OPTISWITCH 3300 C - with transistor output3
About this document
1 About this document
1.1 Function
This operating instructions manual has all the information you
need for quick setup and safe operation. Please read this
manual before you start setup.
1.2 Target group
This operating instructions manual is directed to trained,
qualified personnel. The contents of this manual should be
made available to these personnel and put into practice by
them.
1.3 Symbolism used
Information, tip, note
This symbol indicates helpful additional information.
Caution: If this warning is ignored, faults or
malfunctions can result.
Warning: If this warning is ignored, injury to persons and/or
serious damage to the instrument can result.
Danger: If this warning is ignored, serious injury to persons
and/or destruction of the instrument can result.
Ex applications
This symbol indicates special instructions for Ex applications.
lList
The dot set in front indicates a list with no implied sequence.
àAction
This arrow indicates a single action.
1Sequence
Numbers set in front indicate successive steps in a procedure.
4OPTISWITCH 3300 C - with transistor output
29962-EN-060830
For your safety
2 For your safety
2.1 Authorised personnel
All operations described in this operating instructions manual
must be carried out only by trained specialist personnel
authorised by the operator. For safety and warranty reasons,
any internal work on the instruments must be carried out only
by personnel authorised by the manufacturer.
2.2 Appropriate use
OPTISWITCH 3300 C is a sensor for level detection.
Detailed information on the application range of OPTISWITCH
3300 C is available in chapter "Product description".
2.3 Warning about misuse
Inappropriate or incorrect use of the instrument can give rise to
application-specific hazards, e.g. vessel overfill or damage to
system components through incorrect mounting or adjustment.
2.4 General safety instructions
OPTISWITCH 3300 C is a high-tech instrument requiring the
strict observance of standard regulations and guidelines. The
user must take note of the safety instructions in this operating
instructions manual, the country-specific installation standards
(e.g. the VDE regulations in Germany) as well as all prevailing
safety regulations and accident prevention rules.
2.5 CE conformity
OPTISWITCH 3300 C is in CE conformity with EMC (89/336/
EWG), fulfils NAMUR recommendation NE 21 and is in CEconformity with LVD (73/23/EWG).
Conformity has been judged according to the following
standards:
l EMC:
- Emission EN 61326: 1997 (class B)
- Susceptibility EN 61326: 1997/A1:1998
l LVD: EN 61010-1: 2001
29962-EN-060830
OPTISWITCH 3300 C - with transistor output5
For your safety
2.6 SIL conformity
OPTISWITCH 3300 C fulfills the requirements of functional
safety according to IEC 61508/IEC 61511. You can find further
information in the supplementary instructions manual "Safety
Please note the Ex-specific safety information for installation
and operation in Ex areas. These safety instructions are part of
the operating instructions manual and come with the Exapproved instruments.
6OPTISWITCH 3300 C - with transistor output
29962-EN-060830
3 Product description
3.1 Configuration
Product description
Scope of delivery
Components
The scope of delivery encompasses:
l OPTISWITCH 3300 C level sensor
l Documentation
- this operating instructions manual
- Supplementary instructions manual "Plug connector for
level sensors" (optional)
- Ex specific safety instructions (with Ex versions), if
necessary further certificates
OPTISWITCH 3300 C consists of the following components:
l Housing cover
l Housing with electronics
l process fitting with tuning fork
1
2
3
Fig. 1: OPTISWITCH 3300 C with plastic housing
1Housing cover
2Housing with electronics
3Process fitting
3.2 Principle of operation
Area of application
29962-EN-060830
OPTISWITCH 3300 C - with transistor output7
OPTISWITCH 3300 C is a level sensor with tuning fork for level
detection.
Product description
It is designed for industrial use in all areas of process
technology and is preferably used for bulk solids.
Typical applications are overfill and dry run protection. Thanks
to its simple and robust measuring system, OPTISWITCH3300 C is virtually unaffected by the chemical and physical
properties of the bulk solid.
It functions even when exposed to strong external vibration or
changing products.
Solid detection in water
If OPTISWITCH 3300 C was ordered for detection of solids in
water, the tuning fork is adjusted to the density of water. In the
air or when covered by water (density: 1 g/cm³/0.036 lbs/in)OPTISWITCH 3300 C signals "uncovered". Only if the
vibrating element is also covered with solids (e.g. sand,
sludge, gravel etc.) will the sensor signal "covered".
Fault monitoring
The electronics of OPTISWITCH 3300 C continuously monitors the following criteria:
l Correct vibrating frequency
l Line break to the piezo drive
If one of the stated malfunction is detected or in case of power
failure, the electronics takes on a defined switching condition,
i.e. the output transistor blocks (safe condition).
