Description of PROFIBUS PA interfaceDescription of PROFIBUS PA interface
The documentation is only complete when it is used in combination with the relevant
documentation of the level meter.
www.krohne.com10/2013 - 4003066801 - MA OPTIFLEX2200C-PA-R01-en-AD
OPTIFLEX 2200 C
1.1 Installation
Install the GSD files in your system. If it is necessary to use the process control system to change
the settings of the device, install the DD files. If it is necessary to use PACTware™ to change the
settings of the device, install PACTware™ and the DTM PROFIBUS PA files.
The software, files and installation instructions are given on the DVD-ROM supplied with the
device. You can download the latest version of PACTware™ and the DTM PROFIBUS PA from our
website. For more data, refer to the “readme.txt” files.
1.2 Scope of the document
These instructions are supplementary to the standard product documentation of the signal
converter. The details described herein, in particular the safety information, are valid and shall
be adhered to. The present supplementary instructions provide additional information for the
device when it is connected to a PROFIBUS network.
INFORMATION!
The information in this document only contains the data applicable to the PROFIBUS module.
The technical data in the signal converter Handbook is valid in its current version, provided that it
is not rendered invalid or replaced by these supplementary instructions.
SAFETY INSTRUCTIONS 1
1.3 Scope of delivery
A device for PROFIBUS communication is supplied with:
Supplementary instructions for the PROFIBUS PA interface (this document)
www.krohne.com10/2013 - 4003066801 - MA OPTIFLEX2200C-PA-R01-en-
3
2 PROFIBUS PA
2.1 Software history
Issued Signal converterApplication programSystem integration
OPTIFLEX 2200 C
Mth./
HardwareFirmwareHardwareSoftwareDriverVersionModel name
year
08/13PROFIBUS PA
module Ident.
No
0x4550
(4001858601c)
V2.42.0.42Simatic
2.2 Device description
This device is a 2-wire level transmitter that uses TDR (Time Domain Reflectometry) / Guided
Radar technology. It measures the distance of liquids, liquid gases, pastes, powders, slurries
and granular products.
The level transmitter has an MBP (Manchester-coded, bus-powered) interface to connect the
device to a PROFIBUS PA network, when equipped with the appropriate options.
The level transmitter is approved for use in potentially explosive atmospheres when equipped
with the appropriate options.
PCS7
or
other SPS of
other
manufact.
Laptop / PCPDM
HW Config
or
other
Software of
other SPS
manufact.
(≥ 6.0 SP5)DD(Ident.-No.)
PactwareDTM ≥ 1.0.0
GSD (device
specific)
GSD (profile
specific)
KR014550.GSDOPTIFLEX 2200
PA1397.GSDAI 1 (Phy MBP)
2.3 Function blocks and the PROFIBUS PA Profile
The Analog Input Function Block agrees with PROFIBUS PA Profile 3.02. The Analog Input
Function Block is the data interface to a process control system (a PLC, ...). The control system
(cyclic communication services) can read or write input and output data.
INFORMATION!
The PROFIBUS PA Profile 3.02 has a standard set of parameters and functions available for
PROFIBUS devices used in process control. The PROFIBUS device is a function block application
in which parameters and functions are grouped into different blocks.
The device has these blocks:
BlockUsage
1 Physical Block (PB)contains identification and diagnosis parameters of the device
1 Level Transducer Block (TB-Level)contains parameters and functions to control the level
4 Analog Input Function Blocks (AI-FB)contains parameters and functions to control the measuring
measurement
output; provides the measuring value(s)
4
www.krohne.com10/2013 - 4003066801 - MA OPTIFLEX2200C-PA-R01-en-
OPTIFLEX 2200 C
The device has 4 slots. The Analog Input Function Blocks use slot 1 (as a virtual module). The
user cannot change this setting. But the user can change the measurement name and unit for
each Function Block. Refer to the table that follows:
INFORMATION!
If it is necessary to change the measurement name, change the channel parameter in the acyclic
PROFIBUS services.
PROFIBUS PA 2
Slot Module
type
1AI-FBLevel (default setting)mm 1
1 Default measurement unit
The calibration units are used as default units.
2.4 Technical data
Hardware
TypePROFIBUS MBP interface. This interface agrees with IEC 61158-2 (bit rate
Device power supply9...32 V - bus powered; no additional power supply required
Polarity sensitivityNo
Base current14 mA
FDEYes. The Fault Disconnection Electronics (FDE) operates independently.
