This documentation exclusively describes the E84AYCPM communication module (PROFIBUS).
Note!
This documentation supplements the mounting instructions supplied with the
communication module and the "Inverter Drives 8400" hardware manual.
The hardware manual contains safety instructions which must be observed!
The features and functions of the communication module are described in detail.
Typical applications are explained with the help of examples.
The theoretical connections are only explained in so far as they are necessary for comprehending
the function of the communication module.
This documentation does not describe the software of other manufacturers. No responsibility is
taken for corresponding information given in this documentation. Information on how to use the
software can be obtained from the documents of the control system (master).
All brand names used in this documentation are trademarks of their respective owners.
Tip!
Detailed information about PROFIBUS can be found on the website of the PROFIBUS &
PROFINET user organisation:
www.profibus.com
5Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
This documentation is intended for all persons who plan, install, commission and maintain the
networking and remote servicing of a machine.
Tip!
Current documentation and software updates with regard to Lenze products can be found
in the download area at:
www.Lenze.com
Validity information
The information given in this documentation is valid for the following devices:
Extension moduleType designationFrom hardware
version
PROFIBUS communication moduleE84AYCPMVA01.00
Screenshots/application examples
All screenshots in this documentation are application examples. Depending on the firmware
version of the communication module and the software version of the Engineering tools installed
(»Engineer«, »STEP7«), the screenshots in this documentation may differ from the actual screen
display.
From software
version
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD176
This manual uses the following conventions to distinguish between different types of information:
Type of informationWritingExamples/notes
Numbers
Decimal separatorPointThe decimal point is always used.
Example: 1234.56
Hexadecimal0x[0 ... 9, A ... F]Example: 0x60F4
Binary
• Nibble
Text
Version informationText colour blueAll pieces of information that only apply to or from a specific
Program name» «The Lenze PC software »Engineer«...
WindowitalicsThe message window... / The Options dialog box ...
Variable nameSetting bEnable to TRUE...
Control elementBoldThe OK button ... / The Copy command ... / The Properties tab
Sequence of menu
commands
Hyperlinkunderlined
Symbols
Page reference ( 6)Optically highlighted reference to another page. Can be
Step-by-step instructions
In inverted commas
Point
Example: ’100’
Example: ’0110.0100’
software version of the inverter are highlighted accordingly
in this documentation.
Example: This function extension is available from software
version V3.0!
... / The Name input field ...
If several successive commands are required for executing a
function, the individual commands are separated from each
other by an arrow: Select the command File
Optically highlighted reference to another topic. Can be
activated with a mouse-click in this online documentation.
activated with a mouse-click in this online documentation.
Step-by-step instructions are indicated by a pictograph.
Open to...
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD178
Always observe the specified safety measures to avoid severe injury to persons and
damage to property!
Always keep this documentation to hand in the vicinity of the product during operation.
2.1General safety and application instructions
Danger!
If you disregard the following basic safety measures, this can cause severe injury to
persons and damage to material assets.
Lenze drive and automation components ...
• must only be used as directed.
Application as directed
• must never be commissioned in the event of visible damage.
• must never be technically modified.
• must never be commissioned before they have been completely mounted.
• must never be operated without the covers required.
• can - depending on their degree of protection - have live, moving or rotating parts during and
after operation. Surfaces can be hot.
For Lenze drive components ...
• use only the accessories approved.
• use only original spare parts from the manufacturer.
Observe all specifications given in the attached and associated documentation.
• This is the precondition for safe and trouble-free operation and for obtaining the product
features specified.
Features
• The procedural notes and circuit details described in this document are only proposals. It is up
to the user to check whether they can be adapted to the particular applications. Lenze does not
take any responsibility for the suitability of the procedures and circuit proposals described.
( 14)
( 13)
11
Only qualified personnel may work with and on Lenze drive and automation components.
According to IEC 60364 and CENELEC HD 384, these are persons ...
• who are familiar with the installation, assembly, commissioning and operation of the product.
• who have the corresponding qualifications for their work.
• who know all regulations for the prevention of accidents, directives and laws applicable on site
and are able to apply them.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 12
2Safety instructions
2.2Device- and application-specific safety instructions
2.2Device- and application-specific safety instructions
• During operation, the communication module must be firmly connected to the standard device.
• Only use cables corresponding to the given specifications.
Bus cable specification
( 28)
Documentation for the standard device, control system, plant/machine
All other measures prescribed in this documentation must also be implemented.
Observe the safety instructions and application notes specified in the documentation.
2.3Residual hazards
Protection of persons
If the Inverter Drives 8400 are used on a phase earthed mains with a rated mains voltage ≥ 400 V,
protection against accidental contact is not ensured without implementing external measures.
