This documentation exclusively contains descriptions of the EtherNet/IP ™ bus system for Inverter
Drives 8400 protec.
Note!
This documentation supplements the mounting instructions provided with the inverter
and the hardware manual for Inverter Drives 8400 protec.
The mounting instructions contain safety instructions which must be observed!
The features and functions of EtherNet/IP for Inverter Drives 8400 protec are described in detail.
Examples illustrate typical applications.
The theoretical concepts are only explained to the level of detail required to understand the
function of EtherNet/IP communication with Inverter Drives 8400 protec.
This documentation does not describe the software of another manufacturer. No guarantee can be
given for corresponding information in this documentation. Information on the use of the software
can be found in the documents for the control system (PLC, scanner).
All brand names mentioned in this documentation are trademarks of their corresponding owners.
Tip!
Detailed information on EtherNet/IP can be found on the website of the user organisation
ODVA (Open DeviceNet Vendor Association):
www.odva.org
4Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
This documentation addresses to persons who configure, install, commission, and maintain the
networking and remote maintenance of a machine.
Tip!
Current documentation and software updates with regard to Lenze products can be found
in the download area at:
www.Lenze.com
Information regarding the validity
The information given in this documentation is valid for the following devices:
Product seriesType designationFrom hardware
Inverter Drives 8400 protec
(EtherNet/IP option)
Screenshots/application examples
All screenshots in this documentation are application examples. Depending on the firmware
version of the inverter and software version of the installed engineering tools
»RSLogix 5000«)
representation.
, the screenshots in this documentation may differ from the screen
E84DxxxxxxxxGVB01.00
version
From software
version
(»Engineer«,
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD175
InverterLenze frequency inverters of the "Inverter Drives 8400 protec" product range
Standard device
ARPAddress Resolution Protocol
Use BOOTPBootstrap Protocol
EtherNet/IP™ (EtherNet Industrial Protocol) is a fieldbus system based on
Ethernet which uses the Common Industrial Protocol™ (CIP™) for data exchange.
EtherNet/IP™ and Common Industrial Protocol™ (CIP™) are trademarks and
patented technologies, licensed by the user organisation ODVA (Open
DeviceNet Vendor Association), USA.
Use DHCPDynamic Host Configuration Protocol
DSCPDifferentiated Services Codepoints
EDSElectronic Data Sheet
Explicit messagesExplicit Messages are used to transfer parameter data.
HWHardware
IGMPInternet Group Management Protocol
Implicit messagesImplicit Messages are used to transfer I/O data.
"Class 1" connectionI/O connection
"Class 3" connectionExplicit connection
Level 2EtherNet/IP performance level 2:
I/O Message Server including Explicit Message Server
Lenze settingDefault settings of the device, preconfigured ex works.
Basic setting
PLCProgrammable Logic Controller
QoSQuality of Service
RPIRequested Package Interval:
Interval requested between 2 telegrams for cyclic data transmission
»RSLogix 5000«Programming and development software from Rockwell for control systems
(scanner) in EtherNet/IP networks (e.g. Allen-Bradley Logix controllers).
ScannerEtherNet/IP master or client
Control system
Host
SWSoftware
TTLTime To Live:
Validity time of data packets in the EtherNet/IP network
UCMMUnconnected Message Manager
8
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
It is absolutely vital that the stated safety measures are implemented in order to prevent
serious injury to persons and damage to material assets.
Always keep this documentation to hand in the vicinity of the product during operation.
2.1General safety and application notes
Danger!
If the following basic safety measures are disregarded, severe injuries to persons and
damage to material assets may result.
Lenze drive and automation components ...
• must only be used as directed.
• must never be commissioned if they display signs of damage.
• must never be technically modified.
• must never be commissioned if they are not fully mounted.
• must never be operated without required covers.
• during and after operation can have live, moving and rotating parts, depending on their degree
of protection. Surfaces can be hot.
The following applies to Lenze drive components ...
• only use the accessories approved.
• Only use original manufacturer spare parts.
Observe all specifications contained in the enclosed documentation and related documentation.
• This is the precondition for safe and trouble-free operation and for obtaining the product
features specified.
Properties of the EtherNet/IP with Inverter Drives 8400 protec
• The specifications, processes, and circuitry described in this document are for guidance only and
must be adapted to your own specific application. Lenze does not take responsibility for the
suitability of the process and circuit proposals.
All works on and with Lenze drive and automation components must only be carried out by qualified
personnel. In accordance with IEC 60364 and CENELEC HD 384 these are persons who ...
• are familiar with installing, mounting, commissioning, and operating the product.
• who have the corresponding qualifications for their work.
( 12)
10
• who know and can apply all regulations for the prevention of accidents, directives, and laws
applicable at the place of use.
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
2Safety instructions
2.2Device and application-specific safety instructions
2.2Device and application-specific safety instructions
Only use cables that meet the listed specifications.
Ethernet cable specification
( 20)
Documentation for Inverter Drives 8400 protec, control system, plant/machine
All the other measures prescribed in this documentation must also be implemented.
Observe the safety instructions and application notes contained in this manual.
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1711
EtherNet/IP uses CIP (Common Industrial Protocol) for the data exchange between devices via an
Ethernet network – just like the closely related bus systems DeviceNet and ControlNet™.
Lenze implements the CIP following the ODVA standard (Open DeviceNet Vendor Association,
www.odva.org) and supports the two main types of EtherNet/IP communication:
• Explicit messaging (for parameter data)
• Implicit I/O messaging (for process data)
Tip!
Detailed information on EtherNet/IP can be found on the website of the EtherNet/IP user
organisation ODVA (Open DeviceNet Vendor Association):
www.odva.org
Properties of the EtherNet/IP with Inverter Drives 8400 protec
• The Inverter Drive 8400 protec is always an adapter device:
EtherNet/IP adapter with "Level 2" functionality
• The integrated safety system can be used for the protection of persons on machines.
EtherNet/IP only provides safety option 10 (safe torque off, STO).
• 2-port interface with integrated switch functionality
• Access to all Lenze parameters (configurable via TCP/IP using the Lenze »Engineer«)
• Up to 3 TCP/IP socket connections for communication with the Lenze »Engineer«
• Support of "IP Config Pending" (activation of changed IP configuration by "power off/on" or
"type 0 reset")
• Support of the redundancy protocol DLR (Device Level Ring) as "beacon-based ring node"
• Up to 16 I/O data words (32 bytes) are possible.
• Further CIP features:
• Max. 8 CIP connections
• 1 "exclusive owner" connection
• I/O connection type: cyclic
•Minimum I/O cycle time: 4 ms
• Support of multicast messages, UCMM, ACD, BOOTP/DHCP, VLAN tagging/DSCP
Hardware manual for Inverter Drives 8400 protec
Here you will find detailed information on the integrated safety system (safety option).
