4.3.4 Mapping of DIAGNOSIS_EXTENSION bits into DIAGNOSIS bits........................................... 31
2
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Page 3
MFC 300
CONTENTS
5 Profibus settings34
5.1 Menu A, Quick Setup ...................................................................................................... 34
5.2 Menu B, Test................................................................................................................... 34
5.3 Menu C, Setup................................................................................................................. 35
5.4 Menu D, Service.............................................................................................................. 38
6 Notes39
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
3
Page 4
1 SAFETY INSTRUCTIONS
1.1 Scope of the document
These instructions are supplementary to the signal converter Handbook. For all other data, use
the relevant chapters of the Handbook. If you do not have this document, please contact the
nearest office or download them from the manufacturer's internet site.
INFORMATION!
The information in this chapter only contains the data applicable to PROFIBUS communication.
The technical data in the Handbook shall be valid in its current version, provided that it is not
rendered invalid or replaced by this supplement.
1.2 Scope of delivery
The information in this chapter only contains the data applicable to PROFIBUS communication.
The technical data in the Handbook shall be valid in its current version, provided that it is not
rendered invalid or replaced by this supplement.
A device for PROFIBUS communication is supplied with:
MFC 300
• Supplementary instructions for PROFIBUS communication
• PROFIBUS device data files (GSD) which can be also downloaded from the manufacturer's
internet site
1.3 Special notes
Don't switch off (power off) the signal converter immediately after manual change of parameter
values:
• Please wait approx. 10 seconds before you switch off the signal converter after you have done
both a parameter download via PROFIBUS or a manual change of a parameter value via the
local display.
CAUTION!
Please wait approx. 15 seconds before you switch off the signal converter after you have carried
out a "Factory Reset" (PROFIBUS "Coldstart") via PROFIBUS or local display.
"Deactivation of the Service Parameter Lock" of the signal converter via PROFIBUS:
• After writing down the service password (via PROFIBUS) the "Deactivation of the Service
Parameter Lock" will last at least 20 minutes if the internal password timer of the signal
converter won't be retriggered by writing this password again. The "Deactivation of the
Service Parameter Lock" will be terminated at once by a PROFIBUS Coldstart / Warmstart or
if the internal password timer of the signal converter elapsed.
4
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Page 5
MFC 300
2.1 Software history
Issued Signal converterApplication programSystem integration
PROFIBUS DP 2
Mth./
Hardware FirmwareHardwareSoftwareDriverVersionModel name
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
5
Page 6
2 PROFIBUS DP
2.2 System configuration of PROFIBUS DP network
The following diagram shows a typical network configuration with PROFIBUS devices with RS485
interface in a non-hazardous environment. The PROFIBUS devices with RS485 interface do not
need any segment coupler. They are connected directly to the PROFIBUS DP network.
MFC 300
Figure 2-1: PROFIBUS DP network
1 SPS
2 PROFIBUS DP network with max. 12 Mbit/s
3 Signal converter
4 Other devices with PROFIBUS RS485 interface
6
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Page 7
MFC 300
2.3 Electrical connection for DP signal converter
INFORMATION!
For a detailed description of the electrical connections please refer to the standard signal
converter handbook.
Signal converter terminalsBB-CC-DD-
PROFIBUS designationT+B-A-T+B-A
123456
1Termination positive
2TxD+/RxD+ second connection
3TxD-/RxD- second connection
4Termination negative
5TxD+/RxD+ first connection
6TxD-/RxD- first connection
PROFIBUS DP 2
External connection with spur
CAUTION!
Spurs are not allowed at high data rates!
I = 110 nH
R1 = 390 Ω
R2 = 220 Ω
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
7
Page 8
2 PROFIBUS DP
External connection at last device with active internal bus termination
I = 110 nH
R1 = 390 Ω
R2 = 220 Ω
MFC 300
External connection to a trunk
1 e.g. incoming data lines
2 e.g. outgoing data lines
I = 110 nH
R1 = 390 Ω
R2 = 220 Ω
8
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Page 9
MFC 300
2.4 Technical data
Hardware
TypePROFIBUS RS485 interface according to IEC 61158-2
ConnectionDependent of polarity; please note at electrical connection!
Software
GSDGSD file on CD-ROM or from internet site
Device profilePA Profile compact class B, V 3.0
Address range0…126 (default 126)
Local controlLocal display and operator interface at device
SAPs2 x MS1 SAPs – acyclic interface to PLC
Function blocks1 x TB = Transducer Block: contains the parameters and functions
PROFIBUS DP 2
0…125 via PROFIBUS service set_slave_add
0…126 via local display
126 via factory_reset = 2712
3 x MS2 SAPs – the number of MS2 Service Access Points is typically
equal to the maximum number of master class 2 tools
defined in PA Profile 3.0
1 x PB = Physical Block: contains the parameters defined in PA
Profile 3.0
8 x AI = Analog Input Blocks: contains the parameters defined in PA
Profile 3.0
3 x TOT = Totalizer Function Blocks: contains the parameters defined
in PA Profile 3.0
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
9
Page 10
2 PROFIBUS DP
2.5 GSD files for the data transfer
A PROFIBUS GSD ZIP file (e.g. GSD-31777815.zip; including both all GSD files and additional data
files) you can get on a CD ROM or can be downloaded from the internet. The GSD file contains
information that will be needed for project planning of the PROFIBUS communication network.
The relevant data files (e.g. _ _ _ _ .bmp / _ _ _ _ .dib) must be loaded into the bus configuration
system/master system before start-up of the bus system.
2.5.1 Cyclic data exchange
During network configuration the user has to define which function block outputs of the signal
converter should be transferred cyclically to the master. Network configuration will be done
using one of the GSD files described before. The order of transmission of a function block always
remains the same even if a function block is defined as an "Empty" block (if so, no function block
output data will be sent to the master and all function block outputs following the empty block
output data will be sent to the master and all function block outputs following the empty block
output data will be sent to the master and all function block outputs following the empty block output data will be sent to the master and all function block outputs following the empty block
will move up one position)
will move up one position).
will move up one position)will move up one position)
2.5.2 Baud rate
MFC 300
(if so, no function block
(if so, no function block (if so, no function block
Supported baud rates are listed in the GSD file. After power-on or PROFIBUS timeout a baud rate
search is active to detect the current transfer speed on the bus. It is not necessary to set the
baud rate manually.
If the data transmission rate is changed during operation the baud rate search will not be started
by the device. A new power-up or a manual interruption of the PROFIBUS communication is
required to activate the baud rate search in this case.
2.5.3 Ident.-No. supported
The signal converter with PROFIBUS RS485 interface is based on PROFIBUS PA Profile V 3.0. The
device supports two Ident-No.:
• Ident-No. "4510hex" belongs to the GSD file KR014510.GSD and includes the complete
functionality of the Coriolis mass flowmeter.
