9400 regenerative power supply module | Parameter setting
1About this documentation
This documentation contains information about the regenerative power supply module.
Please read the Mounting Instructions supplied with the regenerative power
supply module before you start working!
The Mounting Instructions contain safety information which must be observed!
Target group
This documentation is directed at all persons who parameterise and diagnose the
regenerative power supply module by means of the L-force »Engineer« software and the
keypad.
Information on the validity
The information provided in this documentation is valid for the following standard
devices:
About this documentation
Product seriesType designationFrom software version
Servo Drives 9400E94AxRNxxxx1.0
Document history
VersionDescription
2.306/2014TD05Error corrections
2.203/2010TD05Error corrections
2.101/2009TD05Error corrections
2.011/2008TD05 • Extended by new functions for regenerative power supply module V2
•New main chapter: "CAN on board" system bus
1.107/2008TD05Error corrections
1.004/2008TD05First edition
EDS94ARNExxxx EN 2.3 - 06/2014L9
9400 regenerative power supply module | Parameter setting
About this documentation
Conventions used
1.1Conventions used
This documentation uses the following conventions to distinguish between different types
of information:
Type of informationWritingExamples/notes
Numbers
Decimal separatorPointGenerally the decimal point is used.
For example: 1234.56
Text
Program name» «The Lenze PC software »Engineer«...
WindowItalicsThe Message window... / The Options dialog box...
Variable identifierBy setting bEnable to TRUE...
Control elementBoldThe OK button... / The Copy command... / The
Sequence of menu
commands
Shortcut<Bold>Use <F1> to open the online Help.
HyperlinkUnderlined
Symbols
Page reference ( 10)Optically highlighted reference to another page. Is
Step-by-step instructions
Properties tab...
If the execution of a function requires several
commands, the individual commands are separated
by an arrow: Select File
If a command requires a combination of keys, a "+" is
placed between the key symbols:
Use <Shift>+<ESC> to...
A hyperlink is an optically highlighted reference
which is activated with a mouse click.
activated via mouse-click in this online
documentation.
Step-by-step instructions are indicated by a
pictograph.
Open to...
1.2Terminology used
TermMeaning
»Engineer«Lenze software which supports you throughout the whole machine life cycle -
Code"Container" for one or several parameters used for parameter setting or
SubcodeIf a code contains several parameters, the individual parameters are stored
from planning to maintenance.
monitoring of the regenerative power supply module.
under "subcodes".
This documentation uses a slash "/" as a separator between code and subcode
(e.g. "C00118/3").
10LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
1.3Definition of notes used
The following signal words and symbols are used in this documentation to indicate
dangers and important information:
Safety instructions
Layout of the safety instructions:
Danger!
(characterises the type and severity of danger)
Note
(describes the danger and gives information about how to prevent dangerous
situations)
About this documentation
Definition of notes used
PictographSignal wordMeaning
Danger!Danger of personal injury through dangerous electrical voltage
Danger!Danger of personal injury through a general source of danger
Stop!Danger of property damage
Application notes
PictographSignal wordMeaning
Note!Important note to ensure trouble-free operation
Reference to an imminent danger that may result in death or serious personal
injury if the corresponding measures are not taken.
Reference to an imminent danger that may result in death or serious personal
injury if the corresponding measures are not taken.
Reference to a possible danger that may result in property damage if the
corresponding measures are not taken.
Tip!Useful tip for simple handling
Reference to another documentation
EDS94ARNExxxx EN 2.3 - 06/2014L11
9400 regenerative power supply module | Parameter setting
Commissioning
2Commissioning
This chapter describes three different commissioning scenarios:
A. Short setup
– Target: Adapting the regenerative power supply module to the electromechanics
and the control system.
B. Device replacement
– Target: Replacing a regenerative power supply module which has failed in a running
system by a replacement device using the "old" memory module.
C. Filter replacement
– Target: Replacing a filter which has failed in a running system.
( 13)
( 20)
( 20)
12LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
L3
N
PE
L1
L2
F1...F3
F4
K1
K1
K2
K1
L1 L2
L3
E94ARNE0xx4
X111
-UG
O
I
RFR
+UG
Rb2
Rb1
R
B
R
B
L1 L2
L3
X112
X5
GI
RFR
J
. . .
+
-
X8
+
+
+
E94AZPP0364
X2
GE24E
+
-
SB
+
-
GE
24E
X323
X324
15
4
4
E94AZMR0xx4xDB
L1 L2
L3
X109
X110
L1.2
L2.2
L3.2
L1.1
L2.1
L3.1
X321
X322
X320
X4
GODO2
K2
2.1Short setup
The short setup described in this chapter serves to adapt the regenerative power supply
module to the electromechanics and the control system. The short setup can be carried out
with the keypad or the Lenze PC software »Engineer«.
2.1.1Example circuit
Commissioning
Short setup
94PSPVR01
NameComponent
E94ARNE0xx4Regenerative power supply module
E94AZPP0364Installation backplane of regenerative power supply module
E94AZMR0...Mains filter
F1 ... F4Fuses
RFRController enable (only for regenerative feedback)
K1Mains contactor
RBBrake resistor
24-V voltage source for the control electronics
24-V voltage source for the digital inputs in accordance with IEC 61131-2
From version 02.00: Overtemperature disconnection (DO2 load: max. 50 mA)
EDS94ARNExxxx EN 2.3 - 06/2014L13
(safely separated power supply unit (SELV/PELV), in accordance with IEC 61131-2)
9400 regenerative power supply module | Parameter setting
Commissioning
Short setup
2.1.2Commissioning with the keypad
1. Switch on 24-V supply of the regenerative power supply module.
– With the first switch-on of the regenerative power supply module, the filter data are
automatically read out of the electronic filter nameplate (ENP) and temporarily
saved in the regenerative power supply module.
2. If the mains voltage is not 400/415 V, adapt the Lenze setting in C00173
– Note: A change of the setting in C00173
utilisation! In the chapter "Rated data" of the Hardware Manual, the device types
and their permissible device utilisation at different mains voltages and switching
frequencies are specified.
3. Carry out optional parameter setting:
– Parameterising the brake chopper/brake resistor
– Signal configuration
4. Save the parameter set (C00002
– By saving the parameter set, certain data such as the filter data are permanently
available in the regenerative power supply module and do not need to be read again
from the electronic filter nameplate at the next switch-on. This shortens the
initialisation time correspondingly.
5. Switch on mains voltage the DC bus is charged.
6. Deactivate controller inhibit via controller enable terminal (RFR) regenerative
feedback is enabled.
7. Controlling the regenerative power supply module via terminals
( 30)
= "11: Save start parameters").
also has an impact on the permissible device
( 22)
. ( 19)
accordingly.
14LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
2.1.3Commissioning with the Engineer
For commissioning with the Lenze PC software »Engineer« you need:
A PC with the following system requirements:
– Processor with at least 1.4 GHz
– At least 512 MB RAM and 650 MB of free hard disk space
– Operating system Microsoft® Windows® 2000 (service pack 2 or higher) or
Windows® XP
A connection to the regenerative power supply module, e. g. via the diagnostic adapter
offered by Lenze.
Commissioning
Short setup
Note!
Please observe the documentation for the diagnostic adapter!
For communication with the regenerative power supply module, at least the
control electronics of the regenerative power supply module must be supplied
with 24-V low voltage via the connector X2; detailed information on this can be
found in the Mounting Instructions for the regenerative power supply module.
Stop!
If you alter parameters in the »Engineer« while an online connection to the
regenerative power supply module is established, the changes are directly
accepted in the regenerative power supply module!
Tip!
An online connection can also be established via optional interfaces which are
provided by corresponding communication modules in the module receptacles
MXI1/MXI2 of the regenerative power supply module.
Detailed information about the different interfaces can be found in the
corresponding Communication Manuals.
EDS94ARNExxxx EN 2.3 - 06/2014L15
9400 regenerative power supply module | Parameter setting
Commissioning
Short setup
How to carry out the commissioning with the »Engineer«:
1. Start the »Engineer«.
2. Select the procedure in the Start-up wizard.
• For instance, select the option "Select component from catalog".
3. Add the corresponding components from the catalog to the project:
• Regenerative power supply module
• Available device modules
•Regenerative power supply module application
Project view example in the »Engineer«:
4. Select the regenerative power supply module in the Project view.
5. Change to the Application parameters tab in the Workspace.
6. If the mains voltage is not 400/415 V, adapt the Lenze setting accordingly in the
Mains voltage list field.
Note: A change of the setting in C00173
device utilisation! In the chapter "Rated data" of the Hardware Manual, the device
types and their permissible device utilisation at different mains voltages and
switching frequencies are specified.
16LEDS94ARNExxxx EN 2.3 - 06/2014
also has an impact on the permissible
9400 regenerative power supply module | Parameter setting
Commissioning
Short setup
7. Carry out optional parameter setting:
• Parameterising the brake chopper/brake resistor
• Signal configuration
• Establish network/communication.
8. Switch on 24-V supply of the regenerative power supply module.
• With the first switch-on of the regenerative power supply module, the filter
data are automatically read out of the electronic filter nameplate (ENP) and
temporarily saved in the regenerative power supply module.
9. Click the icon.
10. Confirm the following note with Yes to accept the changes on the project:
( 30)
( 22)
The Build project dialog box is displayed:
11. Click Build to build the project.
• After the project has been built successfully, a corresponding note is displayed.
EDS94ARNExxxx EN 2.3 - 06/2014L17
9400 regenerative power supply module | Parameter setting
Commissioning
Short setup
12. Confirm the note that the project has been built successfully with OK.
If no communication path has been configured for the regenerative power supply
module yet, the Communication path dialog box is displayed:
13. Set the bus connection (e. g. "Diagnostic adapter") to the regenerative power
supply module in the Communication path dialog box.
14. Click Connect to establish the online connection to the regenerative power supply
module.
• After the connection has been established successfully, the Transfer to device
dialog box is displayed.
