
For specifications of each conversion unit and scale and for purchase, Contact each
corresponding manufacture directly.
Scale Type
SR33 CN33 SONY
LS186/LS486
Combination
conversion unit
IBV610
IBV650 0.1µm 48m/min
IBV660B
Manufacturer
HEIDENHAIN
Minimum
resolution
1µm 150m/min
0.5µm 120m/min
0.1µm 24m/min
0.05µm 12m/min
1µm 120m/min
0.5µm 120m/min
0.1µm 60m/min
0.05µm 30m/min
Maximum speed
4 - 11
4. Dedicated Options
(2) Absolute position detector
The applicable absolute position detectors are as follows.
< Linear scale >
Applicable absolute position detectors for the machine side
Type Manufacturer Maximum feedrateDetector output Detector resolution
AT342 110m/min
AT343 120m/min
AT543
LC191M
LC491M
Mitutoyo
HEIDENHAIN
120m/min
120m/min
120m/min
< Rotary encoder >
Applicable absolute position detectors for the machine side
Type Manufacturer Maximum feedrateDetector output Detector resolution
RCN723 300r/min
RCN223
MPRZ series
+ADB-20J71
HEIDENHAIN
MME Corp. 10000r/min
1500r/min
Confirm each manufacturer specifications before using the machine side
CAUTION
detector.
Serial data
Serial data
Serial data
Serial data
Serial data
Serial data
Serial data
Serial data
0.5µm
0.05µm
0.05µm
0.1µm/ 0.05µm
/0.01µm
0.05µm/ 0.01µm
8,000,000pulse/rev
8,000,000pulse/rev
8,000,000pulse/rev
4 - 12
4. Dedicated Options
4-2 Spindle options
According to the spindle control to be adopted, select the spindle side detector based on the following
table.
(a) No-variable speed control
(When spindle and motor are directly coupled or coupled with a 1:1 gear ratio)
Spindle control
item
Spindle control
Orientation control
Synchronous tap
control
Spindle
synchronous control
C-axis control C-axis control
(Note) { : Control possible
× : Control not possible
Control specifications
Normal cutting control
Constant surface speed control (lathe)
Thread cutting (lathe)
1-point orientation control
Multi-point orientation control
Orientation indexing
Standard synchronous tap
Synchronous tap after zero point return
Without phase alignment function
With phase alignment function
(b) Variable speed control
(When using V-belt, or when spindle and motor are connected with a gear ratio
other than 1:1)
Spindle control
item
Spindle control
Orientation control
Synchronous tap
control
Spindle
synchronous control
C-axis control C-axis control
(Note) { : Control possible
× : Control not possible
U : Control not possible when using V-belt
S : Control not possible when varying the speed with a method other than the gears (when using V-belt or timing belt).
: Control not possible when using V-belt, or control not possible for the RFH-1024-22-1M-68(-8) detector
Control specifications
Normal cutting control
Constant surface speed control (lathe)
Thread cutting (lathe)
1-point orientation control
Multi-point orientation control
Orientation indexing
Standard synchronous tap
Synchronous tap after zero point return
Without phase alignment function
With phase alignment function
Without spindle
side detector
{
{
{
{
{
{
{
{
{
{
{
Without spindle
side detector
{ {
U
×
×
×
×
S
×
U
×
×
With spindle side
detector
This normally is not
used for no-variable
speed control.
With spindle side
detector
{
{
{
{
{
{
{
{
{
4 - 13
4. Dedicated Options
4-2-1 Spindle side detector (OSE-1024-3-15-68, OSE-1024-3-15-68-8)
When a spindle and motor are connected with a V-belt, or connected with a gear ratio other than 1:1,
use this spindle side detector to detect the position and speed of the spindle. Also use this detector
when orientation control and synchronous tap control, etc are executed under the above conditions.
(1) Specifications
Detector type OSE-1024-3-15-68 OSE-1024-3-15-68-8
Mechanical
characteristics
for rotation
Mechanical
configuration
Working
environment
(2) Detection signals
Signal name Number of detection pulses
Pin Function Pin Function
A A phase K 0V
B Z phase L C B phase M D - N A phase
E Case earth P Z phase
F - R B phase
G - S H +5V T -
J -
Inertia
Shaft friction torque 0.98Nm or less 0.98Nm or less
Shaft angle acceleration 104 rad/s2 or less 104 rad/s2 or less
Tolerable continuous rotation speed6000 r/min 8000 r/min
Bearing maximum non-lubrication
time
Shaft amplitude
(position 15mm from end)
Tolerable load
(thrust direction/radial direction)
Weight 1.5kg 1.5kg
Squareness of flange to shaft 0.05mm or less
Flange matching eccentricity 0.05mm or less
Ambient temperature range –5°C to +55°C
Storage temperature range –20°C to +85°C
Humidity 95%Ph
Vibration resistance 5 to 50Hz, total vibration width 1.5mm, each shaft for 30min.
