Lenze E84AYCPM User Manual

Page 1
Accessories
PROFIBUS®
Inverter Drives 8400
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
E84AYCPM
Ä.K6~ä
13422193
L
Page 2

Contents

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
1 About this documentation _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 5
1.1 Document history _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 7
1.2 Conventions used _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 8
1.3 Terminology used _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 9
1.4 Notes used _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 10
2Safety instructions _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 11
2.1 General safety and application instructions _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 11
2.2 Device- and application-specific safety instructions _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 12
2.3 Residual hazards _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 12
3 Product description _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 13
3.1 Application as directed _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 13
3.2 Identification _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 13
3.3 Features _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 14
3.4 Terminals and interfaces _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 14
4 Technical data _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 15
4.1 General data and operating conditions _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 15
4.2 Protective insulation _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 16
4.3 Protocol data _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 19
4.4 Communication time _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 19
4.5 Dimensions _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 20
5Installation _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 21
5.1 Mechanical installation _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 22
5.1.1 Mounting for 0.25 kW and 0.37 kW standard devices _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 22
5.1.2 Mounting for standard devices of 0.55 kW and more _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 23
5.1.3 Replacing the communication module _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 24
5.2 Electrical installation _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 25
5.2.1 Network topology _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 25
5.3 Activating the bus terminating resistor _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 27
5.3.1 Bus cable specification _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 28
5.3.2 PROFIBUS connection _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 29
6 Commissioning _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 30
6.1 Before initial switch-on _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 30
6.2 Configuration of the controller (master) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 31
6.3 Setting the station address _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 32
6.4 Initial switch-on _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 34
6.5 Going online with »Engineer« via TCI _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 35
7 Data transfer _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 44
8 Process data transfer _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 45
8.1 Access to process data / PDO mapping _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 45
8.2 Preconfigured port interconnection of the process data objects (PDO) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 46
8.3 Free configuration of the port interconnection of process data objects (PDO) _ _ _ _ _ _ _ _ _ _ _ _ 47
2 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 3
Contents
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9 Parameter data transfer _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 51
9.1 Addressing of the parameter data _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 51
9.2 DRIVECOM parameter data channel (DP-V0) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 52
9.2.1 Telegram structure (overview) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 52
9.2.2 Byte 1: Service _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 53
9.2.2.1 Reading parameter data from the inverter _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 54
9.2.2.2 Writing parameter data to the inverter _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 54
9.2.2.3 Abort of data transfer by the inverter _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 55
9.2.2.4 Data transfer abort by the master _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 55
9.2.3 Byte 2: Subindex _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 56
9.2.4 Bytes 3 + 4: Index _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 56
9.2.5 Bytes 5 ... 8: Parameter value / error information _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 57
9.2.6 Error codes _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 58
9.2.7 Telegram examples _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 59
9.2.7.1 Read request: Querying the heatsink temperature _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 59
9.2.7.2 Write request: Setting the deceleration time for quick stop (QSP) _ _ _ _ _ _ _ 60
9.3 PROFIdrive parameter data channel (DP-V1) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 61
9.3.1 Connection establishment between master and slave _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 62
9.3.2 Acyclic data transfer _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 63
9.3.3 Telegram structure _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 64
9.3.3.1 Reading parameter data from the inverter _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 65
9.3.3.2 Response to a correctly executed read request _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 66
9.3.3.3 Response to a read error _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 68
9.3.3.4 Writing parameter data to the inverter _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 70
9.3.3.5 Response to a correctly executed write request _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 72
9.3.3.6 Response to a write error _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 73
9.3.4 Error codes _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 74
9.3.5 Telegram examples _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 76
9.3.5.1 Read request: Querying the heatsink temperature _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 76
9.3.5.2 Write request: Setting the deceleration time for quick stop (QSP) _ _ _ _ _ _ _ 78
9.4 Consistent parameter data _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 80
10 Monitoring _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 81
10.1 Permanent interruption of PROFIBUS communication _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 81
10.2 Short-time interruption of PROFIBUS communication _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 82
10.3 Settings and displays in the »Engineer« _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 83
11 Diagnostics _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 84
11.1 LED status displays _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 84
11.1.1 Module status displays _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 85
11.1.2 Fieldbus status displays _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 86
11.2 Diagnosing with the »Engineer« _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 87
11.3 Advanced diagnostic message _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 89
12 Error messages _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 91
12.1 Short overview of the PROFIBUS error messages _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 91
12.2 Possible causes and remedies _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 92
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 3
Page 4
Contents
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
13 Parameter reference _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 95
13.1 Parameters of the communication module _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 95
13.2 Table of attributes _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 103
13.3 Implemented PROFIdrive objects (DP-V1) _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 105
14 DIP switch positions for setting the station address _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 107
Your opinion is important to us _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 114
4 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 5

1 About this documentation

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
1 About this documentation
This documentation exclusively describes the E84AYCPM communication module (PROFIBUS).
Note!
This documentation supplements the mounting instructions supplied with the communication module and the "Inverter Drives 8400" hardware manual.
The hardware manual contains safety instructions which must be observed!
The features and functions of the communication module are described in detail.
Typical applications are explained with the help of examples.
The theoretical connections are only explained in so far as they are necessary for comprehending the function of the communication module.
This documentation does not describe the software of other manufacturers. No responsibility is taken for corresponding information given in this documentation. Information on how to use the software can be obtained from the documents of the control system (master).
All brand names used in this documentation are trademarks of their respective owners.
Tip!
Detailed information about PROFIBUS can be found on the website of the PROFIBUS & PROFINET user organisation:
www.profibus.com
5 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 6
1 About this documentation
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Target group
This documentation is intended for all persons who plan, install, commission and maintain the networking and remote servicing of a machine.
Tip!
Current documentation and software updates with regard to Lenze products can be found in the download area at:
www.Lenze.com
Validity information
The information given in this documentation is valid for the following devices:
Extension module Type designation From hardware
version
PROFIBUS communication module E84AYCPM VA 01.00
Screenshots/application examples
All screenshots in this documentation are application examples. Depending on the firmware version of the communication module and the software version of the Engineering tools installed (»Engineer«, »STEP7«), the screenshots in this documentation may differ from the actual screen display.
From software
version
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 6
Page 7
1 About this documentation

1.1 Document history

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
1.1 Document history
Version Description
1.0 11/2007 TD17 First edition
2.0 11/2008 TD17 General revision
3.0 02/2010 TD17 • Update of chapter structure
• General revision
4.0 11/2010 TD17 General revision
5.0 11/2011 TD17 • New layout
•New: Going online with »Engineer« via TCI
• General corrections
(35)
7
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 8
1 About this documentation

1.2 Conventions used

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
1.2 Conventions used
This manual uses the following conventions to distinguish between different types of information:
Type of information Writing Examples/notes
Numbers
Decimal separator Point The decimal point is always used.
Example: 1234.56
Hexadecimal 0x[0 ... 9, A ... F] Example: 0x60F4
Binary
• Nibble
Text
Version information Text colour blue All pieces of information that only apply to or from a specific
Program name » « The Lenze PC software »Engineer«...
Window italics The message window... / The Options dialog box ...
Variable name Setting bEnable to TRUE...
Control element Bold The OK button ... / The Copy command ... / The Properties tab
Sequence of menu commands
Hyperlink underlined
Symbols Page reference (6) Optically highlighted reference to another page. Can be
Step-by-step instructions
In inverted commas
Point
Example: ’100’ Example: ’0110.0100’
software version of the inverter are highlighted accordingly in this documentation. Example: This function extension is available from software
version V3.0!
... / The Name input field ...
If several successive commands are required for executing a function, the individual commands are separated from each other by an arrow: Select the command File
Optically highlighted reference to another topic. Can be activated with a mouse-click in this online documentation.
activated with a mouse-click in this online documentation.
Step-by-step instructions are indicated by a pictograph.
Open to...
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 8
Page 9
1 About this documentation

1.3 Terminology used

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
1.3 Terminology used
Term Meaning
Inverter Lenze inverter of the "Inverter Drives 8400" product series
Standard device
Code Parameters which serve to parameterise or monitor the inverter. This term is
Subcode If a code contains several parameters, these are stored in subcodes.
GSD / GSE Device data base file (device description for PROFIBUS stations)
HW Hardware
Lenze setting Settings with which the device is preconfigured ex works.
Basic setting
PDO Process data object
PLC Programmable Logic Controller
»STEP7« Siemens software for programming and configuring PROFIBUS Siemens control
SW Software
TCI Tool Calling Interface
usually called "index".
This manual uses a slash "/" as a separator between code and subcode (e.g. "C118/3").
This term is usually called "subindex".
PROFIBUS® (Process Field Bus) is a widely-used fieldbus system for the automation of machines and production plants.
PROFIBUS® is a registered trademark and patented technology licensed by the PROFIBUS & PROFINET International (PI) user organisation.
(German designation: SPS - Speicherprogrammierbare Steuerung)
systems
9
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 10
1 About this documentation

1.4 Notes used

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
1.4 Notes used
The following signal words and symbols are used in this documentation to indicate dangers and important information:
Safety instructions
Structure of the safety instructions:
Danger!
(characterises the type and severity of danger)
Note
(describes the danger and informs how to prevent dangerous situations)
Pictograph Signal word Meaning
Danger! Danger of personal injury through dangerous electrical voltage
Danger! Danger of personal injury through a general source of danger
Stop! Danger of property damage
Application notes
Reference to an imminent danger that may result in death or serious personal injury if the corresponding measures are not taken.
Reference to an imminent danger that may result in death or serious personal injury if the corresponding measures are not taken.
Reference to a possible danger that may result in property damage if the corresponding measures are not taken.
Pictograph Signal word Meaning
Note! Important note to ensure trouble-free operation
Tip! Useful tip for easy handling
Reference to other documents
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 10
Page 11

2 Safety instructions

2.1 General safety and application instructions

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
2 Safety instructions
Note!
Always observe the specified safety measures to avoid severe injury to persons and damage to property!
Always keep this documentation to hand in the vicinity of the product during operation.
2.1 General safety and application instructions
Danger!
If you disregard the following basic safety measures, this can cause severe injury to persons and damage to material assets.
Lenze drive and automation components ...
• must only be used as directed.
Application as directed
• must never be commissioned in the event of visible damage.
• must never be technically modified.
• must never be commissioned before they have been completely mounted.
• must never be operated without the covers required.
• can - depending on their degree of protection - have live, moving or rotating parts during and after operation. Surfaces can be hot.
For Lenze drive components ...
• use only the accessories approved.
• use only original spare parts from the manufacturer.
Observe all specifications given in the attached and associated documentation.
• This is the precondition for safe and trouble-free operation and for obtaining the product features specified.
Features
• The procedural notes and circuit details described in this document are only proposals. It is up to the user to check whether they can be adapted to the particular applications. Lenze does not take any responsibility for the suitability of the procedures and circuit proposals described.
(14)
(13)
11
Only qualified personnel may work with and on Lenze drive and automation components. According to IEC 60364 and CENELEC HD 384, these are persons ...
• who are familiar with the installation, assembly, commissioning and operation of the product.
• who have the corresponding qualifications for their work.
• who know all regulations for the prevention of accidents, directives and laws applicable on site and are able to apply them.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 12
2 Safety instructions

2.2 Device- and application-specific safety instructions

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
2.2 Device- and application-specific safety instructions
• During operation, the communication module must be firmly connected to the standard device.
• Only use cables corresponding to the given specifications.
Bus cable specification
(28)
Documentation for the standard device, control system, plant/machine
All other measures prescribed in this documentation must also be implemented. Observe the safety instructions and application notes specified in the documentation.