• The application of the manufacturer independent Ident-No. "9742hex" (GSD file
"PA039742.GSD") provides interchangeability of devices, i.e. an exchange of Coriolis mass
flowmeters of different vendors.
Please follow the instructions in the manual of the host supplier when installing the GSD File you
need and the additional files (_ _ _ _ .bmp and _ _ _ _ .dib) into the PLC.
INFORMATION!
If separated by the bus configuration system the device entry of the PROFIBUS RS485 interface
with PA Profile 3.0 will be located within the slave family PROFIBUS PA.
10
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Page 11
MFC 300
2.5.4 Manufacturer specific GSD files: KR014510.GSD
The manufacturer delivers the GSD files with the entire device functionality, which is listed as
follows:
PROFIBUS DP 2
Block
number
Default configuration
Function block output: value and
KR014510.GSD
Ident-No. 4510
Default
unit
status
1Mass FlowAI-FBkg/s
2DensityAI-FB
3Medium TemperatureAI-FBK
4Mass TotaliserTotaliser-FBkg
5Volume TotaliserTotaliser-FB
6Mass TotaliserTotaliser-FBkg
7Volume FlowAI-FB
8Concentration 1AI-FB%
9Concentration 2AI-FB%
10Concentration Mass Flow 1AI-FBkg/s
11Concentration Mass Flow 2AI-FBkg/s
kg/m
3
m
m3/h
3
• AI: Analog Input Function Block
• FB: Function Block
There are separate settings to select the units for local display and PROFIBUS. Modifications of
the units of the display will have no effect on the data transferred via PROFIBUS.
A master class 2 tool is required to modify the units for PROFIBUS transfer.
INFORMATION!
During network configuration the user has to define which function block outputs of the signal
converter should be transferred cyclically to the master. This is performed by a bus
configuration tool (e.g. "HW- Config" for PC-S7 from Siemens). This tool offers specific functions
as follows:
1. It is possible to configure an "Empty" block (the code of an "Empty" block is defined as 0x00) on
each block number. This implies: no data are transmitted in the cyclic data telegram for this
block.
2. There is NO "Totaliser (TOT)" function block allowed on block position 1, 2, 3, 7, 8, 9, 10 and 11!
On these positions, only an "Analog Input (AI)" function block or an "Empty" block is allowed!
–
(Note: All codes supported by "Analog Input (AI)" - and "Totaliser (TOT)"
function blocks will
be found in the corresponding GSD files.)
3. There is NO "Analog Input (AI)" function block allowed on block position 4, 5 and 6! On these
positions, only a "Totaliser (TOT)" function block or an "Empty" block is allowed!
4. There is a choice of 7 different totaliser functions, which can be allocated to the blocks 4, 5
and/or 6.
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
11
Page 12
2 PROFIBUS DP
Definition of totaliser functions
Totalcyclic transfer of the totaliser value with status to the master
SetTot + Totalcyclic transfer of the totaliser value with status to the master + cyclic
ModeTot + Totalcyclic transfer of the totaliser value with status to the master + cyclic
SetTot + ModeTot + Totalcyclic transfer of the totaliser value with status to the master + cyclic
SetTotcyclic control data from master to the device via the parameter
ModeTotcyclic control data from master to the device via the parameter
SetTot + ModeTotcyclic control data from master to the device via the parameters
Both, the Byte SetTot and ModeTot are cyclically sent from the master to the device if these bytes
are inserted as output data via the PLC configurator. The meaning of these control bytes are as
follows:
MFC 300
control data from master to the device via the parameter SetTot
control data from master to the device via the parameter ModeTot
control data from master to the device via the parameters SetTot and
ModeTot (in the given order)
SetTot
ModeTot
SetTot and ModeTot (in the given order)
Function of control bytes
SetTot
SetTot
SetTotSetTot
SetTot = 0Totaliser is totalising.
SetTot = 1Totaliser will be reset to 0 and stays at 0 until SetTot is switched back
SetTot = 2Totaliser is set to the value defined by PresetTot. PresetTot can be
SetTot > 2Not allowed. Value is ignored; totaliser remains in its last valid
ModeTot
ModeTot
ModeTotModeTot
ModeTot = 0Totaliser totalises positive and negative values.
ModeTot = 1Totalises only positive values.
ModeTot = 2Totalises only negative values.
ModeTot = 3Totaliser is stopped, no totalisation will be done.
ModeTot = 248Totalises all values as positive, negative values will be multiplied with
ModeTot = 249Totalises all values as negative, positive values will be multiplied with
again to 0. If the value of SetTot changes from "1" to "0" the totaliser
starts counting from 0.
written via an acyclic master (totaliser in block 4 = Slot 4 Index 32;
totaliser in block 5 = Slot 5 Index 32; totaliser in block 6 = Slot 6 Index
32). If the value of SetTot changes from "2" to "0" the totaliser starts
counting from the current value defined by PresetTot.
setting.
-1.0.
-1.0.
12
All other values of ModeTot not allowed. Value is ignored; totaliser remains in its last valid
setting.
The standard block configuration may be changed by the customer but using the default settings
is highly recommended. If the standard block configuration should be changed by the customer
an acyclic master tool or the device display menu must be used to change the "channel
parameter" value of the block which should be connected to another transducer output value.
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Page 13
MFC 300
2.5.5 Profile specific GSD file: PA039742.GSD
The functionality of the profile specific GSD file is limited. This GSD file includes only four blocks:
PROFIBUS DP 2
Block
number
1Mass FlowAI-FBkg/s
2DensityAI-FB
3Medium TemperatureAI-FBK
4Mass TotaliserTotaliser-FBkg
Standard configuration
Function block output value
PA039742.GSD
Ident-No. 9742
Default
unit
3
kg/m
The device has to be switched from full functionality (manufacturer specific) to interchangeable
basic configuration (profile specific) by using both a master class 2 tool or the device display
menu (IDENT_NUMBER_SELECTOR: Slot 0, Index 40; change byte value to 0). In the next step,
the device has to be configured using the PA039742.GSD file.
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
13
Page 14
3 PROFIBUS PA
3.1 Software history
Issued Signal converterApplication programSystem integration
MFC 300
Mth./
Hardware FirmwareHardwareSoftwareDriverVersionModel name
year
11/06Signal
01/11Signal
converter
with MBP
interface +
PA Profile
3.0
converter
with MBP
interface +
PA Profile
3.0
V2.2.1 / 061117Simatic
PCS7
other SPS
of other
manufact.
Laptop / PCPDM
V3.0.3 / 100811Simatic
PCS7
other SPS
of other
manufact.
Laptop / PCPDM
HW Config
other
Software of
other SPS
manufact.
(≥ 6.0 SP3)DD(Ident.-No.)