Impact resistance 294.20m/s
A, B phase 1024p/rev
Z phase 1p/rev
Half of value during operation
Connector pin layout
-4
0.1 × 10
kgm2 or less 0.1 × 10-4kgm2 or less
20000h/6000r/min 20000h/8000r/min
0.02mm or less 0.02mm or less
10kg/20kg
Half of value during operation
2
10kg/20kg
(30G)
4 - 14
(3) Outline dimension drawings
102 33
4. Dedicated Options
68
Ø68
MS3102A20-29P
Ø50
4- Ø5.4 hole
56
3 2
0
-0.11
-0.006
1.15
-0.017
15
Ø
+0.14
0
-0.009
16
Ø
-0.025
50
Ø
2
Ø14.3
20
+0.012
5
0
Shaft section
0
+0.05
3
Key way magnified figure
Spindle side detector (OSE-1024-3-15-68, OSE-1024-3-15-68-8)
4 - 15
[Unit: mm]
4. Dedicated Options
4-2-2 C axis detector (HEIDENHAIN ERM280)
Highly accurate C axis control is possible by connecting HEIDENHAIN incorporable rotary encoder
ERM280 series. ERM280 series encoder provides with high environmental resistance due to the
magnetic memory drum. The spindle motor to be incorporated with is a built-in type, so the motor
specifications must be considered, as well.
Note that HEIDENHAIN serial interface unit APE391M must be purchased as it is required for
connecting ERM280 series to the MDS-D-SPJ3 drive unit.
Incorporable rotary encoder Serial interface conversion unit
ERM280 series APE391M series
(1) Procurement
ERM280 series and APE391M series must be purchased directly from HEIDENHAIN.
APE391M 5V±5%
Number of scale marks 1024 1200 2048
Electrical tolerable rotation
speed
Combined resolution (Note 3)
(Parameter setting value)
Drum inner diameter 80mm 120mm 180mm
Drum outer diameter 128.75mm 150.88mm 257.5mm
Mechanical tolerable rotation
speed
Moment of inertia of rotary 2.7 x 10
Temperature range -10 to 100 °C
Dust/water proof structure
(IEC60529)
Weight Drum section 0.89kg 0.72kg 3.0kg
Scanning head 0.15kg
APE391M C2 1024 APE391M C0 1200 APE391M C2 2048
17500r/min 15000r/min 8780r/min
4,000,000P/rev 4,800,000P/rev 8,000,000P/rev
22000r/min 18000r/min 10000r/min
-3
kg・m2 3.5 x 10-3kg・m2 38×10-3kg・m2
IP67
(Note 1) Specifications are subject to change. Confirm the details with HEIDENHAIN.
(Note 2) The above specifications are for some of the popular products of HEIDENHAIN.
For inquiries about the products having the number of scale marks other than those listed above, contact HEIDENHAIN
directly.
(Note 3) Combined resolutions are not for the guarantee of the system accuracy.
4 - 17
4. Dedicated Options
4-3 Regenerative option
Confirm the regeneration resistor capacity and possibility of connecting with the drive unit. Refer to
"Appendix 3-2 Selecting the regenerative resistor" for details on selecting an regenerative resistor.
The regenerative resistor generates heats, so wire and install the unit while taking care to safety. When
using the regenerative resistor, make sure that flammable matters, such as cables, do not contact the
resistor, and provide a cover on the machine so that dust or oil does not accumulate on the resistor and
ignite.
The power value in the table is a regenerative power by the resistor, not a rated power.
resistor
Regenerative
capacity
Resistance
value
- - ○ ○
- - ○ ○
- - ○ ○
- - ○ ○
- -
- -
MR-RB032 MR-RB12 MR-RB32 MR-RB30 MR-RB50
30W 100W 300W 300W 500W
40Ω 40Ω 40Ω 13Ω 13Ω
External option regenerative resistor
075
FCUA-RB
15
External option regenerative resistor
External option regenerative resistor
FCUA-RB
GZG200W120
OHMK
x 3 units
Only the designated combination can be used for the regenerative option and
CAUTION
drive unit.
There is a risk of fire, so always use the designated combination.
22
FCUA-RB
37
GZG200W39
OHMK
x 3 units
FCUA-RB
55
FCUA
-RB75/2
1 unit
FCUA
-RB75/2
2 units
GZG300W39
OHMK
x 3 units
4 - 19
4. Dedicated Options
4-4 Detector interface unit
4-4-1 MDS-B-HR
This unit superimposes the scale analog output raw waves, and generates high resolution position data.