2.3 Residual hazards

Protection of persons
If the Inverter Drives 8400 are used on a phase earthed mains with a rated mains voltage ≥ 400 V, protection against accidental contact is not ensured without implementing external measures.
Protective insulation
(16)
Device protection
The communication module contains electronic components which may be damaged or destroyed by electrostatic discharge.
Installation
(21)
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 12
Page 13

3 Product description

3.1 Application as directed

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
3 Product description
3.1 Application as directed
The communication module ...
• is an accessory module for use in conjunction with the following Lenze standard devices:
Product series Type designation From software version
Inverter Drives 8400 StateLine E84AVSCxxxxx 01.00
Inverter Drives 8400 HighLine E84AVHCxxxxx 01.00
Inverter Drives 8400 TopLine E84AVTCxxxxx 01.00
• is a device intended for use in industrial power systems.
• is only to be operated under the operating conditions specified in this documentation.
• may only be used in PROFIBUS networks.
Any other use shall be deemed inappropriate!

3.2 Identification

The type designation as well as the hardware and software version of the communication module are indicated on the nameplate:
[3-1] Identification data
8400
Type:
HW:
Ser.No.:
HW:
SW:
SW:
1 Type designation (type)
E84 Product series
AVersion
Y Module identification: extension module
C Module type: communication module
PM PROFIBUS
V/S V: coated version
S: standard version
2 Hardware version (HW)
3 Software version (SW)
E84YCPM001E
13
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 14
3 Product description

3.3 Features

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
3.3 Features
• Interface module for the PROFIBUS communication system for connection to the expansion slots of the Inverter Drives 8400
• Support of parameter data channels DRIVECOM (DP-V0) and PROFIDrive (DP-V1)
• A maximum of 16 process data words per direction can be exchanged.
• The communication module is supplied with voltage via the standard device.
• Bus coupling via remote bus according to the RS485 standard
• Automatic detection of the baud rate (9.6 kbps to 12 Mbps)
• Setting of the station address is possible via DIP switch or code.
• Access to all Lenze parameters

3.4 Terminals and interfaces

[3-2] E84AYCPM communication module (PROFIBUS)
E84YCPM001C
S200 DIP switches for setting the station address
Setting the station address
X201 PROFIBUS connection
• 9-pin Sub-D socket
Network topologyPROFIBUS connection
5 LED status displays for diagnostics
MS
Module status displays
ME
BS
Fieldbus status displays
BE DE
(25)
(32)
(29)
(85)
(86)
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 14
Page 15
4Technical data

4.1 General data and operating conditions

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4 Technical data

"Inverter Drives 8400" hardware manual
Here you can find the ambient conditions and information on the electromagnetic compatibility (EMC) which also apply to the communication module.
4.1 General data and operating conditions
Area Values
Order designation • E84AYCPMV (coated version)
• E84AYCPMS (standard version)
Communication profile • PROFIBUS DP-V0 (DRIVECOM)
• PROFIBUS DP-V1 (PROFIdrive)
Communication medium RS485
Interface 9-pin Sub-D socket
Network topology • Line (without repeater)
• Tree/line (with repeater)
Bus device type PROFIBUS slave
Number of slaves • Max. 31 (without repeater)
• Max. 125 (with repeater)
Max. cable length 1200 m (depending on the selected baud rate and the cable type used)
PNO identification number 0x0A89
Baud rate for cable type A (EN 50170) 9.6 kbps ... 12 Mbps (automatic detection)
Conformities, approvals • CE
•UL
15
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 16
4Technical data

4.2 Protective insulation

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.2 Protective insulation
Danger!
Dangerous voltage
If the Inverter Drives 8400 are used on a phase earthed mains with a rated mains voltage 400 V, protection against accidental contact is not ensured without implementing external measures.
Possible consequences:
Death or severe injury
Protective measures:
If protection against accidental contact is required for the control terminals of the inverter and the terminals of the plugged-in device modules, ...
• a double isolating distance must be provided.
• the components to be connected must be provided with a second isolating distance.
Note!
The existing protective insulation in the Inverter Drives 8400 is implemented according to EN 61800-5-1.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 16
Page 17
4Technical data
4.2 Protective insulation
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
The following illustration ...
• shows the arrangement of the terminal strips and the separate potential areas of the Inverter Drives 8400.
• serves to determine the decisive protective insulation between two terminals located in differently insulated separate potential areas.
Bus
X106X106X106X101
Ext. DC
Reinforced insulation
Basic insulation
X100X100
Functional insulation
MCI
X6
X6
X3
X3
X4
X4
X5
X5
MMI
X105X105
[4-1] Protective insulation in accordance with EN61800-5-1
X106X106X106X106
X1X1
E84YCXX007
Terminal strip Connection
X100 Mains / DC bus connection
X101 Relay contact
X105 Motor/brake resistor
X106 Motor PTC
X1 System bus (CANopen)
X3 Analog inputs/outputs
X4 Digital outputs
X5 Digital inputs
X6 Diagnostics
MCI Slot for communication module
MMI Slot for memory module
17
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 18
4Technical data
4.2 Protective insulation
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Example
Which type of protective insulation is used between the bus terminal of the device module in the MCI slot and the mains terminal X100?
The separate potential area with the better protective insulation is decisive.
• The separate potential area of the device module's bus terminal is "functionally insulated".
• The separate potential area of the mains terminal has a "reinforced insulation".
Result: The insulation between the mains terminal X100 and the bus terminal is of the "reinforced insulation" type.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 18
Page 19
4Technical data

4.3 Protocol data

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.3 Protocol data
Area Values
Process data words (PCD) 1 ... 16 words (16 bits/word)
Cyclic parameter data channel (DP­V0)
Acyclic parameter data channel (DP­V1)
PROFIBUS user data length 1 ... 16 words process data channel + 4 words parameter data channel

4.4 Communication time

The communication time is the time between the start of a request and the arrival of the corresponding response.
The communication times in a PROFIBUS network depend on ...
• the processing time in the inverter;
4 words
Max. 240 bytes
• the transmission delay time (baud rate / telegram length);
• the nesting depth of the network.
Processing time in the inverter
Data Processing time
Process data Approx. 2 ms
+ 0 ... 1 ms + 1 ... x ms
Parameter data Approx. 30 ms + 20 ms tolerance (typical)
For some codes, the processing time may be longer (see software manual// »Engineer« online help for Inverter Drives 8400).
update cycle processing time in the module application task runtime of the technology application used
(tolerance)
There are no interdependencies between parameter data and process data.
19
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 20
4Technical data

4.5 Dimensions

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.5 Dimensions
[4-2] Dimensions
Dimensions in mm
E84YCPM001B
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 20
Page 21

5 Installation

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5 Installation
Stop!
Electrostatic discharge
Electronic components within the communication module can be damaged or destroyed by electrostatic discharge.
Possible consequences:
• The communication module is defective.
• Communication via the fieldbus is not possible or faulty.
Protective measures
Discharge electrostatic charges before touching the module.
21 Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 22
5 Installation

5.1 Mechanical installation

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.1 Mechanical installation
The communication module can be plugged into the MCI slot or unplugged while the inverter is switched on. When the module is plugged in, it is detected automatically, and a plausibility check regarding the function and version is carried out.
5.1.1 Mounting for 0.25 kW and 0.37 kW standard devices
[5-1] Mounting for 0.25 kW and 0.37 kW standard devices
Mounting steps
1. Pry the cover out of the MCI slot using a screwdriver and remove it (1, 2).
2. Loosen the securing screw for the communication module on the standard device (3).
3. Insert the communication module into the MCI slot of the standard device (4).
4. Fasten the securing screw (5).
E84YCPM002D
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 22
Page 23
5 Installation
5.1 Mechanical installation
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.1.2 Mounting for standard devices of 0.55 kW and more
E84YCPM002A
[5-2] Mounting for standard devices of 0.55 kW and more
Mounting steps
1. Slightly press on the area indicated in the illustration at the top of the cover for the standard device's MCI slot (1).
2. Tilt the cover forward and remove it from the standard device (2).
3. Loosen the securing screw for the communication module on the standard device (3).
4. Insert the communication module into the MCI slot of the standard device (4).
5. Fasten the securing screw (5).
23
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 24
5 Installation
5.1 Mechanical installation
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.1.3 Replacing the communication module
E84YCPM002B
[5-3] Replacing the communication module
Mounting steps
1. Loosen the securing screw for the communication module on the standard device (1).
2. Remove the communication module from the MCI slot of the standard device (2).
3. Insert the new communication module into the MCI slot of the standard device (3).
4. Fasten the securing screw (4).
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 24
Page 25
5 Installation

5.2 Electrical installation

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.2 Electrical installation
Documentation for the standard device, control system, plant/machine
Observe the notes and wiring instructions given in the documentation.
5.2.1 Network topology
The following examples show two simple RS485 networks.
Every segment of the network must be terminated at both ends. The bus terminators of the PROFIBUS are marked with a "Z" in the below examples.
In the case of an RS485 network of only one segment, the PROFIBUS master (M) with the integrated bus terminator starts the segment while the bus terminating resistor in the connector of the last PROFIBUS station (S) must be activated.
M
Z
Z
S SS
[5-4] RS485 network with one segment
An RS485 network consisting of several segments contains repeaters (R) for coupling the segments. The repeaters are provided with integrated bus terminating resistors.
1
E94YCPM012a
M
Z
Z
Z
S SS
Z
R
S S
Z
R
Z
1 23
E94YCPM012b
[5-5] RS485 network with a repeater
25
If no repeater is to be used at the end of the segment, the bus terminating resistor must be activated in the connector of the last device. The bus termination is supplied by the station itself.
Stop!
The bus terminator must always be supplied. Otherwise, the bus can get unstable.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 26
5 Installation
5.2 Electrical installation
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Activating the bus terminating resistor
Number of stations
M
SS S S S
[5-6] Number of stations
Segment Master (M) Slave (S) Repeater (R)
1131-
2-301
3-301
(27)
RR
123
2133PFB004
230-
Tip!
Repeaters do not have a station address. When calculating the maximum number of stations, they reduce the number of stations by 1 on each side of the segment.
Repeaters can be used to build up line and tree topologies. The maximum total bus system expansion depends on ...
• the baud rate used;
• the number of repeaters used.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 26
Page 27
5 Installation

5.3 Activating the bus terminating resistor

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.3 Activating the bus terminating resistor
The PROFIBUS must be terminated by a bus terminating resistor at the first and last physical bus station.
The bus terminating resistor in the bus connector of the bus cable is activated by means of a switch.
PROFIBUS cables with integrated bus terminating resistor are offered by several cable manufacturers.
Note!
If you want to disconnect individual bus stations, ensure that the bus terminators at the cable ends remain active.
Please observe that the bus termination is not active any longer if ...
• the bus connector has been disconnected;
• the voltage supply of the Inverter Drive 8400 has been switched off.
27
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 28
5 Installation
5.3 Activating the bus terminating resistor
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.3.1 Bus cable specification
Note!
Only use cables which meet the listed specifications of the PROFIBUS user organisation.
Area Values
Cable resistance 135 ... 165 Ω/km, (f = 3 ... 20 MHz)
Capacitance per unit length 30 nF/km
Loop resistance < 110 Ω/km
Core diameter > 0.64 mm
Core cross-section > 0.34 mm
Cores Twisted in pairs, insulated and shielded
2
Bus cable length
The length of the bus cable depends on the baud rate and cable type used. The data in the following table applies to PROFIBUS cables of "FC-Standard Cable" cable type .
Baud rate Length
9.6 ... 93.75 kbps 1200 m
187.5 kbps 1000 m
500 kbps 400 m
1500 kbps 200 m
3000 ... 12000 kbps 100 m
Note!
The baud rate depending of the data volume, cycle time and number of stations should only be selected as high as required for the application.
Tip!
We recommend taking the use of optical fibres into consideration for high baud rates.
Advantages of optical fibres:
• External electromagnetic interferences have no effect on the transmission path.
• Bus lengths of several kilometres are also possible with higher baud rates.
• The bus length is ...
• independent of the baud rate;
• dependent on the optical fibre used.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 28
Page 29
5 Installation
5.3 Activating the bus terminating resistor
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.3.2 PROFIBUS connection
The 9-pole Sub-D socket X201 serves to connect the communication module to the bus system.
Assignment of the 9-pin Sub-D socket X201
View Pin Assignment Description
1
5
6
9
1Not assigned-
2Not assigned-
3 RxD/TxD-P Data line B (received data/transmitted data, plus)
4 RTS Request To Send (received data/transmitted data, no
differential signal)
5 M5V2 Data ground (ground to 5 V)
6 P5V2 5 V DC / 30 mA (bus termination)
7Not assigned-
8 RxD/TxD-N Data line A (received data/transmitted data, minus)
9Not assigned-
29
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 30