Reference manual / »Engineer« online help for Inverter Drives 8400 protec
Here you will find detailed information on how to configure the safety system (safety
option).
12Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
4Technical data
4.1General data and operating conditions of the EtherNet/IP
The integrated 2-port switch causes runtime delays. For "store-and-forward" and 100 Mbps, these
runtime delays can be calculated as follows.
Runtime delay for an output data packet of the scanners incl.
sequence counter:
Runtime delay = ((66 permanent bytes + I/O data in bytes) x 8 x 10 nsec) + 4 μsec
Runtime delay for an output data packet of an adapter without
Runtime delay = ((62 permanent bytes + I/O data in bytes) x 8 x 10 nsec) + 4 μsec
Example
Delay of an output data packet of the scanners with 8 output data words (16 bytes):
• ((66 permanent bytes + 16 bytes) x 8 x 10 nsec) + 4 μsec
• (82 bytes x 8 x 10 nsec) + 4 μsec
• 6.56 μsec + 4 μsec = 10.56 μsec
32-bit "run/idle header" with 16-bit
32/bit "run/idle header":
Note!
The use of external switches can also lead to runtime delays. Depending on the system
constellation, it may be useful to create a star topology or a line/mix topology.
Network topology
( 16)
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1715
Mounting instructions for the Inverter Drive 8400 protec
Here you will find detailed information on the mechanical and electrical installation of
the device.
Hardware manual for Inverter Drives 8400 protec
Here you can find detailed information on ...
• the digital and analog inputs/outputs;
•the relay output;
• the integrated safety system (safety option);
• the wiring of the terminals.
Observe the notes and wiring instructions contained in this documentation!
5.1Network topology
It is typical of EtherNet/IP to have a rather free topology the limiting factor of which is large
message latencies due to e.g. switches connected in series.
Internal switch latency
The combination of a line and a stub is useful for system wiring.
EtherNet/IP supports the following topologies:
•Line
[5-1]Line topology (S = scanner, A = adapter)
•Switch / star
( 15)
E94AYCEO008
[5-2]Switch / star topology (SW = switch, A = adapter)
16
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
The connection to the EtherNet/IP network is made via the terminals X31 and X32 – depending on
the version via an RJ45 socket or M12 socket (4-pole, D-coded).
E84DWGA010_Kom
[5-5]EtherNet/IP terminals
EtherNet/IP connection via the RJ45 socket ( 19)
EtherNet/IP connection via the M12 socket
( 22)
18
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
A standard Ethernet patch cable is suitable for connecting the Inverter Drive 8400 protec to the
EtherNet/IP fieldbus.
Ethernet cable specification
The installation and removal of the Ethernet cables is optimised for the use of connectors in
accordance with the "Automation Initiative of German Domestic Automobile Manufacturers"
(AIDA).
( 20)
Note!
To prevent the RJ45 socket from being damaged, insert or remove the Ethernet cable
connector straight (at a right angle) into or from the socket.
5.2.1.1Pin assignment
RJ45 socketPinSignal
1Tx +
2Tx -
3Rx +
4-
5-
6Rx -
E94AYCXX004C
7-
8-
Note!
Dependent on the configuration of the Ethernet port of the device to be connected, we
recommend the use of a cross-over cable.
Tip!
The EtherNet/IP interfaces feature an auto MDIX function. This function adjusts the
polarity of the RJ45 interfaces so that a connection is established irrespective of the polarity
of the opposite EtherNet/IP interface, and irrespective of the cable type used (standard
patch cable or crossover cable).
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1719
The wiring and colour code are standardised in EIA/TIA 568A/568B.
In accordance with the industrial standard, the use of 4-pin Ethernet cables is
permissible. The cable type only connects the assigned pins 1, 2, 3 and 6 to one another.
[5-7]Ethernet connector in accordance with EIA/TIA 568A/568B
PairPinSignalEIA/TIA 568AEIA/TIA 568B
31Tx +White / GreenWhite / Orange
2Tx -GreenOrange
23Rx +White / OrangeWhite / Green
14BlueBlue
5White / BlueBlue / White
26Rx -OrangeGreen
47White / BrownWhite / Brown
8BrownBrown
E94YCEI004A
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1721
During commissioning, plant-specific data such as motor parameters, operating parameters,
responses, and parameters for fieldbus communication are defined for the inverter. Lenze devices
use codes for this purpose.
The codes of the inverter and for communication are saved to the memory module in a non-volatile
data set.
In addition, there are codes for diagnosing and monitoring the stations.
Parameter reference
6.1Before initial switch-on
( 88)
Stop!
Before you switch on the Inverter Drive 8400 protec for the first time, check the entire
wiring for completeness, short circuit, and earth fault.
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1723
First you have to configure the host (scanner) for communication with the Inverter Drive 8400
protec.
The configuration of EtherNet/IP networks always requires an EtherNet/IP configuration software
(e.g. »RSLogix 5000« from Rockwell) for the host system (scanner).
The configuration software is necessary for the programming of controller programs, EtherNet/IP
configuration, real-time execution and diagnostics.
The basic parameters of the communication module are stored in the internal configuration
memory and can be used by the scanner when the nodes are being detected.
For node detection (fieldbus scan), the corresponding device descriptions of the Lenze device family
are used.
Tip!
Here you will find information on configuring with the »RSLogix 5000« programming
software from Rockwell:
I/O configuration with »RSLogix 5000« version 19 or lower
( 53)
I/O configuration with »RSLogix 5000« version 20 or higher
( 58)
24
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
Depending on the EtherNet/IP scanner configuration software, the EDS files (Electronic Data Sheet)
may be used for the configuration of the network profile, the communication with the participating
devices and the automatic generation of tags. For this purpose, the EDS files must be imported into
the controller project of the scanner configuration software.
The EDS file required for the configuration can be found in the download area at:
www.Lenze.com
Tip!
From version 20 onwards, Rockwell's »RSLogix 5000« programming software features an
"EDS Hardware Installation Tool" that can be used to ...
• install/import EDS files;
• create EDS files;
• carry out EDS uploads;
• delete EDS files from your controller project.
In »RSLogix 5000«, the dialog for the "EDS Hardware Installation Tool" is self-explanatory
and not described further in this documentation.
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1725
6.2.2Example: IP configuration of the Allen-Bradley 1769-L32E CompactLogix controller
In this example, the Allen-Bradley CompactLogix control unit 1769-L32E with integrated EtherNet/
IP interface is used for communication with the Inverter Drives 8400 protec.
The »RSLogix 5000« programming software from Rockwell is used for the configuration.
To establish communication via an EtherNet/IP network, add the controller and its scanner to the I/
O configuration.
