Lenze ERBDxxxRxxxxRB User Manual [en, de, fr]

EDKRBDRB47R
.=+o
Ä.=+oä
L−force Drives
Montageanleitung
Mounting Instructions
Instructions de montage
ERB
ERBDxxxxxxxxRB
Bremswiderstand
Résistance de freinage
Lesen Sie zuerst diese Anleitung und die Dokumentation zum
Grundgerät, bevor Sie mit den Arbeiten beginnen! Beachten Sie die enthaltenen Sicherheitshinweise.
Please read these instructions and the documentation of the standard
device before you start working! Observe the safety instructions given therein!
Lire le présent fascicule et la documentation relative à l’appareil de base
avant toute manipulation de l’équipement ! Respecter les consignes de sécurité fournies.
Inhalt i
1 Über diese Dokumentation 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Informationen zur Gültigkeit 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Zielgruppe 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Dokumenthistorie 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4 Verwendete Konventionen 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5 Verwendete Hinweise 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 Sicherheitshinweise 8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 Allgemeine Sicherheitshinweise 8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Restgefahren 9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Produktbeschreibung 12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Übersicht 12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Identifikation 13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Bestimmungsgemäße Verwendung 14 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Auslegungsbedingungen 15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Technische Daten 17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 Allgemeine Daten und Einsatzbedingungen 17 . . . . . . . . . . . . . . . . . . . .
4.2 Bemessungsdaten 19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Mechanische Daten 20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Mechanische Installation 21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 Montageschritte 21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 Elektrische Installation 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1 Wichtige Hinweise 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 Anschlussdaten 22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3 Anschlussplan 23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4 Montageschritte 24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 Wartung 25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1 Wartungsintervalle 25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2 Wartungsarbeiten 25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EDKRBDRB47R DE/EN/FR 2.0
3
1
Über diese Dokumentation
Informationen zur Gültigkeit

1 Über diese Dokumentation

0Abb. 0Tab. 0

1.1 Informationen zur Gültigkeit

Diese Anleitung ist gültig für
ƒ Bremswiderstände ERBDxxxRxxxxRB

1.2 Zielgruppe

Diese Dokumentation richtet sich an qualifiziertes Fachpersonal nach IEC 60364.
Qualifiziertes Fachpersonal sind Personen, die für die auszuführenden Tätigkei­ten bei der Aufstellung, Montage, Inbetriebsetzung und dem Betrieb des Pro­dukts über entsprechende Qualifikationen verfügen.
Tipp!
Informationen und Hilfsmittel rund um die Lenze−Produkte finden Sie im Download−Bereich unter
http://www.Lenze.com
4
EDKRBDRB47R DE/EN/FR 2.0

1.3 Dokumenthistorie

Materialnummer Version Beschreibung
13248207 1.0 05/2008 TD29 Erstausgabe
.=+o 2.0 02/2011 TD29 Überarbeitung

1.4 Verwendete Konventionen

Informationsart Auszeichnung Beispiele/Hinweise
Zahlenschreibweise
Dezimaltrennzeichen
Warnhinweise
UL−Warnhinweise
UR−Warnhinweise
Textauszeichnung
Programmname » « PC−Software
Symbole
Seitenverweis Verweis auf eine andere Seite mit
Über diese Dokumentation
Dokumenthistorie
Punkt Es wird generell der Dezimalpunkt
 
verwendet. Zum Beispiel: 1234.56
Werden nur in der englischen Spra­che verwendet.
Zum Beispiel: »Engineer«, »Global Drive Control« (GDC)
zusätzlichen Informationen Zum Beispiel: 16 = siehe Seite 16
1
EDKRBDRB47R DE/EN/FR 2.0
5
1