Max. error current20.5 mA
Start current after 10 ms Lower than base current
Measurement nameUnit
Distancemm 1
ConversionL 1
Conversion DistanceL 1
31.25 kbit/s);
voltage mode (MBP = Manchester-Coded, Bus-Powered)
Software
Supported GSDKR014550.GSD
PA139700.GSD
Device profilePROFIBUS PA Profile V3.02; conformance class B, compact
Address settingDefault:126
Hardware DIP switch:0…125
PROFIBUS service Set_Slave_Add:0...125
Factory_Reset=2712:126
Write protectionPassword and/or hardware switch
SAPs2 × MS1 SAPs – acyclic interface to PLC
3 × MS2 SAPs – the number of MS2 Service Access Points is usually equal to
the maximum number of master class 2 tools
Function blocks1 Physical Block
1 Level Transducer Block
4 Analog Input Function Blocks
www.krohne.com10/2013 - 4003066801 - MA OPTIFLEX2200C-PA-R01-en-
5
3 ELECTRICAL CONNECTION
3.1 Topology of a PROFIBUS PA network
The following diagram shows a typical network configuration with PROFIBUS PA devices in
hazardous and non-hazardous areas, as well as the connection of conventional non-PROFIBUS
devices (e.g. with 4 … 20 mA signals) to a PROFIBUS network.
The PROFIBUS PA segment is connected to a segment coupler which, among other things,
provides the conversion to the PROFIBUS DP bus line. In addition it provides the power supply for
bus–powered PROFIBUS PA devices. Refer to the instruction manual of the segment coupler
concerning the DP bus parameters, e.g. the supported baud rates.
OPTIFLEX 2200 C
Figure 3-1: PROFIBUS PA network
1 Control system (PLC); class 1 master
2 Engineering or operation control tool; class 2 master
3 PROFIBUS DP network with max. 12 Mbit/s
4 PROFIBUS PA segment coupler DP / PA
5 PROFIBUS PA network with 31.25 kbit/s
6 HART
7 More devices with 4…20 mA
8 Analogue I/O module
®
device
Refer also to the PROFIBUS PA User and Installation Guideline (Version 2.2, February 2003 PNO
Order No. 2.092).
6
www.krohne.com10/2013 - 4003066801 - MA OPTIFLEX2200C-PA-R01-en-
OPTIFLEX 2200 C
ELECTRICAL CONNECTION 3
3.2 Electrical connection for signal converter
Bus cable - Shielding and grounding
The statements of the FISCO model only apply if the used bus cable meets the required
specifications.
In order to ensure optimum electromagnetic compatibility of systems it is important that the
system components, and in particular the bus cables, are shielded. These shields must have as
few gaps as possible.
INFORMATION!
The PROFIBUS PA interface of the signal converter will operate only if the power supply is
connected/available. The device terminal is not sensitive to electrical polarity.
Figure 3-2: Electrical installation: terminals
1 Power supply / communication terminal
2 Power supply / communication terminal
3 Grounding terminal
Use the shortest possible length of shield wire to connect the electrical cable to the functional
earth (FE) terminal.
www.krohne.com10/2013 - 4003066801 - MA OPTIFLEX2200C-PA-R01-en-
7
4 COMMISSIONING / OPERATION
4.1 Hardware settings
There is a DIP switch block with 8 switches on the level transmitter module to set the PROFIBUS
device address and prevent changes to the station address from the network.
OPTIFLEX 2200 C
Figure 4-1: How to use the DIP switches to change the station address
1 Hardware DIP switch
OFF: The user can set the station address with the network bus
ON: The user can set the address of the device with the 7 other DIP swtiches (item 2). You cannot use the network bus
or the local display to change the station address.
2 7 "Station Address" DIP switches. Each DIP switch is a bit position (bits 0...6). Bit 0 is on the left side of the switch
block.The base 10 value of each bit is given in the table that follows. This data is used to calculate the "Station Address"
number.
OFF: binary number "0".
ON: binary number "1".
INFORMATION!
If the Hardware DIP switch is set to "ON", the hardware is locked and you cannot use the network
bus to change the station address.
8
www.krohne.com10/2013 - 4003066801 - MA OPTIFLEX2200C-PA-R01-en-
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.