6 Commissioning

6.1 Before initial switch-on

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6 Commissioning
During commissioning, plant-specific data such as motor parameters, operating parameters, responses, and parameters for fieldbus communication are defined for the inverter. Lenze devices use codes for this purpose.
The codes of the inverter and for communication are saved to the memory module in a non-volatile data set.
In addition, there are codes for diagnosing and monitoring the stations.
Parameter reference
6.1 Before initial switch-on
( 95)
Stop!
Before switching on the inverter for the first time, check ...
• the entire wiring for completeness, short circuit and earth fault.
• whether the bus system is terminated by means of a bus terminating resistor at the first and last physical bus station.
Activating the bus terminating resistor
(27)
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 30
Page 31
6 Commissioning

6.2 Configuration of the controller (master)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.2 Configuration of the controller (master)
The controller (master) must be configured before communication with the communication module is possible.
Configuration for the controller (master) and the DP-V0 parameter data channel
For configuring the PROFIBUS you must read the device description file of the communication module into the master.
The device description file for the E84AYCPM communication module (PROFIBUS) can be found in the Download area at:
www.Lenze.com
The following language variants of the device description file can be used:
• LENZ0A89.GSD (source file, English)
• LENZ0A89.GSG (German)
• LENZ0A89.GSE (English)
Defining the user data length
The user data length is defined during the initialisation phase of the master.
The Inverter Drives 8400 support the configuration of a maximum of 16 process data words (max. 32 bytes). The optional activation of the cyclic parameter data channel additionally occupies 4 process data word (8 bytes).
The user data lengths for process input data and process output data are the same.
Description of the device data base file
Selection text Parameter data
with consistency
DRIVECOM-PAR (cons) + PCD (nW cons)
PCD (nW cons) - n words -n words
PCD (nW) - -4 words 4 words
n = 1 ... 16 process data words
Yes n words -4 + n words
with consistency without consistency
Process data Assigned
IO memory
31
Example of selecting the device data base file
DRIVECOM-PAR (cons) + PCD (8W cons)
• "Drivecom-PAR (cons)" = DP-V0 parameter data channel (4 words)
• "PCD (8W cons)" = 8 process data words
Tip!
A detailed description of consistency is given in the chapter "Consistent parameter data
(80).
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
"
Page 32
6 Commissioning

6.3 Setting the station address

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.3 Setting the station address
The station address can be set via DIP switches 1 ... 64 or via the »Engineer« (code C13899
The unlabelled DIP switch (topmost position) does not have any function.
Lenze setting: all switches in OFF position
E84YCPM001G
[6-1] DIP switch
).
The station addresses must differ from each other if several networked PROFIBUS stations are used.
The station address can be set via DIP switches 1 ... 64 or via the »Engineer« (code C13899
Setting the station address via ...
DIP switch C13899
Condition At least one switch 1…64=ON •Switches 1...64=OFF
• All switches 1...64=ON
(invalid value "127")
The housing labelling indicates the valencies of the individual DIP switches for setting the station address.
DIP switch 64 32 16 8 4 2 1
Switch position OFF OFF ON OFF ON ON ON
Value 00
Station address = sum of the valencies = 16 + 4 + 2 + 1 = 23
16 0 4 2 1
).
DIP switch positions for setting the station address (107)
• Valid address range: 1 … 126 (max. 126 slave stations)
C13920
C13864
: Display of the current address setting of the switches
: Display of the station address active on the PROFIBUS
Note!
Switch off the voltage supply of the communication module and then on again in order to activate changed settings.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 32
Page 33
6 Commissioning
6.3 Setting the station address
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Setting the station address via the »Engineer«
In the »Engineer«, the station address can be set via the Settings tab.
Impermissible addresses are displayed in red in the Station address (code C13899
Save the changed settings with device command C00002/11 (save all parameter sets).
).
33
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 34
6 Commissioning

6.4 Initial switch-on

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.4 Initial switch-on
Documentation for the standard device
Observe the safety instructions and residual hazards stated.
Note!
Establishing communication
In order to establish communication via an externally supplied communication module, the standard device must be switched on as well.
After communication has been established, the externally supplied module operates independently of the power on/off state of the standard device.
Protection against uncontrolled restart
After a fault (e.g. short-time mains failure), the restart of a drive is not always wanted and - in some cases - even not allowed.
In the Lenze setting of the Inverter Drives 8400, the restart protection is activated.
The restart behaviour of the inverter can be set via C00142 ("Autostart Option"):
C00142 = 9 (Lenze setting)
• The inverter remains inhibited (even if the fault is no longer active).
• Bit 0 (inhibited at power-on) and bit 3 (inhibited at undervoltage) are set.
• The drive starts in a controlled mode by explicitly enabling the inverter: LOW-HIGH edge at digital input X4/RFR.
C00142 = 8 (enabled)
• To enable the device directly at power-on, bit 0 must be set to zero (FALSE).
• An uncontrolled restart of the drive is possible.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 34
Page 35
6 Commissioning

6.5 Going online with »Engineer« via TCI

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.5 Going online with »Engineer« via TCI
Via Tool Calling Interfaces (TCI) you can connect to a TCI-capable integrated development environment and parameterise and diagnose your field devices without having to exit the integrated development environment.
You cannot set the TCI communication path directly in the »Engineer«. The selection is carried out by the »STEP7« Siemens software.
The TCI function requires a PN/DP-CPU. Information on the Siemens PLC types that are equipped with the TCI function is provided via the Siemens Support at:
http://support.automation.siemens.com
How to configure TCI communication:
1. Allocate names for the individual axes in the »Engineer« project.
In our case, "9400" was allocated for 9400 HighLine, and "8400" for 8400 StateLine:
35
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 36
6 Commissioning
6.5 Going online with »Engineer« via TCI
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
2. In »STEP7« in the »HW Konfig« ...
• create the Lenze PROFIBUS stations with the corresponding station addresses and
•create a PROFIBUS network.
Here a Servo Drive 9400 (address 3) and an Inverter Drive 8400 (address 4) are operated on the PROFIBUS.
• The names of the PROFIBUS slaves in the »HW Konfig« must be identical to those of the corresponding Lenze axes in the »Engineer« (here "9400" and "8400").
• The selection of the process data configuration has no impact on TCI communication.
3. Establish an Ethernet connection to the PROFIBUS CPU.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 36
Page 37
6 Commissioning
6.5 Going online with »Engineer« via TCI
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4. Load the »STEP7« project to the CPU.
5. Use the menu command Insert Station 7PG/PC to integrate a PG/PC station into the
»STEP7« project.
6. By double-clicking the PG/PC station inserted, open its "Properties" dialog.
7. Under the Interfaces tab, select a new Ethernet interface and confirm the selection with OK.
37
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 38
6 Commissioning
6.5 Going online with »Engineer« via TCI
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8. Select the Ethernet connection which you are using to go online with »STEP7« (the same Ethernet connection that has been configured in the »HW Konfig«).
In our case this is the Ethernet(1) connection:
9. Confirm the selection with OK.
The connection has been accepted.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 38
Page 39
6 Commissioning
6.5 Going online with »Engineer« via TCI
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
10. Select the actual PG/PC connection under the Assignment tab.
The connection highlighted is assigned by means of the Assign button.
11. Confirm the following message with OK.
39
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 40
6 Commissioning
6.5 Going online with »Engineer« via TCI
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12. After the assignment, the connection appears in the "Assigned" display area. Close the
dialog with OK.
13. In the »STEP7« project, the PG/PC station is marked with a yellow arrow. (The connection selected is active.)
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 40
Page 41
6 Commissioning
6.5 Going online with »Engineer« via TCI
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
14. Start the transfer of the TCI communication parameters in the »HW Konfig« using the right mouse button and the menu command Start Device Tool L-force Engineer.
15. If the »Engineer« has already been started with the applicable project, the following message will appear:
• The message says that the »Engineer« project is not set to a TCI communication path and provides information about whether this action is to be executed now.
• If you confirm the message with Yes, the applicable TCI communication parameter settings of the »STEP7« project are transferred to the »Engineer«.
41
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 42
6 Commissioning
6.5 Going online with »Engineer« via TCI
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
If the »Engineer« has not already been started, it is started automatically now and you have to open the applicable project.
If the project selected has not been set to a TCI communication path yet, this can now be executed by clicking Yes:
16. The transfer of the TCI communication parameters is documented in the »Engineer« message window.
Here the communication settings have been carried out successfully. The individual PROFIBUS addresses in the respective codes have been adapted to the »STEP7« project.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 42
Page 43
6 Commissioning
6.5 Going online with »Engineer« via TCI
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
17. If you now call the "Go online" function of the »Engineer«, the TCI communication settings are displayed as follows:
• "STEP7 Communication Server" appears as bus connection.
• The device access path contains a very long string.
•Use the Connect button to establish an online connection.
•By means of the Search/Enter button, you can update the TCI communication
parameters.
43
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 44

7 Data transfer

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
7 Data transfer
The PROFIBUS master and inverter communicate through the exchange of data telegrams via PROFIBUS. The user data area of the data telegram contains parameter data or process data. In the inverter, different communication channels are assigned to the parameter data and process data.
Communication channels
The process data channel serves to transfer process data.
• The process data serve to control the inverter.
• The controller (master) can directly access the process data. In the PLC, for instance, the data are directly saved to the I/O area.
• Process data are not saved in the inverter.
• Process data are transferred cyclically between the controller and the inverters (permanent exchange of current input / output data).
• Process data are, for instance, setpoints, actual values, control words and status words.
• The Inverter Drives 8400 can exchange a maximum of 16 process data word (16 bits/word) per direction.
Note!
Observe the direction of the information flow!
• Process input data (Rx data):
• Process data from the inverter (slave) to the master
• Process output data (Tx data):
• Process data from the master to the inverter (slave)
The parameter data channel serves to transfer parameter data.
• The parameter data channel provides access to all Lenze codes.
• In general, the parameter data transfer is not time-critical.
• Parameter data are, for instance, operating parameters, diagnostic information, and motor data.
• Parameter changes must be saved by means of code C00002 of the Inverter Drive 8400.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 44
Page 45

8 Process data transfer

/3B0FL,Q
"
/3B0FL2XW
"

8.1 Access to process data / PDO mapping

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8 Process data transfer
8.1 Access to process data / PDO mapping
Note!
PDO mapping and the objects required for this purpose are not supported in the software version 01.00 of the E84AYCPM communication module.
The process data (MCI-PDOs) are transferred via the MCI interface.
• A maximum of 16 words for each direction is exchanged.
• The process data are accessed via the LP_MciIn and LP_MciOut port blocks. These port blocks are also referred to as process data channels.
• The port/function block interconnection of the process data objects (PDO) takes place via the Lenze »Engineer«.
)LHOGEXV
E&WUOB%
E&WUOB%
Z&WUO
E,QB%
E,QB%
Z,Q
&RPPXQLFDWLRQPRGXOH
0&,LQWHUIDFH

$SSOLFDWLRQ
)%LQWHUFRQQHFWLRQ
E6WDWHB%
E6WDWHB%
Z6WDWH
E2XWB%
E2XWB%
Z2XW
Z,Q
GQ,QBS
[8-1] External and internal data transfer between the bus system, inverter, and function block interconnection
45
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Z2XW
GQ2XWBS
Page 46
8 Process data transfer