How to set the IP configuration of the 1769-L32E CompactLogix controller using the
»RSLogix 5000« programming software:
1. Click on the I/O Configuration folder in the configuration tree.
2. Right click on "1769-L32E Ethernet Port LocalENB" and select "Properties" from the context
menu.
3. Go to the General tab of the "Module Properties: ..." dialog window and enter the IP address
of the scanner.
4. Then click OK.
26
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
6.3Setting the IP configuration of the Inverter Drive 8400 protec
IP configuration is necessary in order to assign an address to the Inverter Drive 8400 protec so that
communication between the PC/»Engineer« or the scanner and the inverter is possible via
EtherNet/IP. For this purpose, an IP address, subnet mask and gateway address have to be assigned.
You can assign these IP parameters for the Inverter Drive 8400 protec in the following ways:
• Setting via the EtherNet/IP configurator of the »Engineer«
• Setting via codes in the »Engineer«
• Setting via a BOOTP/DHCP server
• Setting via the TCP/IP Interface Object (0xF5)
( 31)
( 33)
( 33)
( 29)
Note!
• The assignment of invalid combinations of IP address, subnet mask, and gateway
address can have the consequence that no connection to the EtherNet/IP network can
be established.
•Codes C13010
C13016
• In the case of impermissible settings, the error message EtherNet/IP: Invalid IP
Parameter [0x01bc6533] ( 80) is output.
(IP address), C13011 (subnet mask), C13012 (gateway address), and
(multicast IP address) show the IP parameters currently used.
28
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
6Commissioning
6.3Setting the IP configuration of the Inverter Drive 8400 protec
DHCP is the acronym for "Dynamic Host Configuration Protocol". This protocol is defined in
RFC 2131 and is a compatible advancement of the "Bootstrap Protocol" (BOOTP) according to
RFC 951.
Both protocols enable network nodes to query information about the network configuration (e.g.
the IP address) from a server via a TCP/IP network. The BOOTP/DHCP server assigns the IP address
to the client dynamically from a defined address range. This means that the client receives an
unambiguous IP address.
Code C13005
• Value '0': The IP configuration currently stored in the Inverter Drive 8400 protec is used.
• Value ’1’: BOOTP is used. (Lenze standard setting)
• Value ’2’: DHCP is used.
The setting can also be selected by write access to attribute 3 (configuration control) of instance 1
of the TCP/IP Interface Object (245 / 0xF5)
is used to select how the IP configuration is to be made:
TCP/IP Interface Object (245 / 0xF5).
6.3.4Setting via the TCP/IP Interface Object (0xF5)
With a scanner, the IP configuration can be set via attribute 5 (interface configuration) of instance 1
of the TCP/IP Interface Object (245 / 0xF5)
After the IP configuration, carry out a node reset ("power off/on" or "Type 0 reset" for the Identity
Object (1 / 0x01) ( 108)).
In the »Engineer«, codes C13010
and C13016
(multicast IP address) show the IP parameters currently used.
Several scanners ("Listen only" or "Input only" connections) can access multicast telegrams which
are sent by the inverter. Settings for multicast configuration have to be carried out as well in the
EtherNet/IP configuration software (e.g. »RSLogix 5000« from Rockwell).
By default, the Inverter Drive 8400 protec automatically generates the Multicast IP start address for
I/O data transfer. The standard TTL value for Multicast transfer is ’1’; the Multicast I/O data
packages are therefore distributed solely via the local network.
Note!
You can also explicitly set the multicast IP start address and the multicast TTL value. We
recommend, however, not to change the default settings in order to ensure a secure
multicast transmission.
The following multicast codes are configurable:
CodeDescription
C13018
C13019
C13020
Multicast IP Start Address
Multicast IP start addresses serve to send a message to the members of a certain group (i.e. possibly
to several nodes).
The multicast IP start address is set/changed in C13006
The currently used multicast IP address of the inverter is displayed in C13016/1...4
Example: Display of the multicast IP address 239.64.2.224
CodeC13016/1
Value239642224
Selection for multicast IP addressing via instance attribute 9 (Mcast Config) in the TCP/IP
Interface Object (245 / 0xF5) ( 124)
• Value ’0’: The default algorithm is used.
• Value ’1’: The address from code C13006
Setting of the multicast TTL value for the validity time of data packets in the EtherNet/IP
network
(Instance attribute 8 (TTL Value) in the TCP/IP Interface Object (245 / 0xF5)
Used to set how many multicast IP addresses will be assigned.
(Instance attribute 9 (Num Mcast) in the TCP/IP Interface Object (245 / 0xF5)
C13016/2C13016/3C13016/4
is used as multicast IP start address.
( 124))
( 124))
.
.
34
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
6Commissioning
6.4Establishing an online connection via EtherNet/IP with the Lenze »Engineer«
6.4Establishing an online connection via EtherNet/IP with the Lenze »Engineer«
Note!
• In order to ensure perfect operation of cyclic EtherNet/IP communication, online
access with the »Engineer« should be executed via an IEEE 802.1Q-capable switch.
• The IEEE 8400 802.1Q-capable switch integrated in the Inverter Drive 8400 protec can
manage cyclical EtherNet/IP-communication primarily for normal TCP/IP
communication. In the case of EtherNet/IP, this is done by means of the VLAN
identification in the Ethernet frame (can be set in C13021
• If the redundancy protocol DLR (Device Level Ring) is used, the switch also must be
DLR-compliant.
).
[6-1]Example set-up with an Allen Bradley CompactLogix Controller 1769-L32E (scanner)
For an online connection between the »Engineer« and the inverter, the inverter must have an IP
address (see Setting the IP configuration of the Inverter Drive 8400 protec
( 28)).
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1735
6Commissioning
6.4Establishing an online connection via EtherNet/IP with the Lenze »Engineer«
In the »Engineer«, you can use the Online Set communication path and go online menu
command to select the EtherNet/IP communication path. The previously configured EtherNet/IP
nodes are shown in the "Communication path" dialog window:
If the device access path is not configured correctly, here the IP address of the inverter selected
in the display field can be entered manually.
Via the Search/Enter button, you can establish a connection to devices which have not
appeared in the display field. Corresponding settings for this can be made in the "Enter IP Address"
dialog window that will appear:
Here you can enter an IP address manually or execute the following actions using the buttons:
• Execute the console command Ping.
• Assign the IP address via the Configurator.
Setting via the EtherNet/IP configurator of the »Engineer«
( 29)
36
• Select the device access path to the desired inverter by clicking Find.
After having established the online connection, you can continue work with the »Engineer« as
usual.
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
Mounting instructions for the Inverter Drive 8400 protec
Observe the safety instructions and residual hazards stated.
Note!
Activating changed settings
To activate changed settings ...
• execute device command "11: Save all parameter sets" via inverter code C00002
and ...