1.5 Verwendete Hinweise

Über diese Dokumentation
Verwendete Hinweise
Um auf Gefahren und wichtige Informationen hinzuweisen, werden in dieser Dokumentation folgende Piktogramme und Signalwörter verwendet:
Sicherheitshinweise
Aufbau der Sicherheitshinweise:
Gefahr!
(kennzeichnet die Art und die Schwere der Gefahr)
Hinweistext
(beschreibt die Gefahr und gibt Hinweise, wie sie vermieden werden kann)
Piktogramm und Signalwort Bedeutung
Gefahr!
Gefahr!
Stop!
Anwendungshinweise
Gefahr von Personenschäden durch gefährliche elektri­sche Spannung
Hinweis auf eine unmittelbar drohende Gefahr, die den Tod oder schwere Verletzungen zur Folge haben kann, wenn nicht die entsprechenden Maßnahmen getroffen werden.
Gefahr von Personenschäden durch eine allgemeine Gefahrenquelle
Hinweis auf eine unmittelbar drohende Gefahr, die den Tod oder schwere Verletzungen zur Folge haben kann, wenn nicht die entsprechenden Maßnahmen getroffen werden.
Gefahr von Sachschäden
Hinweis auf eine mögliche Gefahr, die Sachschäden zur Folge haben kann, wenn nicht die entsprechenden Maß­nahmen getroffen werden.
Piktogramm und Signalwort Bedeutung
Hinweis!Tipp!
6
Wichtiger Hinweis für die störungsfreie Funktion
Nützlicher Tipp für die einfache Handhabung
Verweis auf andere Dokumentation
EDKRBDRB47R DE/EN/FR 2.0
Über diese Dokumentation
Verwendete Hinweise
Spezielle Sicherheitshinweise und Anwendungshinweise für UL und UR
Piktogramm und Signalwort Bedeutung
Sicherheitshinweis oder Anwendungshinweis für den Betrieb eines UL−approbierten Geräts in UL−approbier-
Warnings!
Warnings!
ten Anlagen.
Möglicherweise wird das Antriebssystem nicht UL−ge­recht betrieben, wenn nicht die entsprechenden Maß­nahmen getroffen werden.
Sicherheitshinweis oder Anwendungshinweis für den Betrieb eines UR−approbierten Geräts in UL−approbier­ten Anlagen.
Möglicherweise wird das Antriebssystem nicht UL−ge­recht betrieben, wenn nicht die entsprechenden Maß­nahmen getroffen werden.
1
EDKRBDRB47R DE/EN/FR 2.0
7
2
Sicherheitshinweise
Allgemeine Sicherheitshinweise

2 Sicherheitshinweise

2.1 Allgemeine Sicherheitshinweise

Gefahr!
Wenn Sie die folgenden grundlegenden Sicherheitsmaßnahmen missachten, kann dies zu schweren Personenschäden und Sachschäden führen:
ƒ Lenze−Antriebs− und Automatisierungskomponenten ...
... ausschließlich bestimmungsgemäß verwenden. ... niemals trotz erkennbarer Schäden in Betrieb nehmen. ... niemals technisch verändern. ... niemals unvollständig montiert in Betrieb nehmen. ... niemals ohne erforderliche Abdeckungen betreiben. ... können während und nach dem Betrieb − ihrer Schutzart entsprechend −
spannungsführende, auch bewegliche oder rotierende Teile haben. Oberflä­chen können heiß sein.
ƒ Alle Vorgaben der beiliegenden und zugehörigen Dokumentation
beachten. Dies ist Voraussetzung für einen sicheren und störungsfreien Betrieb sowie
für das Erreichen der angegebenen Produkteigenschaften. Die in diesem Dokument dargestellten verfahrenstechnischen Hinweise
und Schaltungsausschnitte sind Vorschläge, deren Übertragbarkeit auf die jeweilige Anwendung überprüft werden muss. Für die Eignung der angege­benen Verfahren und Schaltungsvorschläge übernimmt der Hersteller keine Gewähr.
ƒ Alle Arbeiten mit und an Lenze−Antriebs− und
Automatisierungskomponenten darf nur qualifiziertes Fachpersonal ausführen.
Nach IEC 60364 bzw. CENELEC HD 384 sind dies Personen, ... ... die mit Aufstellung, Montage, Inbetriebsetzung und Betrieb des Produkts
vertraut sind. ... die über die entsprechenden Qualifikationen für ihre Tätigkeit verfügen. ... die alle am Einsatzort geltenden Unfallverhütungsvorschriften, Richtli-
nien und Gesetze kennen und anwenden können.
8
EDKRBDRB47R DE/EN/FR 2.0
Sicherheitshinweise
Restgefahren
2