Protective insulation
( 16)
Device protection
The communication module contains electronic components which may be damaged or destroyed
by electrostatic discharge.
Installation
( 21)
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD1712
If the Inverter Drives 8400 are used on a phase earthed mains with a rated mains voltage
≥ 400 V, protection against accidental contact is not ensured without implementing
external measures.
Possible consequences:
Death or severe injury
Protective measures:
If protection against accidental contact is required for the control terminals of the
inverter and the terminals of the plugged-in device modules, ...
• a double isolating distance must be provided.
• the components to be connected must be provided with a second isolating distance.
Note!
The existing protective insulation in the Inverter Drives 8400 is implemented according
to EN 61800-5-1.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD1716
The communication module can be plugged into the MCI slot or unplugged while the inverter is
switched on. When the module is plugged in, it is detected automatically, and a plausibility check
regarding the function and version is carried out.
5.1.1Mounting for 0.25 kW and 0.37 kW standard devices
[5-1]Mounting for 0.25 kW and 0.37 kW standard devices
Mounting steps
1. Pry the cover out of the MCI slot using a screwdriver and remove it (1, 2).
2. Loosen the securing screw for the communication module on the standard device (3).
3. Insert the communication module into the MCI slot of the standard device (4).
4. Fasten the securing screw (5).
E84YCPM002D
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD1722
Documentation for the standard device, control system, plant/machine
Observe the notes and wiring instructions given in the documentation.
5.2.1Network topology
The following examples show two simple RS485 networks.
Every segment of the network must be terminated at both ends. The bus terminators of the
PROFIBUS are marked with a "Z" in the below examples.
In the case of an RS485 network of only one segment, the PROFIBUS master (M) with the integrated
bus terminator starts the segment while the bus terminating resistor in the connector of the last
PROFIBUS station (S) must be activated.
M
Z
Z
SSS
[5-4]RS485 network with one segment
An RS485 network consisting of several segments contains repeaters (R) for coupling the segments.
The repeaters are provided with integrated bus terminating resistors.
1
E94YCPM012a
M
Z
Z
Z
SSS
Z
R
SS
Z
R
Z
123
E94YCPM012b
[5-5]RS485 network with a repeater
25
If no repeater is to be used at the end of the segment, the bus terminating resistor must be activated
in the connector of the last device. The bus termination is supplied by the station itself.
Stop!
The bus terminator must always be supplied. Otherwise, the bus can get unstable.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Repeaters do not have a station address. When calculating the maximum number of
stations, they reduce the number of stations by 1 on each side of the segment.
Repeaters can be used to build up line and tree topologies. The maximum total bus system
expansion depends on ...
• the baud rate used;
• the number of repeaters used.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD1726
The length of the bus cable depends on the baud rate and cable type used. The data in the following
table applies to PROFIBUS cables of "FC-Standard Cable" cable type .
Baud rateLength
9.6 ... 93.75 kbps1200 m
187.5 kbps1000 m
500 kbps400 m
1500 kbps200 m
3000 ... 12000 kbps100 m
Note!
The baud rate depending of the data volume, cycle time and number of stations should
only be selected as high as required for the application.
Tip!
We recommend taking the use of optical fibres into consideration for high baud rates.
Advantages of optical fibres:
• External electromagnetic interferences have no effect on the transmission path.
• Bus lengths of several kilometres are also possible with higher baud rates.
• The bus length is ...
• independent of the baud rate;
• dependent on the optical fibre used.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD1728
During commissioning, plant-specific data such as motor parameters, operating parameters,
responses, and parameters for fieldbus communication are defined for the inverter. Lenze devices
use codes for this purpose.
The codes of the inverter and for communication are saved to the memory module in a non-volatile
data set.
In addition, there are codes for diagnosing and monitoring the stations.
Parameter reference
6.1Before initial switch-on
( 95)
Stop!
Before switching on the inverter for the first time, check ...
• the entire wiring for completeness, short circuit and earth fault.
• whether the bus system is terminated by means of a bus terminating resistor at the
first and last physical bus station.
Activating the bus terminating resistor
( 27)
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD1730
The controller (master) must be configured before communication with the communication
module is possible.
Configuration for the controller (master) and the DP-V0 parameter data channel
For configuring the PROFIBUS you must read the device description file of the communication
module into the master.
The device description file for the E84AYCPM communication module (PROFIBUS) can be found in
the Download area at:
www.Lenze.com
The following language variants of the device description file can be used:
• LENZ0A89.GSD (source file, English)
• LENZ0A89.GSG (German)
• LENZ0A89.GSE (English)
Defining the user data length
The user data length is defined during the initialisation phase of the master.
The Inverter Drives 8400 support the configuration of a maximum of 16 process data words (max.