8.2 Preconfigured port interconnection of the process data objects (PDO)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Software manual/ »Engineer« online help for Inverter Drives 8400
Here you'll find some detailed information about the port/function block interconnection in the »Engineer« and about port blocks.
8.2 Preconfigured port interconnection of the process data objects (PDO)
The preconfigured port interconnection of the process data objects is activated by setting standard device code C00007 = "40: MCI".
It is possible to display the port blocks "LP_MciIn" and "LP_MciOut" as well as the preconfigured interconnections in the »FB Editor« :
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 46
Page 47
8 Process data transfer

8.3 Free configuration of the port interconnection of process data objects (PDO)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8.3 Free configuration of the port interconnection of process data objects (PDO)
How to freely configure the port interconnection in the »Engineer«:
1. Go to the Process data objects tab and click Go to application.
2. Go to the Ports tab and select the port block "MCI_IN" or "MCI_OUT" via mouse-click. Activate it by clicking Activate.
3. Click the Edit port ... button.
47
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 48
8 Process data transfer
8.3 Free configuration of the port interconnection of process data objects (PDO)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4. Via the button, you can assign signals to the process data words in the Assignment Signal --> Function Block dialog box. Select the signals and then confirm the selection with OK.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 48
Page 49
8 Process data transfer
8.3 Free configuration of the port interconnection of process data objects (PDO)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
For the process data words WORD_1 and WORD_2, you can also assign signals to the individual control bits and status bits via the and buttons.
Select the signals and then confirm the selection with OK.
ü
49
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 50
8 Process data transfer
8.3 Free configuration of the port interconnection of process data objects (PDO)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Tip!
If the port blocks "LP_MciIn" and "LP_MciOut" are activated (see step 1), they are displayed in the »FB Editor«. Here you can also assign signals to the process data words.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 50
Page 51

9 Parameter data transfer

9.1 Addressing of the parameter data

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9 Parameter data transfer
The E84AYCPM communication module supports the cyclic and acyclic transmission of parameter data:
• Cyclic DP-V0 parameter data are based on the DRIVECOM profile. If the DP-V0 parameter data channel is active, it additionally occupies 4 words of the input data
and the output data.
• Acyclic DP-V1 parameter data are based on the PROFIdrive profile.
9.1 Addressing of the parameter data
The parameter data are addressed via codes which can be found in this documentation and in the corresponding documentation of your inverter.
Parameter reference
Addressing of Lenze parameters
In the case of the DP-V0 parameter data channel, the parameters of a device are not addressed directly via Lenze code numbers, but via indices (bytes 3 + 4) and subindices (byte 2).
The conversion is made via an offset (24575 / 0x5FFF):
•PROFIBUS-DP index
•PROFIBUS-DP index
Example of C00105 (quick stop deceleration time):
•PROFIBUS-DP index
•PROFIBUS-DP index
The parameter values are entered into the user data (bytes 5 to 8) of the telegram.
(95)
= 24575 - Lenze code number
dec
= 0x5FFF - Lenze code number
hex
= 24575 - 105 = 24470
dec
= 0x5FFF - 0x69 = 0x5F96
hex
hex
51
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 52
9 Parameter data transfer

9.2 DRIVECOM parameter data channel (DP-V0)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.2 DRIVECOM parameter data channel (DP-V0)
The DRIVECOM parameter data channel (DP-V0) ...
• enables parameter setting and diagnosing of the inverter.
• provides access to all Lenze parameters (codes).
• additionally occupies 4 words (16 bits/word) of the input and output data words in the master.
• is identical for both transmission directions.
9.2.1 Telegram structure (overview)
The telegram of the parameter data channel consists of a total of 8 bytes:
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
Service Subindex Index
High byte
Index
Low byte
Data 4 /
Error 4
Data 3 /
Error 3
Data 2 /
Error 2
Data 1 /
Error 1
The individual bytes are described in detail in the following subchapters.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 52
Page 53
9 Parameter data transfer
9.2 DRIVECOM parameter data channel (DP-V0)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.2.2 Byte 1: Service
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
Service Subindex Index
High byte
Request and response control for the parameter data channel
[9-1] Method of counting for bits 0 ... 7
Bit 0 ... 2: Request
Read/write request from the master to the inverter
000 No request
001 Read request
Reading parameter data from the inverter
010 Write request (write data to the inverter)
Writing parameter data to the inverter
100 Data transfer abort by the master
Data transfer abort by the master
Index
Low byte
76543210
(55)
Data 4 /
Error 4
(54)
(54)
Data 3 /
Error 3
Data 2 /
Error 2
Data 1 /
Error 1
Bit 3
Reserved
Bit 4/5: Data length
Data length 4 bytes in the telegram bytes 5 ... 8 (data 1 ... 4 / error 1 ... 4)
00 1 byte
01 2 bytes
10 3 bytes
11 4 bytes
Bit 6: Handshake
Indicates a new request.
• The state of this (toggle) bit is changed by the master for every new request.
• The inverter copies the bit into its response telegram.
Bit 7: Status
Status information from the inverter to the master when sending the request confirmation. This status bit informs the master whether the request has been carried out without errors.
0 Request completed without errors.
1 Request not completed because of an error.
• The set status bit indicates that the telegram is an "error telegram". The data of bytes 5 ... 8 (data/ error) must be interpreted as an error message.
Error codes
(58)
53
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 54
9 Parameter data transfer
9.2 DRIVECOM parameter data channel (DP-V0)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.2.2.1 Reading parameter data from the inverter
General procedure:
1. Define the user data area of the inverter, i.e. define the location of the DP user data in the controller (observe manufacturer-specific information).
2. Enter the address of the required parameter in the "Index" and "Subindex" fields (DP output data).
3. Request in the service byte = read request. The handshake bit in the service byte must be changed (DP output data).
4. Check whether the handshake bit in the service byte is the same for the DP input data and the DP output data.
• If the handshake bit is the same, the response has been received.
• It is useful to implement a time monitoring tool.
5. Check whether the status bit in the service byte is set:
• Status bit is not
(57)
.
• Status bit is set: The read request has not contains the Error codes
set: The "Data/Error" field contains the required Parameter value (data)
been executed correctly. The "Data/Error" field
(58).
9.2.2.2 Writing parameter data to the inverter
General procedure:
1. Define the user data area of the inverter, i.e. define the location of the DP user data in the controller (observe manufacturer-specific information).
2. Enter the address of the required parameter in the "Index" and "Subindex" fields (DP output data).
3. Enter the parameter value in the "Data/Error" field.
4. Request in the service byte = write request. The handshake bit in the service byte must be changed (DP output data).
5. Check whether the handshake bit in the service byte is the same for the DP input data and the DP output data.
• If the handshake bit is the same, the response has been received.
• It is useful to implement a time monitoring tool.
6. Check whether the status bit in the service byte is set:
• Status bit is not
• Status bit is set: The write request has not contains the Error codes
set: The write request has been executed correctly.
(58).
been executed correctly. The "Data/Error" field
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 54
Page 55
9 Parameter data transfer
9.2 DRIVECOM parameter data channel (DP-V0)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.2.2.3 Abort of data transfer by the inverter
The error telegram is used to abort the transfer.
• The error telegram is marked by a set status bit in the service byte.
• The telegram can either be the response to an "Initiate Read/Write Service" or to a "Read/Write Segment Service".
Inverter response in the event of an error:
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
Service Subindex Index
1t110000 SIDX IDXH IDXL Error Class Error code Additional
High byte
9.2.2.4 Data transfer abort by the master
The master can use this error telegram to abort a running segment transmission.
• The error telegram is marked by a set status bit in the service byte.
Index
Low byte
Data 4 /
Error 4
Data 3 /
Error 3
Data 2 /
Error 2
Code High
Data 1 /
Error 1
Additional
Code Low
• The service byte also contains the request code "4" (100
bin
).
• Bit 4 and bit 5 in the service byte (data length) are without meaning.
• Additional information (subindex, index, error information) is not transmitted.
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
Service Reserved Reserved Reserved Reserved Reserved Reserved Reserved
1txx0100 0 0 0 0000
Inverter response in the case of correct execution:
The inverter confirms the error telegram of the master by also sending an error telegram.
• The error telegram is marked by a set status bit in the service byte.
• In the case of correct execution, the telegram contains the error information "0x00000000" in bytes 5 ... 8.
• Additional information (subindex, index) is not transmitted.
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
Service SIDX IDXH IDXL Error Class Error code Additional
1t110000 0 0 0 0000
Code High
Additional
Code Low
55
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 56
9 Parameter data transfer
9.2 DRIVECOM parameter data channel (DP-V0)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.2.3 Byte 2: Subindex
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
Service Subindex Index
High byte
Additional addressing via the subindex is required for those codes of the Inverter Drives 8400 that contain a subcode (see code table).
9.2.4 Bytes 3 + 4: Index
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
Service Subindex Index
High byte
The parameter (Lenze code) is selected via these two bytes according to the formula:
Index
Low byte
Index
Low byte
Data 4 /
Error 4
Data 4 /
Error 4
Data 3 /
Error 3
Data 3 /
Error 3
Data 2 /
Error 2
Data 2 /
Error 2
Data 1 /
Error 1
Data 1 /
Error 1
Index = 24575 - Lenze code number
(Also see "Addressing of Lenze parameters
" (51))
Example:
The parameter C00105 (quick stop (QSP) deceleration time) is to be addressed:
• Index = 24575 - 105 = 24470 = 0x5F96
• The entries in bytes 3 + 4 for this example would be:
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
Service Subindex 0x5F 0x96 Data 4 /
Error 4
Data 3 /
Error 3
Data 2 /
Error 2
Data 1 /
Error 1
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 56
Page 57
9 Parameter data transfer
9.2 DRIVECOM parameter data channel (DP-V0)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.2.5 Bytes 5 ... 8: Parameter value / error information
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
Service Subindex Index
High byte
The state of status bit 7 in the service byte determines the meaning of this data field:
Status bit Meaning of bytes 5 ... 8
0 Bytes 5 ... 8 contain the parameter value (data 1 ... 4 ).
1 Bytes 5 ... 8 contain an error message (error 1 ... 4) due to an invalid access.
Error codes
(58)
Parameter value (data)
Index
Low byte
Data 4 /
Error 4
Data 3 /
Error 3
Data 2 /
Error 2
Data 1 /
Error 1
Note!
Strings or data blocks cannot be transmitted.
Depending on the data format, the length of the parameter value is between 1 and 4 bytes.
Data are saved in the Motorola format, i.e. first the high byte (high word), then the low byte (low word):
Byte 5 Byte 6 Byte 7 Byte 8
High byte Low byte High byte Low byte
High word Low word
Double word
Principle for the assignment of bytes 5 ... 8 with parameter values of different lengths:
Byte 5 Byte 6 Byte 7 Byte 8
Parameter value (length 1) 0x00 0x00 0x00
Parameter value (length 2) 0x00 0x00
Parameter value (length 4)
57
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 58
9 Parameter data transfer
9.2 DRIVECOM parameter data channel (DP-V0)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.2.6 Error codes
The following error messages may appear:
Byte 8 Byte 7 Byte 6 Byte 5 Meaning
Error 1 Error 2 Error 3 Error 4
0x06 0x03 0x00 0x00 No right to access
0x06 0x05 0x11 Invalid subindex
0x06 0x05 0x12 Data length too large
0x06 0x05 0x13 Data length too small
0x06 0x07 0x00 Object does not exist
0x06 0x08 0x00 Data types do not comply with each other
0x08 0x00 0x00 Request cannot be executed
0x08 0x00 0x20 Request cannot be executed at the moment
0x08 0x00 0x22 Request cannot be executed due to the device status / The
0x08 0x00 0x30 Value ranged exited
0x08 0x00 0x31 Parameter value too high
0x08 0x00 0x32 Parameter value too low
0x08 0x00 0x80 Hardware error
parameter can only be changed in the case of a controller inhibit
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 58
Page 59
9 Parameter data transfer
9.2 DRIVECOM parameter data channel (DP-V0)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.2.7 Telegram examples
9.2.7.1 Read request: Querying the heatsink temperature
The heatsink temperature of the inverter is to be read.
• Code to be read: C00061
• Heatsink temperature: 43 °C
Byte 1: Service (request)
Request = 0t110001
• Bit 0 ... 2 = 001
• Bit 3 = 0 (reserved)
• Bit 4/5 = 01
• Bit 6 = handshake bit (t status is changed in the response telegram)
bin
for read request
bin
for 2-byte data length (only relevant for the response telegram)
bin
• Bit 7 = status bit (only relevant for the response telegram)
Byte 2: Subindex
Subindex = 0 because code C00061 does not contain any subindices.
Bytes 3+4: Index
Index = 24575 - code number = 24575 - 61 = 24514 = 0x5FC2
• Byte 3 (high byte) = 0x5F
• Byte 4 (low byte) = 0xC2
Bytes 5 ... 8: Data
The response telegram contains the value of code C00061:
Data 3 + 4 = 43 [°C] x 1 (internal factor) = 43 = 0x002B
Result:
Request telegram from master to drive:
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
Service Subindex Index
High byte
0x01 0x00 0x5F 0xC2 0x00 0x00 0x00 0x00
0t000001
Waiting for change of handshake bit 6 in service byte 1 of the response.
bin
00000000
bin
01011111
bin
Index
Low byte
11000010
Data 4 Data 3 Data 2 Data 1
bin
00000000
bin
00000000
bin
00000000
bin
00000000
bin
59
Response telegram from drive to master (for correct execution):
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
Service Subindex Index
High byte
0x11 0x00 0x5F 0xC2 0x00 0x2B 0x00 0x00
0t010001
bin
00000000
01011111
bin
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
bin
Index
Low byte
11000010
Data 4 Data 3 Data 2 Data 1
bin
00000000
bin
00101011
bin
00000000
bin
00000000
bin
Page 60
9 Parameter data transfer
9.2 DRIVECOM parameter data channel (DP-V0)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.2.7.2 Write request: Setting the deceleration time for quick stop (QSP)
In the inverter, the deceleration time for quick stop (QSP) is to be set to 50 ms.
• Code to be written: C00105
Byte 1: Service (request)
Request = 0t110010
• Bit 0 ... 2 = 010
• Bit 3 = 0 (reserved)
• Bit 4/5 = 11
• Bit 6 = handshake bit (t status is changed in the response telegram)
• Bit 7 = status bit (only relevant for the response telegram)
Byte 2: Subindex
Subindex = 0 because code C00105 does not contain any subindices.
bin
for write request
bin
for 4-byte data length
bin
Bytes 3+4: Index
Index = 24575 - code number = 24575 - 105 = 24470 = 0x5F96
• Byte 3 (high byte) = 0x5F
• Byte 4 (low byte) = 0x96
Bytes 5 ... 8: Data
The parameter value of 0.05 s to be set is multiplied by the code-specific factor of "1000" and entered in the user data:
Data 1 ... 4 = 0.05 [s] x 1000 (internal factor) = 50 = 0x00000032
Result:
Request telegram from master to drive:
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
Service Subindex Index
High byte
0x72 0x00 0x5F 0x96 0x00 0x00 0x00 0x32
0t110010
Waiting for change of handshake bit 6 in service byte 1 of the response
bin
00000000
bin
01011111
bin
Index
Low byte
10010110
Data 4 Data 3 Data 2 Data 1
bin
00000000
bin
00000000
bin
00000000
bin
00110010
bin
Response telegram from drive to master (for correct execution):
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8
Service Subindex Index
High byte
0x40 0x00 0x5F 0x96 0x00 0x00 0x00 0x32
0t000000
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 60
bin
00000000
bin
01011111
bin
Index
Low byte
10010110
Data 4 Data 3 Data 2 Data 1
bin
00000000
bin
00000000
bin
00000000
bin
00110010
bin
Page 61
9 Parameter data transfer