PactwareDTM ≥ GFP*DTM1.3.1
HW Config
other
Software of
other SPS
manufact.
(≥ 6.0 SP3)DD(Ident.-No.)
PactwareDTM ≥ GFP*DTM1.3.1
GSD
manuf.
specific for
stand.
DP/PA
segment
coupler
GSD
manuf.
specific for
SK2/SK3
segment
coupler of
P&F
GSD
profile
specific
GSD
manuf.
specific for
stand.
DP/PA
segment
coupler
GSD
manuf.
specific for
SK2/SK3
segment
coupler of
P&F
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Page 15
MFC 300
3.2 System configuration of PROFIBUS PA network
The following diagram shows a typical instrumentation with PROFIBUS PA devices with MBP
interface in hazardous and non-hazardous locations, including connections of conventional
devices (e.g. with 4...20 mA signals) in a PROFIBUS network.
As a rule, the PROFIBUS PA segment is connected to a segment coupler which, among other
things, carries out the conversion to the PROFIBUS DP bus line. It should be mentioned that the
segment coupler is normally set to a fixed baud rate on the DP side.
PROFIBUS PA 3
Figure 3-1: PROFIBUS PA network
1 Control system (PLC); class 1 master
2 Engineering or operation control tool; class 2 master
3 PROFIBUS DP network with max. 12 Mbit/s
4 PROFIBUS PA segment coupler DP / PA
5 PROFIBUS PA network with 31.25 kbit/s
6 HART
7 More devices with 4…20 mA
8 Analogue I/O module
®
device
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
15
Page 16
3 PROFIBUS PA
3.3 Electrical connection for PA signal converter
INFORMATION!
The wiring between the device and the PROFIBUS PA bus is independant of polarity.
The signal converter PROFIBUS PA interface will operate only if the additional power supply for
the device is connected/available.
For a detailed description of the electrical connections please refer to the standard signal
converter handbook. Refer also to the PROFIBUS PA user and installation guideline (Version 2.2,
February 2003 PNO order no. 2.092).
Connection to a spur
or
MFC 300
Connection to a trunk
1 e.g. incoming data lines
2 e.g. outgoing data lines
or
16
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Page 17
MFC 300
3.4 Technical data
Hardware
TypePROFIBUS RS485 interface according to IEC 61158-2 with
ConnectionIndependent of polarity at electrical connection
Base current10.5 mA
FDEYes, separate fault disconnection electronics provided (FDE = Fault
Fault current6 mA (fault current = max. continuous current – base current)
Starting current<12 mA
Ex approvalEx ia IIC or Ex ib IIC/IIB, FISCO Device
Software
GSDGSD file on CD-ROM or from internet site
Device profilePA Profile compact class B, V 3.0
Address range0…126 (default 126)
Local controlLocal display and operator interface at device
SAPs2 x MS1 SAPs – acyclic interface to PLC
Function blocks1 x TB = Transducer Block: contains the parameters and functions
PROFIBUS PA 3
31.25 kbits/s; voltage mode
Disconnection Electronics)
For detailed information refer to standard product documentation.
0…125 via PROFIBUS service set_slave_add
0…126 via local display
126 via factory_reset = 2712
3 x MS2 SAPs – the number of MS2 Service Access Points is typically
equal to the maximum number of master class 2 tools
defined in PA Profile 3.0
1 x PB = Physical Block: contains the parameters defined in PA
Profile 3.0
8 x AI = Analog Input Blocks: contains the parameters defined in PA
Profile 3.0
3 x TOT = Totalizer Function Blocks: contains the parameters defined
in PA Profile 3.0
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
17
Page 18
3 PROFIBUS PA
3.5 GSD files for the data transfer
A PROFIBUS GSD ZIP file (e.g. GSD-31777815.zip; including both all GSD files and additional data
files) you can get on a CD ROM or can be downloaded from the internet. The GSD file contains
information that will be needed for project planning of the PROFIBUS communication network.
The relevant data files (e.g. _ _ _ _ .bmp / _ _ _ _ .dib) must be loaded into the bus configuration
system/master system before start-up of the bus system.
3.5.1 Cyclic data exchange
During network configuration the user has to define which function block outputs of the signal
converter should be transferred cyclically to the master. Network configuration will be done
using one of the GSD files described before. The order of transmission of a function block always
remains the same even if a function block is defined as an "Empty" block (if so, no function block
output data will be sent to the master and all function block outputs following the empty block
output data will be sent to the master and all function block outputs following the empty block
output data will be sent to the master and all function block outputs following the empty block output data will be sent to the master and all function block outputs following the empty block
will move up one position)
will move up one position).
will move up one position)will move up one position)
3.5.2 Ident.-No. supported
MFC 300
(if so, no function block
(if so, no function block (if so, no function block
The signal converter with PROFIBUS MBP interface is based on PROFIBUS PA Profile V 3.0. The
device supports three Ident-No.:
• Ident-No. "4511hex" belongs to the GSD file KR014511.GSD and YP014511.GSD and includes
the complete functionality of the Coriolis mass flowmeter.
• The application of the manufacturer independent Ident-No. "9742hex" (GSD file
"PA139742.GSD") provides interchangeability of devices, i.e. an exchange of Coriolis mass
flowmeters of different vendors.
• Ident-No. "E801hex"
For detailed information refer to
as replacement for older signal converter MFC 050/051 PA
Please follow the instructions in the manual of the host supplier when installing the GSD File you
need and the additional files (_ _ _ _ .bmp and _ _ _ _ .dib) into the PLC.
Signal converter MFC 300 PROFIBUS PA with MBP interface
on page 22.
INFORMATION!
If separated by the bus configuration system the device entry of the PROFIBUS MBP interface
with PA Profile 3.0 will be located within the slave family PROFIBUS PA.
18
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Page 19
MFC 300
PROFIBUS PA 3
3.5.3 Manufacturer specific GSD files: KR014511.GSD and YP014511.GSD
The KR014511.GSD file is for use with the standard DP/PA coupler and the YP014511.GSD file is
for use with the transparent DP/PA coupler SK2/SK3 of Pepperl & Fuchs (up to 12 MBaud on the
DP segment).
INFORMATION!
For devices with MBP interface there are always two types of GSD files in our GSD compilation:
•
One standard GSD file for a standard DP/PA segment coupler with file name: "KR0….GSD"
•
One special GSD file specific for the segment coupler SK2/SK3 of Pepperl & Fuchs with file
…
name: "YP0
It should be noted that both GSD files support device functionality as described below:
.GSD"
Block
number
1Mass FlowAI-FBkg/s
2DensityAI-FB
3Medium TemperatureAI-FBK
4Mass TotaliserTotaliser-FBkg
5Volume TotaliserTotaliser-FB
6Mass TotaliserTotaliser-FBkg
7Volume FlowAI-FB
8Concentration 1AI-FB%
9Concentration 2AI-FB%
10Concentration Mass Flow 1AI-FBkg/s
11Concentration Mass Flow 2AI-FBkg/s
Default configuration
Function block output: value and
status
KR014511.GSD
YP014511.GSD
Ident-No. 4511
Default
unit
3
kg/m
3
m
m3/h
• AI: Analog Input Function Block
• FB: Function Block
There are separate settings to select the units for local display and PROFIBUS. Modifications of
the units of the display will have no effect on the data transferred via PROFIBUS.