32 bytes). The optional activation of the cyclic parameter data channel additionally occupies 4
process data word (8 bytes).
The user data lengths for process input data and process output data are the same.
Description of the device data base file
Selection textParameter data
with consistency
DRIVECOM-PAR
(cons) + PCD (nW
cons)
PCD (nW cons)-n words-n words
PCD (nW)--4 words4 words
n = 1 ... 16 process data words
Yesn words-4 + n words
with consistencywithout consistency
Process dataAssigned
IO memory
31
Example of selecting the device data base file
DRIVECOM-PAR (cons) + PCD (8W cons)
• "Drivecom-PAR (cons)" = DP-V0 parameter data channel (4 words)
• "PCD (8W cons)" = 8 process data words
Tip!
A detailed description of consistency is given in the chapter "Consistent parameter data
( 80).
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Via Tool Calling Interfaces (TCI) you can connect to a TCI-capable integrated development
environment and parameterise and diagnose your field devices without having to exit the
integrated development environment.
You cannot set the TCI communication path directly in the »Engineer«. The selection is carried out
by the »STEP7« Siemens software.
The TCI function requires a PN/DP-CPU. Information on the Siemens PLC types that are equipped
with the TCI function is provided via the Siemens Support at:
http://support.automation.siemens.com
How to configure TCI communication:
1. Allocate names for the individual axes in the »Engineer« project.
In our case, "9400" was allocated for 9400 HighLine, and "8400" for 8400 StateLine:
35
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
• create the Lenze PROFIBUS stations with the corresponding station addresses and
•create a PROFIBUS network.
Here a Servo Drive 9400 (address 3) and an Inverter Drive 8400 (address 4) are operated on
the PROFIBUS.
• The names of the PROFIBUS slaves in the »HW Konfig« must be identical to those of the
corresponding Lenze axes in the »Engineer« (here "9400" and "8400").
• The selection of the process data configuration has no impact on TCI communication.
3. Establish an Ethernet connection to the PROFIBUS CPU.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD1736
8. Select the Ethernet connection which you are using to go online with »STEP7« (the same
Ethernet connection that has been configured in the »HW Konfig«).
In our case this is the Ethernet(1) connection:
9. Confirm the selection with OK.
The connection has been accepted.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD1738
14. Start the transfer of the TCI communication parameters in the »HW Konfig« using the right
mouse button and the menu command Start Device Tool L-force Engineer.
15. If the »Engineer« has already been started with the applicable project, the following
message will appear:
• The message says that the »Engineer« project is not set to a TCI communication path and
provides information about whether this action is to be executed now.
• If you confirm the message with Yes, the applicable TCI communication parameter
settings of the »STEP7« project are transferred to the »Engineer«.
41
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
If the »Engineer« has not already been started, it is started automatically now and you have
to open the applicable project.
If the project selected has not been set to a TCI communication path yet, this can now be
executed by clicking Yes:
16. The transfer of the TCI communication parameters is documented in the »Engineer«
message window.
Here the communication settings have been carried out successfully. The individual
PROFIBUS addresses in the respective codes have been adapted to the »STEP7« project.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD1742
The PROFIBUS master and inverter communicate through the exchange of data telegrams via
PROFIBUS. The user data area of the data telegram contains parameter data or process data. In the
inverter, different communication channels are assigned to the parameter data and process data.
Communication channels
The process data channel serves to transfer process data.
• The process data serve to control the inverter.
• The controller (master) can directly access the process data. In the PLC, for instance, the data are
directly saved to the I/O area.
• Process data are not saved in the inverter.
• Process data are transferred cyclically between the controller and the inverters (permanent
exchange of current input / output data).
• Process data are, for instance, setpoints, actual values, control words and status words.
• The Inverter Drives 8400 can exchange a maximum of 16 process data word (16 bits/word) per
direction.
Note!
Observe the direction of the information flow!
• Process input data (Rx data):
• Process data from the inverter (slave) to the master
• Process output data (Tx data):
• Process data from the master to the inverter (slave)
The parameter data channel serves to transfer parameter data.
• The parameter data channel provides access to all Lenze codes.
• In general, the parameter data transfer is not time-critical.
• Parameter data are, for instance, operating parameters, diagnostic information, and motor
data.
• Parameter changes must be saved by means of code C00002 of the Inverter Drive 8400.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD1744
4. Via the button, you can assign signals to the process data words in the Assignment Signal --> Function Block dialog box.
Select the signals and then confirm the selection with OK.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD1748
Page 49
8Process data transfer
8.3Free configuration of the port interconnection of process data objects (PDO)
If the port blocks "LP_MciIn" and "LP_MciOut" are activated (see step 1), they are displayed
in the »FB Editor«. Here you can also assign signals to the process data words.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD1750
The E84AYCPM communication module supports the cyclic and acyclic transmission of parameter
data:
• Cyclic DP-V0 parameter data are based on the DRIVECOM profile.