Increasing the detector resolution is effective for the servo high-gain. MDS-B-HR-12(P) is used for the
synchronous control system that 1-scale 2-drive operation is possible.
< Type configuration >
< Specifications >
Type MDS-B-HR- 11 12 11P 12P
Compatible scale (example) LS186 / LS486 (HEIDENHAIN)
Signal 2-division function
Analog signal input specifications A-phase, B-phase, Z-phase (2.5V reference Amplitude 1V
Compatible frequency Analog raw waveform max. 200kHz
Scale resolution Analog raw waveform/512 division
Input/output communication style High-speed serial communication I/F, RS485 or equivalent
Working ambient temperature 0 to 55°C
Working ambient humidity 90%RH or less (with no dew condensation)
Atmosphere No toxic gases
Tolerable vibration 98.0 m/s
Tolerable impact 294.0 m/s
Tolerable power voltage
Maximum heating value 2W
Weight 0.5kg or less
Protective structure IP65 IP67
MDS-B-HR-
(1) (2)
(2) Protective structure
NoneIP65 P IP67
(1) Signal division function class
11 Output number 1 12 Output number 2 (with division)
Symbol
Symbol
×
Protective structure
Scale output voltage class
{
5VDC±5%
2
(10G)
2
(30G)
×
P-P
{
)
4 - 20
< Outline dimension drawings >
• MDS-B-HR
6.5
5
4. Dedicated Options
152
46 6.5
RM15WTR-10S
70
5
RM15WTR-8Px2
CON1CON2
165
CON3 CON4
4-
Ø5 hole RM15WTR-12S
< Explanation of connectors >
Connector name Application Remarks
CON1 For connection with servo drive unit (2nd system)Not provided for 1-part system specifications
CON2 For connection with servo drive unit
CON3 For connection with scale
CON4
For connection with pole detection unit
(MDS-B-MD)
*Used for linear servo system
Connector pin layout
CON1 CON2 CON3 CON4
Pin No. Function Pin No. Function Pin No.Function Pin No. Function
1 RQ+ signal 1 RQ+ signal 1 A+ phase signal 1 A phase signal
2 RQ- signal 2 RQ- signal 2 A- phase signal 2 REF signal
3 SD+ signal 3 SD+ signal 3 B+ phase signal 3 B phase signal
4 SD- signal 4 SD- signal 4 B- phase signal 4 REF signal
5 P5 5 P5 5 Z+ phase signal 5 P24
6 P5 6 P5 6 Z- phase signal 6 MOH signal
7 GND 7 GND 7 - 7 P5
8 GND 8 GND 8 - 8 P5
Compatible scale LS186/LS486 etc.ERM280 1024 ERM280 1200 ERM280 2048
Analog signal input
specification
Compatible frequency Analog raw waveform max.400kHz
Scale resolution Analog raw waveform/ 4096 division
Input/output communication
style
Working ambient temperature 0 to 70℃
Atmosphere No toxic gases
Tolerable vibration 100 m/s2
Tolerable impact 200 m/s2
Tolerable power voltage 5VDC±5%
Weight
Protective structure
Pin No. Function Pin No. FunctionPin No.FunctionPin No. Function
1
2 0V U 10 0V sensor2 0V Un 10 0V sensor
3
4 5V Up 12 5V sensor4 5V Up 12 5V sensor
5 - 13 - 5 SD+ signal13 SD- signal
6 - 14
7 R- phase
8 - 8 RQ+ signal
A+ phase
signal
B+ phase
signal
signal
9
11 B- phase
15 - 7
(Note) Usually not used.
For details, contact the corresponding manufacture.
A- phase
R+ phase
signal
signal
signal
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
1
3 B+ phase
6 - 14
A+ phase
signal
(Note)
signal (Note)
R- phase
signal (Note)
A- phase signal
9
11 A- phase signal
R+ phase
signal
15 RQ- signal
(Note)
(Note)
(Note)
4 - 22
e
4. Dedicated Options
4-4-3 MJ831
<Specifications>
Type MJ831
Manufacture SONY
Compatible scale SH13
Analog signal input specification A phase, B phase, Z phase (2.5V reference Amplitude 1V
Compatible frequency Analog raw waveform max.140kHz
Divide analog raw waveform as below.
Scale resolution
Input/output communication style High-speed serial communication I/F, RS485or equivalent
Working ambient temperature 0 to 55℃
Atmosphere No toxic gases
Tolerable vibration 100 m/s2
Tolerable impact 200 m/s2
Tolerable power voltage DC11V to 32V
Weight 140g
Protective structure IP50
For details, contact the corresponding manufacture.