• carry out a "type 0 reset" to the Identity Object (1 / 0x01)
switch the voltage supply of the communication module off and then on again.
Protection against uncontrolled restart
After a fault (e.g. short-time mains failure), the restart of a drive is not always wanted
and - in some cases - even not allowed.
( 108) of the bus node or
In the Lenze setting of the Inverter Drives 8400 protec, the restart protection is activated.
The restart behaviour of the inverter can be set via C00142 ("Autostart Option"):
C00142 = 9 (Lenze setting)
• The inverter remains inhibited (even if the fault is no longer active).
• Bit 0 (inhibit at "power-on") and bit 3 (inhibit in the case of undervoltage) are set.
• The drive starts in a controlled mode by an explicit controller enable: LOW-HIGH edge
on a digital input configured correspondingly (terminals X41, X42, X43).
C00142 = 8 (enabled)
• In order to enable the device directly when switching it on, set bit 0 to zero.
• An uncontrolled restart of the drive is possible.
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1737
EtherNet/IP uses CIP™ (Common Industrial Protocol) for the data exchange between devices via an
Ethernet network – just like the closely related bus systems DeviceNet and ControlNet.
Lenze implements the CIP following the ODVA standard (Open DeviceNet Vendor Association,
www.odva.org
• Explicit messaging (for parameter data)
• Implicit messaging (for I/O data)
) and supports the two main types of EtherNet/IP communication:
38Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
The terms "input" and "output" refer to the point of view of the scanner:
• Input data is produced by the adapter and consumed by the scanner.
• Output data is produced by the scanner and consumed by the adapter.
EtherNet/IP transmits parameter data and I/O data between the host system (scanner) and the
inverters (adapters) connected to the fieldbus. The data are transmitted via corresponding
communication channels depending on their time-critical behaviour.
The I/O data channel transmits I/O data by means of "implicit messages".
• The inverter is controlled by means of the I/O data.
• The transmission of I/O data is time-critical.
• I/O data are transmitted cyclically between the host system (scanner) and the inverters
(adapters) (permanent exchange of current input and output data).
• The host system (scanner) has direct access to the I/O data (the data are, for example, stored
directly in the I/O area).
• In the case of Inverter Drives 8400 protec, maximally 16 data words (max. 32 bytes) can be
exchanged for each direction.
• I/O data are not stored in the inverter.
• I/O data are e.g. setpoints, actual values, control and status words
The parameter data channel transmits parameter data by means of "explicit messages".
• The transmission of parameter data is usually not time-critical.
• Examples of parameter data are operating parameters, motor data, and diagnostic information.
• The parameter data channel provides access to all Lenze codes.
• Parameter changes must be saved by means of code C00002 of the Inverter Drive 8400 protec.
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1739
The "implicit message" and "explicit message" telegram types are transmitted between the host
system (scanner) and the inverter (adapter).
Implicit messages (I/O data transfer)
"Implicit messages" are transmitted or received according to the producer/consumer principle.
There is one transmitter and no receiver or an optional number of receivers.
The "cyclic I/O data" transmission mode is supported. The scanner and the adapter use "cyclic I/O
data" to generate their data independently of each other, which are then transmitted depending on
a timer. The user must set the value of the timer in the scanner.
Explicit messages (parameter data transfer)
"Explicit messages" serve to configure and parameterise the individual EtherNet/IP nodes.
Two nodes have a client/server relationship:
The client transmits a job (request). The server receives this job and tries to accomplish it. The server
then transmits the requested data (positive response) or an error message (negative response).
40
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
The Inverter Drives 8400 protec is provided with various drive profiles. They define a standardised
or individual control and status word assignment and the standardisation of setpoints and actual
value scalings.
The following drive profiles are supported by the inverter:
The technology applications integrated in the inverter provide the main signal flow for realising a
general or specific drive solution.
For using the Lenze technology application selection in the »Engineer« via standard device code
C00005, the following assembly object instances have to be used in the host (scanner):
Instance IDAssembly object instance
[dec][hex]
1100x6ECustom Output
(from the adapter to the scanner)
1110x6FCustom Input
(from the adapter to the scanner)
See also Assembly Object (4 / 0x04)
The custom assemblies also allow for a user-definable parameter setting, depending on the
application. Hence, 16 data words (32 bytes) can be freely assigned with variables of the MCI port
blocks in the »Engineer«.
The user-definable parameter setting can be used in addition to the previously set technology
application.
"AC Drive Profile" application200x14Basic Speed Control Output
1100x6ECustom Output
1110x6FCustom Input
210x15Extended Speed Control Output
220x16Speed and Torque Control Output
230x17Extended Speed and Torque Control Output
700x46Basic Speed Control Input
710x47Extended Speed Control Input
720x48Speed and Torque Control Input
730x49Extended Speed and Torque Control Input
( 43)).
Assembly output objects (outputs) are usually used for controlling the enable/disable state of the
inverter and for supplying the speed or torque references.
Assembly input objects (inputs) are usually used to monitor the drive status and the runtime values
such as actual speed, current, actual position and position error.
Depending on the data length defined by the scanner, the memory map of the I/O data can have
different sizes.
46
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
Assembly output objects are assumed to have a 4-byte header (32-bit "run/idle header"). When
mapping the assemblies, this header will automatically be added to the data stream by most AllenBradley PLC/SLC equipment.
If your PLC does not support this header (like the Rockwell PLCs do), add a preceding 32-bit header
to the output image.
You can then define the bit 0 of this header in the process image of your PLC:
•0: Idle mode
• 1: Run mode
For the operation with Rockwell PLCs, adaptations are not required.
Assembly input objects (adapter scanner)
The assembly input objects are mapped in the adapter memory starting with byte 0.
The input objects are transmitted in a "modeless" manner, i.e. a 4-byte header (32-bit "Run/Idle
header") is not included in the transfer.
So the start address in the assembly memory map is the actual start of the first assembly data
element.
Please observe the actual assembly lengths when mapping the input objects to the controller
memory.
The contents of the input data depends on the I/O data arrangement in the inverter (I/O data
mapping ( 43)).
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1747
4. In the "Edit port" dialog window, you can assign signals to the I/O data words via the
button.
Select the signals and confirm the selection with OK.
50
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
8.5I/O configuration with »RSLogix 5000« version 19 or lower
The following example describes the I/O configuration of the Allen-Bradley 1769-L32E
CompactLogix controller using the Rockwell »RSLogix 5000« programming software up to version
19.
Up to and including software version 19 the I/O configuration is carried out without
EDS files ( 25).
How to carry out the I/O configuration, taking the CompactLogix controller 1769-L32E
with »RSLogix 5000« as an example:
1. Click the I/O Configuration folder in the configuration tree.
For the 1769-L32E CompactLogix controller, the I/O configuration already includes a local
Ethernet port.