If the DP-V0 parameter data channel is active, it additionally occupies 4 words of the input data
and the output data.
• Acyclic DP-V1 parameter data are based on the PROFIdrive profile.
9.1Addressing of the parameter data
The parameter data are addressed via codes which can be found in this documentation and in the
corresponding documentation of your inverter.
Parameter reference
Addressing of Lenze parameters
In the case of the DP-V0 parameter data channel, the parameters of a device are not addressed
directly via Lenze code numbers, but via indices (bytes 3 + 4) and subindices (byte 2).
The conversion is made via an offset (24575 / 0x5FFF):
•PROFIBUS-DP index
•PROFIBUS-DP index
Example of C00105 (quick stop deceleration time):
•PROFIBUS-DP index
•PROFIBUS-DP index
The parameter values are entered into the user data (bytes 5 to 8) of the telegram.
( 95)
= 24575 - Lenze code number
dec
= 0x5FFF - Lenze code number
hex
= 24575 - 105 = 24470
dec
= 0x5FFF - 0x69 = 0x5F96
hex
hex
51
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Request and response control for the parameter data channel
[9-1]Method of counting for bits 0 ... 7
Bit 0 ... 2: Request
Read/write request from the master to the inverter
000 No request
001 Read request
Reading parameter data from the inverter
010 Write request (write data to the inverter)
Writing parameter data to the inverter
100 Data transfer abort by the master
Data transfer abort by the master
Index
Low byte
76543210
( 55)
Data 4 /
Error 4
( 54)
( 54)
Data 3 /
Error 3
Data 2 /
Error 2
Data 1 /
Error 1
Bit 3
Reserved
Bit 4/5: Data length
Data length ≤ 4 bytes in the telegram bytes 5 ... 8 (data 1 ... 4 / error 1 ... 4)
00 1 byte
01 2 bytes
10 3 bytes
11 4 bytes
Bit 6: Handshake
Indicates a new request.
• The state of this (toggle) bit is changed by the master for every new request.
• The inverter copies the bit into its response telegram.
Bit 7: Status
Status information from the inverter to the master when sending the request confirmation.
This status bit informs the master whether the request has been carried out without errors.
0 Request completed without errors.
1 Request not completed because of an error.
• The set status bit indicates that the telegram is an "error telegram". The data of bytes 5 ... 8 (data/
error) must be interpreted as an error message.
Error codes
( 58)
53
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
1. Define the user data area of the inverter, i.e. define the location of the DP user data in the
controller (observe manufacturer-specific information).
2. Enter the address of the required parameter in the "Index" and "Subindex" fields (DP output
data).
3. Request in the service byte = read request.
The handshake bit in the service byte must be changed (DP output data).
4. Check whether the handshake bit in the service byte is the same for the DP input data and the
DP output data.
• If the handshake bit is the same, the response has been received.
• It is useful to implement a time monitoring tool.
5. Check whether the status bit in the service byte is set:
• Status bit is not
( 57)
.
• Status bit is set: The read request has not
contains the Error codes
set: The "Data/Error" field contains the required Parameter value (data)
been executed correctly. The "Data/Error" field
( 58).
9.2.2.2Writing parameter data to the inverter
General procedure:
1. Define the user data area of the inverter, i.e. define the location of the DP user data in the
controller (observe manufacturer-specific information).
2. Enter the address of the required parameter in the "Index" and "Subindex" fields (DP output
data).
3. Enter the parameter value in the "Data/Error" field.
4. Request in the service byte = write request.
The handshake bit in the service byte must be changed (DP output data).
5. Check whether the handshake bit in the service byte is the same for the DP input data and the
DP output data.
• If the handshake bit is the same, the response has been received.
• It is useful to implement a time monitoring tool.
6. Check whether the status bit in the service byte is set:
• Status bit is not
• Status bit is set: The write request has not
contains the Error codes
set: The write request has been executed correctly.
( 58).
been executed correctly. The "Data/Error" field
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD1754
Data communication with PROFIBUS-DP-V0 is characterised by cyclic diagnostics and cyclic process
data and parameter data transfer.
An optional service expansion is the acyclic parameter data transfer of PROFIBUS-DP-V1. This
service does not impair the functionality of the standard services under PROFIBUS-DP-V0.
PROFIBUS-DP-V0 and PROFIBUS-DP-V1 can be operated simultaneously in the same network. This
enables the step-by-step expansion or retrofitting of a system.
The services of PROFIBUS-DP-V1 can be used by the class 1 master (PLC) and the class 2 master
(diagnostics master, etc.).