A master class 2 tool is required to modify the units for PROFIBUS transfer.
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
19
Page 20
3 PROFIBUS PA
INFORMATION!
During network configuration the user has to define which function block outputs of the signal
converter should be transferred cyclically to the master. This is performed by a bus
configuration tool (e.g. "HW- Config" for PC-S7 from Siemens). This tool offers specific functions
as follows:
1. It is possible to configure an "Empty" block (the code of an "Empty" block is defined as 0x00) on
each block number. This implies: no data are transmitted in the cyclic data telegram for this
block.
2. There is NO "Totaliser (TOT)" function block allowed on block position 1, 2, 3, 7, 8, 9, 10 and 11!
On these positions, only an "Analog Input (AI)" function block or an "Empty" block is allowed!
(Note: All codes supported by "Analog Input (AI)" - and "Totaliser (TOT)"
be found in the corresponding GSD files.)
3. There is NO "Analog Input (AI)" function block allowed on block position 4, 5 and 6! On these
positions, only a "Totaliser (TOT)" function block or an "Empty" block is allowed!
4. There is a choice of 7 different totaliser functions, which can be allocated to the blocks 4, 5
and/or 6.
Definition of totalizer functions
Totalcyclic transfer of the totalizer value with status to the master
SetTot + Totalcyclic transfer of the totalizer value with status to the master + cyclic
ModeTot + Totalcyclic transfer of the totalizer value with status to the master + cyclic
SetTot + ModeTot + Totalcyclic transfer of the totalizer value with status to the master + cyclic
SetTotcyclic control data from master to the device via the parameter
ModeTotcyclic control data from master to the device via the parameter
SetTot + ModeTotcyclic control data from master to the device via the parameters
MFC 300
–
function blocks will
control data from master to the device via the parameter SetTot
control data from master to the device via the parameter ModeTot
control data from master to the device via the parameters SetTot and
ModeTot (in the given order)
SetTot
ModeTot
SetTot and ModeTot (in the given order)
20
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Page 21
MFC 300
PROFIBUS PA 3
Both, the Byte SetTot and ModeTot are cyclically sent from the Master to the device if these bytes
are inserted as output data via the PLC configurator. The meaning of these control bytes are as
follows:
Function of control bytes
SetTot
SetTot
SetTotSetTot
SetTot = 0Totaliser is totalising.
SetTot = 1Totaliser will be reset to 0 and stays at 0 until SetTot is switched back
SetTot = 2Totaliser is set to the value defined by PresetTot. PresetTot can be
SetTot > 2Not allowed. Value is ignored; totaliser remains in its last valid
ModeTot
ModeTot
ModeTotModeTot
ModeTot = 0Totaliser totalises positive and negative values.
ModeTot = 1Totalises only positive values.
ModeTot = 2Totalises only negative values.
ModeTot = 3Totaliser is stopped, no totalisation will be done.
ModeTot = 248Totalises all values as positive, negative values will be multiplied with
ModeTot = 249Totalises all values as negative, positive values will be multiplied with
again to 0. If the value of SetTot changes from "1" to "0" the totaliser
starts counting from 0.
written via an acyclic master (totaliser in block 4 = Slot 4 Index 32;
totaliser in block 5 = Slot 5 Index 32; totaliser in block 6 = Slot 6 Index
32). If the value of SetTot changes from "2" to "0" the totaliser starts
counting from the current value defined by PresetTot.
setting.
-1.0.
-1.0.
All other values of ModeTot not allowed. Value is ignored; totaliser remains in its last valid
setting.
The standard block configuration may be changed by the customer but using the default settings
is highly recommended. If the standard block configuration should be changed by the customer
an acyclic master tool or the device display menu must be used to change the "channel
parameter" value of the block which should be connected to another transducer output value.
3.5.4 Profile specific GSD file: PA139742.GSD
The functionality of the profile specific GSD file is limited. This GSD file includes only four blocks:
Block
number
1Mass FlowAI-FBkg/s
2DensityAI-FB
3Medium TemperatureAI-FBK
4Mass TotaliserTotaliser-FBkg
The device has to be switched from full functionality to interchangeable basic configuration by
using one of both a master class 2 tool (IDENT_NUMBER_SELECTOR: Slot 0, Index 40; change
byte value to 0) or the device display menu. In the next step, the device has to be configured using
the PA139742.GSD file.
Standard configuration
Function block output value
PA139742.GSD
Ident-No. 9742
Default
unit
3
kg/m
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
21
Page 22
3 PROFIBUS PA
3.5.5 Using the display menu to distinguish the current revision of the device (PA)
Use the display to open the Fct. B3.5 or C6.8.2 of the signal converter. You will get the following
information:
• KROHNE Ident.-No. (of the assembled PROFIBUS PCB)
• Software revision (of the PROFIBUS software)
• Date of production (of the PROFIBUS device)
3.6 Signal converter MFC 300 PROFIBUS PA with MBP interface as
replacement for older signal converter MFC 050/051 PA
3.6.1 Ident.-No. supported
Ident.-No. "E801hex":
Ident.-No. "E801hex": This Ident.-No. belongs to KROHE801.GSD / YP01E801.GSD and supports
Ident.-No. "E801hex":Ident.-No. "E801hex":
a compatibility mode concerning the cyclic data transfer (cyclic measurement values and
diagnosis) if the MFC300 with PROFIBUS MBP interface will be used for replacement of an
"MFC050/051PA". It is not
are restricted to those functions supported by MFC050/051 converters. Take care to set the
"MFC300 PROFIBUS MBP interface" parameters in a way to get the same behaviour as of
"MFC050/051PA" concerning calculation of measuring values and totalizers (this has to be done
manually).
not necessary to adapt the PLC configuration. Communication functions
notnot
MFC 300
CAUTION!
This Ident.-No. will be available only if a PROFIBUS PA software version ≥3.0.0 is used.
3.6.2 Manufacturer specific GSD files (PA): KROHE801.GSD and YP01E801.GSD for the
older signal converter MFC050/051 with PROFIBUS MBP interface
The PROFIBUS signal converter with MBP Interface operating in the MFC050/051 compatibility
mode ensures operation with a PLC system with software parameters based on the
MFC050/051PA. This option is important for those customers who do not want to change the
parameters in the PLC software after having replaced the MFC050/051PA by an MFC300 with
PROFIBUS MBP interface. The existing GSD files of the MFC050/051PA ("KROHE801.GSD" or
"YP01E801.GSD") can still be used.