Power connector Drive unit connection side connector
Polarity label
Power connector
Drive unit connection side connector
4 - 23
4. Dedicated Options
4-5 Cables and connectors
4-5-1 Cable connection diagram
The cables and connectors that can be ordered from Mitsubishi Electric Corp. as option parts are shown
below. Cables can only be ordered in the designated lengths. Purchase a connector set, etc., to create
special length cables.
L11
L21
Servo drive unit
(MDS-D-SVJ3)
(5)
L1
L2
L3
CNP1
P
C
CNP2
U
V
CNP3
W
(1) From NC
CN1A
CN1B
CN2
CN3
Spindle drive unit
(MDS-D-SPJ3)
(5)
L1
L2
L3
CNP1
L11
L21
P
C
CNP2
U
V
CNP3
W
(1) Optical communication
cable
CN1A
CN2
CN3
Spindle side
detector
(6) Spindle detector cable
<Spindle side detector cable>
(6) Spindle detector cable
<Motor side PLG cable>
(2) Servo detector cable
<MDS-B-HR unit cabl e>
Servo detector cable
<Cable for linear scale>
(This cable must be prepared by the user.)
(2) Servo detector cable
<Ball screw side detector cable>
(2) Servo detector cable
<Motor side dete ctor cable>
Detector conversion unit
4 - 24
(MDS-B-HR)
Servo detector cable
<Linear scale cable for MDS-B-HR>
(This cable must be prepared by the user.)
Ball screw side detector
(3) Brake connecto r
Spindle motor
(Note) The linear scale must
be prepared by the user.
(4) Power
connector
Servo motor
4. Dedicated Options
4-5-2 List of cables and connectors
(1) Optical communication cable
Item Model Contents
For
CN1A/
CN1B
0.3,3,0.5,5m1,2,
For
CN1A/
CN1B
5,
Optical communication cable
For wiring between drive units (inside panel)
Optical communication cable
For wiring between drive units (outside panel)
G396-L□.□M
G380-L□□M
15,7,20m
: Length
: Length
10, 13,
Drive unit side connector
(Japan Aviation Electronics
Industry)
Connector : 2F-2D103
Drive unit side connector
(Tyco Electronics AMP)
Connector : 1123445-1
(Note1) For details on the optical communication cable, refer to the section “4-5-3 optical communication cable specification”
(Note2) For details on the optical communication cable for wiring between NC and drive unit, refer to the instruction manual for NC
controller.
(2) Servo detector cable and connector
Item Model Contents
For
CN2/3
For
servomotor
detector
/ Ball
screw
side
detector
CN3 MDS-B-HR unit cable CNV2E-HP- M
For
MDS-BHR unit
For
CN2/3
Motor side detector cable /
Ball screw side detector cable
Motor side detector connector /
Ball screw side detector connector
MDS-B-HR connector CNEHRS (10) MDS-B-HR unit side connector
Servo detector connector CNU2S (AWG18) Servo drive unit side connector
CNV2E-8P- M
: Length
3,
2,
10,
7,
30m
25,
CNV2E-9P- M
: Length
3,
2,
10,
7,
30m
25,
CNE10-R10S (9) Servomotor detector/
Applicable cable outline
ø6.0 to 9.0mm
CNE10-R10L (9) Servomotor detector/
Applicable cable outline
ø6.0 to 9.0mm
: Length
3,
2,
10,
7,
30m
25,
Applicable cable outline
ø8.5 to 11mm
4,
15,5,20,
4,
15,5,20,
4,
15,5,20,
Servo drive unit side
connector
(3M)
Receptacle
Shell kit
Servo drive unit side
connector
(3M)
Receptacle
Shell kit
Servo drive unit side
connector
(3M)
Receptacle
Shell kit
(Hirose Electric)
Plug
Clamp: RM15WTP-CP (10)
: 36210-0100JL
: 36310-3200-008
: 36210-0100JL
: 36310-3200-008
: 36210-0100JL
: 36310-3200-008
: RM15WTP-8S (for CON1, 2)
RM15WTP-12P (for CON3)
(3M)
Receptacle
Shell kit
: 36210-0100JL
: 36310-3200-008
Drive unit side connector
(Japan Aviation Electronics
Industry)
Connector : 2F-2D103
Drive unit side connector
(Tyco Electronics AMP)
Connector : 1123445-1
Servomotor detector/
Ball screw side detector side
connector (DDK)
Plug
: CM10-SP10S-M
Contact
: CM10-#22SC
Servomotor detector/
Ball screw side detector side
connector (DDK)
Plug
: CM10-AP10S-M
Contact
: CM10-#22SC
Ball screw side detector side
connector (DDK)
Plug
: CM10-SP10S-M
Contact
: CM10-#22SC
Ball screw side detector side
connector (DDK)
Plug
: CM10-AP10S-M
Contact
: CM10-#22SC
MDS-B-HR unit side
connector
(Hirose Electric)
Plug
: RM15WTP-8S
Clamp
: RM15WTP-CP (10)
4 - 25
4. Dedicated Options
(3) Brake connector
Item Model Contents
For motor
brake
CNB10-R2L (6) Servomotor side brake
Brake connector for HF,HP CNB10-R2S (6) Servomotor side brake
(Note1) This temperature range for use is the value for optical cable (cord) only. Temperature condition for the connector is the same
as that for drive unit.