Note: The following parameters are set automatically in the regenerative power
supply module via the electronic filter nameplate (ENP): C00070
C00076
• »Engineer« versions ≥ V2.9 do not
• If an older »Engineer« version is used, these parameters have to be saved prior
15. Click Start in the Transfer to device dialog box.
16. Confirm the query on whether the device is to be inhibited and the application is
to be stopped with Yes.
• Then the transmission is started.
17. After the transmission has been carried out successfully, confirm the query on
whether the application is to be started with Yes.
, C00084 and C00085.
overwrite these parameters during a
parameter download.
to a parameter download and then reset manually to the saved values.
, C00071, C00075,
18. Also confirm the query on whether the device is to be enabled with Yes.
19. Switch on mains voltage the DC bus is charged.
20. Deactivate controller inhibit via controller enable terminal (RFR) regenerative
feedback is enabled.
21. Controlling the regenerative power supply module via terminals
18LEDS94ARNExxxx EN 2.3 - 06/2014
.
9400 regenerative power supply module | Parameter setting
Note!
The regenerative power supply module still remains inhibited via the controller
enable terminal (RFR) if this terminal is set to LOW level.
Commissioning
Short setup
Please note that the regenerative power supply module will only be enabled if all
sources for controller inhibit are reset!
• The sources or trip elements that are active for controller inhibit are displayed
in a bit-coded manner in C00158
2.1.4Controlling the regenerative power supply module via terminals
If the regenerative power supply module is enabled, the application can be controlled via
the digital inputs and/or MotionBus (if it is integrated in a network).
Terminal assignment of digital inputs
TerminalAssignment (Lenze setting)
X5RFRController enable
DI1Inhibit regenerative feedback
• Function also possible via bit 01 of control word 1.
DI2Activate brake chopper
• Function also possible via bit 02 of control word 1.
DI3Reset (acknowledge) error
• A pending error message can be reset (acknowledged) by a LOW-HIGH edge if the cause of
the error message has been eliminated.
• Function also possible via bit 07 of control word 1.
.
Tip!
Detailed information on device applications can be found in the chapter
"Regenerative power supply module application
". ( 21)
EDS94ARNExxxx EN 2.3 - 06/2014L19
9400 regenerative power supply module | Parameter setting
Commissioning
Device replacement
2.2Device replacement
Scenario: The regenerative power supply module in a running system has failed.
Note!
For the procedure described below we assume that the memory module and
possibly available extension modules in the regenerative power supply module
and the filter are not affected by the failure and all parameters have been stored
with mains failure protection.
Worksteps
Replacement of the regenerative power supply module:
1. Replace regenerative power supply module.
See Mounting Instructions for the regenerative power supply module!
2. Insert memory module of the regenerative power supply module that has failed into the replacement
device.
3. If further extension modules are plugged into the failed regenerative power supply module, they must
also be inserted into the replacement device.
Further steps are not required since all required data are stored on the memory module.
2.3Filter replacement
Scenario: The filter in a running system has failed.
Note!
In the procedure described below we assume that the regenerative power
supply module is not affected by the failure.
Worksteps
Replacement of the filter:
1. Replace filter.
For a filter with an electronic nameplate (ENP):
2. Restart regenerative power supply module with connected filter to read out the filter data from the
3. Execute device command C00002
For a filter without an electronic nameplate (ENP):
See Mounting Instructions for the regenerative power supply module!
electronic nameplate.
• Restart the device either by switching the voltage supply off and on again, or via the device
command C00002
Note:
The filter is operated with the filter data from the memory module.
= "11000: Restart regenerative power supply module".
= "11: Save start parameters".
20LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
Regenerative power supply module application
3Regenerative power supply module application
This chapter provides you with information on the "Regenerative power supply module"
application by which the regenerative power supply module can be controlled via digital
inputs and input ports. Status information is provided to other applications via digital
outputs and output ports.
How to get to the parameterisation dialog of the application:
1. Select the regenerative power supply module in the Project view of the »Engineer«.
2. Change to the Application parameters tab in the Workspace.
Parameterisation dialog in the »Engineer«
The white buttons show the assignment of the control inputs and status outputs of the
application.
– The assignment is defined by the "Regenerative power supply module" application
and can, if required, be reconfigured by clicking the corresponding button.
If you click the button marked with the icon, you get to the parameterisation dialog
for the brake chopper/brake resistor, which is one level beneath.
EDS94ARNExxxx EN 2.3 - 06/2014L21
9400 regenerative power supply module | Parameter setting
Regenerative power supply module application
Parameterising the brake chopper/brake resistor
3.1Parameterising the brake chopper/brake resistor
The regenerative power supply module is equipped with an integrated brake transistor.
The required brake resistor has to be connected externally (see mounting instructions/
hardware manual).
The rated values for the brake transistor are listed in the Hardware Manual, chapter
"Rated data".
Stop!
If the connected brake resistor has a lower resistance than the parameterised
brake resistor, the brake transistor may be damaged!
The brake resistor can be thermally overloaded. Carry out protective measures
suitable for the system, e.g.:
• Parameterisation of an error response in C00574
parameterised error message in the application or machine control. I2t
utilisation of brake resistor ( 27)
• External wiring using the temperature contact on the brake resistor (e.g.
interruption of the supply via mains contactor and activation of the
mechanical brakes).
and evaluation of the
22LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
Regenerative power supply module application
Parameterising the brake chopper/brake resistor
The brake chopper/brake resistor can be parameterised in the »Engineer» on the
9400 regenerative power supply module | Parameter setting
Regenerative power supply module application
Parameterising the brake chopper/brake resistor
3.1.1Setting the voltage threshold for braking operation
The voltage threshold for braking operation is set via C00173
(reduced brake chopper threshold). When the brake chopper threshold is exceeded in the
DC bus, the brake chopper is switched on.
Mains voltage selected in C00173Effective brake chopper threshold
230 V390 V - value in C00181
400/415 V725 V - value in C00181
460/480 V765 V - value in C00181
500 V790 V - value in C00181
3.1.2Setting the brake chopper mode
For software versions below V2.0, the following applies:
The regenerative power supply module only feeds back to the mains and activates the
brake chopper if the inverter-side current reaches the maximum device current. If the
current is below the maximum device current and the DC-bus voltage is below the brake
chopper threshold, the brake chopper is not activated.
From software version V2.0 onwards, the following applies:
C00132
can be used to set the conditions for brake chopper activation:
(mains voltage) and C00181
(0 ... 100 V)
(0 ... 100 V)
(0 ... 100 V)
(0 ... 100 V)
Only at overvoltage:
The brake chopper is only activated if the DC-bus voltage has reached the brake
chopper threshold. This setting corresponds to the behaviour of the 9400 controller.
At overvoltage and overcurrent (Lenze setting):
This setting corresponds to the behaviour of regenerative power supply modules with
software versions below V2.0.
At overvoltage and overcurrent and overload:
With this setting, the brake chopper is used for energy consumption if a device
utilisation of 90 % is reached during feedback operation.
– The "normal" voltage thresholds for braking operation still apply. Setting the
voltage threshold for braking operation ( 24)
– To protect the brake chopper against damage, monitoring of the Ixt utilisation is still
active. Ixt utilisation of brake transistor
( 26)
24LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
3.1.3Monitoring
3.1.3.1Overcurrent protection
The brake chopper hardware is monitored for overcurrent (short circuit or earth fault).
Note!
Monitoring for overcurrent can only be activated if a real brake current flows. A
test in idle state (without a brake resistor connected) is not possible.
If the monitoring function responds:
– The brake chopper is switched off immediately.
– The "Fault" response that is set fixedly is activated.
– The "Brake transistor: overcurrent" error message is entered in the logbook of the
regenerative power supply module.
Regenerative power supply module application
Parameterising the brake chopper/brake resistor
Note!
The error can only be acknowledged after 2 seconds at the earliest to resume the
braking operation.
Tip!
In addition to the overcurrent protection, the regenerative power supply module is
provided with two more monitoring modes for braking operation, which are active
even if no brake resistor is connected (testing mode for checking the parameter
setting):
Ixt utilisation of brake transistor
I2t utilisation of brake resistor
( 26)
( 27)
EDS94ARNExxxx EN 2.3 - 06/2014L25
9400 regenerative power supply module | Parameter setting
Ixt
C00137
1
0
C00134
C00129
C00133
T=0
Off
T=1
On
100 %
C00570
C00569
C00573
Logbook entry "Brake chopper: Ixt > C00570"
Logbook entry ""Brake chopper: Ixt overload
U
DC_act
U
DC_act
I=
Br
I=
Br
I
Br
= f(duty cycle, R )
Br
Regenerative power supply module application
Parameterising the brake chopper/brake resistor
3.1.3.2Ixt utilisation of brake transistor
The regenerative power supply module monitors the Ixt utilisation of the internal brake
transistor.
Note!
The braking operation will never be switched off by this monitoring function.
[3-1]Signal flow of Ixt utilisation - brake chopper
The monitoring function is based on a mathematical model which calculates the
braking current from the current DC-bus voltage and the brake resistance
parameterised.
– Hence, the monitoring function can respond even if no brake resistor is connected
and can therefore also be used for a testing mode to check the parameterisation.
The calculation considers the thermal utilisation of the brake transistor by a
correspondingly adapted time constant.
Use C00133
setting in C00173
C00129
C00137
to select whether the minimum brake resistance depending on the mains
(display in C00134), or the brake resistance value parameterised in
is to be used as a reference for calculating the utilisation.
displays the calculated utilisation of the brake transistor in [%].
– A 100 % utilisation corresponds to the continuous braking power which is provided
by the brake chopper at a DC-bus voltage of 790 V (or 390 V at a mains voltage of
230 V).
– The maximum braking power (assuming that the utilisation starts at 0 %) can be
provided for a period depending on the device.
– The calculated utilisation is also provided as the oscilloscope signal
Common.dnIxtBrakeChopper to check the braking operation while the system is
running
30
(scaling: 2
≡ 100 %).
If the utilisation exceeds the advance warning threshold set in C00570
, the message
"Brake chopper: Ixt > C00570" is entered into the logbook and the response set in
C00569
26LEDS94ARNExxxx EN 2.3 - 06/2014
(default setting: "Warning") is activated.