If a SoftLogic or ControlLogix controller is used, an Ethernet port scanner needs to be added
to the configuration.
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1753
8I/O data transfer (implicit messages)
8.5I/O configuration with »RSLogix 5000« version 19 or lower
5. Go to the "New Module" dialog window and define the properties of the newly added
device .
The terms "input" and "output" refer to the point of view of the scanner:
• Assembly input objects (input) are sent from the adapter to the scanner.
• Assembly output objects (output) are sent from the scanner to the adapter.
Settings for Lenze technology applications or user-definable parameter sets:
If a Lenze technology application or an individual parameter set is used in the inverter, the
assembly object instances "Input = 111" and "Output = 110" can be used to
exchange up to 16 user-definable words (INT) via ports MCI_IN and MCI_OUT.
Go to "Configuration" and enter the Assembly instance "130" and the Size "0".
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1755
8I/O data transfer (implicit messages)
8.5I/O configuration with »RSLogix 5000« version 19 or lower
The assembly object instances "Input = 73" and "Output = 23" shown here
exemplify the use of the AC Drive Profile "Extended Speed and Torque".
SettingsDescription
NameDevice name or type of inverter, usually with reference to the process (in the
Comm FormatData format for the assembly object instances ("connection parameters" area)
IP AddressIP address of the inverter
InputAssembly object instance for input objects
OutputAssembly object instance for output objects
ConfigurationSelect the Assembly instance "130" and the Size "0" for the configuration. These
example "My_E84AYCEO")
• T he IP address must be in the same subnetwork like the controller. (Depending on
the subnet mask; in general, the first 3 octets of the IP address must be identical.)
• DNS is not supported; the host name merely describes the device.
• Max. 16 input data words (32 bytes, 16 bits/word)
• The number of input data must correspond to the length of the mapped ports in
the transmit PDO (PDO_TX0), otherwise the adapter will reject the connection
with the error message "Invalid Target to Originator Size" (0x0128).
I/O data mapping
• Max. 16 output data words (32 bytes, 16 bits/word)
• The number of output data must correspond to the length of the mapped ports
in the receive PDO (PDO_RX0), otherwise the adapter will reject the connection
with the error message "Invalid Originator to Target Size" (0x0127).
I/O data mapping
values are required!
( 43)
( 43)
56
6. Complete the settings with OK.
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
8I/O data transfer (implicit messages)
8.5I/O configuration with »RSLogix 5000« version 19 or lower
8.6I/O configuration with »RSLogix 5000« version 20 or higher
The following example describes the I/O configuration of the Allen-Bradley 1769-L32E
CompactLogix controller using the Rockwell »RSLogix 5000« programming software from version
20.
From software version 20 onwards, EDS files
( 25) are used for the I/O configuration.
How to carry out the I/O configuration, taking the CompactLogix controller 1769-L32E
with »RSLogix 5000« as an example:
1. Use the "EDS Hardware Installation Tool" item to import the EDS files
EtherNet/IP nodes.
In »RSLogix 5000«, the dialog for the "EDS Hardware Installation Tool" is self-explanatory
and not described further in this documentation.
2. Click the I/O Configuration folder in the configuration tree.
( 25) of the
58
For the 1769-L32E CompactLogix controller, the I/O configuration already includes a local
Ethernet port.
If a SoftLogic or ControlLogix controller is used, an Ethernet port scanner needs to be added
to the configuration.
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
8I/O data transfer (implicit messages)
8.6I/O configuration with »RSLogix 5000« version 20 or higher
8. Go to the "Module Definition" dialog window and make the connection settings.
The terms "input" and "output" refer to the point of view of the scanner:
• Assembly input objects (input) are sent from the adapter to the scanner.
• Assembly output objects (output) are sent from the scanner to the adapter.
Settings for Lenze technology applications or user-definable parameter sets:
•Select "Exclusive Owner - Custom" connection.
If you use the Lenze technology applications or user-definable parameter sets in the
inverter, the "Exclusive Owner - Custom" assembly object instance always has to be
selected.
•SetData type = INT.
The INT data type is exchanged via the ports MCI_IN and MCI_OUT of the Inverter Drives
8400 protec. In case of the SINT data type, an additional PLC logic is required for
conversion.
•SetTag Suffix = 1.
A tag suffix formulates a module-describing tag name.
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1761
8I/O data transfer (implicit messages)
8.6I/O configuration with »RSLogix 5000« version 20 or higher
In the example, the AC Drive Profile "Exclusive Owner - AC Drive Ext. Speed & Torque" is
used.
•SetData type = INT.
The INT data type is exchanged via the ports MCI_IN and MCI_OUT of the Inverter Drives
8400 protec. In case of the SINT data type, an additional PLC logic is required for
conversion.
•SetTag Suffix = 1.
A tag suffix formulates a module-describing tag name.
9. Complete the settings with OK.
62
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
8I/O data transfer (implicit messages)
8.6I/O configuration with »RSLogix 5000« version 20 or higher
• The inverter is inserted in the configuration tree under the "I/O Configuration".
• The corresponding tags are created in the "Controller Tags".
• The example shows the ...
input assembly tags as "MY_EIP8400_FROM_EDS:I1";
output assembly tags as "MY_EIP8400_FROM_EDS:O1";
If you click the "+" in front of the assembly tag name, all data contained in the assembly
tags are shown below it. You can create "alias tags" to reference to single bits of the
assembly tag.
64
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
8I/O data transfer (implicit messages)
8.6I/O configuration with »RSLogix 5000« version 20 or higher
• NetCtrl (Bit 5) and NetRef (Bit 6) have to be set in order that the inverter can receive
start/stop commands and speed/torque command via the network.
• In order to be able to use the torque control of the assembly object distance 23 (0x17),
the "DriveMode" attribute has to be written by means of explicit message
transmission.
Write "DriveMode" attribute
( 137)
Right-click an assembly tag and select the command "New Tag..." in the context menu.
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1765
8I/O data transfer (implicit messages)
8.6I/O configuration with »RSLogix 5000« version 20 or higher
After adding the scanner and the adapter to the I/O configuration, the configuration must be
downloaded to the controller. The configuration file should also be saved on your computer.
How to save the I/O configuration:
1. Select the menu command Communications Download.
• The "Download" dialog box will open.
• If a message box reports that »RSLogix 5000« is unable to go online, select the menu
command Communications Communications Who Active and try to find your
controller in the "Who Active" dialog box. If the controller is not shown there, the
EtherNet/IP driver needs to be added to »RSLinx« or configured in »RSLinx«. For more
information, please refer to the »RSLinx« online help.
2. Click the Download button.
• The I/O configuration is downloaded to the controller.
• When the download has been successfully completed, »RSLogix 5000« changes to online
mode and the I/O OK box in the upper left of the screen is green.