(Note2) Do not see directly the light generated from CN1A/CN1B connector of drive unit or the end of cable. When the light gets into
eye, you may feel something is wrong for eye.
(The light source of optical communication corresponds to class1 defined in JISC6802 or IEC60825-1.)
4 - 29
4. Dedicated Options
(2) Cautions for using optical communication cable
Optical communication cable is made from optical fiber. If optical fiber is added a power such as a
major shock, lateral pressure, haul, sudden bending or twist, its inside distorts or breaks, and
optical transmission will not be available. Especially, as optical fiber for G396-L□. □M is made of
synthetic resin, it melts down if being left near the fire or high temperature. Therefore, do not make
it touched the part, which becomes high temperature, such as radiator or regenerative brake option
of drive unit.
Read described item in this section carefully and handle it with caution.
(a) Minimum bend radius
Make sure to lay the cable with greater radius than the minimum bend radius. Do not press the
cable to edges of equipment or others. For the optical communication cable, the appropriate
length should be selected with due consideration for the dimensions and arrangement of drive
unit so that the cable bend will not become smaller than the minimum bend radius in cable
laying. When closing the door of control box, pay careful attention for avoiding the case that
optical communication cable is hold down by the door and the cable bend becomes smaller
than the minimum bend radius.
(b) Bundle fixing
When using optical communication cable of 3m or longer, fix the cable at the closest part to the
connector with bundle material in order to prevent optical communication cable from putting its
own weight on CN1A/CN1B connector of drive unit. Optical cord should be given loose slack to
avoid from becoming smaller than the minimum bend radius, and it should not be twisted.
When tightening up the cable with nylon band, the sheath material should not be distorted. Fix
the cable with tightening force of 1 to 2kg or less as a guide.
Minimum bend radius
For wiring inside pane l: 25mm
wall
For wiring outside panel: 50mm
When laying cable, fix and hold it in position with using cushioning such as sponge or rubber
which does not contain plasticizing material.
Never use vinyl tape for cord. Plasticizing material in vinyl tape goes into optical fiber and
lowers the optical characteristic. At worst, it may cause wire breakage. If using adhesive tape
for cable laying, the fire resistant acetate cloth adhesive tape 570F (Teraoka Seisakusho Co.,
Ltd) is recommended.
If laying with other wires, do not make the cable touched wires or cables made from material
which contains plasticizing material.
4 - 30
4. Dedicated Options
(c) Tension
If tension is added on optical fiber, the increase of transmission loss occurs because of
external force which concentrates on the fixing part of optical fiber or the connecting part of
optical connector. At worst, the breakage of optical fiber or damage of optical connector may
occur. For cable laying, handle without putting forced tension.
(d) Lateral pressure
If lateral pressure is added on optical communication cable, the optical cable itself distorts,
internal optical fiber gets stressed, and then transmission loss will increase. At worst, the
breakage of optical cable may occur. As the same condition also occurs at cable laying, do not
tighten up optical communication cable with a thing such as nylon band (TY-RAP).
Do not trample it down or tuck it down with the door of control box or others.
(e) Twisting
If optical fiber is twisted, it will become the same stress added condition as when local lateral
pressure or bend is added. Consequently, transmission loss increases, and the breakage of
optical fiber may occur at worst.
(f) Cable selection
• When wiring is outside the power distribution panel or machine cabinet, there is a highly
possibility that external power is added. Therefore, make sure to use the cable for wiring
outside panel (G380-L□□M)
• If a part of the wiring is moved, use the cable for wiring outside panel.
• In a place where sparks may fly and flame may be generated, use the cable for wiring outside
panel.
(g) Method to lay cable
When laying the cable, do not haul the optical fiver or connector of the optical communication
cable strongly. If strong force is added between the optical fiver and connector, it may lead to a
poor connection.
(h) Protection in unuse
When the CN1A/CN1B connector of the drive unite or the optical communication cable
connector is not used such as pulling out the optical communication cable from drive unit ,
protect the joint surface with attached cap or tube for edge protection. If the connector is left
with its joint surface bared, it may lead to a poor connection caused by dirty.