9400 regenerative power supply module | Parameter setting
I2t
C00138
C00129
T=0
Off
T=1
On
100 %
C00572
C00571
C00574
C00129
C00130
C00131
Logbook entry ""Brake resistor: I2t > C00572
Logbook entry ""Brake resistor: I2t overload
U
DC_act
Temperature model
I=
Br
I
Br
When the utilisation reaches the limit value (100 %):
– The activation of the brake chopper is reset to the permanently permissible pulse-
no-pulse ratio (taking into account the parameterised brake resistance). (The brake
chopper is activated with 4 kHz, which means that it can be switched on/off at
minimum intervals of 250 μs.)
– The response set in C00573
corresponding effects on the state machine and the inverter.
Note!
If the DC-bus voltage exceeds the overvoltage threshold due to a too high
braking energy, the monitoring function for overvoltage in the DC bus responds.
DC-bus overvoltage
3.1.3.3I2t utilisation of brake resistor
Regenerative power supply module application
Parameterising the brake chopper/brake resistor
(default setting: "No response") is activated with the
( 29)
The regenerative power supply module is provided with a monitoring function for the I
utilisation of the brake resistor which is proportional to the converted braking power.
Note!
The braking operation will never be switched off by this monitoring function.
The monitoring function is based on a mathematical model which calculates the
braking current from the current DC-bus voltage and the brake resistance
parameterised in C00129
– Hence, the monitoring function can respond even if no brake resistor is connected
and can therefore also be used for a testing mode to check the parameterisation.
.
2
t-
The calculation considers the thermal utilisation of the brake resistor based on the
following parameters:
– Resistance value (C00129
– Continuous power (C00130
– Thermal capacity (C00131
EDS94ARNExxxx EN 2.3 - 06/2014L27
)
)
)
9400 regenerative power supply module | Parameter setting
Regenerative power supply module application
Parameterising the brake chopper/brake resistor
C00138 displays the calculated utilisation of the brake resistor in [%].
– A 100 % utilisation corresponds to the continuous power of the brake resistor
resulting at the maximum permissible temperature limit of the brake resistor.
– The calculated utilisation is also provided as the oscilloscope signal
Common.dnI2tBrakeResistor to check the braking operation while the system is
running
(scaling: 2
30
≡ 100 %).
If the utilisation exceeds the advance warning threshold set in C00572
"Brake resistor: I2t > C00572" is entered into the logbook and the response set in
C00571
When the utilisation reaches the limit value (100 %):
– The response set in C00574
– The activation of the brake chopper is reset to the permanently permissible pulse-
(default setting: "Warning") is activated.
(default setting: "No response") is activated with the
corresponding effects on the state machine and the inverter.
no-pulse ratio (taking into account the parameterised brake resistance). (The brake
chopper is activated with 4 kHz, which means that it can be switched on/off at
minimum intervals of 250 μs.)
, the message
Stop!
The brake resistor can be thermally overloaded. Carry out protective measures
suitable for the system, e.g.:
• Parameterisation of an error response in C00574
parameterised error message in the application or machine control.
• External wiring using the temperature contact on the brake resistor (e.g.
interruption of the supply via mains contactor and activation of the
mechanical brakes).
and evaluation of the
Note!
If the system is dimensioned correctly, this monitoring function should not
respond. If individual rated data of the connected brake resistor are not known,
they must be determined "empirically".
From software version V2.0 onwards,C00571
the error response "Brake chopper is inhibited".
• If this error response occurs, the brake chopper is inhibited without providing
feedback to the device control. Instead, feedback is provided via the
LI_bChopperOffByTrouble output of the LS_LineInterface
• If the corresponding trigger threshold is fallen below by 5 %, the pulse inhibit
of the brake chopper is deactivated again and the status signal
LI_bChopperOffByTrouble is reset to FALSE.
and C00574 additionally provide
system block.
28LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
3.1.3.4DC-bus overvoltage
If the braking energy is too high and the DC-bus voltage therefore exceeds the overvoltage
threshold which results from the mains setting in C00173
error message is output and the response set in C00600
"Trouble").
Note!
For hoist applications the "Fault" response should be selected in C00600 (in
combination with an emergency stop via mechanical brakes).
Regenerative power supply module application
Parameterising the brake chopper/brake resistor
, the "Overvoltage in the DC bus"
is activated (default setting:
EDS94ARNExxxx EN 2.3 - 06/2014L29
9400 regenerative power supply module | Parameter setting
Regenerative power supply module application
Signal configuration
3.2Signal configuration
3.2.1Device and line interface
If required, the default signal configuration of the control and setpoint inputs of the device
and line interface can be easily reconfigured by parameterising the multiplexer
parameters assigned.
Device interface
Signal (Lenze setting)Control inputSignal configuration
DIGIN 1 Set controller inhibit
(inhibit regenerative feedback)
Control word 1 bit 01 Set controller inhibit
(inhibit regenerative feedback)
DIGIN 3 Reset error 1C03130/3
Control word 1 bit 07 Reset error 2C03130/4
C03130/1
C03130/2
Line interface
Signal (Lenze setting)Control inputSignal configuration
DIGIN 2 Activate brake chopperC03190/1
Control word 1 bit 02 Activate brake chopperC03190/2
30LEDS94ARNExxxx EN 2.3 - 06/2014
3.2.2Output ports
If required, the default signal configuration of the output ports can be easily reconfigured
by parameterising the multiplexer parameters assigned.
Output port "LPortAxisOut1"
The output port LPortAxisOut1 is intended for the connection to a following axis.
Signal (Lenze setting)Output portSignal configuration
Axis status word
• Application-specific signals can be added.
Setpoints for horizontal communication
9400 regenerative power supply module | Parameter setting
Regenerative power supply module application
Signal configuration
FALSE Axis status word bit 00C03120/1
FALSE Axis status word bit 01C03120/2
FALSE Axis status word bit 02C03120/3
FALSE Axis status word bit 03C03120/4
FALSE Axis status word bit 04C03120/5
FALSE Axis status word bit 05C03120/6
FALSE Axis status word bit 06C03120/7
FALSE Axis status word bit 07C03120/8
FALSE Axis status word bit 08C03120/9
FALSE Axis status word bit 09C03120/10
FALSE Axis status word bit 10C03120/11
FALSE Axis status word bit 11C03120/12
FALSE Axis status word bit 12C03120/13
FALSE Axis status word bit 13C03120/14
FALSE Axis status word bit 14C03120/15
FALSE Axis status word bit 15C03120/16
0 % Axis port out 1 (16 bits)C03124/1
0 % Axis port out 2 (32 bits)C03124/2
EDS94ARNExxxx EN 2.3 - 06/2014L31
9400 regenerative power supply module | Parameter setting
Regenerative power supply module application
Signal configuration
Output port "LPortStatus1"
The output port LPortStatus1 is intended for the connection to a higher-level control
system.
Signal (Lenze setting)Output portSignal configuration
Status word 1
FALSE Status word 1 bit 00C03121/1
FALSE Status word 1 bit 01C03121/2
FALSE Status word 1 bit 02C03121/3
FALSE Status word 1 bit 03C03121/4
FALSE Status word 1 bit 04C03121/5
FALSE Status word 1 bit 05C03121/6
FALSE Status word 1 bit 06C03121/7
FALSE Status word 1 bit 07C03121/8
FALSE Status word 1 bit 08C03121/9
FALSE Status word 1 bit 09C03121/10
FALSE Status word 1 bit 10C03121/11
FALSE Status word 1 bit 11C03121/12
FALSE Status word 1 bit 12C03121/13
FALSE Status word 1 bit 13C03121/14
FALSE Status word 1 bit 14C03121/15
FALSE Status word 1 bit 15C03121/16
Output port "LPortStatus2"
The output port LPortStatus2 is intended for the connection to a higher-level control
system.
Signal (Lenze setting)Output portSignal configuration
Status word 2
FALSE Status word 2 bit 00C03122/1
FALSE Status word 2 bit 01C03122/2
FALSE Status word 2 bit 02C03122/3
FALSE Status word 2 bit 03C03122/4
FALSE Status word 2 bit 04C03122/5
FALSE Status word 2 bit 05C03122/6
FALSE Status word 2 bit 06C03122/7
FALSE Status word 2 bit 07C03122/8
FALSE Status word 2 bit 08C03122/9
FALSE Status word 2 bit 09C03122/10
FALSE Status word 2 bit 10C03122/11
FALSE Status word 2 bit 11C03122/12
FALSE Status word 2 bit 12C03122/13
FALSE Status word 2 bit 13C03122/14
FALSE Status word 2 bit 14C03122/15
FALSE Status word 2 bit 15C03122/16
32LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
Regenerative power supply module application
Signal configuration
Output port "LPortStatus2"
The output port LPortStatus2 is intended for the connection to a higher-level control
system.
Signal (Lenze setting)Output portSignal configuration
Status word 2
FALSE Status word 2 bit 00C03122/1
FALSE Status word 2 bit 01C03122/2
FALSE Status word 2 bit 02C03122/3
FALSE Status word 2 bit 03C03122/4
FALSE Status word 2 bit 04C03122/5
FALSE Status word 2 bit 05C03122/6
FALSE Status word 2 bit 06C03122/7
FALSE Status word 2 bit 07C03122/8
FALSE Status word 2 bit 08C03122/9
FALSE Status word 2 bit 09C03122/10
FALSE Status word 2 bit 10C03122/11
FALSE Status word 2 bit 11C03122/12
FALSE Status word 2 bit 12C03122/13
FALSE Status word 2 bit 13C03122/14
FALSE Status word 2 bit 14C03122/15
FALSE Status word 2 bit 15C03122/16
EDS94ARNExxxx EN 2.3 - 06/2014L33
9400 regenerative power supply module | Parameter setting
Regenerative power supply module application
Assignment of the I/O terminals
3.3Assignment of the I/O terminals
In the following tables the Lenze assignment of the I/O terminals for the "Regenerative
power supply module" application is listed.
If required, the default signal configuration can be easily reconfigured via the
parameterisation dialog on the Application parameters tab, or via parameterisation of
the multiplexer parameters assigned.