3. Select the menu command File Save.
• If this is the first time the I/O configuration is saved, the "Save As" dialog box will open.
• Select a folder and enter a file name to save the configuration to a file on your computer.
• Finally, click the Save button.
68
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
An "explicit message" is a logical instruction in the PLC program used for messaging. It can be used
to read or write to either a parameter setting or the data of an assembly.
For all Allen-Bradley devices of the CompactLogix, ControlLogix and SoftLogix series, the MSG
instruction provides the application possibilities described in this chapter. For other PLC types,
please consult the programming documentation for the corresponding PLC.
Note!
When you use several MSG BLOCKs per adapter, you can work resource-friendly by
sequential triggering and hold available enough communication reserves in the
EtherNet/IP module for further possible clients.
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1769
In order to write data into code C00011 of the Inverter Drive 8400 protec by means of explicit
message transfer, for example, the following settings are necessary:
SettingsValue / description
Message Type"CIP Generic"
Service Type"Set Attribute Single" (service code "0x10")
Class"0x6E" (access to Lenze code)
Instance"11" = Lenze code C00011 of Inverter Drive 8400 protec
Attribute"1" = Subcode of the Lenze code
• If the corresponding Lenze code does not have a subcode, the value ’1’
must be entered here.
• A display code cannot be configured by the "SET" service.
Source ElementVariable in the PLC program used as data source for writing.
Source LengthFor writing to code C00011, set the source length to "2 bytes".
70
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
In order to read out Lenze code C00011 of the Inverter Drive 8400 protec by means of explicit
message transfer, for example, the following settings are necessary:
SettingsValue / description
Message Type"CIP Generic"
Service Type"Get Attribute Single" (service code "0x0E")
Class"0x6E" (access to Lenze code)
Instance"11" = Lenze code C00011 of Inverter Drive 8400 protec
Attribute"1" = Subcode of the Lenze code
If the corresponding Lenze code does not have a subcode, the value ’1’ must
be entered here.
DestinationVariable in the PLC program the drive data will be copied to.
When reading code C00011, make sure that the tag used as destination is a
single word in UINT16 format.
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1771
For every "explicit message", the path for sending the message via the Ethernet port of the drive to
the IP address of the inverter needs to be set under the Communication tab.
If you need assistance with the setting of this path, please consult the PLC manufacturer.
72
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
You can set the reactions of the Inverter Drive 8400 protec to a fault in EtherNet/IP communication
in »Engineer« by opening the Monitoring tab and making the appropriate settings.
SettingsDescription
Idle ModeThe 32-bit real time header sent by the scanner is evaluated.
Run/idle flag (bit 0) = 1:
• The scanner indicates the validity of the I/O data.
Run/idle flag (bit 0) = 0:
• The I/O data are invalid and the response parameterised here (C13880/1
is executed on the inverter.
• The I/O data are processed as set in (C13885
Overall Ethernet
Communication Timeout
Fault ModeThe adapter (Inverter Drive 8400 protec) monitors the I/O connection to the
Overall Ethernet Timeout Time Here, the overall message timeout time (C13881) is set.
Explicit Msg Timeout If no "explicit message" has been received within the timeout time for
Clear I/O Data(C13885
If there is no reception of explicit or implicit messages after expiry of the
time set in (C13881
after this time, the reaction parameterised here takes place in the inverter
(C13880/4
Access to the web server is not monitored.
scanner.
If no "implicit message" has been received within the timeout time for
implicit messages parameterised by the scanner, the response
parameterised here (C13880/2
If no message has been received within this time, the response
parameterised in (C13880/4
The following messages are monitored:
• Implicit messages
• Explicit messages
• »Engineer« access via EtherNet/IP
explicit messages parameterised by the scanner, the response
parameterised here (C13880/3
maintain internal communication if ...
• the CIP network status (C13862
• an idle event has occurred.
).
), serves to set the I/O data to be processed by the adapter to
"Connected" or
) or if access via »Engineer« no longer takes place
) is executed on the inverter.
) is executed.
) is executed on the inverter.
) of the controlling I/O connection is not
).
)
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1773
The LEDs on the front of the inverter are provided for the purpose of fault diagnostics. In addition,
»Engineer« enables comprehensive diagnosis of the entire EtherNet/IP network.
Safety engineering manual for Inverter Drives 8400 protec
Here you can find detailed information on the LED status displays for devices with an
integrated safety system.
11.1LED status displays
E84DPSO06
[11-1] LED display on the front of the Inverter Drive 8400 protec
74
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
The communication module is not supplied with voltage.
OffOn
CIP module status: "Major Unrecoverable Fault"
The device displays an unrecoverable fault.
The status is set if the pending status-determining device error has the
reaction 'system fault'.
OffBlinking
CIP module status: "Major Recoverable Fault"
The device displays a recoverable fault.
The status is set if the pending status-determining device error has the
reaction 'error', 'fault', 'quick stop by trouble', 'warning locked' or
'warning'..
OnOff
BlinkingOff
BlinkingBlinking
CIP module status: "Operational"
The device is working correctly.
CIP module status: "Standby"
The device has not been completely configured yet or the configuration
is incorrect (e.g. invalid IP address).
CIP module status: "Device Self Testing"
The device is in the state of self testing.
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1775
This chapter supplements the error list in the reference manual and the »Engineer« online help for
the Inverter Drive 8400 protec by the EtherNet/IP error messages.
Reference manual / »Engineer« online help for Inverter Drives 8400 protec
Here you will find general information on diagnostics & fault analysis and on error
messages.
12.1Short overview of the EtherNet/IP error messages
The following table lists all EtherNet/IP error messages in the numerical order of the error numbers.
Furthermore, the preset error response and - if available - the parameter for setting the error
response are specified.
Tip!
If you click on the cross-reference in the first column, you will get a detailed description
(causes and remedies) of the corresponding error message.
Error no.
[hex]
0x01bc3100
0x01bc5531
0x01bc5532
0x01bc5533
0x01bc6010
0x01bc6011
0x01bc6100
0x01bc6101
0x01bc641f
0x01bc6420
0x01bc6430
0x01bc6533
0x01bc8111
0x01bc8112 44433042EtherNet/IP: Explicit Message Timeout0: No ResponseC13880/3
0x01bc8114 44433044EtherNet/IP: Overall Ethernet Timeout0: No ResponseC13880/4
0x01bc8121 44433057EtherNet/IP: Ethernet cable pulled out1: No Response-
0x01bc8132
0x01bc8273 44433395EtherNet/IP: Duplicate IP Address1: No Response-
Subject area
no.