(i) Attaching /Detaching optical communication cable connector
With holding the connector body, attach/detach the optical communication cable connector.
If attaching/detaching the optical communication cable with directly holding it, the cable may be
pulled out, and it may cause a poor connection.
When pulling out the optical communication connector, pull out it after releasing the lock of
clock lever.
(j) Cleaning
If CN1A and CN1B connector of the drive unit or optical communication cable connector is dirty,
it may cause poor connection. If it becomes dirty, wipe with a bonded textile, etc. Do not use
solvent such as alcohol.
(k) Disposal
When incinerating optical communication cable, hydrogen fluoride gas or hydrogen chloride
gas which is corrosive and harmful may be generated. For disposal of optical communication
cable, request for specialized industrial waste disposal services that has incineration facility for
disposing hydrogen fluoride gas or hydrogen chloride gas.
4 - 31
4. Dedicated Options
(l) Return in troubles
When asking repair of drive unit for some troubles, make sure to put a cap on CN1A/CN1B
connector. When the connector is not put a cap, the light device may be damaged at the transit.
In this case, exchange and repair of light device is required.
4 - 32
5. Selection of Peripheral Devices
5-1 Selection of wire................................................................................................................................. 5-2
5-1-1 Example of wires by unit .............................................................................................................5-2
5-2 Selection of no-fuse breaker and contactor ....................................................................................... 5-4
5-2-1 Selection of no-fuse breaker .......................................................................................................5-4
5-2-2 Selection of contactor..................................................................................................................5-5
5-3 Selection of earth leakage breaker ....................................................................................................5-6
5-4 Branch-circuit protection (for control power supply)........................................................................... 5-7
Selected wires must be able to tolerate rated current of the unit’s terminal to which the wire is connected.
How to calculate tolerable current of an insulated wire or cable is shown in “Tol erable current of electri c
cable” (1) of Japanese Cable Makers’ Association Standard (JCS)-168-E (1995), its electric equipment
technical standards or JEAC regulates tolerable current, etc. wire.
When exporting wires, select them according to the related standards of the country or area to export. In
the UL standards, certification con dition s are to use wires of 60
Wire’s tolerable current is different depending on conditions such as its material, structure, ambient
temperature, etc. Check the tolerable current described in the specification of the wire to use.
Example of wire selections according to each standard is as follows.
• Cable installed on walls without ducts or conduits.
To use the wire under conditions other than above, check the standards you
CAUTION
are supposed to follow.
2. The maximum wiring length to the motor is 30m.
If the wiring distance between the drive unit and motor is 20m or longer, use a
thick wire so that the cable voltage drop is 2% or less.
3. Always wire the grounding wire.
CNP2
o
C product
CNP3
(U, V, W, )
5.5 10
3.5 12
CNP2
(P,C)
2 14
3.5 12
2 14 1.2516
Magnetic
brake
- -
5 - 3
5. Selection of Peripheral Devices
5-2 Selection of no-fuse breaker and contactor
Always select the no-fuse breaker and contactor properly, and install them to each drive unit to prevent
disasters.
5-2-1 Selection of no-fuse breaker
Calculate a breaker selection current from the rated output and th e nominal input voltage of the drive unit
as in the expression below. And then select the minimum capacity no-fuse breaker whose rated current
meets the breaker selection current.
Breaker selection current [A] =
Unit type
Rated output
Breaker selection
current
Recommended
breaker
(Mitsubishi Electric
Corp.: option part)
Rated current of the
recommended
breaker
Unit type
Rated output
Breaker selection
current
Recommended
breaker
(Mitsubishi Electric
Corp.: option part)
Rated current of the
recommended
breaker
Option part: A breaker is not prepared as an NC unit accessory, so purchase the part from your dealer, etc.
No-fuse breaker selection current for 200V input [A]
Nominal input voltage [V]
Selection of no-fuse breaker for 200V input [A]
NF30-
SW3P-10A
NF30-
SW3P-20A
MDS-D-SVJ3-
NF30-
SW3P-15A
MDS-D-SPJ3-
NF30-
SW3P-30A
NF30-
SW3P-15A
NF50-
CW3P-50A
NF30-
SW3P-20A
NF100-
CW3P-60A
× 200 [V]
NF30-
SW3P-30A
NF100-
CW3P-100A
1. It is dangerous to share a no-fuse breaker for multiple drive units, so do not
share it. Always install the breakers for each drive unit.
CAUTION
2. If the control power (L11, L21) must be protected, select according to the
section "5-4-1 Circuit protector ".
5 - 4
5. Selection of Peripheral Devices
5-2-2 Selection of contactor
Select the contactor selection current that is calculated from the rated output and the nominal input
voltage of the drive unit as in the expression below. And then select the contactor whose conventional
free-air thermal current meets the contactor selection current.