9.3 PROFIdrive parameter data channel (DP-V1)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3 PROFIdrive parameter data channel (DP-V1)
Data communication with PROFIBUS-DP-V0 is characterised by cyclic diagnostics and cyclic process data and parameter data transfer.
An optional service expansion is the acyclic parameter data transfer of PROFIBUS-DP-V1. This service does not impair the functionality of the standard services under PROFIBUS-DP-V0.
PROFIBUS-DP-V0 and PROFIBUS-DP-V1 can be operated simultaneously in the same network. This enables the step-by-step expansion or retrofitting of a system.
The services of PROFIBUS-DP-V1 can be used by the class 1 master (PLC) and the class 2 master (diagnostics master, etc.).
The integration of the acyclic service into the fixed bus cycle depends on the corresponding configuration of the class 1 master:
• With configuration, a time slot is reserved.
• Without configuration the acyclic service is appended when a class 2 master acyclically accesses a DP-V1 slave.
Features
• Parameter number and subindex addresses with a width of 16 bits each.
• Several parameter requests can be combined to one request (multi-parameter request).
• There is always only one parameter request in process (no pipelining).
• A parameter request/response must fit into a data block (max. 240 bytes). Requests/responses cannot be split into several data blocks.
• No spontaneous messages are transferred.
• There are only acyclic parameter requests.
• Profile-specific parameters can be read independently of the slave state.
61
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 62
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.1 Connection establishment between master and slave
A class 1 master can always request parameters from a slave if the slave is in the "Data_Exchange" state.
In addition to the class 1 master, a class 2 master can establish a communication connection to the slave:
DPV1­parameter data channel
Slave
[9-2] Data communication via the DP-V1 parameter data channel
Master class 1
Read
Write
Master class 2
E94YCPM010
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 62
Page 63
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.2 Acyclic data transfer
Note!
A parameter request refers to one or several parameter(s) (multi-parameter request).
Master
Parameter request
DP-V1
Write.req
with data (parameter request)
Write.res
without data
Read.req
without data
Read.res (-)
without data
Read.req
without data
Read.res (+)Parameter response
with data (parameter response)
[9-3] Transmission directions
Slave
Parameter request
Parameter response
Parameter processing
E94YCPM011
Explanation
• A "Write.req" is used to pass the data set (DB47) to the slave in the form of a parameter request.
• With "Write.res" the master receives the confirmation for the receipt of the message.
63
• The master requests the response of the slave with "Read.req".
• The slave responds with "Read.res (-)" if processing has not yet been completed.
• After parameter processing, the parameter request is completed by transmitting the parameter response to the master with "Read.res (+)".
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 64
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.3 Telegram structure
SD LE LEr SD DA SA FCS EDFC DSAP SSAP
[9-4] PROFIBUS data telegram
The data unit (DU) contains the DP-V1 header and the parameter request or the parameter response.
The following subchapters describe the parameter request and the parameter response in detail.
DU
Note!
The DP-V1 header consists of:
• Function identification
•Slot number
• Data set
• Length of the user data
Please refer to the corresponding PROFIBUS specification for further information on the DP-V1 header.
Assignment of the user data depending on the data type
Depending on the data type used, the user data are assigned as follows:
E82ZAFP015
Data type Length User data assignment
Byte 1 Byte 2 Byte 3 Byte 4 Byte ...
String x bytes
U8 1 byte 0x00
U16 2 bytes
U32 4 bytes High word Low word
High byte Low byte
High byte Low byte High byte Low byte
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 64
Page 65
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.3.1 Reading parameter data from the inverter
Note!
• When a read request is processed, no parameter value is written to the slave.
• In the case of a multi-parameter read request, the parameter attribute, index, and subindex are repeated with the number "n" of the requested parameters.
• A read request must not exceed the maximum data length of 240 bytes.
Request header
Byte 1 Byte 2 Byte 3 Byte 4
Request reference Request identification Axis Number of indices
Field Data type Values
Request reference U8 This value is specified by the master
Request identification U8 0x01: Request parameters for reading
Axis U8 0x00 or 0x01
Number of indices U8 0x"n" (n = number of parameters requested)
Parameter attribute
Field Data type Values
Attribute U8 0x10: Value
Number of subindices U8 0x00
Index and subindex
Field Data type Values
Index U16 0x0001 ... 0xFFFF (1 ... 65535)
Subindex U16 0x0001 ... 0xFFFF (1 ... 65535)
Byte 5 Byte 6
Attribute Number of subindices
(For array elements: Enter the number of array elements required.)
Byte 7 Byte 8 Byte 9 Byte 10
Index Subindex
High byte Low byte High byte Low byte
65
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 66
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.3.2 Response to a correctly executed read request
Note!
Responses to a read request do not contain parameter attributes, indices and subindices.
Response header
Byte 1 Byte 2 Byte 3 Byte 4
Request reference
(mirrored)
Field Data type Values
Request reference U8 Mirrored value of the parameter request
Response identification U8 0x01: Parameter has been read
Axis U8 0x00 or 0x01
Number of indices U8 0x"n" (n = number of parameters requested)
Response identification Axis
(mirrored)
Number of indices
Parameter format
Byte 5 Byte 6
Format Number of values
Field Data type Values
Format U8 0x02: Integer8
0x03: Integer16 0x04: Integer32 0x05: Unsigned8 0x06: Unsigned16 0x07: Unsigned32 0x09: Visible string 0x0A: Octet string 0x40: Zero 0x41: Byte 0x42: Word 0x43: Double word
Number of values U8 0x01 or number of requested subindices/parameters
(with several subindices/parameters only the parameter value is repeated).
In the case of string codes, the number of characters is entered here.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 66
Page 67
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Parameter value
Byte 7 Byte 8 Byte 9 Byte 10
Value
Field Data type Values
Value String Any (length > 4 bytes possible)
U8 0x00 .... 0xFF
U16 0x0000 .... 0xFFFF
U32 0x0000 0000 .... 0xFFFF FFFF
67
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 68
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.3.3 Response to a read error
Note!
In the case of a multi-parameter request, correct and possible faulty messages are summarised in one telegram. They have the following data contents:
Correct message
• Format: data type of the value requested
• Number of values: as described in the chapter "Reading parameter data from the
inverter" (65).
• Parameter value: value requested
Faulty message
• Format: 0x44
• Number of values: 0x01 or 0x02
• Error code without additional information (for number of values = 0x01) or
• Error code with additional information (for number of values = 0x02)
A faulty access to a parameter "n" is indicated at the nth position in the response telegram of a multi-parameter request.
Response header
Byte 1 Byte 2 Byte 3 Byte 4
Request reference
(mirrored)
Field Data type Values
Request reference U8 Mirrored value of the parameter request
Response identification U8 0x81: Parameter has not been read
Axis U8 0x00 or 0x01
Number of indices U8 0x"n" (n = number of parameters requested)
Parameter format
Byte 5 Byte 6
Format Number of values
Field Data type Values
Format U8 0x44: Error
Number of values U8 0x01: Error code without additional information
Response identification Axis
(mirrored)
• The data in the bytes 7 + 8 must be interpreted as an error code.
0x02: Error code with additional information
Number of indices
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 68
Page 69
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Error code
Byte 7 Byte 8 Byte 9 Byte 10
Error code Additional information
(if available)
High byte Low byte High byte Low byte
Field Data type Values
Error code U16 0x0000 .... 0xFFFF
Additional information (if available)
U16
Error codes
(74)
69
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 70
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.3.4 Writing parameter data to the inverter
Note!
When a multi-parameter write request is transferred, the ...
• Parameter attribute
• Index and subindex
and then the ...
• Parameter format
• Parameter value
... are repeated with the number "n" of the parameters addressed.
A write request must not exceed the maximum data length of 240 bytes.
Request header
Byte 1 Byte 2 Byte 3 Byte 4
Request reference Request identification Axis Number of indices
Field Data type Values
Request reference U8 This value is defined by the master.
Request identification U8 0x02: Write parameter
Axis U8 0x00 or 0x01
Number of indices U8 0x"n" (n = number of parameters addressed)
Parameter attribute
Byte 5 Byte 6
Attribute Number of subindices
Field Data type Values
Attribute U8 0x10: Value
Number of subindices U8 0x00
(For array elements: Enter the number of array elements required.)
Index and subindex
Byte 7 Byte 8 Byte 9 Byte 10
Index Subindex
High byte Low byte High byte Low byte
Field Data type Values
Index U16 0x0001 ... 0xFFFF (1 ... 65535)
Subindex U16 0x0001 ... 0xFFFF (1 ... 65535)
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 70
Page 71
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Parameter format
Byte 11 Byte 12
Format Number of values
Field Data type Values
Format U8 0x02: Integer8
0x03: Integer16 0x04: Integer32 0x05: Unsigned8 0x06: Unsigned16 0x07: Unsigned32 0x09: Visible string 0x0A: Octet string 0x40: Zero 0x41: Byte 0x42: Word 0x43: Double word
Number of values U8 0x01 or number of written subindices/parameters (with
several subindices/parameters only the parameter value is repeated). In the case of string codes, the number of characters is entered here.
Parameter value
Byte 13 Byte 14 Byte 15 Byte 16
Field Data type Values
Value String Any (length > 4 bytes possible)
U8 0x00 .... 0xFF
U16 0x0000 .... 0xFFFF
U32 0x0000 0000 .... 0xFFFF FFFF
Value
71
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 72
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.3.5 Response to a correctly executed write request
Note!
In the case of a multi-parameter request, correct and possible faulty messages are summarised in one telegram. They have the following data contents:
Correct message
• Format: 0x40
• Number of values: 0x00
Faulty message
• Format: 0x44
• Number of values: 0x01 or 0x02
• Error code without additional information (for number of values = 0x01) or with additional information (for number of values = 0x02)
A faulty access to a parameter "n" is indicated at the nth position in the response telegram of a multi-parameter request.
Response header
Byte 1 Byte 2 Byte 3 Byte 4
Request reference
(mirrored)
Field Data type Values
Request reference U8 Mirrored value of the parameter request
Response identification U8 0x02: Parameter has been written
Axis U8 0x00 or 0x01
Number of indices U8 0xn (n = number of parameter addressed)
Response identification Axis
(mirrored)
Number of indices
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 72
Page 73
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.3.6 Response to a write error
Response header
Byte 1 Byte 2 Byte 3 Byte 4
Request reference
(mirrored)
Field Data type Values
Request reference U8 Mirrored value of the parameter request
Response identification U8 0x82: Parameter has not been written
Axis U8 0x00 or 0x01
Number of indices U8 0x"n" (n = number of parameters addressed)
Parameter format
Response identification Axis
(mirrored)
• The data in the bytes 7 + 8 must be interpreted as an error code.
Number of indices
Byte 5 Byte 6
Format Number of values
Field Data type Values
Format U8 0x44: Error
Number of values U8 0x01: Error code without additional information
0x02: Error code with additional information
Error code
Byte 7 Byte 8 Byte 9 Byte 10
Error code Additional information
(if available)
High byte Low byte High byte Low byte
Field Data type Values
Error code U16 0x0000 .... 0xFFFF
Additional information (if available)
U16
Error codes
(74)
73
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 74
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.4 Error codes
Error code Description Explanation Additional
0x0000 Impermissible parameter
number
0x0001 Parameter value cannot be
changed
0x0002 Lower or upper value limit
exceeded
0x0003 Faulty subindex Access to unavailable subindex Subindex
0x0004 No array Access with subindex to non-indicated parameter -
0x0005 Wrong data type Change access with value that does not match the
0x0006 No setting permitted (only
resettable)
0x0007 Description element cannot
be changed
0x0008 Reserved (PROFIdrive profile V2: PPO-Write requested in the IR
0x0009 Description data not
available
0x000A Reserved (PROFIdrive profile V2: Wrong access group) -
0x000B No parameter change rights Change access without parameter change rights -
0x000C Reserved (PROFIdrive profile V2: Wrong password) -
0x000D Reserved (PROFIdrive profile V2: Text in the cyclic traffic
0x000E Reserved (PROFIdrive profile V2: Name in the cyclic traffic
0x000F No text array available Access to unavailable text array (parameter value is
0x0010 Reserved (PROFIdrive profile V2: Missing PPO-Write) -
0x0011 Request cannot be executed
due to the operating state
0x0012 Reserved (PROFIdrive profile V2: Other error) -
0x0013 Reserved (PROFIdrive profile V2: date in the cyclic traffic
0x0014 Value impermissible Change access with the value that is inside the value
0x0015 Response too long The length of the current response exceeds the
0x0016 Parameter address
impermissible
0x0017 Format impermissible Write request: Impermissible or non-supported
0x0018 Number of values not
consistent
0x0019 Reserved - -
...
0x0064
Access to unavailable parameter -
Change access to a parameter value that cannot be changed
Change access with value beyond the value limits Subindex
data type of the parameter
Change access with value unequal to 0 where this is not permitted
Change access to a description element that cannot be changed
is not available)
Access to unavailable description (parameter value is available)
cannot be read)
cannot be read)
available)
Access is not possible due to temporary reasons not specified here
cannot be read)
limits but not permissible for other permanent reasons (parameters with defined individual values)
maximum transmittable length
Impermissible or non-supported value for attribute, number of subindices, parameter number, or subindex, or a combination
format of parameter data
Write request: Number of values of the parameter data do not match the number of subindices in the parameter address
information
Subindex
-
Subindex
Subindex
-
-
-
-
-
-
-
Subindex
-
-
-
-
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 74
Page 75
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Error code Description Explanation Additional
0x0065 Manufacturer-specific - -
...
0x00FF
information
75
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 76
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.5 Telegram examples
9.3.5.1 Read request: Querying the heatsink temperature
The heatsink temperature of the inverter is to be read.
• Code to be read: C00061
• Heatsink temperature: 43 °C
Parameter request
Byte 1 Byte 2 Byte 3 Byte 4
Request reference Request identification Axis Number of indices
0xXX 0x01 0x00 0x01
Request parameters for reading
Byte 5 Byte 6
Attribute Number of subindices
0x10 0x00
Value No subindex
Byte 7 Byte 8 Byte 9 Byte 10
Index Subindex
High byte Low byte High byte Low byte
0x5F 0xC2 0x00 0x00
Index = 24575 - code no. = 24575 - 61 = 24514 = 0x5F C2 No subindex
Parameter response to a correctly executed read request
Byte 1 Byte 2 Byte 3 Byte 4
Request reference
(mirrored)
0xXX 0x01 0x00 0x01
Byte 5 Byte 6
Format Number of values
0x03 0x01
Integer16 1 value
Byte 7 Byte 8
High byte Low byte
0x00 0x2B
Value read = 0x 00 2B = 43 x 1 (internal factor) = 43 [°C]
Response identification Axis
(mirrored)
Parameter has been read
Value
Number of indices
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 76
Page 77
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Parameter response to a read error
Byte 1 Byte 2 Byte 3 Byte 4
Request reference
(mirrored)
0xXX 0x81 0x00 0x01
Byte 5 Byte 6
Format Number of values
0x44 0x01
Error Error code without
Byte 7 Byte 8
High byte Low byte
For the meaning, see the "Error codes" (74) chapter
Response identification Axis
Parameter has not been read
additional information
Error code
Number of indices
(mirrored)
77
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 78
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.5.2 Write request: Setting the deceleration time for quick stop (QSP)
In the inverter, the deceleration time for quick stop (QSP) is to be set to 50 ms.
Code to be written: C00105
Parameter request
Byte 1 Byte 2 Byte 3 Byte 4
Request reference Request identification Axis Number of indices
0xXX 0x02 0x00 0x01
Write parameter Axis 0 1 index
Byte 5 Byte 6
Attribute Number of subindices
0x10 0x00
Value No subindex
Byte 7 Byte 8 Byte 9 Byte 10
Index Subindex
High byte Low byte High byte Low byte
0x5F 0x96 0x00 0x00
Index = 24575 - code no. = 24575 - 105 = 24470 = 0x5F 96 No subindex
Byte 11 Byte 12
Format Number of values
0x43 0x01
Double word 1 value
Byte 13 Byte 14 Byte 15 Byte 16
Value
High word: high byte High word: low byte Low- word: high byte Low word: low byte
0x00 0x00 0x00 0x32
Value to be written = 0.05 [s] x 1000 (internal factor) = 50 = 0x00 00 00 32
Parameter response to a correctly executed write request
Byte 1 Byte 2 Byte 3 Byte 4
Request reference
(mirrored)
0xXX 0x02 0x00 0x01
Response identification Axis
(mirrored)
Parameter has been written 1 index
Number of indices
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 78
Page 79
9 Parameter data transfer
9.3 PROFIdrive parameter data channel (DP-V1)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Parameter response to a read error
Byte 1 Byte 2 Byte 3 Byte 4
Request reference
(mirrored)
0xXX 0x82 0x00 0x01
Byte 5 Byte 6
Format Number of values
0x44 0x01
Error Error code without
Byte 7 Byte 8
High byte Low byte
For the meaning, see the Error codes (74)
Response identification Axis
(mirrored)
Parameter has not been written 1 index
additional information
Error code
Number of indices
79
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 80
9 Parameter data transfer