2.2 Restgefahren

Gefahr!
Gefährliche elektrische Spannung Während des Betriebs des Grundgeräts und bis zu 3 Minuten nach
dem Netzabschalten können an den Anschlüssen des
Bremswiderstands gefährliche elektrische Spannungen anliegen.
Mögliche Folgen:
ƒ Tod oder schwere Verletzungen beim Berühren der
Anschlussklemmen.
Schutzmaßnahmen:
ƒ Vor allen Arbeiten am Bremswiderstand das Grundgerät vom
Netz trennen.
ƒ Alle Leistungsklemmen auf Spannungsfreiheit prüfen. ƒ Den Montageort so wählen, dass die in den Technischen Daten
genannten Einsatzbedingungen immer gewährleistet sind.
Gefahr!
Heiße Oberfläche während des Betriebs
Der Bremswiderstand wird während des Betriebs sehr heiß. (Temperaturen siehe Technische Daten.)
Mögliche Folgen:
ƒ Schwere Verbrennungen beim Berühren des Bremswiderstands. ƒ Feuer oder Schwelbrand, wenn sich brennbare Materialien oder
Stoffe in der Nähe des Bremswiderstands befinden oder dorthin gelangen können.
Schutzmaßnahmen:
ƒ Vor Arbeiten am Bremswiderstand dessen
Oberflächentemperatur prüfen.
ƒ Den Montageort so wählen, dass die in den Technischen Daten
genannten Einsatzbedingungen immer gewährleistet sind.
ƒ Den Montageort durch geeignete Brandschutzmaßnahmen und
einen Berührschutz sichern.
EDKRBDRB47R DE/EN/FR 2.0
9
2
Sicherheitshinweise
Restgefahren
Stop!
Mögliche Überhitzung des Bremswiderstands während des Betriebs
Durch ungenügende Wärmeabfuhr kann der Bremswiderstand während des Betriebs überhitzen.
Mögliche Folgen:
ƒ Der Bremswiderstand wird zerstört. ƒ Der Antrieb wird nicht abgebremst sondern trudelt aus.
Schutzmaßnahmen:
ƒ Den Thermokontakt des Bremswiderstands immer anschließen. ƒ Den Thermokontakt so in die Anlagenüberwachung einbinden,
dass bei Überhitzung des Bremswiderstands die Netzversorgung des Grundgerätes abgeschaltet wird (z. B. die Netzschütz−Ansteuerung abschalten).
10
EDKRBDRB47R DE/EN/FR 2.0
Sicherheitshinweise
Restgefahren
Warnings!
Conditions of Acceptability:
ƒ These devices are only intended to be used as an integral part of
power conversion equipment (UL508C applications).
ƒ They shall be mounted on an appropriate surface (in order to
maintain enclosure rating type 1).
ƒ The terminals "Terminal block" (RB1/RB2) and "Terminal Block"
(T1/T2) have been evaluated for field wiring.
ƒ No performance tests (e.g. temperature, dielectric strength and
abnormal operation tests) have been performed. Since these devices are intended to be used as an integral part of
power conversion equipment (UL508C applications) only, the performance tests for these devices shall be carried out in accordance with the requirements in the standard for Power Conversion Equipment UL508C.
Tests shall be based on the duty cycle indicated and determined by the end−use application.
Following UL508C tests shall be considered: – Temperaturetests – Dielectric strength tests – Breakdown of component tests (e.g. failure of the control
circuitry to maintain the proper duty cycle)
ƒ Settings and suitability of thermal protectors and thermal
overload relays have not been evaluated. The need for additional tests shall be reconsidered in the end−use application.
2
EDKRBDRB47R DE/EN/FR 2.0
11
3
Produktbeschreibung
Übersicht

3 Produktbeschreibung

3.1 Übersicht

Lieferumfang
Pos. Beschreibung
Bremswiderstand Montageanleitung
Elemente am Bremswiderstand
ERBDRB001
12
Pos. Beschreibung
Klemmenkasten Kabelverschraubung Bremswiderstand−Leitung Kabelverschraubung Thermokontakt−Leitung Befestigungswinkel Warnhinweis Typenschild
EDKRBDRB47R DE/EN/FR 2.0
Produktbeschreibung
Identifikation
3

3.2 Identifikation

Typenschlüssel ERBx xxxx xxxx R B
Produktreihe
Widerstand RB [W] z. B. 470R = 47 W
075D = 7,5 W
Dauerleistung Pd [W] z. B. 120W = 120 W
01K2 = 1,2 kW
Ausführung R = Rüttelfest
ERBDRB002
Schutzart B = IP20
EDKRBDRB47R DE/EN/FR 2.0
13
3