In this application, the compatibility mode of the MFC300 with PROFIBUS MBP interface has to
be selected (display menu D2.2.4 - Identification No. -> choose MFC050/051); some other entries
have to be performed in a next step.
In order to provide communication between "MFC300 with PROFIBUS MBP interface" and the
PLC, you may - in principle – use the GSD of the "MFC050/051PA" ("KROHE801.GSD" or
"YP01E801.GSD") and –alternatively - the GSD of the "MFC300 with PROFIBUS MBP interface"
("KR014511.GSD" or "YP014511.GSD") which performs full functionality of the "MFC300 with
PROFIBUS MBP interface".
22
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Page 23
MFC 300
PROFIBUS PA 3
INFORMATION!
The "MFC050/051 compatibility mode" is not recommended for MFC300 PROFIBUS module with
RS485 interface. The GSD file has to be exchanged because of its different timings and supported
baud rates. Nevertheless the feature is not blocked in this case because RS485 interface will
operate under the MFC050/051 conditions, too. The user has to take care about the different bus
connections.
If the GSDs of the "MFC050/051PA" ("KROHE801.GSD" or "YP01E801.GSD") are used…
• The MFC050/051PA parameter set for the PLC control software will be maintained, i.e. there
is no adaptation needed with reference to the replaced interface of the MFC300 with
PROFIBUS MBP interface.
• In this usage of the GSD the PA Profile 3.0
replacements.
• Compatibility is restricted to the PROFIBUS MS0 services. In addition the "MFC050/051
status" is provided for AI Block and Totalizer outputs if the related parameters are accessed
via acyclic MS2 services and "MFC050/051 compatibility mode" is enabled. This is to get a
unique value independent from the access mechanism.
• There is no further compatibility mode regarding the acyclic parameter access, i.e. MFC300
Device Description or DTM has to be used even if "MFC050/051 compatibility mode" is
enabled. This mode does not provide mechanical or electrical compatibility (i.e. housing size
and connector positions, measuring sensor, power consumption, etc.).
• If an MFC300 signal converter is operating in "MFC050/051 compatibility mode" its
functionality is restricted to the MFC050/051 features, e.g. there will be no possibility to
transfer more than two Totalizer Function Block outputs. MS1 services, i.e. acyclic parameter
accesses by a master class 1, are not supported in "MFC050/051 compatibility mode".
PA Profile 3.0 functionality is provided in the PLC for both
PA Profile 3.0PA Profile 3.0
If the GSD of "MFC300 with PROFIBUS MBP interface” (KR014511.GSD or
YP014511.GSD) is used…
• The MFC050/051PA parameter set for the PLC control software has to be adapted with
reference to the MFC300 PROFIBUS MPB interface.
• In this usage of the GSD the PA Profile 3.0
of the "MFC300 with PROFIBUS MBP interface" are being made available.
PA Profile 3.0 functionality is provided and all diagnostic features
PA Profile 3.0PA Profile 3.0
INFORMATION!
Even if the PROFIBUS module is operating in "MFC050/051 compatibility mode" the behaviour
might be different from MFC050/051 devices. Because of additional self-tests warnings or
failure messages may occur under conditions when MFC050/051 will not report any problem.
Unexpected status messages may occur.
There is no warranty that MFC300 PROFIBUS PA devices can replace the MFC050/051 PA device
in any case without modifications of the PLC/PCS software.
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
23
Page 24
3 PROFIBUS PA
3.6.3 Manufacturer specific GSD file: KROHE801.GSD
This GSD file is for use with standard DP/PA segment coupler if the "MFC050/051 compatibility
mode" is selected of the MFC300 PROFIBUS PA device with MBP interface.
3.6.4 Manufacturer specific GSD file: YP01E801.GSD
This GSD file is for use with the transparent DP/PA segment coupler SK2/SK3 of Pepperl&Fuchs
(up to 12 MBaud on the DP segment) and supports the same device functionality as listed before
(Manufacturer specific GSD file: KROHE801.GSD).
INFORMATION!
However, both sets of GSDs, when applied, do not
PLC.
do not provide the same level of functionality in the
do notdo not
MFC 300
24
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Page 25
MFC 300
APPLICATION PROFILE 4
4.1 Function blocks
The PROFIBUS MBP interface is based on the PROFIBUS PA Profile Version 3.0 and supports the
following blocks:
• 1 physical block.
This block contains the parameters defined in PA Profile 3.0.
• 1 transducer block for Coriolis mass flow devices.
This block provides the parameters and functions defined in PA Profile 3.0.
• 8 Analog Input (AI) function blocks.
As default: Mass Flow / Density / Medium Temperature / Volume Flow / Concentration 1 /
Concentration 2 / Concentration Mass Flow 1 / Concentration Mass Flow 2 /.
• 3 totalizer (TOT) function blocks.
As default the first and the third totalizers will totalize "Mass" and the second one will totalize
"Volume".
4.2 Data structure of function block output values
The data structure of function block outputs consists of 5 bytes: a 4 byte float value (Float Format
according IEEE Standard 754 Short Real Number) followed by a 1 byte status value. If all 11
function block outputs have been configured (see above), 55 bytes will be transmitted.
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
25
Page 26
4 APPLICATION PROFILE
4.2.2 Status value
The meanings of the status byte (unsigned integer) are described in the following tables.
QualityQuality substatusLimits
GrGrQSQSQSQSQuQu
7
6
5
4
2
2
2
00= bad
01= uncertain
10= good (Non Cascade)
11= good (Cascade) - not supported
Status = bad
QualityQuality substatusLimits
GrGrQSQSQSQSQuQu
7
6
2
000000= non-specific
000001= configuration error
000010= not connected
000011= device failure
000100= sensor failure
000101= no communication (last usable value)
000110= no communication (no usable value)
000111= out of service
5
2
2
3
2
2
4
3
2
2
MFC 300
2
1
2
2
2
0
2
2
1
0
2
2
Status = uncertain
QualityQuality substatusLimits
GrGrQSQSQSQSQuQu
7
6
5
4
3
2
1
2
2
2
2
2
2
010000= non-specific
010001= last usable value
010010= substitute-set
010011= initial value
010100= sensor conversion not accurate
010101= engineering unit violation (unit not in the valid set)
010110= sub-normal
010111= configuration error
011000= simulated value
0
2
2
26
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Page 27
MFC 300
APPLICATION PROFILE 4
Status = good (Non Cascade)
QualityQuality substatusLimits
GrGrQSQSQSQSQuQu
7
6
5
4
3
2
1
2
2
2
2
2
2
100000= ok
100001= update event
100010= active advisory alarm (priority < 8)
100011= active advisory alarm (priority > 8)
100100= unacknowledged update event
100101= unacknowledged advisory alarm
100110= unacknowledged critical alarm
101000= initiate fail safe
101001= maintenance required
Status = Limits
0
2
2
QualityQuality substatusLimits
GrGrQSQSQSQSQuQu
7
6
5
4
3
2
1
2
2
2
2
2
2
0
2
2
00= ok
01= low limited
10= high limited
11= constant
Check the first two quality bits in order to get the quality information of the measurement value:
• Good (Non Cascade):
Good (Non Cascade): function block output value is ok and can be used without restrictions
Good (Non Cascade):Good (Non Cascade):
• Good (Cascade):
Good (Cascade): will not be supported, because it is not applicable for the device
Good (Cascade):Good (Cascade):
• Uncertain:
Uncertain: function block output value can be used but the accuracy can not be guaranteed
Uncertain:Uncertain:
(e.g. function block outputs value has been frozen or A/D converter is saturated or out of
range)
• Bad:
Bad: function block output value is bad - don’t use it for process control!