Digital inputs
TerminalAssignment (Lenze setting)
X5RFRController enable
DI1Inhibit regenerative feedback
• Function also possible via bit 01 of control word 1.
DI2Activate brake chopper
• Function also possible via bit 02 of control word 1.
DI3Reset (acknowledge) error
• A pending error message can be reset (acknowledged) by a LOW-HIGH edge if the cause of
the error message has been eliminated.
• Function also possible via bit 07 of control word 1.
• There is no device overload, i.e. the device utilisation (C00064
below the warning threshold set in C00123
DO2"Filter overtemperature" stateC03100/2
DO3"Fault active - acknowledgement required" state
• A monitoring function with the "Fault" response has been triggered
and the regenerative power supply module is in the "Fault active"
device state.
DO4"Warning active" state
• A filter overload or device overload warning has occurred or another
monitoring function with the "Warning" error response has been
triggered and the regenerative power supply module is in the
"Warning active" device state.
.
) is
C03100/1
C03100/3
C03100/4
34LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
Note!
"Ready for regenerative feedback" status message via digital output DO1:
• If one of the conditions listed in the table for digital output DO1 is not met
anymore, the digital output DO1 is reset to LOW level.
Conditions for returning to the "ready for regenerative feedback" state:
• If a mains failure has been detected, the mains voltage has to be applied for
at least two complete periods after mains recovery, before the digital output
DO1 is reset to HIGH level.
• If a short circuit or earth fault has occurred, the device is ready for operation
again after approx. 2 s, i.e. after this time the digital output DO1 is
automatically reset to HIGH level.
• The device utilisation evaluation has a hysteresis of 5 %. This means that the
device utilisation (C00064
output DO1 is reset to HIGH level.
Regenerative power supply module application
Assignment of the I/O terminals
) must drop to < (C00123 - 5 %) before the digital
Display elements
User LEDSignal (Lenze setting)Signal configuration
9400 regenerative power supply module | Parameter setting
Device interface
4Device interface
This chapter will provide you with information on the device interface via which you can
query the states of the regenerative power supply module and set it to specific states.
How to get to the parameterisation dialog of the device interface:
1. Select the regenerative power supply module in the Project view of the »Engineer«.
2. Change to the Application parameters tab in the Workspace.
3. Click the Device interface button in the Overview dialog box.
Parameterisation dialog in the »Engineer«
The white buttons display the configuration of the device interface inputs.
LS_DriveInterface - device interface
– The assignment is defined by the technology application selected and can, if
required, be reconfigured by clicking the corresponding button.
If you click a button marked with the icon, you get one level deeper in the
corresponding parameterisation dialog.
( 259)
36LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
4.1Device commands
The following subchapters describe the device commands of the regenerative power
supply module, which are available in C00002
or via the »Engineer« when an online connection has been established.
Note!
Before switching off the supply voltage after a device command has been
executed, check via the status display in C00003
been executed successfully!
Device interface
Device commands
and which can be executed using the keypad
that the device command has
The meaning of the status display in C00003
subchapter for the corresponding device command.
Activating frequently required device commands via the toolbar
Frequently required device commands can be executed very easily directly via the Toolbar
of the »Engineer« when an online connection has been established.
IconFunction
Enable controller
Inhibit controller
Start application
Stop application and Inhibit controller
can be obtained from the
Note!
Device commands that can be executed via the Toolbar of the »Engineer« always
affect the element that is currently selected in the Project View and all
subelements!
• If, for example, a system module is selected in the Project view instead of the
regenerative power supply module, the corresponding device command will
be activated in all lower-level regenerative power supply modules &
controllers that are currently connected online with the »Engineer«.
Before the corresponding action is executed, a confirmation prompt is displayed
to ask you if this action should really be carried out.
EDS94ARNExxxx EN 2.3 - 06/2014L37
9400 regenerative power supply module | Parameter setting
Device interface
Device commands
Activating device commands via the "Device commands" dialog box
All device commands of the regenerative power supply module are available in the
»Engineer« in the Device Commands dialog box:
The Device Commands dialog box can be opened by clicking on the setting of C00002
on the All Parameters tab.
Note!
If you click on a device command in the list field of the Device Commands dialog
box, the corresponding device command is executed immediately!
During and after the execution of the device command, the processing status is
displayed in the Device Commands dialog box:
38LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
Application 3
PS
Application 2
PS
Memory module MM
PS
9400
PS
RAM
FirmwareApplication 1Application
PS
4.1.1Load Lenze setting
Device interface
Device commands
The C00002
= "0: Load Lenze setting" device command can be used to reset the parameters
of the active application to the Lenze setting which is stored in the firmware of the
regenerative power supply module:
[4-1]"Load Lenze setting" function
Only possible when the controller is inhibited and the application has been stopped.
All parameter changes made since the last saving of the parameter set will get lost!
This device command only has an impact on the settings of the operating system,
application, and module parameters, the active application remains unchanged.
Possible status displays for this device command
Status (C00003)Meaning
34050 Device command in process
0 Device command executed successfully
1 General fault
39424 CAN fault
... ...
39679 CAN fault
Related device commands
Load start parameters
Save start parameters
( 40)
( 44)
EDS94ARNExxxx EN 2.3 - 06/2014L39
9400 regenerative power supply module | Parameter setting
PS
9400
RAM
FirmwareApplication 1*
PS
Application 3
PS
Application 2
PS
Memory module MM
PS
Application 1*
Device interface
Device commands
4.1.2Load start parameters
The C00002
= "1: Load start parameters" device command can be used to reload the start
parameters of the active application from the memory module into the regenerative
power supply module:
* In this example application 1 is the active application
[4-2]"Load start parameters" function
Only possible when the controller is inhibited and the application has been stopped.
All parameter changes made since the last saving of the parameter set will get lost!
This device command only has an impact on the settings of the operating system,
application, and module parameters, the active application remains unchanged.
Possible status displays for this device command
Status (C00003)Meaning
99586 Device command in process
65536 Device command executed successfully
65537 General fault
99371 Fault while reading the parameter set partition
99374 No memory module available
104960 CAN fault
... ...
105215 CAN fault
Related device commands
Save start parameters
Load Lenze setting
( 44)
( 39)
40LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
4.1.3Load route data from the ENP
If the Lenze filter connected to the regenerative power supply module is provided with an
electronic nameplate (ENP), at the first switch-on of the regenerative power supply module
all filter data are automatically read out from the electronic nameplate of the filter and
temporarily saved in the regenerative power supply module.
Device interface
Device commands
The C00002
= "2: ENP: Load route data" device command can be used to reload the filter
data from the electronic nameplate (ENP) of the filter.
Only possible when the controller is inhibited and the application has been stopped.
For a permanent availability of the filter data, the parameter set must then be
saved.Save start parameters
( 44)
Possible status displays for this device command
Status (C00003)Meaning
165122 Device command in process
131072 Device command executed successfully
131073 General fault
EDS94ARNExxxx EN 2.3 - 06/2014L41
9400 regenerative power supply module | Parameter setting
PS
9400
RAM
FirmwareApplication
PS
Application 3
Memory module MM
Application 1
Application 2*
PS
Device interface
Device commands
4.1.4Activate application
If several applications are available on the memory module, the C00002
="5: Activate
application" device command can be used to activate the application with the number set
in C00005
* In this example the application selection "2" is set in C00005
[4-3]"Activate application" function
.
Only possible when the controller is inhibited and the application has been stopped.
The auto-start setting selected in C02104
determines whether the application is
started at the same time.
After mains switching, the default application is reloaded into the regenerative power
supply module.
If after mains switching another application than the one preset by Lenze is to be
loaded, this application must be activated first and then the selected application must
be saved with the device command "Save selected application
The number of the currently active application is displayed in C00007
" ( 43)
.
Note!
When the application is activated, the corresponding start parameter set is
loaded automatically and parameter settings executed before will get lost
unless the parameter set has been saved before!
Possible status displays for this device command
Status (C00003)Meaning
361730 Device command in process
327680 Device command executed successfully
327681 General fault
Related device commands
Save selected application
Start application
( 48) / Stop application ( 49)
( 43)
42LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
PS
9400
RAM
FirmwareApplication 2*
PS
Application 3
Memory module MM
Application 1
Application 2*
PS
4.1.5Save selected application
After mains switching, the regenerative power supply module always loads the default
start application from the memory module, even if a different application has been active
before.
Device interface
Device commands
The device command C00002
= "7: Save selected application" can be used to define the
active application as start application.
* In this example the active application 2 is defined as start application
[4-4]"Save selected application" function
When this device command is executed, the parameter set is also saved automatically.
The number of the currently active application is displayed in C00007
Possible status displays for this device command
Status (C00003)Meaning
492802 Device command in process
458752 Device command executed successfully
.
458753 General fault
Related device commands
Activate application
Start application
Stop application
( 42)
( 48)
( 49)
EDS94ARNExxxx EN 2.3 - 06/2014L43
9400 regenerative power supply module | Parameter setting
PS
9400
RAM
FirmwareApplication 1*
PS
Application 3
PS
Application 2
PS
Memory module MM
PS
Application 1*
Device interface
Device commands
4.1.6Save start parameters
Parameter changes in the regenerative power supply module carried out via the
»Engineer« or keypad will get lost after mains switching of the regenerative power supply
module, or after loading another application, unless the settings have been explicitly
saved.
The C00002
parameter settings of the active application with mains failure protection in the memory
module of the regenerative power supply module.
* In this example application 1 is the active application
[4-5]"Save start parameters" function
= "11: Save start parameters" device command can be used to save the current
Tip!
The left function key of the keypad can be used to execute this device command if
the function is currently assigned to this key.
Note!
The storing process can take a few seconds. Before switching off the supply
voltage after this device command has been executed, check via the status
display in C00003
that the device command has been executed successfully!
44LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
Possible status displays for this device command
Status (C00003)Meaning
754946 Device command in process
720896 Device command executed successfully
720897 General fault
754718 Fault while writing to a file
754734 No memory module available
761857 Access to file has been denied since the file is already accessed from another position.
761861 I/O fault during accessing the file system
761868 RAM memory is full
761869 Access authorisation denied
761884 No free memory on the memory module
Device interface
Device commands
Related device commands
Load start parameters
( 40)
EDS94ARNExxxx EN 2.3 - 06/2014L45
9400 regenerative power supply module | Parameter setting
Device interface
Device commands
4.1.7Delete logbook
The C00002
logbook.
= "20: Delete logbook" device command serves to delete all entries in the
Tip!
To display the logbook in the »Engineer«, click the Logbook button on the
Diagnostics tab.
You can also delete all entries in the logbook by clicking the Delete button in the
Logbook dialog box.
Further information on the logbook can be found in the chapter "Diagnostics &
fault analysis". ( 187)
Possible status displays for this device command
Status (C00003)Meaning
1344770 Device command in process
1310720 Device command executed successfully
1310721 General fault
Related device commands
Archive log file
( 47)
46LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
4.1.8Archive log file
Device interface
Device commands
The C00002
= "21: Archive log file" device command serves to archive the logbook entries.
Tip!
To display the logbook in the »Engineer«, click the Logbook button on the
Diagnostics tab.
You can also export the logbook entries to a file (*.log) by clicking the Export button
in the Logbook dialog box.
Further information on the logbook can be found in the chapter "Diagnostics &
fault analysis". ( 187)
Possible status displays for this device command
Status (C00003)Meaning
1410306 Device command in process
1376256 Device command executed successfully
1376257 General fault
Related device commands
Delete logbook
( 46)
EDS94ARNExxxx EN 2.3 - 06/2014L47
9400 regenerative power supply module | Parameter setting
Memory module MM
9400
RAM
FirmwareApplication 1Application
Application 2
Application 3
Device interface
Device commands
4.1.9Start application
The C00002
= "31: Start application" device command serves to start the active application
in the regenerative power supply module.
[4-6]"Start application" function
The number of the currently active application is displayed in C00007.
The current program state is displayed in C02108
Tip!
This device command can also be activated via the icon in the Toolbar.
Possible status displays for this device command
.
Status (C00003)Meaning
2065666 Device command in process
2031616 Device command executed successfully
2031617 General fault
Related device commands
Stop application
( 49)
48LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
Memory module MM
9400
RAM
FirmwareApplication 1Application
Application 2
Application 3
4.1.10Stop application
Device interface
Device commands
The C00002
= "32: Stop application" device command serves to stop the application
started in the regenerative power supply module.
[4-7]"Stop application" function
Only possible when controller is inhibited.
Tip!
The icon in the Toolbar inhibits the regenerative power supply module and
stops the application in the regenerative power supply module at the same time.
Possible status displays for this device command
Status (C00003)Meaning
2131202 Device command in process
2097152 Device command executed successfully
2097153 General fault
Related device commands
Start application
Inhibit controller
( 48)
( 55)
EDS94ARNExxxx EN 2.3 - 06/2014L49
9400 regenerative power supply module | Parameter setting
Device interface
Device commands
4.1.11Reset program
The C00002
= "33: Reset program" device command serves to reset the application
program in the regenerative power supply module.
All variables are reset to their initialisation values.
The situation corresponds to the start of a new program loaded into the control system
(cold start).
Possible status displays for this device command
Status (C00003)Meaning
2196738 Device command in process
2162688 Device command executed successfully
2162689 General fault
Related device commands
Delete program
Restart program
( 51)
( 52)
50LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
4.1.12Delete program
Device interface
Device commands
The device command C00002
= "34: Delete program" serves to delete the application
program in the regenerative power supply module and reset the regenerative power
supply module to its original state.
All variables are reset to their initialisation values.
Possible status displays for this device command
Status (C00003)Meaning
2262274 Device command in process
2228224 Device command executed successfully
2228225 General fault
Related device commands
Reset program
Restart program
( 50)
( 52)
EDS94ARNExxxx EN 2.3 - 06/2014L51
9400 regenerative power supply module | Parameter setting
Device interface
Device commands
4.1.13Restart program
The C00002
= "35: Restart program" device command serves to restart the application
program in the regenerative power supply module.
All variables except for the RETAIN variables are reset to their initialisation values.
The situation corresponds to a power failure or a switching off and on again of the
regenerative power supply module (warm start) while the program is running.
Possible status displays for this device command
Status (C00003)Meaning
2327810 Device command in process
2293760 Device command executed successfully
2293761 General fault
Related device commands
Reset program
Delete program
( 50)
( 51)
52LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
01 ms4 ms
T1
T2T2
T1T1T1T1T1
T3
1
0
2
3
4.1.14Reset runtime measurement
When the application is started, the regenerative power supply module continuously
measures the runtime of the interval-controlled ApplicationTask, the interval-controlled
UserTask and the free-running IdleTask, and displays the current and maximum task
runtimes via parameters.
Device interface
Device commands
The C00002
= "36: Reset runtime measurement" device command serves to reset the
runtime measurement, i.e. the memory for the maximum values is reset to "0".
Possible status displays for this device command
Status (C00003)Meaning
2393346 Device command in process
2359296 Device command executed successfully
2359297 General fault
Note!
The runtime measurement is also reset by the following actions:
T1 = runtime of the ApplicationTask
T2 = runtime of the UserTask
T3 = runtime of the IdleTask
9400 regenerative power supply module | Parameter setting
Device interface
Device commands
Display parameters
ParameterInformationLenze setting
C02121/1Current runtime ApplicationTask- μs
C02121/2Maximum runtime ApplicationTask- μs
C02122/1Current runtime UserTask- μs
C02122/2Maximum runtime UserTask- μs
C02123/1Current runtime IdleTask- μs
C02123/2Maximum runtime IdleTask- μs
Highlighted in grey = display parameter
Value Unit
54LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
4.1.15Inhibit controller
Device interface
Device commands
With the device command C00002
the regenerative power supply module can be inhibited for power recovery. The supply to
the DC bus is not affected by this "controller inhibit".
The controller can also be inhibited by other sources, e.g. via the digital input RFR or by
the application.
The sources or trip elements that are active for controller inhibit are displayed in a bit-
coded manner in C00158
.
= "41: Inhibit controller", the power output stages in
Note!
This device command has no status display in C00003, i.e. the display remains
unchanged showing the previous device command status.
Tip!
This device command can also be activated via the icon in the Toolbar.
Related device commands
Enable controller
( 56)
EDS94ARNExxxx EN 2.3 - 06/2014L55
9400 regenerative power supply module | Parameter setting
Device interface
Device commands
4.1.16Enable controller
The device command C00002
regenerative power supply module.
= "42: Enable controller" serves to re-enable an inhibited
Note!
Please note that the regenerative power supply module will only be enabled if all
sources for controller inhibit are reset!
• The sources or trip elements that are active for controller inhibit are displayed
in a bit-coded manner in C00158
This device command has no status display in C00003
unchanged showing the previous device command status.
Tip!
This device command can also be activated via the icon in the Toolbar.
Related device commands
Inhibit controller
( 55)
.
, i.e. the display remains
56LEDS94ARNExxxx EN 2.3 - 06/2014
4.1.17Reset error
9400 regenerative power supply module | Parameter setting
Device interface
Device commands
The C00002
message, provided that the error cause is eliminated and thus no error is pending.
= "43: Reset error" device command is used to acknowledge an existing error
Tip!
An error message can also be acknowledged by clicking the Reset error button on
the Diagnostics tab.
Further information on error messages can be found in the chapter "Diagnostics &
fault analysis". ( 187)
Note!
This device command has no status display in C00003, i.e. the display remains
unchanged showing the previous device command status.
EDS94ARNExxxx EN 2.3 - 06/2014L57
9400 regenerative power supply module | Parameter setting
Device interface
Device commands
4.1.18Reset max DC power mot.
This function is available from software version V2.0 onwards!
The C00002
displayed in C00143/1
display value (C00144/1
reset). Display of peak power
= "60: Reset max DC power mot." device command serves to reset the value
to zero. At the same time, the time stamp corresponding to this
) is set to the current state of the elapsed-hour meter (= time of
( 87)
Possible status displays for this device command
Status (C00003)Meaning
3966210 Device command in process
3932160 Device command executed successfully
3932161 General fault
Related device commands
Reset max DC power reg.
Reset max. line power reg.
( 59)
( 60)
58LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
4.1.19Reset max DC power reg.
This function is available from software version V2.0 onwards!
Device interface
Device commands
The C00002
displayed in C00143/2
display value (C00144/2
reset). Display of peak power
= "61: Reset max DC power reg." device command serves to reset the value
to zero. At the same time, the time stamp corresponding to this
) is set to the current state of the elapsed-hour meter (= time of
( 87)
Possible status displays for this device command
Status (C00003)Meaning
4031746 Device command in process
3997696 Device command executed successfully
3997697 General fault
Related device commands
Reset max DC power mot.
Reset max. line power reg.
( 58)
( 60)
EDS94ARNExxxx EN 2.3 - 06/2014L59
9400 regenerative power supply module | Parameter setting
Device interface
Device commands
4.1.20Reset max. line power reg.
This function is available from software version V2.0 onwards!
The C00002
displayed in C00143/3
display value (C00144/3
reset). Display of peak power
= "62: Reset max. line power reg." device command serves to reset the value
to zero. At the same time, the time stamp corresponding to this
) is set to the current state of the elapsed-hour meter (= time of
( 87)
Possible status displays for this device command
Status (C00003)Meaning
4097282 Device command in process
4063232 Device command executed successfully
4063233 General fault
Related device commands
Reset max DC power mot.
Reset max DC power reg.
( 58)
( 59)
60LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
4.1.21Reset transmitted energy
This function is available from software version V2.0 onwards!
Device interface
Device commands
The C00002
displayed in C00145/1
Display of output and regenerated energy
= "65: Reset transmitted energy" device command serves to reset the value
to zero.
( 88)
Possible status displays for this device command
Status (C00003)Meaning
4293890 Device command in process
4259840 Device command executed successfully
4259841 General fault
Related device commands
Reset regenerated energy
( 62)
EDS94ARNExxxx EN 2.3 - 06/2014L61
9400 regenerative power supply module | Parameter setting
Device interface
Device commands
4.1.22Reset regenerated energy
This function is available from software version V2.0 onwards!