3.3 Bestimmungsgemäße Verwendung

Produktbeschreibung
Bestimmungsgemäße Verwendung
Bremswiderstände
ƒ nur unter den in dieser Betriebsanleitung vorgeschriebenen
Einsatzbedingungen betreiben.
ƒ sind Komponenten
zum Einbau in eine Maschine.zum Zusammenbau mit anderen Komponenten zu einer Maschine.
Die Inbetriebnahme des Bremswiderstands ist solange untersagt, bis fest­gestellt wurde, dass die Maschine, in welche der Bremswiderstand einge­baut werden soll, den Bestimmungen der EG−Maschinenrichtlinie ent­sprechen.
ƒ sind elektrische Betriebsmittel zum Einbau in Schaltschränke oder
ähnliche abgeschlossene Betriebsräume.
ƒ erfüllen die Schutzanforderungen der EG−Richtlinie "Niederspannung". ƒ sind keine Maschinen im Sinne der EG−Richtlinie Maschinen. ƒ sind keine Haushaltsgeräte, sondern als Komponenten ausschließlich für
die Weiterverwendung zur gewerblichen Nutzung bestimmt.
Antriebssysteme mit Bremswiderständen
ƒ Die Verantwortung für die Einhaltung der EG−Richtlinien in der
Maschinenanwendung liegt beim Weiterverwender.
Jede andere Verwendung gilt als sachwidrig!
14
EDKRBDRB47R DE/EN/FR 2.0
Produktbeschreibung
Auslegungsbedingungen
3

3.4 Auslegungsbedingungen

Beim Einsatz von Bremswiderständen beachten:
ƒ Mittelwert der generatorischen Leistung < Dauerleistung P
Bremswiderstands.
ƒ Generatorische Leistung während der Bremszeit < Wärmemenge Q
Bremswiderstands.
ƒ Bremszeit < 10 % der Zykluszeit (Bremszeit + Pausenzeit). ƒ Thermokontakt immer anschließen und so in die Anlagenüberwachung
einbinden, dass bei Überhitzung des Bremswiderstands die Netzversorgung des Grundgeräts abgeschaltet wird.
Zu jedem Zeitpunkt muss gelten: Im Zeitintervall t klus) müssen die kumulierten Bremszeiten t
brk,max
sein.
dauer t
Berechnung
Bremswiderstand−Zyklus t
Q
+
+
B
P
d
Q
B
P
d
QB@ R
U
Q
B
R
B
U
max
mit
Wärmemenge in Ws Dauerleistung in W
brk,max
B
mit
2
max
Wärmemenge in Ws Widerstand in W Max. Betriebsspannung in V
t
cyc,RB
Max. Bremsdauer t
t
brk,max
cyc,RB
immer £ der maximalen Brems-
brk
:
cyc,RB
innerhalb des Zeitintervalls t
des
d
des
B
(Bremswiderstandzy-
:
cyc,RB
EDKRBDRB47R DE/EN/FR 2.0
15
3
£
£
£
£
³
£
Produktbeschreibung
Auslegungsbedingungen
Beispiele für die Auswertung der Bedingung
Gegeben ist der Bremswiderstandzyklus t dauer t
= 10 s. Die Bremszeiten t
brk,max
brk
= 150 s und die max. Brems-
cyc,RB
und der Prozesszyklus t
cyc,Prc
sind bei-
spielhaft.
0.5 0.5 1
1
ü
0.5 0.5 1
ü
ü
0.5 0.5 1
= 6.5 s
brk brk,max
tt
S
= 150 s
cyc,RB
t
Im oberen Beispiel wird die Auslegungsbedingung zu jedem Zeitpunkt einge­halten. Im unteren Beispiel wird die Auslegungsbedingungen einmal nicht ein­gehalten, das heißt, der gewählte Bremswiderstand ist für den vorgegebenen
= 6.5 s
brk brk,max
tt
S
0.5 0.5
0.5 0.5
1 1
[s]
brk
t
= 7 s
brk brk,max
tt
S
1 11
û
ü
ü
= 11 s
1 1
brk brk,max
tt
S
= 10 s
brk brk,max
tt
S
1 1
11111
1 1
1010 5050 100100 200200150150
t [s]
[s]
brk
t
cyc,Prs
t
û
cyc,Prs
t
cyc,Prs
t
ü
= 10 s
cyc,Prs
t
brk brk,max
tt
S
cyc,Prs
t
1010 5050 100100 200200150150
t [s]
Prozess nicht geeignet. Setzen Sie einen Bremswiderstand mit größerer Lei­stung (kürzerem Bremswiderstandzyklus t
cyc,RB
) ein.
16
EDKRBDRB47R DE/EN/FR 2.0
Allgemeine Daten und Einsatzbedingungen