Physical principle
The tuning fork is piezoelectrically energised and vibrates at its
mechanical resonance frequency of approx. 150 Hz. When the
tuning fork is submerged in the product, the vibration
amplitude changes. This change is detected by the integrated
oscillator and converted into a switching command.
Power supply
OPTISWITCH 3300 C is a compact instrument, i.e. it can be
operated without external evaluation system. The integrated
electronics evaluates the level signal and outputs a switching
signal. With this switching signal, a connected device can be
directly activated (e.g. a warning system, a PLC, a pump etc.).
The exact range of the power supply is stated in the "Technical
data" in the "Supplement".
8OPTISWITCH 3300 C - with transistor output
29962-EN-060830
Product description
3.3 Operation
With the factory setting, products with a density of >0.02 g/cm³
(>0.0008 lbs/in³) can be measured. The instrument can alsobe adapted to products with lower density >0.008 g/cm³
(>0.0003 lbs/in³).
On the electronics module you will find the following indicating
and adjustment elements:
l signal lamp for indication of the switching condition (green/
red)
l potentiometer for adaptation to the product density
l Mode switch for selecting the switching condition (min./
max.)
3.4 Storage and transport
Packaging
Storage and transport tem-
perature
Your instrument was protected by packaging during transport.
Its capacity to handle normal loads during transport is assuredby a test according to DIN 55439.
The packaging of standard instruments consists of environ-
ment-friendly, recyclable cardboard. In addition, the sensor is
provided with a protective cover of cardboard. For special
versions PE foam or PE foil is also used. Dispose of the
packaging material via specialised recycling companies.
l Storage and transport temperature see "Supplement -
Technical data - Ambient conditions"
l Relative humidity 20 … 85 %
29962-EN-060830
OPTISWITCH 3300 C - with transistor output9
Mounting
4 Mounting
4.1 General instructions
Switching point
Moisture
In general, OPTISWITCH 3300 C can be mounted in any
position. The instrument must be mounted in such a way that
the vibrating element is at the height of the requested switching
point.
Use the recommended cables (see chapter "Connecting to
power supply") and tighten the cable gland.
You can give your OPTISWITCH 3300 C additional protection
against moisture penetration by leading the connection cable
downward in front of the cable entry. Rain and condensation
water can thus drain off. This applies mainly to mounting
outdoors, in areas where moisture is expected (e.g. by
cleaning processes) or on cooled or heated vessels.
Fig. 2: Measures against moisture penetration
Transport
Do not hold OPTISWITCH 3300 C on the vibrating element.
Especially with flange and tube versions, the sensor can be
damaged by the weight of the instrument.
Remove the protective cover just before mounting.
Pressure/Vacuum
The process fitting must be sealed if there is gauge or low
pressure in the vessel. Before use, check if the seal material is
resistant against the measured product and the process
temperature.
The max. permissible pressure is stated in the "Technical
data" in the "Supplement" or on the type label of the sensor.
10OPTISWITCH 3300 C - with transistor output
29962-EN-060830
Mounting
Handling
Agitators and fluidization
The vibrating level switch is a measuring instrument and must
be treated accordingly. Bending the vibrating element will
destroy the instrument.
Warning:
The housing must not be used to screw in the instrument!
Applying tightening force on the housing can damage its
internal mechanical parts.
To screw in, use the hexagon above the thread.
4.2 Mounting instructions
Agitators, equipment vibration, etc., can cause the level switch
to be subjected to strong lateral forces. For this reason, do not
use an overly long extension tube for OPTISWITCH 3300 C,
but check if you can mount a short level switch on the side of
the vessel in horizontal position.
Extreme vibration caused by the process or the equipment, e.
g. agitators or turbulence in the vessel e.g. from fluidization,
can cause the extension tube of OPTISWITCH 3300 C to
vibrate in resonance. This leads to increased stress on the
upper weld joint. Should a longer tube version be necessary,
you can provide a suitable support or guy directly above the
tuning fork to secure the extension tube.
This measure applies particularly to applications in Ex areas.
Make sure that the tube is not subjected to bending forces
through this measure.
Inflowing medium
If OPTISWITCH 3300 C is mounted in the filling stream,
unwanted switching signals may be generated. Mount OPTI-SWITCH 3300 C at a location in the vessel where no disturbing
influence from e.g. filling openings, agitators etc. can occur.
This applies particularly to instrument types with long
extension tube.
29962-EN-060830
OPTISWITCH 3300 C - with transistor output11