The integration of the acyclic service into the fixed bus cycle depends on the corresponding
configuration of the class 1 master:
• With configuration, a time slot is reserved.
• Without configuration the acyclic service is appended when a class 2 master acyclically accesses
a DP-V1 slave.
Features
• Parameter number and subindex addresses with a width of 16 bits each.
• Several parameter requests can be combined to one request (multi-parameter request).
• There is always only one parameter request in process (no pipelining).
• A parameter request/response must fit into a data block (max. 240 bytes). Requests/responses
cannot be split into several data blocks.
• No spontaneous messages are transferred.
• There are only acyclic parameter requests.
• Profile-specific parameters can be read independently of the slave state.
61
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
• When a read request is processed, no parameter value is written to the slave.
• In the case of a multi-parameter read request, the parameter attribute, index, and
subindex are repeated with the number "n" of the requested parameters.
• A read request must not exceed the maximum data length of 240 bytes.
Request header
Byte 1Byte 2Byte 3Byte 4
Request referenceRequest identificationAxisNumber of indices
FieldData typeValues
Request referenceU8This value is specified by the master
Request identificationU80x01: Request parameters for reading
AxisU80x00 or 0x01
Number of indicesU80x"n" (n = number of parameters requested)
Parameter attribute
FieldData typeValues
AttributeU80x10: Value
Number of subindicesU80x00
Index and subindex
FieldData typeValues
IndexU160x0001 ... 0xFFFF (1 ... 65535)
SubindexU160x0001 ... 0xFFFF (1 ... 65535)
Byte 5Byte 6
AttributeNumber of subindices
(For array elements: Enter the number of array elements
required.)
Byte 7Byte 8Byte 9Byte 10
IndexSubindex
High byteLow byteHigh byteLow byte
65
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
In the PROFIBUS communication system, data are permanently exchanged between the control
system (CPU + PROFIBUS master) and the inverter via the plugged-on slave interface module. Both
the PROFIBUS master and the CPU (central processing unit) of the control system access a joint
memory: the dual port memory (DPM).
The DPM permits a data exchange in both directions (write/read):
Central processing unit
(CPU)
It could happen that a slower PROFIBUS master writing would be overtaken by a faster CPU reading
within a cycle time without any further data organisation.
In order to avoid such an impermissible state, the parameter data to be transmitted must be marked
as "consistent".
Data communication with consistent data
With consistency, either "reading" or "writing" is possible when the master and the CPU
simultaneously access the memory:
• The PROFIBUS master transfers data only as a complete data set.
• The CPU can only access completely updated data sets.
• The PROFIBUS master cannot read or write data as long as the CPU accesses consistent data.
The result becomes clear from the example below:
CPU wants to read!Master wants to write simultaneously!
Central processing unit
(CPU)
Dual port memory
(DPM)
Dual port memory
(DPM)
PROFIBUS master
PROFIBUS master
1. As the master can only write if the CPU does not read, the master waits until the data are read
completely by the CPU.
2. The master only writes a complete data set into DPM.
Configuring consistent data
Note!
Consistency is achieved by an appropriate PROFIBUS master configuration.
For this purpose, refer to the documentation for your configuring software.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD1780
Page 81
10Monitoring
10.1Permanent interruption of PROFIBUS communication
10.1Permanent interruption of PROFIBUS communication
If PROFIBUS communication is interrupted permanently, e.g. by cable breakage or failure of the
PROFIBUS master, no process data are transmitted to the slave being in the "Data Exchange" state.
After the watchdog monitoring time determined by the master has expired, the response
parameterised in C13880/1
The process data are treated according to the setting in C13885
can be used or can be set to zero.)
Preconditions for a inverter (slave) response
is executed in the inverter (slave).
. (The data sent last by the master
• A monitoring time of 1 ... 65534 ms for the "Data_Exchange" status (C13881
A value of "65535 ms" (Lenze setting) deactivates the monitoring.
• A response for the slave is set in C13880/1
• The slave is in the "Data_Exchange" state.
• The watchdog monitoring time is configured correctly in the master.
If one of these preconditions is not met, the response to the absence of cyclic process data telegrams
from the master is not executed.
Settings and displays in the »Engineer«
(Lenze setting "No response").
( 83)
) is set.
81
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 82
10Monitoring
10.2Short-time interruption of PROFIBUS communication
10.2Short-time interruption of PROFIBUS communication
POWER ON
Set_Slave_Add
Slave_Diag
Chk_Cfg, not o.k.
Set_Prm, not o.k.
[10-1] DP states (Decentralized Peripherals) for short-time interruption of communication
The master detects the communication fault and, only after a few microseconds, transfers the slave
to the "WAIT_PRM" status of the DP state machine (see fig. [10-1]
Only after the state chain of the DP state machine ending in the "Data_Exchange" state
(DATA_EXCH) has been passed through, the watchdog monitoring time calculated for the slave (in
milliseconds) continues to run.