9.4 Consistent parameter data

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.4 Consistent parameter data
In the PROFIBUS communication system, data are permanently exchanged between the control system (CPU + PROFIBUS master) and the inverter via the plugged-on slave interface module. Both the PROFIBUS master and the CPU (central processing unit) of the control system access a joint memory: the dual port memory (DPM).
The DPM permits a data exchange in both directions (write/read):
Central processing unit
(CPU)
It could happen that a slower PROFIBUS master writing would be overtaken by a faster CPU reading within a cycle time without any further data organisation.
In order to avoid such an impermissible state, the parameter data to be transmitted must be marked as "consistent".
Data communication with consistent data
With consistency, either "reading" or "writing" is possible when the master and the CPU simultaneously access the memory:
• The PROFIBUS master transfers data only as a complete data set.
• The CPU can only access completely updated data sets.
• The PROFIBUS master cannot read or write data as long as the CPU accesses consistent data.
The result becomes clear from the example below:
CPU wants to read! Master wants to write simultaneously!
Central processing unit
(CPU)
Dual port memory
(DPM)
Dual port memory
(DPM)
PROFIBUS master
PROFIBUS master
1. As the master can only write if the CPU does not read, the master waits until the data are read completely by the CPU.
2. The master only writes a complete data set into DPM.
Configuring consistent data
Note!
Consistency is achieved by an appropriate PROFIBUS master configuration.
For this purpose, refer to the documentation for your configuring software.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 80
Page 81

10 Monitoring

10.1 Permanent interruption of PROFIBUS communication

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
10 Monitoring
10.1 Permanent interruption of PROFIBUS communication
If PROFIBUS communication is interrupted permanently, e.g. by cable breakage or failure of the PROFIBUS master, no process data are transmitted to the slave being in the "Data Exchange" state.
After the watchdog monitoring time determined by the master has expired, the response parameterised in C13880/1
The process data are treated according to the setting in C13885 can be used or can be set to zero.)
Preconditions for a inverter (slave) response
is executed in the inverter (slave).
. (The data sent last by the master
• A monitoring time of 1 ... 65534 ms for the "Data_Exchange" status (C13881 A value of "65535 ms" (Lenze setting) deactivates the monitoring.
• A response for the slave is set in C13880/1
• The slave is in the "Data_Exchange" state.
• The watchdog monitoring time is configured correctly in the master.
If one of these preconditions is not met, the response to the absence of cyclic process data telegrams from the master is not executed.
Settings and displays in the »Engineer«
(Lenze setting "No response").
(83)
) is set.
81
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 82
10 Monitoring

