4.3.4 Mapping of DIAGNOSIS_EXTENSION bits into DIAGNOSIS bits........................................... 31
2
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
MFC 300
CONTENTS
5 Profibus settings34
5.1 Menu A, Quick Setup ...................................................................................................... 34
5.2 Menu B, Test................................................................................................................... 34
5.3 Menu C, Setup................................................................................................................. 35
5.4 Menu D, Service.............................................................................................................. 38
6 Notes39
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
3
1 SAFETY INSTRUCTIONS
1.1 Scope of the document
These instructions are supplementary to the signal converter Handbook. For all other data, use
the relevant chapters of the Handbook. If you do not have this document, please contact the
nearest office or download them from the manufacturer's internet site.
INFORMATION!
The information in this chapter only contains the data applicable to PROFIBUS communication.
The technical data in the Handbook shall be valid in its current version, provided that it is not
rendered invalid or replaced by this supplement.
1.2 Scope of delivery
The information in this chapter only contains the data applicable to PROFIBUS communication.
The technical data in the Handbook shall be valid in its current version, provided that it is not
rendered invalid or replaced by this supplement.
A device for PROFIBUS communication is supplied with:
MFC 300
• Supplementary instructions for PROFIBUS communication
• PROFIBUS device data files (GSD) which can be also downloaded from the manufacturer's
internet site
1.3 Special notes
Don't switch off (power off) the signal converter immediately after manual change of parameter
values:
• Please wait approx. 10 seconds before you switch off the signal converter after you have done
both a parameter download via PROFIBUS or a manual change of a parameter value via the
local display.
CAUTION!
Please wait approx. 15 seconds before you switch off the signal converter after you have carried
out a "Factory Reset" (PROFIBUS "Coldstart") via PROFIBUS or local display.
"Deactivation of the Service Parameter Lock" of the signal converter via PROFIBUS:
• After writing down the service password (via PROFIBUS) the "Deactivation of the Service
Parameter Lock" will last at least 20 minutes if the internal password timer of the signal
converter won't be retriggered by writing this password again. The "Deactivation of the
Service Parameter Lock" will be terminated at once by a PROFIBUS Coldstart / Warmstart or
if the internal password timer of the signal converter elapsed.
4
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
MFC 300
2.1 Software history
Issued Signal converterApplication programSystem integration
PROFIBUS DP 2
Mth./
Hardware FirmwareHardwareSoftwareDriverVersionModel name
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
5
2 PROFIBUS DP
2.2 System configuration of PROFIBUS DP network
The following diagram shows a typical network configuration with PROFIBUS devices with RS485
interface in a non-hazardous environment. The PROFIBUS devices with RS485 interface do not
need any segment coupler. They are connected directly to the PROFIBUS DP network.
MFC 300
Figure 2-1: PROFIBUS DP network
1 SPS
2 PROFIBUS DP network with max. 12 Mbit/s
3 Signal converter
4 Other devices with PROFIBUS RS485 interface
6
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
MFC 300
2.3 Electrical connection for DP signal converter
INFORMATION!
For a detailed description of the electrical connections please refer to the standard signal
converter handbook.
Signal converter terminalsBB-CC-DD-
PROFIBUS designationT+B-A-T+B-A
123456
1Termination positive
2TxD+/RxD+ second connection
3TxD-/RxD- second connection
4Termination negative
5TxD+/RxD+ first connection
6TxD-/RxD- first connection
PROFIBUS DP 2
External connection with spur
CAUTION!
Spurs are not allowed at high data rates!
I = 110 nH
R1 = 390 Ω
R2 = 220 Ω
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
7
2 PROFIBUS DP
External connection at last device with active internal bus termination
I = 110 nH
R1 = 390 Ω
R2 = 220 Ω
MFC 300
External connection to a trunk
1 e.g. incoming data lines
2 e.g. outgoing data lines
I = 110 nH
R1 = 390 Ω
R2 = 220 Ω
8
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
MFC 300
2.4 Technical data
Hardware
TypePROFIBUS RS485 interface according to IEC 61158-2
ConnectionDependent of polarity; please note at electrical connection!