WAIT_PRM
WAIT_CFG
Chk_Cfg, o.k.
DATA_EXCH
Slave_Diag
Get_Cfg
Slave_Diag
Set_Prm
Get_Cfg
).
Note!
The watchdog monitoring time does not continue running if the slave does not reach the
"Data_Exchange" state due to repeated communication errors (e.g. caused by loose
contact).
2133PFB006
Additional monitoring for the data exchange
For this reason an additional monitoring function for the data exchange is available with C13881
which is activated when "Data_Exchange" is exited and the parameterised time (0 ... 65535 ms) has
expired. The active monitoring triggers the response parameterised in C13880/1
.
Note!
Observe the following condition for the time setting:
Monitoring time for the data exchange (C13881
PROFIBUS (C13882/1
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD1782
On the Monitoring tab of the »Engineer«, you can set or display the following parameters:
ParameterDescription
Reaction on communication
fault
(C13880/1
Clear process data
(C13885
Monitoring time: Data
exchange
(C13881
Monitoring time: Watchdog
(C13882/1
Set ext. diagnostic bit upon
(C13886
)
)
)
)
)
The response set here takes place if the PROFIBUS station ...
• does not receive a message from the master within the watchdog
monitoring time (displayed in C13882/1) if there is an active connection;
• recognises that it is not in the "Data_Exchange" status anymore.
Please see also the information on .
Selection of the process data which the inverter will process in the event of
a PROFIBUS failure in order to maintain internal communication.
The process data sent last by the master can be used or the process data can
be set to zero.
After the monitoring time set here has elapsed, the response set in takes
place for the data exchange.
• The value "65535" deactivates the monitoring function.
• The monitoring time set here must be smaller than the watchdog
monitoring time .
• A change in monitoring is effective immediately.
Permanent interruption of PROFIBUS communication
Display of the watchdog monitoring time determined by the PROFIBUS
master
• Monitoring starts with the receipt of the first telegram.
• When a value of "0" is displayed, the monitoring function is deactivated.
• A change in the watchdog monitoring time in the master is immediately
effective.
Permanent interruption of PROFIBUS communication
Bit-coded selection of the error responses in the standard device causing the
external diagnostic bit ("diag bit") to be set (see PROFIBUS specification; bit 3
of byte 1 of the DP diagnostic messages).
• The diagnostic bit is sent to the PROFIBUS master where it is evaluated
separately.
• The diagnostic bit is always set when a system error occurs.
• The Lenze setting "0" means that the diagnostic bit is not set for the
following error responses.
• An advanced diagnostic message is always sent.
( 81)
( 81)
83
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
For diagnosing faults of the PROFIBUS module, the LEDs on the front panel are provided.
Furthermore you can query the current bus status via code C13861
11.1LED status displays
.
Note!
During normal operation, the LED BS ( 86) blinks and the LED MS ( 86) is lit
permanently.
The following status displays are distinguished:
• Module status displays
• Fieldbus status displays
( 85)
( 86)
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD1784
The LEDs MS, ME and DE indicate the module status.
MS
ME
DE
E84YCPM006
[11-1] LED status displays MS, ME, and DE
LEDColourStateDescription
MSGreenOn
The communication module is supplied with voltage and has
established a connection to the standard device.
Blinking
200 ms
200 ms
The communication module is supplied with voltage, but has not yet
established a connection to the standard device. (Standard device is
switched off, initialising or not present.)
MERedOn
An error concerning the communication module has occurred.
DERedOn
The communication module is not accepted by the standard device or
the standard device is not active. (See notes in the documentation for
the standard device.)
85
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Errors in the inverter and its plugged-in modules are transmitted to the PROFIBUS master in the
form of advanced diagnostic messages.
Structure of the diagnostic message
ByteDescription
1 Bit 0: Station does not exist (set by the master).
Bit 1: Slave is not ready for data exchange.
Bit 2: Configuration data do not correspond.
Bit 3: Slave has extended diagnostic data.
Bit 4: Requested function is not supported by the slave.
Bit 5: Slave response is invalid (set by the master)
Bit 6: Incorrect parameter setting
Bit 7: Slave has been parameterised by another master (set by the master).
2 Bit 0: Slave must be parameterised again.
Bit 1: Static diagnostics
Bit 2: Permanently set to "1".
Bit 3: Watchdog active
Bit 4: Freeze command received.
Bit 5: Sync command received.
Bit 6: Reserved
Bit 7: Slave is deactivated (set by the master).
3 Bit 7: Diagnostics overflow - amount of diagnostic information present in the slave is too large to fit
into one telegram.