10.2 Short-time interruption of PROFIBUS communication

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
10.2 Short-time interruption of PROFIBUS communication
POWER ON
Set_Slave_Add
Slave_Diag
Chk_Cfg, not o.k. Set_Prm, not o.k.
[10-1] DP states (Decentralized Peripherals) for short-time interruption of communication
The master detects the communication fault and, only after a few microseconds, transfers the slave to the "WAIT_PRM" status of the DP state machine (see fig. [10-1]
Only after the state chain of the DP state machine ending in the "Data_Exchange" state (DATA_EXCH) has been passed through, the watchdog monitoring time calculated for the slave (in milliseconds) continues to run.
WAIT_PRM
WAIT_CFG
Chk_Cfg, o.k.
DATA_EXCH
Slave_Diag Get_Cfg
Slave_Diag Set_Prm Get_Cfg
).
Note!
The watchdog monitoring time does not continue running if the slave does not reach the "Data_Exchange" state due to repeated communication errors (e.g. caused by loose contact).
2133PFB006
Additional monitoring for the data exchange
For this reason an additional monitoring function for the data exchange is available with C13881 which is activated when "Data_Exchange" is exited and the parameterised time (0 ... 65535 ms) has expired. The active monitoring triggers the response parameterised in C13880/1
.
Note!
Observe the following condition for the time setting:
Monitoring time for the data exchange (C13881 PROFIBUS (C13882/1
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 82
).
) watchdog monitoring time of the
,
Page 83
10 Monitoring

10.3 Settings and displays in the »Engineer«

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
10.3 Settings and displays in the »Engineer«
On the Monitoring tab of the »Engineer«, you can set or display the following parameters:
Parameter Description
Reaction on communication fault
(C13880/1
Clear process data
(C13885
Monitoring time: Data exchange
(C13881
Monitoring time: Watchdog
(C13882/1
Set ext. diagnostic bit upon
(C13886
)
)
)
)
)
The response set here takes place if the PROFIBUS station ...
• does not receive a message from the master within the watchdog monitoring time (displayed in C13882/1) if there is an active connection;
• recognises that it is not in the "Data_Exchange" status anymore.
Please see also the information on .
Selection of the process data which the inverter will process in the event of a PROFIBUS failure in order to maintain internal communication.
The process data sent last by the master can be used or the process data can be set to zero.
After the monitoring time set here has elapsed, the response set in takes place for the data exchange.
• The value "65535" deactivates the monitoring function.
• The monitoring time set here must be smaller than the watchdog monitoring time .
• A change in monitoring is effective immediately.
Permanent interruption of PROFIBUS communication
Display of the watchdog monitoring time determined by the PROFIBUS master
• Monitoring starts with the receipt of the first telegram.
• When a value of "0" is displayed, the monitoring function is deactivated.
• A change in the watchdog monitoring time in the master is immediately effective.
Permanent interruption of PROFIBUS communication
Bit-coded selection of the error responses in the standard device causing the external diagnostic bit ("diag bit") to be set (see PROFIBUS specification; bit 3 of byte 1 of the DP diagnostic messages).
• The diagnostic bit is sent to the PROFIBUS master where it is evaluated separately.
• The diagnostic bit is always set when a system error occurs.
• The Lenze setting "0" means that the diagnostic bit is not set for the following error responses.
• An advanced diagnostic message is always sent.
(81)
(81)
83
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 84

11 Diagnostics

11.1 LED status displays

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11 Diagnostics
For diagnosing faults of the PROFIBUS module, the LEDs on the front panel are provided. Furthermore you can query the current bus status via code C13861
11.1 LED status displays
.
Note!
During normal operation, the LED BS (86) blinks and the LED MS (86) is lit permanently.
The following status displays are distinguished:
Module status displays
Fieldbus status displays
(85)
(86)
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 84
Page 85
11 Diagnostics
11.1 LED status displays
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.1.1 Module status displays
The LEDs MS, ME and DE indicate the module status.
MS
ME
DE
E84YCPM006
[11-1] LED status displays MS, ME, and DE
LED Colour State Description
MS Green On
The communication module is supplied with voltage and has established a connection to the standard device.
Blinking
200 ms
200 ms
The communication module is supplied with voltage, but has not yet established a connection to the standard device. (Standard device is switched off, initialising or not present.)
ME Red On
An error concerning the communication module has occurred.
DE Red On
The communication module is not accepted by the standard device or the standard device is not active. (See notes in the documentation for the standard device.)
85
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 86
11 Diagnostics
11.1 LED status displays
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.1.2 Fieldbus status displays
The LEDs BS and BE indicate the fieldbus status.
BS
BE
[11-2] LED status displays BS and BE
LED Colour State Description
BS Green Off The communication module is not active on the fieldbus or is being
BE Red Blinking
Blinking
On
E84YCPM006
initialised.
200 ms
200 ms
The communication module is in the DATA_EXCH state ("Data_Exchange"). Data are exchanged via PROFIBUS.
200 ms
200 ms
Incorrect setting for the station address. The communication module is initialised and internally operates with
the respective default values.
Bus error/fault is active (e.g. bus cable unplugged).
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 86
Page 87
11 Diagnostics

11.2 Diagnosing with the »Engineer«

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.2 Diagnosing with the »Engineer«
In the »Engineer«, the Diagnostics tab displays various pieces of PROFIBUS diagnostic information.
87
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 88
11 Diagnostics
11.2 Diagnosing with the »Engineer«
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Querying the current bus status
Code C13861
Bit assignment Description
Bit 3 Bit 2 Bit 1 Bit 0 Reserved
displays the current PROFIBUS status in a bit-coded form:
Bit 5 Bit 4 Status of the DP state machine (DP-STATE)
0 0 WAIT_PRM The slave waits for a parameter data telegram after
0 1 WAIT_CFG The slave waits for the configuration telegram that specifies
1 0 DATA_EXCH If the parameter settings as well as the configuration have
1 1 Not possible
Bit 7 Bit 6 Status of the watchdog state machine (WD-STATE)
0 0 BAUD_SEARCH The PROFIBUS slave is able to automatically detect the baud
0 1 BAUD_CONTROL After recognising the correct baud rate, the slave status
1 0 DP_CONTROL The DP_CONTROL status serves for response monitoring of
1 1 Not possible
acceleration. Other types of telegrams will not be processed. Data exchange is not yet possible.
the number of input and output bytes. The master informs the slave about the number of I/O bytes that will be transferred.
been accepted by the firmware and by the application, the slave state changes to DATA_EXCH ("Data Exchange", exchange of user data with the master).
rate.
changes to BAUD_CONTROL and the baud rate is monitored.
the master.
Bit 11 Bit 10 Bit 9 Bit 8 PROFIBUS baud rate detected
000012 Mbps
00016 Mbps
00103 Mbps
00111.5 Mbps
0 1 0 0 500 kbps
0 1 0 1 187.5 kbps
011093.75 kbps
011145.45 kbps
100019.2 kbps
10019.6 kbps
Bit 15 Bit 14 Bit 13 Bit 12 Reserved
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 88
Page 89
11 Diagnostics

11.3 Advanced diagnostic message

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
11.3 Advanced diagnostic message
Errors in the inverter and its plugged-in modules are transmitted to the PROFIBUS master in the form of advanced diagnostic messages.
Structure of the diagnostic message
Byte Description
1 Bit 0: Station does not exist (set by the master).
Bit 1: Slave is not ready for data exchange. Bit 2: Configuration data do not correspond. Bit 3: Slave has extended diagnostic data. Bit 4: Requested function is not supported by the slave. Bit 5: Slave response is invalid (set by the master) Bit 6: Incorrect parameter setting Bit 7: Slave has been parameterised by another master (set by the master).
2 Bit 0: Slave must be parameterised again.
Bit 1: Static diagnostics Bit 2: Permanently set to "1". Bit 3: Watchdog active Bit 4: Freeze command received. Bit 5: Sync command received. Bit 6: Reserved Bit 7: Slave is deactivated (set by the master).
3 Bit 7: Diagnostics overflow - amount of diagnostic information present in the slave is too large to fit
into one telegram.
4 Bits 0 ... 7: Master address after parameterisation ("0xFF" without parameterisation)
5 Bits 0 ... 7: ID number (high byte)
6 Bits 0 ... 7: ID number (low byte)
7Header
• The header contains the block length of the advanced diagnostics including the header byte.
• In this case, the value of the entry is "0x0A" (bytes 7 ... 16 = 10 bytes).
8 Status_Type
The value of this entry is fixed. For the following bit assignment it is "0x81":
• Bit 7 = 1: "status"
• Bit 0 = 1: "status message"
• Value of all other bits = 0
9Slot_Number
The value of the slot number is "0x00".
10 Specifier
• An indicated error is entered in the specifier with the identification "0x1" (status coming).
• An eliminated error is entered in the specifier with the identification "0x02" (status going).
• If no errors are indicated, the entry in the specifier has the value "0x00" (no further differentiation).
11 Reserved
12
13 ... 16 Error code of the Inverter Drive 8400
•Code C00165 can be used to read out the contents of the fault memory.
• Detailed information regarding the error codes of the Inverter Drive 8400 can be found in the documentation of the inverter.
89
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 90
11 Diagnostics
11.3 Advanced diagnostic message
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Example: "Short circuit (OC1)" error in the Inverter Drive 8400
Byte Value
[hex]
1 x Standard data (PRM_Fault)
...
6
7 0A Block length of the advanced diagnostics = 10 bytes
8 81 Status message
900Slot 0
10 01 Status coming
11 00
12 00
13 0B Error message 0x11C4000B "Short circuit (OC1)"
14 00
15 C4
16 11
Description
• Error type: "Warning locked"
• Subject area: 0x11C4 (current)
• Error ID: 0x000B
The error number "0x11C4000B" indicates the following: In the "Current" subject area, an overcurrent has been detected. The error response
to this is a "Warning locked", which must be unlocked separately after the error has been eliminated.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 90
Page 91

12 Error messages

12.1 Short overview of the PROFIBUS error messages

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12 Error messages
This chapter supplements the error list contained in the software manual and in the »Engineer« online help for Inverter Drives 8400 by the error messages of the communication module.
Software manual/online help for Inverter Drives 8400
Here you can find general information on diagnostics & fault analysis and on error messages.
12.1 Short overview of the PROFIBUS error messages
The following table lists all PROFIBUS error messages in numerical order of the error number. Furthermore the preset error response and – if available – the parameters for setting the error response are specified.
Tip!
When you click the cross-reference in the first column, you will see a detailed description (causes and remedies) of this error message.
Error number Error text Error type Adjustable
hex dec
0x01bc3100 444 12544 Connection to 8400 standard device lost Error -
0x01bc5531
0x01bc5532
0x01bc5533
0x01bc6010
0x01bc6011
0x01bc6100
0x01bc6101
0x01bc6110
0x01bc641f
0x01bc6420
0x01bc8130
0x01bc8131 444 33073 Profibus: Data_Exchange state exited No response C13880/1
0x01bc8132 444 33074 Profibus Watchdog: DP-V1 MSC2 monitoring time
(subject area no.)
444 21809 Memory: No access Error -
444 21810 Memory: Read error Error -
444 21811 Memory: Write error Error -
444 24592 Restart after watchdog reset Error -
444 24593 Internal error Error -
444 24832 Internal error Error -
444 24833 Internal error Error -
444 24848 Internal error Error -
444 25631 Invalid parameter set Error -
444 25632 Error: Lenze settings loaded Error -
444 33072 Profibus watchdog: Monitoring time elapsed No response C13880/1
dec (error no.)
exceeded
No response C13880/2
in
91
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 92
12 Error messages