Contactor selection current [A] =
Contactor selection current for 200V input [A]
Nominal input voltage [V]
× 200 [V]
Unit type
Rated output
Contactor selection
current
Recommended
contactor
(Mitsubishi Electric
Corp.: option part)
Free-air thermal
current of the
recommended
contactor
Unit type
Rated output
Contactor selection
current
Recommended
contactor
(Mitsubishi Electric
Corp.: option part)
Free-air thermal
current of the
recommended
contactor
Option part: A breaker is not prepared as an NC unit accessory, so purchase the part from your dealer, etc.
Select a contactor whose excitation coil does not operate at 15mA or less.
5 - 5
5. Selection of Peripheral Devices
5-3 Selection of earth leakage breaker
When installing an earth leakage breaker, select the breaker on the following basis to prevent the
breaker from malfunctioning by the higher frequency earth leakage current generated in the servo or
spindle drive unit.
(1) Selection
Obtaining the earth leakage current for all drive units referring to the following table, select an earth
leakage breaker within the “rated non-operation sensitivity current”.
Usually use an earth leakage breaker for inverter products that function at a leakage current within
the commercial frequency range (50 to 60Hz).
If a product sensitive to higher frequencies is used, the breaker could malfunction at a level less
than the maximum earth leakage current value.
Unit Earth leakage current Maximum earth leakage current
MDS-D-SPJ3-075 to 110 6mA 15mA
MDS-D-SVJ3-03 to 35 1mA 2mA
(Note) Maximum earth leakage current: Value that considers wiring length and grounding, etc.
(Commercial frequency 50/60Hz)
Earth leakage current for each drive unit
(2) Measurement of earth leakage current
When actually measuring the earth leakage current, use a product that is not easily affected by the
higher frequency earth leakage current. The measurement range should be 50 to 60Hz.
1. The earth leakage current tends to increase as the motor capacity increases.
2. A higher frequency earth leakage current will always be generated because the
inverter circuit in the drive unit switches the transistor at high speed. Always
POINT
ground to reduce the higher frequency earth leakage curre nt as much as
possible.
3. An earth leakage current containing higher frequency may reach approx. several
hundreds of mA. According to IEC479-2, this level is not hazardous to the
human body.
5 - 6
5. Selection of Peripheral Devices
5-4 Branch-circuit protection (for control power supply)
5-4-1 Circuit protector
This breaker is used to switch the control power and to provide overload and short-circuit protection.
When connecting a circuit protector or breaker to the power input (TE3 terminals L11 and L21) for the
control circuit, use a product that does not trip (incorrectly activate) by a rush current when the power is
turned ON. A circuit protector with inertial delay and an operation delayed type breaker are available to
prevent unnecessary tripping. Select the product to be used according to the machine specifications.
The rush current and rush conductivity time differ according to the power impedance and power ON
timing, so select a product that does not trip even under the conditions listed in the following table.
Rush current: Ip = 30A
(per 1 unit)
POINT
36.8%
I [A]
Time
constant: T = 9ms
Rush conductivity time:
Time to reach 36.8% of rush current Ip,
equivalent to breaker operation characteristics operation time.
t [ms]
When collectively protecting the control circuit power for multiple units, select a
circuit protector or breaker that satisfies the total sum of the rush current Ip.
The largest value is used for the rush conductivity time T.
5-4-2 Fuse protection
The fuse of branch-circuit protection must use UL class CC, J or T. In the selection, please consider rush
current and rush conductive time.
Selection of branch-circuit protection fuse
Connected total of unit
1 – 4 20
5 – 8
Rated [V] Current [A] AWG
Fuse (Class CC) Wire Size
600
35
16 to 14
For continued protection against risk of fire, replace only with same type 600
CAUTION
V, 20 or 35 A (UL CLASS CC) fuse.
5 - 7
5-5 Noise filter
(1) Selection
Use an EMC noise filter if the noise conducted to the power line must be reduced. Select an EMC
noise filter taking the drive unit's input rated voltage and input rated current into consideration.
(2) Noise filter mounting position
Install the noise filter to the drive unit’s power input as the diagram below indicates.
Power distribu tion
panel
Breaker
Power
supply
5. Selection of Peripheral Devices
Noise filter
AC reactor
Contactor
R
S
Drive unit
T
(Note) The noise filter must be prepared by the user.
Recommended devices: Densei-lambda MX13 Series
Soshin Electric HF3000C-TM Series
(Note) The above devices may be changed at the manufacturer's discretion.
Contact each manufacturer for more information.
5 - 8
5. Selection of Peripheral Devices
5-6 Surge absorber
When controlling a magnetic brake of a servomotor in DC OFF circuit, a surge absorber must be
installed to protect the relay contacts and brakes. Commonly a varistor is used.