The C00002
displayed in C00145/2
Display of output and regenerated energy
= "66: Reset regenerated energy" device command serves to reset the value
to zero.
( 88)
Possible status displays for this device command
Status (C00003)Meaning
4359426 Device command in process
4325376 Device command executed successfully
4325377 General fault
Related device commands
Reset transmitted energy
( 61)
62LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
4.1.23CAN on-board: Reset node
Device interface
Device commands
The C00002
= "91: CAN on-board: Reset node" device command serves to reinitialise the
CANopen system bus interface of the regenerative power supply module ("CAN on board"),
which for instance is required, for instance, after changing the data transfer rate, the node
address, or identifiers.
Tip!
For detailed information about the "CAN on board" CANopen system bus interface,
please see the "CAN" Communication Manual.
Possible status displays for this device command
Status (C00003)Meaning
5997826 Device command in process
5963776 Device command executed successfully
5963777 General fault
6003200 CAN fault
... ...
6003455 CAN fault
Related device commands
CAN on-board: Pred.Connect.Set
CAN on-board: Identify node
( 67)
( 65)
EDS94ARNExxxx EN 2.3 - 06/2014L63
9400 regenerative power supply module | Parameter setting
Device interface
Device commands
4.1.24CAN module: Reset node
The C00002
CANopen interface of a CANopen communication module inserted in module slot MXI1 or
MXI2. This is required, for instance, after changing the data transfer rate, the node address,
or identifiers.
= "92: CAN module: Reset node" device command serves to reinitialise the
Tip!
Detailed information on the CANopen communication module (E94AYCCA) can be
found in the "CAN" Communication Manual.
Possible status displays for this device command
Status (C00003)Meaning
6063362 Device command in process
6029312 Device command executed successfully
6029313 General fault
6068736 CAN fault
...
6068991 CAN fault
Related device commands
CAN module: Pred.Connect.Set
CAN module: Identify node
( 66)
( 68)
64LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
4.1.25CAN on-board: Pred.Connect.Set
Device interface
Device commands
The C00002
basic identifiers for the CANopen system bus interface of the regenerative power supply
module ("CAN on board") according to the "Predefined Connection Set" (DS301V402).
= "93: CAN on-board: Pred.Connect.Set" device command serves to set the
Tip!
For detailed information about the "CAN on board" CANopen system bus interface,
please see the "CAN" Communication Manual.
Possible status displays for this device command
Status (C00003)Meaning
6128898 Device command in process
6094848 Device command executed successfully
6094849 General fault
Related device commands
CAN on-board: Reset node
CAN on-board: Identify node
( 63)
( 67)
EDS94ARNExxxx EN 2.3 - 06/2014L65
9400 regenerative power supply module | Parameter setting
Device interface
Device commands
4.1.26CAN module: Pred.Connect.Set
The C00002
identifiers for the CANopen system bus interface of a CANopen communication module
inserted in module slot MXI1 or MXI2 according to the "Predefined Connection Set"
(DS301V402).
= "94: CAN module: Pred.Connect.Set" device command serves to set the basic
Tip!
Detailed information on the CANopen communication module (E94AYCCA) can be
found in the "CAN" Communication Manual.
Possible status displays for this device command
Status (C00003)Meaning
6194434 Device command in process
6160384 Device command executed successfully
6160385 General fault
Related device commands
CAN module: Reset node
CAN module: Identify node
( 64)
( 68)
66LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
4.1.27CAN on-board: Identify node
Device interface
Device commands
The C00002
nodes connected to the CANopen system bus interface of the regenerative power supply
module ("CAN on board").
The result of the CAN bus scan is displayed in C00393
= "95: CAN on-board: Identify node" device command serves to identify the
.
Tip!
For detailed information about the "CAN on board" CANopen system bus interface,
please see the "CAN" Communication Manual.
Possible status displays for this device command
Status (C00003)Meaning
6259970 Device command in process
6225920 Device command executed successfully
6225921 General fault
Related device commands
CAN on-board: Reset node
CAN on-board: Pred.Connect.Set
( 63)
( 65)
EDS94ARNExxxx EN 2.3 - 06/2014L67
9400 regenerative power supply module | Parameter setting
Device interface
Device commands
4.1.28CAN module: Identify node
The C00002
nodes connected to the CANopen system bus interface of a CANopen communication
module inserted in module slot MXI1 or MXI2.
The result of the CAN bus scan is displayed in C13393
MXI2).
= "96: CAN module: Identify node" device command serves to identify the
(for MXI1) or in C14393 (for
Tip!
Detailed information on the CANopen communication module (E94AYCCA) can be
found in the "CAN" Communication Manual.
Possible status displays for this device command
Status (C00003)Meaning
6325506 Device command in process
6291456 Device command executed successfully
6291457 General fault
Related device commands
CAN module: Reset node
CAN module: Pred.Connect.Set
( 64)
( 66)
68LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
4.1.29Unbind/bind Ethernet module MXI1
Device interface
Device commands
The C00002
reinitialise the Ethernet interface of an Ethernet communication module inserted in
module slot MXI1, for instance in order to accept a newly set IP or gateway address without
switching the mains.
= "101: Unbind/bind Ethernet module MXI1" device command serves to
Tip!
Detailed information on the Ethernet communication module (E94AYCEN) can be
found in the "Ethernet" Communication Manual.
Possible status displays for this device command
Status (C00003)Meaning
6653186 Device command in process
6619136 Device command executed successfully
6619137 General fault
Related device commands
Unbind/bind Ethernet module MXI2
( 70)
EDS94ARNExxxx EN 2.3 - 06/2014L69
9400 regenerative power supply module | Parameter setting
Device interface
Device commands
4.1.30Unbind/bind Ethernet module MXI2
The C00002
reinitialise the Ethernet interface of an Ethernet communication module inserted in
module slot MXI2, for instance in order to accept a newly set IP or gateway address without
switching the mains.
= "102: Unbind/bind Ethernet module MXI2" device command serves to
Tip!
Detailed information on the Ethernet communication module (E94AYCEN) can be
found in the "Ethernet" Communication Manual.
Possible status displays for this device command
Status (C00003)Meaning
6718722 Device command in process
6684672 Device command executed successfully
6684673 General fault
Related device commands
Unbind/bind Ethernet module MXI1
( 69)
70LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
PS 4
PS 3
PS 2
Application 2
PS 1
PS
PS 4
PS 3
PS 2
Memory module MM
PS
9400
PS
RAM
FirmwareApplication 1*Application 1*
PS
PS 1
4.1.31Activate parameter sets 1 ... 4
In addition to the start parameters, up to four more parameter sets can be stored in the
memory module for each application. This, for instance, serves to define different
controller settings for an application, which can then be simply activated via device
command.
The following device commands can be used to activate parameter sets 1 ... 4 for the active
application (if available on the memory module):
Device interface
Device commands
C00002
C00002
C00002
C00002
* In this example application 1 is the active application
[4-9]Example: "Activate parameter set 1" function
= "201: Activate parameter set 1"
= "202: Activate parameter set 2"
= "203: Activate parameter set 3"
= "204: Activate parameter set 4"
Only possible when the controller is inhibited and the application has been stopped.
All parameter changes made since the last saving of the previously active parameter
set will get lost!
These device commands only have an impact on the settings of the operating system,
application, and module parameters, the active application remains unchanged.
EDS94ARNExxxx EN 2.3 - 06/2014L71
9400 regenerative power supply module | Parameter setting
Device interface
Device commands
Possible status displays for these device commands
Status (C00003)Meaning
for command
201
13206786132723221333785813403394 Device command in process
13213724132792601334479613410332 No free memory on the memory module
for command
202
............ ...
for command
203
for command
204
already accessed from another position.
Related device commands
Archive parameter sets 1 ... 4
( 73)
72LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
PS 4
PS 3
PS 2
Application 2
PS 1
PS
PS 4
PS 3
PS 2
Memory module MM
PS
9400
PS
RAM
FirmwareApplication 1*Application 1*
PS
PS 1
4.1.32Archive parameter sets 1 ... 4
In addition to the start parameters, up to four more parameter sets can be stored in the
memory module for each application. This, for instance, serves to define different
controller settings for an application, which can then be simply activated via device
command.
The following device commands can be used to archive the current parameter settings of
the regenerative power supply module as parameter sets 1 ... 4 for the active application in
the memory module:
Device interface
Device commands
C00002
C00002
C00002
C00002
* In this example application 1 is the active application
[4-10] Example: "Archive parameter set 1" function
= "301: Archive parameter set 1"
= "302: Archive parameter set 2"
= "303: Archive parameter set 3"
= "304: Archive parameter set 4"
Previously archived parameter settings will be overwritten with the current parameter
settings!
EDS94ARNExxxx EN 2.3 - 06/2014L73
9400 regenerative power supply module | Parameter setting
Device interface
Device commands
Possible status displays for these device commands
Status (C00003)Meaning
for command
301
19760386198259221989145819956994 Device command in process
19767324198328601989839619963932 No free memory on the memory module
for command
302
for command
303
for command
304
already accessed from another position.
Related device commands
Activate parameter sets 1 ... 4
( 71)
74LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
4.1.33Format file system
Device interface
Device commands
The C00002
in the memory module.
= "1030: Format file system" device command serves to format the file system
Note!
This device command irrevocably deletes all folders and files available in the file
system of the memory module!
The application has to be redownloaded with the »Engineer«.
Possible status displays for this device command
Status (C00003)Meaning
67536130 Device command in process
67502080 Device command executed successfully
67502081 General fault
Related device commands
Restore file system
( 76)
EDS94ARNExxxx EN 2.3 - 06/2014L75
9400 regenerative power supply module | Parameter setting
Device interface
Device commands
4.1.34Restore file system
The C00002
formatting of the file system in the memory module.
= "1040: Restore file system" device command serves to carry out a low level
Note!
This device command irrevocably deletes all folders and files available in the file
system of the memory module and all internal information on the file system
management!