12.2 Possible causes and remedies

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12.2 Possible causes and remedies
This chapter lists all PROFIBUS error messages in the numerical order of the error numbers. Possible causes and remedies as well as responses to the error messages are described in detail.
Connection to 8400 standard device lost [0x01bc3100]
Response (Lenze setting printed in bold) Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
• Network cable (plug) is defective.
• Network cable is not connected to the PROFIBUS terminal X201.
• Voltage supply is interrupted.
Memory: No access [0x01bc5531]
Check cables and terminals. Connect network cable to the PROFIBUS terminal X201.
Response (Lenze setting printed in bold) Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Access to memory was not possible. Repeat the download of the application
Memory: Read error [0x01bc5532]
Response (Lenze setting printed in bold) Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Parameter could not be read. Repeat the download of the application
Memory: Write error [0x01bc5533]
Response (Lenze setting printed in bold) Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Parameter could not be written. Repeat the download of the application
(including module)
(including module)
(including module)
Restart after watchdog reset [0x01bc6010]
Response (Lenze setting printed in bold) Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Module defective. If this occurs repeatedly, contact the Lenze service.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 92
Page 93
12 Error messages
12.2 Possible causes and remedies
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Internal error [0x01bc6011]
Response (Lenze setting printed in bold) Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Module defective. If this occurs repeatedly, contact the Lenze service.
Internal error [0x01bc6100]
Response (Lenze setting printed in bold) Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Internal error. If this occurs repeatedly, contact the Lenze service.
Internal error [0x01bc6101]
Response (Lenze setting printed in bold) Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
The communication module carries out an automatic software reset and reinitialises itself.
Internal error [0x01bc6110]
Invalid parameter set [0x01bc641f]
Error: Lenze settings loaded [0x01bc6420]
Response (Lenze setting printed in bold) Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
Module defective. If this occurs repeatedly, contact the Lenze service.
Response (Lenze setting printed in bold) Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause Remedy
No active parameter set could be loaded. Repeat the download of the application
Response (Lenze setting printed in bold) Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
If this occurs repeatedly, contact the Lenze service.
(including module)
93
Cause Remedy
Access to parameter set was not successful. Repeat the download of the application
(including module).
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 94
12 Error messages
12.2 Possible causes and remedies
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Profibus watchdog: Monitoring time elapsed [0x01bc8130]
Response (Lenze setting printed in bold) Setting: C13880/1 (; Adjustable response)
: None  System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause Remedy
Permanent interruption of communication to the PROFIBUS master.
Also see the chapter "Permanent interruption of
PROFIBUS communication" (81).
Profibus: Data_Exchange state exited [0x01bc8131]
Response (Lenze setting printed in bold) Setting: C13880/1 (; Adjustable response)
: None  System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause Remedy
Data exchange via PROFIBUS has been stopped. Also see the chapter "Permanent interruption of
PROFIBUS communication" (81).
Check cables and terminals.
Check cables and terminals. The slave must receive new parameterisation and configuration files from the master in order to be able to
exchange data again.
Profibus watchdog: DP-V1 MSC2 monitoring time exceeded [0x01bc8132]
Response (Lenze setting printed in bold) Setting: C13880/2 (; Adjustable response)
: None  System fault ; Fault Trouble ; Quick stop by trouble ; Warning locked Warning ; Information
Cause Remedy
Permanent interruption of communication to C2­PROFIBUS master.
Also see the chapter "Permanent interruption of
PROFIBUS communication" (81).
Check cables and terminals.
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 94
Page 95

13 Parameter reference

13.1 Parameters of the communication module

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
13 Parameter reference
This chapter supplements the parameter list and the table of attributes contained in the software manual and in the »Engineer« online help for Inverter Drives 8400 by the parameters of the E84AYCPM communication module (PROFIBUS).
Software manual/»Engineer« online help for Inverter Drives 8400
Here you can find general information on parameters.
13.1 Parameters of the communication module
This chapter lists the parameters of the E84AYCPM communication module (PROFIBUS) in numerically ascending order.
C13850
C13851
Parameter | Name:
C13850 | All words to master
Display of the process data words transferred from the communication module to the PROFIBUS master. In subcodes 1 ... 16, all process data words to the master are displayed. Only the process data words configured are
valid.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C13850/1
...
C13850/16
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13851 | All words from master
Display of the process data words transferred from the PROFIBUS master to the communication module. In subcodes 1 ... 16, all process data words to the master are displayed. Only the process data words configured are valid.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C13851/1
...
C13851/16
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Data type: UNSIGNED_16
Index: 10725
Data type: UNSIGNED_16
Index: 10724
= 29E5
d
= 29E4
d
h
h
95
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 96
13 Parameter reference
13.1 Parameters of the communication module
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13852
C13853
Parameter | Name:
C13852 | All words to standard device
Data type: UNSIGNED_16
Index: 10723
= 29E3
d
Display of process data words 1 ... 16 which are transferred from the communication module to the standard device. In subcodes 1 ... 16, all process data words from the communication module are displayed.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C13852/1
...
C13852/16
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13853 | All words from standard device
Data type: UNSIGNED_16
Index: 10722
= 29E2
d
Display of process data words 1 ... 16 which are transferred from the standard device to the communication module. In subcodes 1 ... 16, all process data words from the standard device are displayed.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C13853/1
...
C13853/16
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
h
h
C13860
Parameter | Name:
C13860 | Settings
Data type: UNSIGNED_8
Index: 10715
Display of the current configuration data.
Display area (min. value | unit | max. value)
0 255
Subcodes Info
C13860/1 Reserved
C13860/2 Number of process data words (1 ... 16 words)
C13860/3 DRIVECOM parameter data channel
• 0: Not active
•1: Active
C13860/4 Reserved
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
= 29DB
d
h
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 96
Page 97
13 Parameter reference
13.1 Parameters of the communication module
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13861
C13862
C13863
Parameter | Name:
Data type: UNSIGNED_16
C13861 | Bus status
Bit-coded display of the current bus state.
Querying the current bus status
(88)
Display area (min. value | unit | max. value)
0 65535
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
Data type: UNSIGNED_16
C13862 | Bus counter
When the maximum count value of 65535 is reached, the counter starts again with 0.
Display area (min. value | unit | max. value)
0 65535
Subcodes Info
C13862/1 Data cycles per second
C13862/2 Total data cycles
C13862/3 Total parameterisation events
C13862/4 Total configuration events
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
Data type: UNSIGNED_8
C13863 | Baud rate
Display of the baud rate
Selection list (read only)
0 12.00 Mbps
1 6.00 Mbps
2 3.00 Mbps
3 1.50 Mbps
4 500.00 kbps
5 187.50 kbps
6 93.75 kbps
7 45.45 kbps
8 19.20 kbps
9 9.60 kbps
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Index: 10714
Index: 10713
Index: 10712
= 29DA
d
= 29D9
d
= 29D8
d
h
h
h
97
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 98
13 Parameter reference
13.1 Parameters of the communication module
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13864
C13865
C13866
C13867
Parameter | Name:
C13864 | Active station address
Data type: UNSIGNED_8
Index: 10711
= 29D7
d
Display of the active station address If all DIP switches 1 ... 64 are in the "OFF" position (Lenze setting), the station address set in C13899
becomes active
and is displayed here after switching on.
Setting the station address
(32)
Display area (min. value | unit | max. value)
0 255
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13865 | Display: Most recent PRM data
Data type: OCTET_STRING
Index: 10710
= 29D6
d
Display of the last parameter data sent by the PROFIBUS master with the "Set-Prm" telegram (ASCII string with 24 characters)
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13866 | Display: Most recent CFG data
Data type: OCTET_STRING
Index: 10709
= 29D5
d
Display of the last configuration data sent by the PROFIBUS master with the "Chk-Cfg" telegram (ASCII string with 22 characters)
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
h
h
h
Parameter | Name:
Data type: OCTET_STRING
C13867 | Display: Most recent diagnostic data
Display of the last diagnostic data sent to the PROFIBUS master (ASCII string with 16 characters)
Advanced diagnostic message
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
(89)
Index: 10708
= 29D4
d
h
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 98
Page 99
13 Parameter reference
13.1 Parameters of the communication module
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13880
Parameter | Name:
C13880 | Reaction on communication fault
Data type: UNSIGNED_8
Index: 10695
= 29C7
d
h
Monitoring response to a communication fault on the PROFIBUS A change in the monitoring response is effective immediately.
Permanent interruption of PROFIBUS communication
(81)
Selection list
0 No response
1 Error
3 Quick stop by trouble
4 Warning locked
6 Information
Subcodes Lenze setting Info
C13880/1 0: No response The response set here for the "Watchdog/Data
Exchange" monitoring function is executed if the bus station ...
• does not receive a message from the master within the watchdog monitoring time (displayed in C13882/
1) if there is an active connection.
• detects that it is no longer in the "Data_Exchange" status. Please see also the notes given under C13881
.
C13880/2 0: No response The response set here for the "DPV1 MSAC2" monitoring
is executed if the bus station does not receive any "DPV1 MSAC2" message from the master within the monitoring time (displayed in C13882/2
if there is an active connection) and the MSAC2 connection is stopped by the slave. Note: We recommend only setting "information" as response so that no drive-relevant response is executed.
; Read access ; Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT
C13881
Parameter | Name:
C13881 | Monitoring time: Data exchange
Data type: UNSIGNED_16
Index: 10694
If the "Data Exchange" state is exited, the response parameterised under C13880/1 is carried out when the monitoring time for data exchange set here has expired.
• A value of "65535" in this code deactivates the monitoring function.
• A change in monitoring is effective immediately.
• The value set here for the monitoring time must be smaller than the watchdog monitoring time (C13882/1
Permanent interruption of PROFIBUS communication
(81)
Setting range (min. value | unit | max. value) Lenze setting
0 ms 65535 65535 ms
; Read access ; Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT
= 29C6
d
h
).
99
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17
Page 100
13 Parameter reference
13.1 Parameters of the communication module
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13882
C13885
C13886
Parameter | Name:
C13882 | Monitoring time: Watchdog
Data type: UNSIGNED_32
Index: 10693
= 29C5
d
Display of the watchdog monitoring time determined by the PROFIBUS master
• A change in the watchdog monitoring time is immediately effective.
• Monitoring starts with the receipt of the first telegram.
• When a value of "0" is displayed, the monitoring function is deactivated.
Permanent interruption of PROFIBUS communication
(81)
Display area (min. value | unit | max. value)
0 ms 4294967295
Subcodes Info
C13882/1 Watchdog monitoring time
C13882/2 DP-V1 MSC2
; Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13885 | Clear process data
Data type: UNSIGNED_8
Index: 10690
= 29C2
d
Selection of the process data which the inverter will process in the event of a PROFIBUS failure in order to maintain internal communication.
Selection list (Lenze setting printed in bold)
0 Use of most recent master PDOs
1 PDOs are set to the value '0'
; Read access ; Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT
h
h
Parameter | Name:
C13886 | Set ext. diagnostic bit by
Data type: BITFIELD_8
Index: 10689
= 29C1
d
Bit-coded selection of the error responses in the standard device causing the external diagnostic bit ("diag bit") to be set (see PROFIBUS specification; bit 3 of byte 1 of the DP diagnostic messages).
• The diagnostic bit is sent to the PROFIBUS master where it is evaluated separately.
• The diagnostic bit is always set when a system error occurs.
• The Lenze setting "0" means that the diagnostic bit is not set for the following error responses.
• An advanced diagnostic message is always sent.
Value is bit-coded:
Bit 0 Error
Bit 1 Trouble
Bit 2 Quick stop by trouble
Bit 3 Warning locked
Bit 4 Warning
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
; Read access ; Write access  CINH  PLC-STOP  No transfer  PDO_MAP_RX  PDO_MAP_TX  COM  MOT
h
Lenze · E84AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 5.0 EN · 11/2012 · TD17 100
Loading...