(1) Selection of varistor
When a varistor is installed in parallel with the coil, the surge voltage can be adsorbed as heat to
protect a circuit. Commonly a 120V product is applied. When the brake operation time is delayed,
use a 220V product. Always confirm the operation with an actual machine.
(2) Specifications
Select a varistor with the following or equivalent specifications. To prevent short-circuiting, attach a
flame resistant insulation tube, etc., onto the leads as shown in the following outline dimension
drawing.
Varistor specifications
Varistor
voltage
Varistor type
ERZV10D121
TNR10V121K
ERZV10D221
TNR10V221K
(Note 1) Selection condition: When ON/OFF frequency is 10 times/min or less, and exciting current is 2A or less
(Note 2) ERZV10D121 and ERZV10D221 are manufactured by Matsushita Electric Industrial Co., Ltd.
TNR10V121K and TNR10V221K are manufactured by MARCON Electronics Co., Ltd.
Normally use a product with 120V varistor voltage. If there is no allowance for the
POINT
brake operation time, use the 220V product. A varistor whose voltage exceeds 220V
cannot be used, as such varistor will exceed the specifications of the relay in the unit.
Max.
limit
Electrostatic
capacity
(reference
value)
5 - 9
5. Selection of Peripheral Devices
5-7 Relay
Use the following relays for the input/output interface (motor brake output: MBR, contactor output: MC,
near point dog : DOG external emergency stop : EMGX.)
Interface name Selection example
For digital input signal (DOG, EMGX) Use a minute signal relay (twin contact) to prevent a contact defect.
<Example> OMRON: G2A type, MY type
For digital output signal (MBR, MC) Use a compact relay with 24VDC, 40mA or less.
<Example> OMROM: MY type
5 - 10
Appendix 1. Outline Dimension Drawings
Appendix 1-1 Outline dimension drawings of servomotor....................................................................A1-2
Appendix 1-1 Outline dimension drawings of servomotor
Appendix 1-1-1 HF motor
• HF75S-A48 • HF105S-A48
• HF75T-A48 • HF105T-A48
L
38
33
5.5
7.5 3
25
Ø14h6
[Unit: mm]
4-Ø6.6 mounting hole
Use a hexagon
socket bolt.
F90
45°
Ø118
Ø100
88.5
54
50.9
13
Detector connector
CM10-R10P
Power connector
CE05-2A18-10PD-B
21
KL
Oil seal
Ø36
Ø80h7
44
5.3
14
3
18
12
A A
Ø14
8.9
Ø18
M8×1.0
14
screw
Oil seal
Plain washer 8
U nut M8×1.0
Ø36
Ø80h7
Ta
1/10
4-Ø6.6 mounting hole
Use a hexagon
socket bolt.
F
90
45°
Ø100
Ø118
88.5
-0.03
-0.03
5
5
3.55
0
Cross section A-A
Servomotor type L KL
HF75F-A48 126.5 61
HF105F-A48 162.5 97
(Note 1) Use a friction coupling (Spun ring, etc.) to connect with the load.
(Note 2) Attach the cannon connector facing downward to improve the splash-proof performance.
A1 - 2
54
0
per
Appendix 1. Outline Dimension Drawings
• HF75BS-A48 • HF105BS-A48
• HF75BT-A48 • HF105BT-A48
38
[Unit: mm]
4-Ø6.6 mounting hole
Use a hexagon
L
33
5.5
7.5 3
25
Ø14h6
socket bolt.
F90
45°
Ø118
Ø100
88.5
54
12.5
63.4
Detector connector
CM10-R10P
50.9
13
66
Brake connector
CM10-R2P
Power connector
CE05-2A18-10PD-B
21
KL
Oil seal
Ø36
Ø80h7
44
5.3
14
3
18
12
A A
Ø14
8.9
Ø18
screw
M8×1.0
U nut M8×1.0
14
Ta
Oil seal
Plain washer 8
Ø36
Ø80h7
1/10
4-Ø6.6 mounting hole
Use a hexagon
socket bolt.
F
90
45°
Ø100
Ø118
88.5
-0.03
-0.03
5
5
3.55
0
Cross section A-A
Servomotor type L KL
HF75B□-A48 167.5 61
HF105B□-A48 203.5 97
(Note 1) Use a friction coupling (Spun ring, etc.) to connect with the load.
(Note 2) Attach the cannon connector facing downward to improve the splash-proof performance.
(Note 1) Use a friction coupling (Spun ring, etc.) to connect with the load.
(Note 2) Attach the cannon connector facing downward to improve the splash-proof performance.
A1 - 4
112.5
13.5
58
0
5
-0.03
4.3
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.