Bad:Bad:
The "Quality-Substatus" and "Limit" bits will be used for further diagnostics or limit checking.
INFORMATION!
The status should be monitored because a number will be transmitted even if the status of the
measurement value is bad or uncertain. This is the only way to check the quality of the
transmitted measurement values.
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
27
Page 28
4 APPLICATION PROFILE
4.3 Diagnosis parameter
4.3.1 Diagnosis
Parameter DIAGNOSIS will contain detailed information of the device, bitwise coded. More than
one message possible at once (as below-mentioned). If MSB of byte 4 is set to 1 than more
diagnose information is available in the DIAGNOSIS_EXTENSION parameter.
The manufacturer specific parameter "DIAGNOSIS_EXTENSION" will contain bitwise coded
more detailed information of the internal status conditions and error conditions of the
PROFIBUS device.
The corresponding GSD file will contain all messages supported by this device - have a look at
the UNIT_DIAG_BIT(i) definitions.
4.3.2 DIAGNOSIS
MFC 300
Octet number
Bit number
Subparameter
10DIA_HW_ELECTRR0Hardware failure electronics
1DIA_HW_MECHR0Hardware failure mechanics
2DIA_TEMP_MOTORR0Motor temperature too high
3DIA_TEMP_ELECTRR0Electronic temperature too high
4DIA_MEM_CHKSUMR0Memory error
5DIA_MEASUREMENTR0Failure in Measurement / Sensor
6DIA_NOT_INITR0Device not initialized (no selfcalibration)
Set to 1 if the Ident_Number of the running cyclic
data transfer and the value of physical block
IDENT_NUMBER_SELECTOR parameter are
different
28
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Page 29
MFC 300
APPLICATION PROFILE 4
Octet number
Bit number
Subparameter
30Reserved0Reserved for use by PNO
1Reserved0Reserved for use by PNO
2Reserved0Reserved for use by PNO
3Reserved0Reserved for use by PNO
4Reserved0Reserved for use by PNO
5Reserved0Reserved for use by PNO
6Reserved0Reserved for use by PNO
7Reserved0Reserved for use by PNO
40Reserved0Reserved for use by PNO
1Reserved0Reserved for use by PNO
2Reserved0Reserved for use by PNO
3Reserved0Reserved for use by PNO
4Reserved0Reserved for use by PNO
5Reserved0Reserved for use by PNO
6Reserved0Reserved for use by PNO
7EXTENSION_AVAILABLE0Extension available:
Indication type
Default value
Description
More diagnose information available in the
Diagnosis_Extension parameter (if available)
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
29
Page 30
4 APPLICATION PROFILE
4.3.3 DIAGNOSIS_EXTENSION
Octet number
Bit number
Subparameter
10F - Device Error
20IO 2IO2 error - general info
30Reserved
40S - Sensor Signal ErrorDrive signal is switched off due to sensor signals
F - Device ErrorFatal device error - general info
F - Device ErrorF - Device Error
1F - Application ErrorFatal application error - general info
2S - Out Of SpecificationUncertain Measurement - general info
3C - Checks In ProgressTest function activated - general info
4Parameter (DM)Parameter error - general info
5DisplayDisplay error - general info
6Sensor Electronic (ADC)Sensor error - general info
7IO 1IO1 error - general info
1Output AOutput A (Puls / Current) error - general info
2Output BOutput B (Puls / Current) error - general info
3FieldbusFieldbus module error - general info
4F - No Device CommunicationInternal Communication failure
5F - Parameter Update Error
F - Parameter Update ErrorParameter requested not available
F - Parameter Update ErrorF - Parameter Update Error
6I - Power FailDevice has been powered up
7I - Write Cycles OverflowToo much write cycles occured
1F - Sensor Exceeding LimitMass flow is greater than max. flowrate
2F - Tube Not OscillatingMeasurement tube is not oscillating
3F - System ControlSystem control generated an application error
4F - Stop ModeSensor is switched off
5F - SE System ErrorSensor error
6F - SE Comms. FailureCommunication error with sensor electronics
7Reserved
1S - Excessive Noise(for future use only)
2S - External Vibration(for future use only)
3S - Sensor LevelsOscillation amplitude of sensor A or sensor B to low
4S - Temperature Drift(for future use only)
5S - Tube Asymmetry(for future use only)
6S - System controlSystem control caused "out of spec" flag
7S - SE PCB TemperatureTemperature on SE PCB is exceeding maximum limit
MFC 300
Comment*
30
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Page 31
MFC 300
APPLICATION PROFILE 4
Octet number
Bit number
Subparameter
50S - Tube TemperatureTemperature is exceeding limits
1S - DensityProcess density is over range
2S - StartupThe device is in startup mode
3S - Power FailDevice has been powered up
4S - Resistor Circuit DefectiveTemperature and strain measurement defective
5S - SE Defective"Operational fault in sensor electronics"
6S - 2 Phase Flow2 phase signal is above the programmed threshold
7S - Density Calib. FailedDensity calibration failed
60S - BE PCB TemperatureTemperature on BE PCB is exceeding maximum limit
1S - Interface PCB FaultError detected during self-monitoring of interface card
2Reserved
3Reserved
4Reserved
5Reserved
6C - Zero CalibrationZero calibration performed
7C - Standby ModeDevice is in standby mode
Comment*
*: for a more detailed description of the above-mentioned subparameters please check the
signal converter handbook (section: Status messages and diagnostic information)
(F): Device Error
(F): Device Error
(F): Device Error(F): Device Error
(F): Application Error