4 Bits 0 ... 7: Master address after parameterisation ("0xFF" without parameterisation)
5 Bits 0 ... 7: ID number (high byte)
6 Bits 0 ... 7: ID number (low byte)
7Header
• The header contains the block length of the advanced diagnostics including the header byte.
• In this case, the value of the entry is "0x0A" (bytes 7 ... 16 = 10 bytes).
8 Status_Type
The value of this entry is fixed. For the following bit assignment it is "0x81":
• Bit 7 = 1: "status"
• Bit 0 = 1: "status message"
• Value of all other bits = 0
9Slot_Number
The value of the slot number is "0x00".
10 Specifier
• An indicated error is entered in the specifier with the identification "0x1" (status coming).
• An eliminated error is entered in the specifier with the identification "0x02" (status going).
• If no errors are indicated, the entry in the specifier has the value "0x00" (no further
differentiation).
11 Reserved
12
13 ... 16 Error code of the Inverter Drive 8400
•Code C00165 can be used to read out the contents of the fault memory.
• Detailed information regarding the error codes of the Inverter Drive 8400 can be found in the
documentation of the inverter.
89
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
This chapter supplements the error list contained in the software manual and in the »Engineer«
online help for Inverter Drives 8400 by the error messages of the communication module.
Software manual/online help for Inverter Drives 8400
Here you can find general information on diagnostics & fault analysis and on error
messages.
12.1Short overview of the PROFIBUS error messages
The following table lists all PROFIBUS error messages in numerical order of the error number.
Furthermore the preset error response and – if available – the parameters for setting the error
response are specified.
Tip!
When you click the cross-reference in the first column, you will see a detailed description
(causes and remedies) of this error message.
Error numberError textError typeAdjustable
hexdec
0x01bc3100 44412544Connection to 8400 standard device lostError-
0x01bc5531
0x01bc5532
0x01bc5533
0x01bc6010
0x01bc6011
0x01bc6100
0x01bc6101
0x01bc6110
0x01bc641f
0x01bc6420
0x01bc8130
0x01bc8131 44433073Profibus: Data_Exchange state exitedNo responseC13880/1
0x01bc8132 44433074Profibus Watchdog: DP-V1 MSC2 monitoring time
(subject area
no.)
44421809Memory: No accessError-
44421810Memory: Read errorError-
44421811Memory: Write errorError-
44424592Restart after watchdog resetError-
44424593Internal errorError-
44424832Internal errorError-
44424833Internal errorError-
44424848Internal errorError-
44425631Invalid parameter setError-
44425632Error: Lenze settings loadedError-
44433072Profibus watchdog: Monitoring time elapsedNo responseC13880/1
dec
(error no.)
exceeded
No responseC13880/2
in
91
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
This chapter lists all PROFIBUS error messages in the numerical order of the error numbers. Possible
causes and remedies as well as responses to the error messages are described in detail.
Connection to 8400 standard device lost [0x01bc3100]
Response (Lenze setting printed in bold)Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
CauseRemedy
• Network cable (plug) is defective.
• Network cable is not connected to the PROFIBUS
terminal X201.
• Voltage supply is interrupted.
Memory: No access [0x01bc5531]
Check cables and terminals.
Connect network cable to the PROFIBUS terminal X201.
Response (Lenze setting printed in bold)Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
CauseRemedy
Access to memory was not possible.Repeat the download of the application
Memory: Read error [0x01bc5532]
Response (Lenze setting printed in bold)Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
CauseRemedy
Parameter could not be read.Repeat the download of the application
Memory: Write error [0x01bc5533]
Response (Lenze setting printed in bold)Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
CauseRemedy
Parameter could not be written.Repeat the download of the application
(including module)
(including module)
(including module)
Restart after watchdog reset [0x01bc6010]
Response (Lenze setting printed in bold)Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
CauseRemedy
Module defective.If this occurs repeatedly, contact the Lenze service.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD1792
This chapter supplements the parameter list and the table of attributes contained in the software
manual and in the »Engineer« online help for Inverter Drives 8400 by the parameters of the
E84AYCPM communication module (PROFIBUS).
Software manual/»Engineer« online help for Inverter Drives 8400
Here you can find general information on parameters.
13.1Parameters of the communication module
This chapter lists the parameters of the E84AYCPM communication module (PROFIBUS) in
numerically ascending order.
C13850
C13851
Parameter | Name:
C13850 | All words to master
Display of the process data words transferred from the communication module to the PROFIBUS master.
In subcodes 1 ... 16, all process data words to the master are displayed. Only the process data words configured are
valid.
Display area (min. value | unit | max. value)
065535
SubcodesInfo
C13850/1
...