[dec]
44412544EtherNet/IP: Exist. connect. to 8400 lost0: No Response-
44421809EtherNet/IP: Memory: No Access1: No Response-
44421810EtherNet/IP: Memory: Read Error1: No Response-
44421811EtherNet/IP: Memory: Write Error1: No Response-
44424592EtherNet/IP: Restart by Watchdogreset1: No Response-
44424593EtherNet/IP: Internal Error1: No Response-
44424832EtherNet/IP: Internal Error1: No Response-
44424833EtherNet/IP: Internal Error1: No Response-
44425631EtherNet/IP: Invalid Parameter Set1: No Response-
44425632EtherNet/IP: Error: Lenze Setting Loaded1: No Response-
44425648EtherNet/IP: Invalid Configuration1: No Response-
44425907EtherNet/IP: Invalid IP Parameter1: No Response-
44433041EtherNet/IP: Fault Mode1: No ResponseC13880/2
44433074EtherNet/IP: Idle Mode0: No ResponseC13880/1
Error no.
[dec]
Error textError type
(Error response)
Adjustable
in
78
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
This chapter lists all EtherNet/IP error messages in the numerical order of the error numbers.
Possible causes and remedies as well as responses to the error messages are described in detail.
EtherNet/IP: Exist. connect. to 8400 lost [0x01bc3100]
Response (Lenze setting printed in bold)Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
CauseRemedy
• Network cable (plug) is defective.
• Network cable at EtherNet/IP terminal X31 or X32 is
disconnected.
• Voltage supply is interrupted.
EtherNet/IP: Memory: No Access [0x01bc5531]
• Check cables and terminals.
• Plug in network cable at EtherNet/IP terminal X31 or
X32.
Response (Lenze setting printed in bold)Setting: not possible
None System fault Fault Trouble Quick st op by trouble Warning locked Warning Information
CauseRemedy
Access to memory was not possible.Send the device and a description of the fault to Lenze.
EtherNet/IP: Memory: Read Error [0x01bc5532]
Response (Lenze setting printed in bold)Setting: not possible
None System fault Fault Trouble Quick st op by trouble Warning locked Warning Information
CauseRemedy
Parameter could not be read.Send the device and a description of the fault to Lenze.
EtherNet/IP: Memory: Write Error [0x01bc5533]
Response (Lenze setting printed in bold)Setting: not possible
None System fault Fault Trouble Quick st op by trouble Warning locked Warning Information
CauseRemedy
Parameter could not be written.Send the device and a description of the fault to Lenze.
EtherNet/IP: Restart by Watchdogreset [0x01bc6010]
Response (Lenze setting printed in bold)Setting: not possible
None System fault Fault Trouble Quick st op by trouble Warning locked Warning Information
CauseRemedy
Device is defective.Send the device and a description of the fault to Lenze.
EtherNet/IP: Internal Error [0x01bc6011]
Response (Lenze setting printed in bold)Setting: not possible
None System fault Fault Trouble Quick st op by trouble Warning locked Warning Information
CauseRemedy
Device is defective.Send the device and a description of the fault to Lenze.
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1779
12.4Mapping of Lenze device errors to DRIVECOM errors
Via the instance attribute "FaultCode" of the Control Supervisor Object (41 / 0x29) ( 133) Lenze
device errors are output with the DRIVECOM error numbers.
The following tables show the assignment of the Lenze device errors to the "CAN Emergency Error
Codes" and DRIVECOM errors.
Reference manual / »Engineer« online help for Inverter Drives 8400 protec
Here you will find detailed information about the Lenze error messages listed in the
following table.
Lenze errorCAN DRIVECOM error
Error number
[32 bits]
xx.0111.00002Su02: One mains phase is missing0x30000x3000Voltage
xx.0111.00003Su03: Too frequent mains switching0x30000x3000Voltage
xx.0111.00004Su04: CU insufficiently supplied0x30000x3000Voltage
This chapter supplements the parameter list and the table of attributes in the reference manual and
the »Engineer« online help for the Inverter Drives 8400 protec by the EtherNet/IP parameters.
Reference manual / »Engineer« online help for Inverter Drives 8400 protec
Here you will find general information on parameters.
13.1Parameters relevant for communication
This chapter lists the EtherNet/IP parameters in numerically ascending order.
C13000
C13001
Parameter | Name:
C13000 | IP Address
Setting of the IP address
Setting the IP configuration of the Inverter Drive 8400 protec
Setting range (min. value | unit | max. value)
0255
SubcodesLenze settingInfo
C13000/1192IP address (most significant byte)
C13000/2168IP address
C13000/3124IP address
C13000/416IP address (least significant byte)
Read access Write access CINH PLC STOP No transfer PDO_MAP_ RX PDO_MAP_TX COM MOT
Parameter | Name:
C13001 | Subnetwork Mask
Setting of the subnet mask
Setting the IP configuration of the Inverter Drive 8400 protec
Setting range (min. value | unit | max. value)
0255
SubcodesLenze settingInfo
C13001/1255Subnet mask (most significant byte)
C13001/2255Subnet mask
C13001/3255Subnet mask
C13001/40Subnet mask (least significant byte)
Read access Write access CINH PLC STOP No transfer PDO_MAP_ RX PDO_MAP_TX COM MOT
( 28)
( 28)
Data type: UNSIGNED_8
Index: 11575
Data type: UNSIGNED_8
Index: 11574
= 2D37
d
= 2D36
d
h
h
88
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
Setting of the baud rate for the Ethernet connections
Connection via RJ45 socket: Dependent on the configuration of the Ethernet port of the device to be connected, we
recommend to use a cross-over cable.
EtherNet/IP connection via the RJ45 socket
( 19)
Selection list
0Auto-Negotiation
1 10 Mbps
2 100 Mbps
3 Reserved
4 Reserved
5 10 Mbps/Half Duplex
6 10 Mbps/Full Duplex
7 100 Mbps/Half Duplex
8 100 Mbps/Full Duplex
9 Reserved
10 Reserved
11 Reserved
12 Reserved
SubcodesLenze settingInfo
C13017/10: Auto-NegotiationEthernet setting port X31
C13017/20: Auto-NegotiationEthernet setting port X32
Read access Write access CINH PLC STOP No transfer PDO_MAP_ RX PDO_MAP_TX COM MOT
C13018
C13019
Parameter | Name:
C13018 | Multicast Config Alloc Control
Data type: UNSIGNED_8
Index: 11557
= 2D25
d
Selection for multicast IP addressing via instance attribute 9 (Mcast Config) in the TCP/IP Interface Object (245 /
0xF5) ( 124)
Selection list (Lenze setting printed in bold)
0 Default Allocation Algorithm
1 Multicast IP Start Address
Read access Write access CINH PLC STOP No transfer PDO_MAP_ RX PDO_MAP_TX COM MOT
Parameter | Name:
C13019 | Multicast Config TTL Value
Data type: UNSIGNED_8
Index: 11556
= 2D24
d
Setting of the multicast TTL value for the validity time of data packets in the EtherNet/IP network
(Instance attribute 8 (TTL Value) in the TCP/IP Interface Object (245 / 0xF5)
( 124))
Setting range (min. value | unit | max. value)Lenze setting
1255 1
Read access Write access CINH PLC STOP No transfer PDO_MAP_ RX PDO_MAP_TX COM MOT
h
h
92
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
Used to set how many multicast IP addresses will be assigned.