(S): Uncertain measurement / measurement out of specification
(C): Simulation of the measured value
(I): Information
4.3.4 Mapping of DIAGNOSIS_EXTENSION bits into DIAGNOSIS bits
How to read this table:
If e.g. an S - Temperature Drift error has been detected the below-mentioned
DIAGNOSIS_EXTENSION bits will be set:
• DIAGNOSIS_EXTENSION (Octet 1 / Bit 2): S - Out Of Specification
• DIAGNOSIS_EXTENSION (Octet 4 / Bit 4): S - Temperature Drift
These bits will be mapped to the below-mentioned DIAGNOSIS bits (which will be set
additionally):
• DIAGNOSIS (Octet 2 / Bit 5): DIA_MAINTENANCE
• DIAGNOSIS (Octet 4 / Bit 7): EXTENSION_AVAILABLE
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
31
Page 32
4 APPLICATION PROFILE
MFC 300
DIAGNOSIS_EXTENSIONDIAGNOSIS
123 ... 4
01234567012345670 ... 6 7
Octet number
Bit number
Subparameter
1 0 FFFF - Device ErrorXXXXX
1 F - Application ErrorXX
2 S - Out Of SpecificationXX
3 C - Checks In ProgressX
4 Parameter (DM)X
5 DisplayX
6 Sensor Electronic (ADC)X
7 IO 1X
2 0 IO 2X
1 Output AX
2 Output BX
3 FieldbusX
4 F - No Device
Communication
5 FFFF - Parameter Update ErrorXX
6 I - Power FailX
7 I - Write Cycles OverflowXX
3 0 Reserved
1 F - Sensor Exceeding LimitXX
2 F - Tube Not OscillatingXX
3 F - System ControlXX
4 F - Stop ModeXX
5 F - SE System ErrorXX
6 F - SE Comms. FailureXX
7 Reserved
DIA_HW_ELECTR
DIA_HW_MECH
DIA_TEMP_MOTOR
DIA_TEMP_ELECTR
DIA_MEM_CHKSUM
DIA_MEASUREMENT
DIA_NOT_INIT
DIA_INIT_ERR
DIA_ZERO_ERR
DIA_SUPPLY
DIA_CONF_INVAL
DIA_WARMSTART
DIA_COLDSTART
DIA_MAINTENANCE
DIA_CHARACT
IDENT_NUMBER_Violation
Reserved
...
XX
Reserved
EXTENSION_AVAILABLE
32
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Page 33
MFC 300
APPLICATION PROFILE 4
DIAGNOSIS_EXTENSIONDIAGNOSIS
123 ... 4
01234567012345670 ... 6 7
Octet number
Bit number
Subparameter
4 0 S - Sensor Signal ErrorXX
1 S - Excessive NoiseXX
2 S - External VibrationXX
3 S - Sensor LevelsXX
4 S - Temperature DriftXX
5 S - Tube AsymmetryXX
6 S - System controlXX
7 S - SE PCB TemperatureXX
5 0 S - Tube TemperatureXX
1 S - DensityXX
2 S - StartupXX
3 S - Power FailXX
4 S - Resistor Circuit DefectiveXX
5 S - SE DefectiveXX
6 S - 2 Phase FlowXX
7 S - Density Calib. FailedXX
6 0 S - BE PCB TemperatureXX
1 S - Interface PCB FaultXX
2 Reserved
3 Reserved
4 Reserved
5 Reserved
6 C - Zero CalibrationX
7 C - Standby ModeX
DIA_HW_ELECTR
DIA_HW_MECH
DIA_TEMP_MOTOR
DIA_TEMP_ELECTR
DIA_MEM_CHKSUM
DIA_MEASUREMENT
DIA_NOT_INIT
DIA_INIT_ERR
DIA_ZERO_ERR
DIA_SUPPLY
DIA_CONF_INVAL
DIA_WARMSTART
DIA_COLDSTART
DIA_MAINTENANCE
DIA_CHARACT
IDENT_NUMBER_Violation
Reserved
...
Reserved
EXTENSION_AVAILABLE
X :Ext_Diag (Bit 3 of Station_Status_1) will be set too!
X :Corresponding DIAGNOSIS bits is set to 1 if status occured
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
33
Page 34
5 PROFIBUS SETTINGS
MFC 300
Detailed description of special settings concerning the PROFIBUS features easily operated via
the local display menu of the signal converter (refer to the following sections). For a detailed
description of the menus and functions in general please refer to the standard product
documentation of the signal converter.
5.1 Menu A, Quick Setup
No.FunctionSettings / descriptions
A2 Tag
A2TagTag descriptor of the physical block of the PROFIBUS module will be
A3 Reset
A3Reset-
A3.1Reset ErrorsThis menu function can be used to reset all errors that are not removed
The following reset menus for the totaliser are only available, if the quick access has been activated in the menu "Setup
> Device > Quick Setup". Each totaliser can be activated for quick access independently.
A3.2FB4 totaliser 1For PROFIBUS devices: The totaliser can be reset to zero in this menu.
A3.3FB5 totaliser 2
A3.4FB6 totaliser 3
displayed. The Tag descriptor provides an application specific reference to
the blocks. It will be assigned by the user of the device. The Tag descriptor is
an octet string (a visible string will be preferred) consisting of 32 byte. The
first 21 characters will be displayed only!
automatically (power fail, totaliser overflow)
Reset? Select: no / yes
No: Exit the function.
Yes: Resets the errors and exits the function.
A4 Station Address
A4Station AddressSelects the address of the device at the PROFIBUS interface.
The PROFIBUS address can also be changed using the PROFIBUS service
"set_slave_add". The input range is 0...125 according to the PROFIBUS
specification. Address 126 is the default address and cannot be set via the
PROFIBUS service "set_slave_add" - use menu instead to reset to default
address.
5.2 Menu B, Test
No.FunctionSettings / descriptions
B3 Information
B3.5PROFIBUSAvailable if there is a PROFIBUS interface in existence; displays the
following mentioned information about the PROFIBUS interface:
Ident No. / software revision no. of the PROFIBUS software / production date
34
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Page 35
MFC 300
PROFIBUS SETTINGS 5
5.3 Menu C, Setup
No.FunctionSettings / descriptions
C4 I/O Totaliser
C4.1FB4 Totaliser 1Set function of Totaliser _
C4.2FB5 Totaliser 2
C4.3FB6 Totaliser 3
C4._.1Totaliser FunctionSelect:
C4._.2MeasurementSelect:
C4._.3Preset ValuePredefines a threshold (using high low limit value of the totaliser affected;
C4._.4Reset TotaliserThe current value of the totaliser can be set to zero.
C4._.5Error Behaviour Defines the behaviour of this function block in case of errors.