4 Technische Daten

4.1 Allgemeine Daten und Einsatzbedingungen

Konformität und Approbation
Konformität
CE
Approbation
UR UL508 Industrial Control Equipment, Underwriter Laborato-
Personenschutz und Geräteschutz
Schutzart
Thermokontakt
Ausführung Öffner, 180 °C Schaltleistung 250 V AC / 2.5 A
Umweltbedingungen
Klima
Lagerung Transport 7K2 (−25 ... +70 °C) Betrieb 7K2 (−10 ... +55 °C)
Aufstellhöhe 0 ... 4000 m üNN
Verschmutzung EN 61800−5−1 Verschmutzungsgrad 2 Rüttelfestigkeit
Transport IEC/EN 60721−3−7
Betrieb IEC/EN 60721−3−3
2006/95/EG Niederspannungsrichtlinie
ries (File−No. E212934) for USA and Canada
EN 60529 NEMA 250 Berührschutz nach
IEC/EN 60721−3−7
IEC/EN 60721−3−7
IP20
Typ 1
7K2 (−25 ... +55 °C)
Stromreduzierung von +45 ... +55 °C: 2.5 %/°C
1000 ... 4000 m üNN: Stromreduzierung 5 %/1000 m
7M3 2 ... 9 Hz: Amplitude 7.5 mm 9 ... 200 Hz: beschleunigungsfest bis 20 m/s 200 ... 500 Hz: beschleunigungsfest bis 40 m/s 3M8 ortsfest 2 ... 9 Hz: Amplitude 15 mm 9 ... 200 Hz: beschleunigungsfest bis 50 m/s 7M3 ortsveränderlich 2 ... 9 Hz: Amplitude 7.5 mm 9 ... 200 Hz: beschleunigungsfest bis 20 m/s 200 ... 500 Hz: beschleunigungsfest bis 40 m/s
Technische Daten
4
2
2
2
2
2
EDKRBDRB47R DE/EN/FR 2.0
17
4
Technische Daten
Bemessungsdaten
Montagebedingungen
Montageort
Einbaulage Vertikal−hängend mit Anschlussleitungen unten. Einbaufreiräume
oben > 200 mm unten > 100 mm seitlich > 25 mm

4.2 Bemessungsdaten

Elektrische Daten
ERBD020R03K0RB 20 3000 450 ERBD033R01K9RB 33 1900 285 ERBD047R01K2RB 47 1200 180
R
B
P
d
Q
B
U
max
l Der Montageort muss den in den "Allgemeinen
Daten" genannten Geräteeigenschaften ent­sprechen.
l Brennbare Materialien oder Stoffe dürfen sich
nicht in der Nähe des Bremswiderstands befinden.
l Die vom Bremswiderstand erzeugte Wärme muss
ungehindert abgeführt werden.
R
B
[W] [W] [kWs] [VDC]
Widerstand Dauerleistung Wärmemenge Max. Betriebsspannung
P
d
Q
B
U
max
800
18
Temperaturen
T
nom
Innen 500 650 1000 Am Gehäuse 250 400 750 An der Einbaufrei-
raumgrenze
*)
T
nom
T
TK
T
max
*) Gemessen bei Umgebungsmedium Luft (kleine Wärmeleitzahl); wenn sich
200 300 500
Maximale Temperatur bei Bessungsdaten Temperatur bei der der Thermokontakt auslöst Maximale Temperatur bei sachwidriger Verwendung
Materialien/Stoffe an der Einbaufreiraumgrenze befinden, die sich aufheizen (größere Wärmeleitzahl), steigt die Temperatur weiter an.
T
[°C]
TK
T
max
EDKRBDRB47R DE/EN/FR 2.0

4.3 Mechanische Daten

Technische Daten
Mechanische Daten
4
ERBD020R03K0RB ERBD033R01K9RB ERBD047R01K2RB
EDKRBDRB47R DE/EN/FR 2.0
ERBDRB003
a b c3 d1 d3 e g1 g2 h1 h2 k1 k2 o1
[mm] [kg]
275 749 240
185 749 150 628 6.6
185 549 150 428 4.8
628
9
120 6.5 12 25 25 200 100 25
9.1
19
5
Mechanische Installation
Montageschritte