Software
GSDGSD file on CD-ROM or from internet site
Device profilePA Profile compact class B, V 3.0
Address range0…126 (default 126)
Local controlLocal display and operator interface at device
SAPs2 x MS1 SAPs – acyclic interface to PLC
Function blocks1 x TB = Transducer Block: contains the parameters and functions
PROFIBUS DP 2
0…125 via PROFIBUS service set_slave_add
0…126 via local display
126 via factory_reset = 2712
3 x MS2 SAPs – the number of MS2 Service Access Points is typically
equal to the maximum number of master class 2 tools
defined in PA Profile 3.0
1 x PB = Physical Block: contains the parameters defined in PA
Profile 3.0
8 x AI = Analog Input Blocks: contains the parameters defined in PA
Profile 3.0
3 x TOT = Totalizer Function Blocks: contains the parameters defined
in PA Profile 3.0
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
9
2 PROFIBUS DP
2.5 GSD files for the data transfer
A PROFIBUS GSD ZIP file (e.g. GSD-31777815.zip; including both all GSD files and additional data
files) you can get on a CD ROM or can be downloaded from the internet. The GSD file contains
information that will be needed for project planning of the PROFIBUS communication network.
The relevant data files (e.g. _ _ _ _ .bmp / _ _ _ _ .dib) must be loaded into the bus configuration
system/master system before start-up of the bus system.
2.5.1 Cyclic data exchange
During network configuration the user has to define which function block outputs of the signal
converter should be transferred cyclically to the master. Network configuration will be done
using one of the GSD files described before. The order of transmission of a function block always
remains the same even if a function block is defined as an "Empty" block (if so, no function block
output data will be sent to the master and all function block outputs following the empty block
output data will be sent to the master and all function block outputs following the empty block
output data will be sent to the master and all function block outputs following the empty block output data will be sent to the master and all function block outputs following the empty block
will move up one position)
will move up one position).
will move up one position)will move up one position)
2.5.2 Baud rate
MFC 300
(if so, no function block
(if so, no function block (if so, no function block
Supported baud rates are listed in the GSD file. After power-on or PROFIBUS timeout a baud rate
search is active to detect the current transfer speed on the bus. It is not necessary to set the
baud rate manually.
If the data transmission rate is changed during operation the baud rate search will not be started
by the device. A new power-up or a manual interruption of the PROFIBUS communication is
required to activate the baud rate search in this case.
2.5.3 Ident.-No. supported
The signal converter with PROFIBUS RS485 interface is based on PROFIBUS PA Profile V 3.0. The
device supports two Ident-No.:
• Ident-No. "4510hex" belongs to the GSD file KR014510.GSD and includes the complete
functionality of the Coriolis mass flowmeter.
• The application of the manufacturer independent Ident-No. "9742hex" (GSD file
"PA039742.GSD") provides interchangeability of devices, i.e. an exchange of Coriolis mass
flowmeters of different vendors.
Please follow the instructions in the manual of the host supplier when installing the GSD File you
need and the additional files (_ _ _ _ .bmp and _ _ _ _ .dib) into the PLC.
INFORMATION!
If separated by the bus configuration system the device entry of the PROFIBUS RS485 interface
with PA Profile 3.0 will be located within the slave family PROFIBUS PA.
10
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
MFC 300
2.5.4 Manufacturer specific GSD files: KR014510.GSD
The manufacturer delivers the GSD files with the entire device functionality, which is listed as
follows:
PROFIBUS DP 2
Block
number
Default configuration
Function block output: value and
KR014510.GSD
Ident-No. 4510
Default
unit
status
1Mass FlowAI-FBkg/s
2DensityAI-FB
3Medium TemperatureAI-FBK
4Mass TotaliserTotaliser-FBkg
5Volume TotaliserTotaliser-FB
6Mass TotaliserTotaliser-FBkg
7Volume FlowAI-FB
8Concentration 1AI-FB%
9Concentration 2AI-FB%
10Concentration Mass Flow 1AI-FBkg/s
11Concentration Mass Flow 2AI-FBkg/s
kg/m
3
m
m3/h
3
• AI: Analog Input Function Block
• FB: Function Block
There are separate settings to select the units for local display and PROFIBUS. Modifications of
the units of the display will have no effect on the data transferred via PROFIBUS.