C13850/16
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13851 | All words from master
Display of the process data words transferred from the PROFIBUS master to the communication module.
In subcodes 1 ... 16, all process data words to the master are displayed. Only the process data words configured are
valid.
Display area (min. value | unit | max. value)
065535
SubcodesInfo
C13851/1
...
C13851/16
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Data type: UNSIGNED_16
Index: 10725
Data type: UNSIGNED_16
Index: 10724
= 29E5
d
= 29E4
d
h
h
95
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Display of process data words 1 ... 16 which are transferred from the communication module to the standard device.
In subcodes 1 ... 16, all process data words from the communication module are displayed.
Display area (min. value | unit | max. value)
065535
SubcodesInfo
C13852/1
...
C13852/16
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13853 | All words from standard device
Data type: UNSIGNED_16
Index: 10722
= 29E2
d
Display of process data words 1 ... 16 which are transferred from the standard device to the communication module.
In subcodes 1 ... 16, all process data words from the standard device are displayed.
Display area (min. value | unit | max. value)
065535
SubcodesInfo
C13853/1
...
C13853/16
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
h
h
C13860
Parameter | Name:
C13860 | Settings
Data type: UNSIGNED_8
Index: 10715
Display of the current configuration data.
Display area (min. value | unit | max. value)
0255
SubcodesInfo
C13860/1Reserved
C13860/2Number of process data words (1 ... 16 words)
C13860/3DRIVECOM parameter data channel
• 0: Not active
•1: Active
C13860/4Reserved
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
= 29DB
d
h
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD1796
Monitoring response to a communication fault on the PROFIBUS
A change in the monitoring response is effective immediately.
Permanent interruption of PROFIBUS communication
( 81)
Selection list
0 No response
1 Error
3 Quick stop by trouble
4 Warning locked
6 Information
SubcodesLenze settingInfo
C13880/10: No responseThe response set here for the "Watchdog/Data
Exchange" monitoring function is executed if the bus
station ...
• does not receive a message from the master within
the watchdog monitoring time (displayed in C13882/
1) if there is an active connection.
• detects that it is no longer in the "Data_Exchange"
status. Please see also the notes given under C13881
.
C13880/20: No responseThe response set here for the "DPV1 MSAC2" monitoring
is executed if the bus station does not receive any "DPV1
MSAC2" message from the master within the monitoring
time (displayed in C13882/2
if there is an active
connection) and the MSAC2 connection is stopped by the
slave.
Note: We recommend only setting "information" as
response so that no drive-relevant response is executed.
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
C13881
Parameter | Name:
C13881 | Monitoring time: Data exchange
Data type: UNSIGNED_16
Index: 10694
If the "Data Exchange" state is exited, the response parameterised under C13880/1 is carried out when the
monitoring time for data exchange set here has expired.
• A value of "65535" in this code deactivates the monitoring function.
• A change in monitoring is effective immediately.
• The value set here for the monitoring time must be smaller than the watchdog monitoring time (C13882/1
Permanent interruption of PROFIBUS communication
( 81)
Setting range (min. value | unit | max. value)Lenze setting
0ms65535 65535 ms
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
= 29C6
d
h
).
99
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Display of the watchdog monitoring time determined by the PROFIBUS master
• A change in the watchdog monitoring time is immediately effective.
• Monitoring starts with the receipt of the first telegram.
• When a value of "0" is displayed, the monitoring function is deactivated.
Permanent interruption of PROFIBUS communication
( 81)
Display area (min. value | unit | max. value)
0ms4294967295
SubcodesInfo
C13882/1Watchdog monitoring time
C13882/2DP-V1 MSC2
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13885 | Clear process data
Data type: UNSIGNED_8
Index: 10690
= 29C2
d
Selection of the process data which the inverter will process in the event of a PROFIBUS failure in order to maintain
internal communication.
Selection list (Lenze setting printed in bold)
0 Use of most recent master PDOs
1 PDOs are set to the value '0'
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
h
h
Parameter | Name:
C13886 | Set ext. diagnostic bit by
Data type: BITFIELD_8
Index: 10689
= 29C1
d
Bit-coded selection of the error responses in the standard device causing the external diagnostic bit ("diag bit") to
be set (see PROFIBUS specification; bit 3 of byte 1 of the DP diagnostic messages).
• The diagnostic bit is sent to the PROFIBUS master where it is evaluated separately.
• The diagnostic bit is always set when a system error occurs.
• The Lenze setting "0" means that the diagnostic bit is not set for the following error responses.
• An advanced diagnostic message is always sent.
Value is bit-coded:
Bit 0 Error
Bit 1 Trouble
Bit 2 Quick stop by trouble
Bit 3 Warning locked
Bit 4 Warning
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
h
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17100
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.