C4._.6InformationSerial no. of the I/O board, software version no. and production date of the
_ stands for 1, 2, 3 (= Totaliser 1, 2, 3)
Absolute Total (counts positive and negative values) /
Incremental Total (counts only the positive values) /
Decremental Total (counts only the negative values) /
Stop Totaliser (totaliser is stopped, no counting) /
All As Positive (neg. input will be multiplied with -1.0) /
All As Negative (pos. values will be multiplied with 1.0)
Volume Flow / Mass Flow / Contentration Total 1 / Contentration Total 2 /
Conc. volume flow 1 / Conc. volume flow 2
the THRESHOLD bit will be set in the long status information bytes of the
interface if the actual value of the totaliser is outside these limits. This can
be also used for a status output.
Select: No / Yes (reset totaliser 1…3)
Select: hold meas. value / ignore error / stop totaliser
hold meas. value:
hold meas. value: Totalization is continued based on the last incoming value
hold meas. value:hold meas. value:
with good status before the first occurrence of bad status.
ignore error:
ignore error: Totalization is continued using the input values despite the bad
ignore error:ignore error:
status. The status is ignored.
stop totaliser:
stop totaliser: Totalization is stopped during occurrence of bad status of
stop totaliser:stop totaliser:
incoming values.
circuit board will be displayed
C5 I/O PROFIBUS
C5I/O PROFIBUSUsing the menu functions mentioned below you will be able to control
C5.1FB1 Analog Inp.There are 8 analog input blocks.
C5.2FB2 Analog Inp.
C5.3FB3 Analog Inp.
C5.4FB7 Analog Inp.
C5.5FB8 Analog Inp.
C5.6FB9 Analog Inp.
C5.7FB10 Analog Inp.
C5.8FB11 Analog Inp.
C5._.1MeasurementSelect measurement for the analog input blocks:
basically the five analog input blocks of this PROFIBUS device. These eights
menus are identical so they are grouped together and their functions are
described in one go.
displayed. The Tag descriptor provides an application specific reference to
the blocks. It will be assigned by the user of the device. The Tag descriptor is
an octet string (a visible string will be preferred) consisting of 32 byte. The
first 21 characters will be displayed only!
Select: one line / two lines / three lines
Select: Volume Flow / Mass Flow / Temperature / Density / Flow Velocity /
Diagnosis 1 / Diagnosis 2 / Diagnosis 3 / Concentration 1 / Concentration
Flow 1
For PROFIBUS devices this page shows only the PROFIBUS values
FB1…FB8.
Select the measurement of the 1st, 2nd and 3rd line:
FB1 Analog inp. 1 / FB2 Analog inp. 2 / FB3 Analog inp. 3 / FB4 Totaliser 1 /
FB5 Totaliser 2 / FB6 Totaliser 3 / FB7 Analog inp. 4 / FB8 Analog inp. 5 /
FB9 Analog inp. 6 / FB10 Analog inp. 7 / FB11 Analog inp. 8
Fixed number of digits after the decimal point or automatic, where the
number of digits is automatically adjusted to the available space.
automatically (power fail, totalizer overflow)
reset? Select: no / yes
Select: break (exit function without saving) / backup 1 (save in storage
location 1) / backup 2 (save in storage location 2)
Query: continue copy? (cannot be undone)
Select: no (exit function without saving) / yes (copy current settings to
storage backup 1 or backup 2)
36
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Page 37
MFC 300
No.FunctionSettings / descriptions
PROFIBUS SETTINGS 5
C6.6.3Load SettingsLoad saved settings.
C6.8Physical BlockThis menu is only available, if a PROFIBUS interface is present.
C6.8.1Station AddressSelects the PROFIBUS station address of the device.
C6.8.2InformationAvailable if there is a PROFIBUS interface in existence; displays the
C6.8.3Diag. extensionContent of the PROFIBUS diagnosis extension is displayed.
C6.8.4Diag. extension 2Content of the additional diagnosis stored is displayed.
C6.8.5Diag. extension iContent of the internal diagnosis stored is displayed.
C6.8.6Diag. extension hh = history
C6.9Quick SetupActivate quick access in quick setup menu; default setting: quick setup is
C6.9.1Reset Totaliser 1The reset can be activated in the "Quick Setup" to get a quick access of the
C6.9.2Reset Totaliser 2
C6.9.3Reset Totaliser 3
Select: break (exit function without loading) / factory settings (load in state
as delivered) / backup 1 (load data from storage location 1) / backup 2 (load
data from storage location 2) / load sensor data (factory settings of
calibration data)
Query: continue copy? (cannot be undone)
Select: no (exit the function without saving) / yes (load data from the selected
storage location)
The PROFIBUS address can also be changed using the PROFIBUS service
"set_slave_add". The input range is 0...125 according to the PROFIBUS
specification. Address 126 is the default address and cannot be set via the
PROFIBUS service "set_slave_add" - use menu instead to reset to default
address.
following mentioned information about the PROFIBUS interface:
Ident No. / software revision no. of the PROFIBUS software / production date
Content of the PROFIBUS diagnosis extension is displayed.
Shows diagnosis information of all diagnosis bits, which are set again since
the last delete.
active (yes)
Select: yes (switched on) / no (switched off)
function.
Select: yes (activated) / no (switched off)
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
37
Page 38
5 PROFIBUS SETTINGS
MFC 300
5.4 Menu D, Service
This menu is protected. You will need to use the service password to gain access.
No.FunctionSettings / descriptions
D2In this menu all functions related to different data sets can be found.
D2.2Service Parameters
D2.2.1Cold StartResetting of the signal converter can be done here but all changes up to this
D2.2.2Save Factory DataCopies the actual data into the factory setting; this overwrites the factory
D2.2.4Identification No.Sets different device modes for the cyclic communication of the PROFIBUS
D2.2.5PB Cold StartInitiates a PROFIBUS cold start.
D2.2.7Diag. extension hh = history
point are automatically stored and cannot be discarded.
Select: no (terminates the function) / yes (performs the reset and leaves the
setting mode)
settings done during calibration!
Query: save settings? (cannot be undone)
Select: break (exit function without saving) / factory settings (saves the
settings as factory settings)
Query: continue copy? (cannot be undone)
Select: no (exit function without saving) / yes (copy current settings to the
selected storage location)
interface.
Select: signal converter (the normal settings incl. all manufacturer specific
parameters are supported) / profile (uses only the profile defined functions,
no extras, only profile specific parameters are supported) / MFC050/051
(compatibility mode)
During a PROFIBUS cold start nearly all parameter values of the whole
device will be set to their default values (Exceptions are the PROFIBUS
address and the identification No.). The cold start will be carried out without
disconnecting an already established connection to a PROFIBUS master
system.
Query: reset? (to default values) = cold start begins
Select: no (terminates the function) / yes (PROFIBUS cold start will be
carried out at once; the setting mode is terminated)
Delete the stored history.
Query: reset? = reset history to 0)
Select: no (no change) / yes (all saved data are deleted)
38
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Page 39
MFC 300
NOTES 6
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en