A master class 2 tool is required to modify the units for PROFIBUS transfer.
INFORMATION!
During network configuration the user has to define which function block outputs of the signal
converter should be transferred cyclically to the master. This is performed by a bus
configuration tool (e.g. "HW- Config" for PC-S7 from Siemens). This tool offers specific functions
as follows:
1. It is possible to configure an "Empty" block (the code of an "Empty" block is defined as 0x00) on
each block number. This implies: no data are transmitted in the cyclic data telegram for this
block.
2. There is NO "Totaliser (TOT)" function block allowed on block position 1, 2, 3, 7, 8, 9, 10 and 11!
On these positions, only an "Analog Input (AI)" function block or an "Empty" block is allowed!
–
(Note: All codes supported by "Analog Input (AI)" - and "Totaliser (TOT)"
function blocks will
be found in the corresponding GSD files.)
3. There is NO "Analog Input (AI)" function block allowed on block position 4, 5 and 6! On these
positions, only a "Totaliser (TOT)" function block or an "Empty" block is allowed!
4. There is a choice of 7 different totaliser functions, which can be allocated to the blocks 4, 5
and/or 6.
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
11
2 PROFIBUS DP
Definition of totaliser functions
Totalcyclic transfer of the totaliser value with status to the master
SetTot + Totalcyclic transfer of the totaliser value with status to the master + cyclic
ModeTot + Totalcyclic transfer of the totaliser value with status to the master + cyclic
SetTot + ModeTot + Totalcyclic transfer of the totaliser value with status to the master + cyclic
SetTotcyclic control data from master to the device via the parameter
ModeTotcyclic control data from master to the device via the parameter
SetTot + ModeTotcyclic control data from master to the device via the parameters
Both, the Byte SetTot and ModeTot are cyclically sent from the master to the device if these bytes
are inserted as output data via the PLC configurator. The meaning of these control bytes are as
follows:
MFC 300
control data from master to the device via the parameter SetTot
control data from master to the device via the parameter ModeTot
control data from master to the device via the parameters SetTot and
ModeTot (in the given order)
SetTot
ModeTot
SetTot and ModeTot (in the given order)
Function of control bytes
SetTot
SetTot
SetTotSetTot
SetTot = 0Totaliser is totalising.
SetTot = 1Totaliser will be reset to 0 and stays at 0 until SetTot is switched back
SetTot = 2Totaliser is set to the value defined by PresetTot. PresetTot can be
SetTot > 2Not allowed. Value is ignored; totaliser remains in its last valid
ModeTot
ModeTot
ModeTotModeTot
ModeTot = 0Totaliser totalises positive and negative values.
ModeTot = 1Totalises only positive values.
ModeTot = 2Totalises only negative values.
ModeTot = 3Totaliser is stopped, no totalisation will be done.
ModeTot = 248Totalises all values as positive, negative values will be multiplied with
ModeTot = 249Totalises all values as negative, positive values will be multiplied with
again to 0. If the value of SetTot changes from "1" to "0" the totaliser
starts counting from 0.
written via an acyclic master (totaliser in block 4 = Slot 4 Index 32;
totaliser in block 5 = Slot 5 Index 32; totaliser in block 6 = Slot 6 Index
32). If the value of SetTot changes from "2" to "0" the totaliser starts
counting from the current value defined by PresetTot.
setting.
-1.0.
-1.0.
12
All other values of ModeTot not allowed. Value is ignored; totaliser remains in its last valid
setting.
The standard block configuration may be changed by the customer but using the default settings
is highly recommended. If the standard block configuration should be changed by the customer
an acyclic master tool or the device display menu must be used to change the "channel
parameter" value of the block which should be connected to another transducer output value.
www.krohne.com07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.