(Instance attribute 9 (Num Mcast) in the TCP/IP Interface Object (245 / 0xF5)
( 124))
Setting range (min. value | unit | max. value)Lenze setting
181
Read access Write access CINH PLC STOP No transfer PDO_MAP_ RX PDO_MAP_TX COM MOT
Parameter | Name:
C13021 | Quality of Service (VLAN-Tagging)
Data type: UNSIGNED_8
Index: 11554
= 2D22
d
Used to set whether QoS tags will be used for the prioritisation of the data packets to be transferred.
(Instance attribute 1 (802.1Q Tag Enable) in the TCP/IP Interface Object (245 / 0xF5)
( 124))
Selection list (Lenze setting printed in bold)
0 802.1Q Tag Disable
1 802.1Q Tag Enable
Read access Write access CINH PLC STOP No transfer PDO_MAP_ RX PDO_MAP_TX COM MOT
Parameter | Name:
C13022 | Quality of Service (DSCP)
Data type: UNSIGNED_8
Index: 11553
= 2D21
d
Setting for the prioritisation of the data packets to be transferred using Differentiated Services Codepoints (DSCP)
Setting range (min. value | unit | max. value)
063
SubcodesLenze settingInfo
C13022/159Reserved
C13022/247Reserved
C13022/355Reserved
C13022/447QoS DSCP Scheduled
(Instance attribute 5 (DSCP Scheduled) in the Quality of
Service (QoS) Object (72 / 0x48) ( 122))
C13022/543QoS DSCP High Prio
(Instance attribute 6 (DSCP High Prio) in the Quality of
Service (QoS) Object (72 / 0x48) ( 122))
C13022/631Reserved
C13022/727QoS DSCP Explicit Msg
(Instance attribute 8 (DSCP Explicit Msg.) in the Quality
of Service (QoS) Object (72 / 0x48) ( 122))
Read access Write access CINH PLC STOP No transfer PDO_MAP_ RX PDO_MAP_TX COM MOT
h
h
h
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1793
Display of the used DLR network topology (Device Level Ring)
(Instance attribute 1 (Network Topology) in the Device Level Ring (DLR) Object (71 / 0x47)
( 120))
Selection list (read only)
0 Linear
1 Ring
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13841 | DLR Network Status
Display of the DLR network status (Device Level Ring)
(Instance attribute 2 (Network Status) in the Device Level Ring (DLR) Object (71 / 0x47)
( 120))
Selection list (read only)
0 Normal
1 Ring Fault
2 Unexpected Loop detected
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Data type: UNSIGNED_8
Index: 10735
Data type: UNSIGNED_8
Index: 10734
= 29EF
d
= 29EE
d
h
h
C13843
Parameter | Name:
C13842 | Supervisor IP Address
Data type: UNSIGNED_8
Index: 10733
Display of the supervisor IP address
(Instance attribute 10 (Supervisor IP Address) in the Device Level Ring (DLR) Object (71 / 0x47)
( 120))
Display range (min. value | unit | max. value)
0255
SubcodesInfo
C13842/1Supervisor IP address (most significant byte)
C13842/2Supervisor IP Address
C13842/3Supervisor IP Address
C13842/4Supervisor IP address (least significant byte)
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13843 | Supervisor MAC ID
Data type: OCTET_STRING
Index: 10732
Display of the supervisor MAC ID
(Instance attribute 10 (Supervisor MAC Address) in the Device Level Ring (DLR) Object (71 / 0x47)
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
( 120))
= 29ED
d
= 29EC
d
h
h
94
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
Display of the MAC address of the EtherNet/IP node with the last address conflict (ACD).
The data of the last conflict will only be saved in this code if ACD is active at the moment when the conflict occurs
(C13846
(Instance attribute 11 (RemoteMAC) in the TCP/IP Interface Object (245 / 0xF5)
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13849 | Last Conflicted IP Address
=1).
( 124))
Data type: UNSIGNED_8
Index: 10726
= 29E6
d
Display of the MAC address of the EtherNet/IP node with the last address conflict (ACD).
The data of the last conflict will only be saved in this code if ACD is active at the moment when the conflict occurs
(C13846
=1).
Display range (min. value | unit | max. value)
0255
SubcodesInfo
C13849/1Last conflicted IP address (most significant byte)
C13849/2Last conflicted IP address
C13849/3Last conflicted IP address
C13849/4Last conflicted IP address (least significant byte)
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
h
h
C13850
Parameter | Name:
C13850 | All words to scanner
Data type: INTEGER_16
Index: 10725
= 29E5
d
Indication of the I/O data words that are transferred from the Inverter Drive 8400 protec (adapter) to the scanner.
In the subcodes, all I/O data words transferred to the scanner are displayed. However, only the configured I/O data
words are valid.
Display range (min. value | unit | max. value)
-3276832767
SubcodesInfo
C13850/1
...
C13850/16
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
h
96
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD17
Indication of the I/O data words that are transferred from the scanner to the Inverter Drive 8400 protec (adapter).
In the subcodes, all I/O data words transferred from the scanner are displayed. However, only the configured I/O
data words are valid.
Display range (min. value | unit | max. value)
-3276832767
SubcodesInfo
C13851/1
...
C13851/16
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13852 | All words to the basic device
Data type: INTEGER_16
Index: 10723
= 29E3
d
Indication of the I/O data words that are transferred from the scanner to the Inverter Drive 8400 protec (adapter).
In the subcodes, all I/O data words transferred from the scanner are displayed. However, only the configured I/O
data words are valid.
Display range (min. value | unit | max. value)
-3276832767
SubcodesInfo
C13852/1
...
C13852/16
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
h
h
C13853
Parameter | Name:
C13853 | All words to the basic device
Data type: INTEGER_16
Index: 10722
= 29E2
d
Indication of the I/O data words that are transferred from the Inverter Drive 8400 protec (adapter) to the scanner.
In the subcodes, all I/O data words transferred to the scanner are displayed. However, only the configured I/O data
words are valid.
Display range (min. value | unit | max. value)
-3276832767
SubcodesInfo
C13853/1
...
C13853/16
Read access Write access CINH PLC STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
h
Lenze · Decentralised frequency inverter 8400 protec (EtherNet/IP™ option) · Communication Manual · DMS 3.0 EN · 07/2014 · TD1797