5 Mechanische Installation

5.1 Montageschritte

So montieren Sie den Bremswiderstand:
1. Wählen Sie einen geeigneten Montageort.
Der Montageort muss die in den Technischen Daten genannten
Einsatzbedingungen immer gewährleisten; ggf. zusätzliche Maßnahmen ergreifen.
Eine ungehinderte Luftzirkulation zum Abführen der Wärme muss
gewährleistet sein.
2. Verschrauben Sie den Bremswiderstand am Montageort.
Der Montageort und das Montagematerial muss die mechanische
Verbindung dauerhaft gewährleisten.
20
EDKRBDRB47R DE/EN/FR 2.0

6 Elektrische Installation

6.1 Wichtige Hinweise

Stop!
Mögliche Überhitzung des Bremswiderstands während des Betriebs
Durch ungenügende Wärmeabfuhr kann der Bremswiderstand während des Betriebs überhitzen.
Mögliche Folgen:
ƒ Der Bremswiderstand wird zerstört. ƒ Der Antrieb wird nicht abgebremst sondern trudelt aus.
Schutzmaßnahmen:
ƒ Den Thermokontakt des Bremswiderstands immer anschließen. ƒ Den Thermokontakt so in die Anlagenüberwachung einbinden,
dass bei Überhitzung des Bremswiderstands die Netzversorgung des Grundgerätes abgeschaltet wird (z. B. die Netzschütz−Ansteuerung abschalten).

6.2 Anschlussdaten

Elektrische Installation
Wichtige Hinweise
6
RB1, RB2 (Bremswider­stand)
PE (Schutzleiter)
T1, T2 (Thermokontakt)
EDKRBDRB47R DE/EN/FR 2.0
Kabelverschrau-
bung
M25
M12 Schraubklemme
Anschlussart Anschlussgröße Anzugsmoment
Schraubklemme
0.5 ... 10 mm 20 ... 6 AWG
Schraube M4
0.25 ... 4 mm
24 ... 12 AWG
2
1.5 ... 1.8 Nm
13.3 ... 15.9 lb−in
2.2 ... 2.7 Nm
19.5 ... 23.9 lb−in
2
0.6 ... 0.8 Nm
5.3 ... 7.1 lb−in
21
6
Elektrische Installation
Anschlussplan

6.3 Anschlussplan

Variante 1 (kurze Leitungen)
R
B
RB1 RB2
Variante 2 (lange Leitungen)
R
B
RB1 RB2
T1 T2
PE
< 0.5 m
ERBG008
Verdrillte Leitungen
T1 T2
PE
PES
<5m
PES
22
HF−Schirmabschluss durch großflächige PE−Anbindung
Verdrillte Leitungen
ERBG007
EDKRBDRB47R DE/EN/FR 2.0

6.4 Montageschritte

So schließen Sie den Bremswiderstand an:
1. Grundgerät vom Netz trennen und alle Leistungsklemmen auf Spannungsfreiheit prüfen.
2. Klemmenabdeckung demontieren.
3. Bremswiderstand−Leitung auflegen:
Bei einer Leitungslänge bis 0.5 m verdrillte Leitung verwenden
(Anschlussplan Variante 1).
Bei einer Leitungslänge bis 5 m geschirmte Leitung verwenden
(Anschlussplan Variante 2).
Leitung durch Kabelverschraubung ziehen.Adern am Bremswiderstand am Anschluss RB1, RB2 und PE auflegen,
dabei Anzugsmoment beachten. PE−Anschluss nach EN 61800−5−1 ausführen.
Kabelverschraubung festziehen.
Bei geschirmter Leitung: Der Schirm muss fest und großflächig mit der Kabelverschraubung verbunden sein.
Adern und Schirm am Grundgerät auflegen, dabei Dokumentation des
Grundgerätes beachten.
4. Thermokontakt−Leitungen auflegen:
Verdrillte Leitung verwenden.Leitung durch Kabelverschraubung ziehen.Adern am Bremswiderstand am Anschluss T1 und T2 auflegen, dabei
Anzugsmoment beachten.
Kabelverschraubung  festziehen.Den Thermokontakt so in die Anlagenüberwachung einbinden, dass bei
Überhitzung des Bremswiderstands die Netzversorgung abgeschaltet wird.
5. Klemmenabdeckung montieren.
Elektrische Installation
Montageschritte
6
ERBDRB004
EDKRBDRB47R DE/EN/FR 2.0
23