This device command has no status display in C00003
unchanged showing the previous device command status.
Stop!
The low level formatting of the file system by the user is only intended for the
exceptional case when the standard formatting of the file system via the
C00002
due to damaged internal management information.
Related device commands
= "1030: Format file system" device command is no longer possible, e.g.
, i.e. the display remains
Format file system
( 75)
76LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
4.1.35Prepare firmware update
Note!
For Lenze service only!
Device interface
Device commands
The C00002
the regenerative power supply module to the firmware update mode to carry
out a possibly required update of the firmware using the corresponding
software.
Only possible when the controller is inhibited and the application has been stopped.
Possible status displays for this device command
Status (C00003)Meaning
655394050 Device command in process
655360000 Device command executed successfully
655360001 General fault
= "10000: Prepare firmware update" device command serves to set
EDS94ARNExxxx EN 2.3 - 06/2014L77
9400 regenerative power supply module | Parameter setting
Device interface
Device commands
4.1.36Restart controller
The device command C00002
regenerative power supply module by parameter setting.
Only possible when the controller is inhibited and the application has been stopped.
Possible status displays for this device command
Status (C00003)Meaning
720930050 Device command in process
720896001 General fault
= "11000: Restart controller" serves to restart the
Note!
Because of the restart in the case of a successful execution of the device
command, this status will not be displayed in
If this device command is used, the "Undervoltage in DC bus (0x007b000f)"
message may appear in the logbook.
C00003.
78LEDS94ARNExxxx EN 2.3 - 06/2014
4.2Device states
2
0
1
Controller inhibit
Ready to
switch on
Initialisation
active
Switched
on
Operation
Trouble
active
Power on
System fault
active
Fault
active
Warning/
Warning locked
active
The state control of the regenerative power supply module is operated internally via a
state machine which can adopt the following "device states":
9400 regenerative power supply module | Parameter setting
Device interface
Device states
, From all states
[4-11] Device states of the state machine for the device control
Note!
The "Warning active"/"Warning locked active" status can occur simultaneously to other states.
The device state "Quick stop by trouble", which a controller can adopt as a
response to a fault, is not
supported by the regenerative power supply module!
Requests for this device state made by a parameterisable device module in slot
MXI1/MXI2 or via the control word of the device interface are ignored by the
regenerative power supply module without feedback.
EDS94ARNExxxx EN 2.3 - 06/2014L79
9400 regenerative power supply module | Parameter setting
Device interface
Device states
Display parameters for diagnostic purposes
The current device state is displayed in C00183
C00150
(status word 1) displays the current device state in a bit-coded manner via
.
bits 8 ... 11:
Bit 11Bit 10Bit 9Bit 8Meaning
0000State "Initialisation active"
0001State "Device is ready to switch on"
0010-
0011State "Device is switched on"
0100-
0101-
0110State "Operation"
0111State "Warning active" or State "Warning locked active"
The regenerative power supply module is ready to switch on,
switched on, or operation is enabled and a warning is indicated.
1000State "Trouble active"
1001-
1010-
1011-
1100State "Fault active"
1101-
1110-
1111-
4.2.1State "Initialisation active"
LED DRIVE READYLED DRIVE ERRORDisplay in C00183
OFFOFF10: Initialisation active
This is the device state of the regenerative power supply module directly after switching
on the supply voltage.
In this device state the operating system is initialised.
The application is not processed yet.
The monitoring mode is not active yet.
Communication is not possible yet.
The regenerative power supply module cannot be parameterised yet and no device
commands can be executed.
When the device initialisation is completed, the device state is automatically changed
to "Device is ready to switch on".
80LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
4.2.2State "Device is ready to switch on"
LED DRIVE READYLED DRIVE ERRORDisplay in C00183
OFF141: Device ready to start
This is the device state of the regenerative power supply module directly after the
initialisation has been completed and a DC-bus voltage is not applied yet.
The bus systems are running and the terminals and encoders are evaluated.
The monitoring functions are active.
The regenerative power supply module can be parameterised and device commands
can be executed to a limited extent.
The application is basically executable.
Note!
Device interface
Device states
The "Device is ready to switch on" state is not only entered after power-on, but
also when a "Trouble" or "Fault" is reset.
•For C00142
ready to switch on" state to the "Device is switched on" state (Lenze setting).
•For C00142
to get from the "Device is ready to switch on" state to the "Device is switched
on" state.
Automatic restart after power-on/trouble/fault
4.2.3State "Device is switched on"
LED DRIVE READYLED DRIVE ERRORDisplay in C00183
This is device state of the regenerative power supply module when the DC-bus voltage is
applied and the regenerative power supply module is still inhibited by the user (controller
inhibit).
The bus systems are running and the terminals and encoders are evaluated.
The monitoring functions are active.
= "1: Enabled", the device changes directly from the "Device is
= "0: Inhibited", at least one source for controller must be active
OFF90: Drive switched on
( 84)
The regenerative power supply module can be parameterised and device commands
can be executed to a limited extent.
The application is basically executable.
EDS94ARNExxxx EN 2.3 - 06/2014L81
9400 regenerative power supply module | Parameter setting
Device interface
Device states
4.2.4State "Operation"
LED DRIVE READYLED DRIVE ERRORDisplay in C00183
OFF0: Operation
This is the device state of the regenerative power supply module during operation.
4.2.5State "Warning active"
LED DRIVE READYLED DRIVE ERRORDisplay in C00183
1: Operation/Warning active
This state can occur simultaneously to the device states "Device is ready to switch on",
"Device is switched on" and "Operation" if a monitoring function responds for which the
error response "Warning" has been parameterised.
4.2.6State "Warning locked active"
LED DRIVE READYLED DRIVE ERRORDisplay in C00183
This state can occur simultaneously to the device states "Device is ready to switch on",
"Device is switched on" and "Operation" if a monitoring function responds for which the
error response "Warning locked" has been parameterised.
4.2.7State "Trouble active"
LED DRIVE READYLED DRIVE ERRORDisplay in C00183
OFF104: Trouble active
This device state becomes active as soon as a monitoring function responds for which the
error response "Trouble" has been parameterised.
The device state is automatically exited when the error cause has been eliminated:
– "Trouble active" state < 500 ms: return to the original device state.
– "Trouble active" state > 500 ms: return via the device state "Device is ready to switch
on".
2: Operation/Warning locked act.
82LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
4.2.8State "Fault active"
LED DRIVE READYLED DRIVE ERRORDisplay in C00183
OFF102: Fault active
This device state becomes active as soon as a monitoring function responds for which the
error response "Fault" has been parameterised.
4.2.9State "System fault active"
LED DRIVE READYLED DRIVE ERRORDisplay in C00183
OFF20: System fault active
This device state becomes active if a system fault occurs.
The device state can only be exited by mains switching.
Device interface
Device states
EDS94ARNExxxx EN 2.3 - 06/2014L83
9400 regenerative power supply module | Parameter setting
RFR
01
RFR
RFR
RFR
t
t
InitialisationSwitched onOperationReady to switch on
OperationInitialisationSwitched onReady to switch on
Device interface
Automatic restart after power-on/trouble/fault
4.3Automatic restart after power-on/trouble/fault
C00142
serves to parameterise the starting performance of the regenerative power supply
module after power-on or after resetting a "Trouble" or "Fault".
Auto-start option 1: auto-restart enabled after power-on
The following illustration shows the state change for the auto-start option 1 (Lenze
setting) as a function of controller inhibit:
Pulses of the regenerative power supply module are inhibited
Pulses of the regenerative power supply module are enabled
[4-12] State change when auto-restart is enabled (C00142 = "1: Enabled")
With controller inhibit at power-on
Without controller inhibit at power-on
84LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
RFR
01
RFR
RFR
RFR
t
t
InitialisationSwitched onOperationReady to switch on
InitialisationSwitched onOperationReady to switch on
Device interface
Automatic restart after power-on/trouble/fault
Auto-start option 0: auto-restart inhibited after power-on
If auto-start option 0 has been selected, the controller inhibit must be explicitly set after
power-on or after resetting a "Trouble" or "Fault" in order that the state of the regenerative
power supply module changes from "Device is ready to switch on" to "Device is switched
on". The subsequent change to the "Operation" state takes place when the controller is
enabled:
Pulses of the regenerative power supply module are inhibited
Pulses of the regenerative power supply module are enabled
With controller inhibit at power-on
Without controller inhibit at power-on
[4-13] State change when auto-restart is inhibited (C00142 = "0: Inhibited")
EDS94ARNExxxx EN 2.3 - 06/2014L85
9400 regenerative power supply module | Parameter setting
Device interface
Monitoring the device utilisation
4.4Monitoring the device utilisation
C00064
If the value displayed in C00064
If the value displayed in C00064
displays the device utilisation (I x t) over the last 180 seconds in [%].
exceeds the warning threshold set in C00123, the error
message "Device utilisation Ixt > C00123" is output and the error response set in
C00604
Ixt > 100 %" is output and the error response "Fault" occurs.
– The error can only be reset if the value displayed in C00064
occurs (default setting: "Warning").
exceeds 100 %, the error message "Device utilisation
drops to < 95 % again.
86LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
4.5Display of peak power
This function is available from software version V2.0 onwards!
The following parameters display the peak power of the regenerative power supply
module and the corresponding state of the elapsed-hour meter, at which the respective
peak power has been reached:
ParameterInformationLenze setting
C00143/1Max. DC-power mot.- kW
C00144/1Time stamp max. DC-power mot.- s
C00143/2Max. DC-power reg. (+ br. chop.)- kW
C00144/2Time stamp max. DC-power reg.- s
C00143/3Max. line power reg.- kW
C00144/3Time stamp max. line power reg.- s
Highlighted in grey = display parameter
Device interface
Display of peak power
Value Unit
The display values are stored in the memory module with power failure protection and
are therefore even available after device replacements. After a device replacement,
however, the time reference is updated only after a new peak value has been recorded.
The display values can be reset to zero via the following device commands (C00002
–60: Reset max DC power mot.
–61: Reset max DC power reg.
–62: Reset max. line power reg.
( 58)
( 59)
( 60)
):
Resetting of the display values also sets the corresponding time stamp to the current
state of the elapsed-hour meter (= time of reset).
EDS94ARNExxxx EN 2.3 - 06/2014L87
9400 regenerative power supply module | Parameter setting
Device interface
Display of output and regenerated energy
4.6Display of output and regenerated energy
This function is available from software version V2.0 onwards!
The following parameters display the energy of the regenerative power supply module
output at the DC side and the energy fed back to the mains:
ParameterInformationLenze setting
C00145/1Output energy, DC side- kWh
C00145/2Regenerated energy- kWh
Highlighted in grey = display parameter
The display values are stored in the memory module with power failure protection and
are therefore even available after device replacements.
Value Unit
The display values can be reset to zero via the following device commands (C00002
–65: Reset transmitted energy
–66: Reset regenerated energy
( 61)
( 62)
):
Note!
The kWh display does not completely replace a three-phase meter!
88LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
GE
24E
SB
X2
X3
GA
AO1
AO2
A1+
A1-
A1-
A1R
A2+
A2-
GO
24O
DO1
DO2
DO3
DO4
X4
X5
GI
RFR
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
5I/O terminals
This chapter provides you with information on possible parameter settings for the input
and output terminals of the regenerative power supply module.
Tip!
Information on terminal wiring can be found in the Mounting Instructions of the
regenerative power supply module!
5.1Overview
Front viewTerminal assignmentInformation
"State bus" monitoring function
I/O terminals
Overview
( 96)
Analog inputs
Analog outputs
Digital outputs
Digital inputs
( 90)
( 92)
( 95)
( 94)
EDS94ARNExxxx EN 2.3 - 06/2014L89
9400 regenerative power supply module | Parameter setting
A1+
A1-
A1-
A1R
A2+
A2-
X3
I/O terminals
Analog inputs
5.2Analog inputs
The regenerative power supply module has two analog inputs which can be used to detect
differential voltage signals in the range of ±10 V, for instance an analog speed setpoint
selection or the voltage signal of an external sensor (temperature, pressure, etc.).
Optionally, analog input 1 can also be used to detect current setpoints.
5.2.1Terminal assignment/electrical data
TerminalUseElectrical data
X3/A1X3/A1+
X3/A2X3/A2+
Differential voltage input 1
(no jumper between A1R and A1)
Conversion rate: 1 kHz
Current input
(jumper between A1R and A1)
Conversion rate: 1 kHz
Differential voltage input 2Level: -10 V ... +10 V
Conversion rate: 1 kHz
Level: -10 V ... +10 V
Resolution: 11 bits + sign
Scaling: When C00034
±10 V ≡ ±2
Level: -20 mA ... +20 mA
Resolution: 10 bits + sign
Scaling: When C00034
-20 mA ... -4 mA = -2
+4 mA ... +20 mA = 0 ... 2
When C00034 ="2":
±20 mA ≡ ±2
Resolution: 11 bits + sign
Scaling: ±10 V ≡ ±2
30
30
30
="0":
="1":
30
... 0
30
90LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
5.2.2Parameter setting
Short overview of the parameters for the analog inputs:
5.2.3Reconfiguring analog input 1 into current input
Proceed as follows to reconfigure analog input 1 into a current input:
1. Jumper terminals A1R and A1 on terminal strip X3 by means of wiring.
2. Select the corresponding current loop under C00034
Open-circuit monitoring
Under C00598
you can select an error response to an open circuit for the 4 ...20 mA current
loop.
.
EDS94ARNExxxx EN 2.3 - 06/2014L91
9400 regenerative power supply module | Parameter setting
GA
AO1
AO2
X3
I/O terminals
Analog outputs
5.3Analog outputs
The regenerative power supply module is provided with 2 analog outputs which can be
used to output internal analog signals as voltage signals, e.g. for display via analog
indicating instruments.
Note!
Initialisation behaviour:
• After mains switching until the start of the application, the analog outputs
remain set to 0 V.
Exception handling:
• In the case of a critical exception within the application (e.g. reset), the analog
outputs are set to 0 V.
5.3.1Terminal assignment/electrical data
TerminalUseElectrical data
X3/AO1Voltage output 1Level: -10 V ... +10 V
X3/AO2Voltage output 2Level: -10 V ... +10 V
X3/GAReference potential (analog ground)
(max. 2 mA)
Resolution: 11 bits + sign
Scaling: ±2
Conversion rate: 1 kHz
Resolution: 11 bits + sign
Scaling: ±2
Conversion rate: 1 kHz
30
(max. 2 mA)
30
≡ ±10 V
≡ ±10 V
92LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
5.3.2Parameter setting
Short overview of the parameters for the analog outputs:
ParameterInformation
C02733/1
C02733/2
C02734/1
C02734/2
C02801/1Analog output 1: Output signal
C02801/2Analog output 2: Output signal
Highlighted in grey = display parameter
I/O terminals
Analog outputs
Analog output 1: Gain
Analog output 2: Gain
Analog output 1: Offset
Analog output 2: Offset
EDS94ARNExxxx EN 2.3 - 06/2014L93
9400 regenerative power supply module | Parameter setting
X5
GI
RFR
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
I/O terminals
Digital inputs
5.4Digital inputs
The regenerative power supply module is equipped with 8 freely configurable digital
inputs.
Control input RFR of terminal strip X5 for controller enable is permanently connected
to the device control.
5.4.1Terminal assignment/electrical data
TerminalUseElectrical data
X5/DI1
X5/DI8
X5/RFRController enableSee digital inputs
X5/GIReference potential (digital ground)
5.4.2Parameter setting
Short overview of parameters for the digital inputs:
ParameterInformation
C00114
C00443Status: Digital inputs
C02803Status word: Digital inputs
C02830
Highlighted in grey = display parameter
Digital input 1 ... 8LOW level: 0 ... +5 V
HIGH level: +15 ... +30 V
Input current: 8 mA per input
(at 24 V)
Interference-voltage-
Conversion rate: 1 kHz
Dig. input x: Terminal polarity
Digital inputs: Delay time
max. ±30 V
proof:
94LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
GO
24O
DO1
DO2
DO3
DO4
X4
5.5Digital outputs
The regenerative power supply module is equipped with 4 freely configurable digital
outputs.
Note!
Initialisation behaviour:
• After mains switching until the start of the application, the digital outputs
remain set to FALSE.
Exception handling:
• In the case of a critical exception within the application (e.g. reset), the digital
outputs are set to FALSE, taking the terminal polarity parameterised in
C00118
I/O terminals
Digital outputs
into consideration.
5.5.1Terminal assignment/electrical data
TerminalUseElectrical data
X4/DO1
...
X4/DO4
X4/24OExternal 24 V voltage supply for the digital outputs
X4/GOReference potential (digital ground)
Digital output 1 ... 4LOW level: 0 ... +5 V
5.5.2Parameter setting
HIGH level: +15 ... +30 V
Output current: max. 50 mA per output (external
resistance > 480 Ω at 24 V)
Conversion rate: 1 kHz
Short overview of parameters for the digital outputs:
ParameterInformation
C00118
C00444Status: Digital outputs
C02802Status word: Digital outputs
Highlighted in grey = display parameter
EDS94ARNExxxx EN 2.3 - 06/2014L95
Dig. output x: Terminal polarity
9400 regenerative power supply module | Parameter setting
X2X2X2
GE
24E
SB
GE
24E
SB
GE
24E
SB
I/O terminals
"State bus" monitoring function
5.6"State bus" monitoring function
The state bus has been designed exclusively for Lenze controllers. The bus system can
interconnect up to 20 controllers and can be used to simulate the function of a "rip cord":
X2/SB = State bus In/Out (reference potential GE)
[5-1]Schematic diagram: Networking via state bus
The state bus only knows the states "OK" and "Error".
The state bus is a multi-master bus system, i.e. each node connected to the state bus
can set the state bus to the "Error" state by setting it to LOW level.
In the "Error" state, all nodes initiate their adjustable response, e.g. synchronised
braking of the drive system to standstill.
The "Error" state is also set if a node connected to the state bus is not supplied with
voltage.
Note!
Exception handling:
• In the case of a critical exception within the application (e.g. reset), the "rip
cord" is not "pulled", the state bus remains in the "OK" state.
96LEDS94ARNExxxx EN 2.3 - 06/2014
9400 regenerative power supply module | Parameter setting
6"CAN on board" system bus
The regenerative power supply module is provided with an integrated CANopen system
bus interface ("CAN on board"), which can, for instance, be used to exchange process data
and parameter values between the connected devices. This interface also enables the
connection of additional components such as distributed terminals, operator and input
devices ("HMIs") as well as external control and host systems.
The interface transmits CAN objects following the CANopen communication profile
(CiA DS301, version 4.02) developed by the umbrella association of CiA (CAN in
Automation) in conformity with the CAL (CAN Application Layer).
Tip!
• In the »Engineer« parameter list and in the keypad, the parameters relevant for
the CANopen system bus interface are grouped in different subcategories of the
category CAN.
• The "CAN" communication manual of the Lenze library provides information
about CAN communication modules and CANopen system bus interfaces of
other Lenze devices.
"CAN on board" system bus
EDS94ARNExxxx EN 2.3 - 06/2014L97
9400 regenerative power supply module | Parameter setting
"CAN on board" system bus
General information
6.1General information
For many years the system bus (CAN) based on the CANopen communication profile has
been integrated in Lenze controllers. Due to the lower number of data objects available,
the functionality and compatibility of the old system bus are lower as compared with
CANopen. For parameter setting, two parameter data channels are always available to the
user while CANopen provides only one active parameter data channel (along with the
possibility to establish further channels).
The system bus (CANopen) integrated in the Servo Drives 9400 has been developed from
the system bus (CAN) used in the controllers of the ”9300” series, and it has the following
features:
Full compatibility to CANopen DS301 V4.02.
Support of the NMT master/slave function "Node Guarding" (DS301 V4.02).
Support of the NMT slave function "Heartbeat" (DS301 V4.02).
No restrictions regarding the selection of node addresses.
Number of parameterisable server and client SDO channels: