• Large, clear display with backlight shows the current
and set temperature and time—even in the dark.
• Touchscreen interaction
• Real-time clock keeps time during power failures and
automatically updates to daylight savings.
• Change/check reminders let you know when to service
or replace filters.
• Various Hold options allow you to override the
program schedule, as desired.
• Controls humidification to increase homeowner
comfort while protecting woodwork and furnishings.
• Controls dehumidification using air conditioner with
high or low speed fan or a whole house dehumidifier.
• Controls ventilation with other HRV, ERV, or Freshair
damper. Vent on demand and automatically using
patented advanced ventilation control.
APPLICATION
• Advanced heat pump control featuring balance point
plus 2°F droop to increase homeowner comfort.
PRODUCT DATA
The VisionPRO® IAQ Total Home Comfort System features an
effortless, 7-Day programmable touchscreen thermostat that
provides control of temperature, humidification,
dehumidification, and ventilation.
Heating: 40°F to 90°F(4.5°C to 32°C).
Cooling: 50°F to 99°F (10°C to 37°C).
Operating Ambient Temperature:
VisionPRO
®
IAQ Thermostats: 0°F to 120°F
(-18°C to 49°C).
THM5421C1008: -30°F to 150°F (-34°C to 66°C).
C7089U1006: -40°F to 120°F (-40°C to 49°C).
C7189U1005: 45°F to 88°F (7°C to 32°C).
Shipping Temperature:
VisionPRO
®
IAQ Thermostats: -30°F to 150°F
(-34°C to 66°C).
THM5421C1008: -30°F to 150°F (-34°C to 66°C).
Operating Relative Humidity (Non-condensing):
VisionPRO
®
IAQ Thermostats: 5% to 90%.
THM5421C1008: 5% to 90%.
C7089U1006: 5% to 95%.
C7189U1005: 5% to 95%.
Humidification Setting Range:
Heating: 10% to 60% RH.
Dehumidification Setting Range:
Heating: 40% to 80% RH.
Humidity Display Range:
0% to 99%.
Finish:
VisionPRO
THM5421C1008: Premier White
C7189U1005 Wall Mount Remote Indoor Sensor: Premier
White
®
IAQ Thermostats: Premier White® color.
®
color.
®
color.
Clock Accuracy: +/- 1 minute per year.
Resistance Characteristics of Remote Sensors:
C7089U1006 Outdoor Sensor: Negative temperature coeffi-
cient (NTC) means that resistance decreases as the temperature increases. See Table 12 in the Operation section
for sensor resistance characteristics.
C7189U1005 Remote Indoor Sensor: Negative temperature
coefficient (NTC), means that resistance decreases as the
temperature increases. See Table 13 in the Operation section for sensor resistance characteristics.
Cool Indication:
VisionPRO
®
IAQ Comfort Systems show “Cool On” on the
thermostat screen when Cool is activated.
Heat Indication:
VisionPRO
®
IAQ Comfort Systems show “Heat On” on the
thermostat screen when Heat is activated.
Auxiliary Heat Indication:
VisionPRO
®
IAQ Comfort Systems show “Aux. Heat On” on
the thermostat screen when Auxiliary Heat is activated.
Calibration:
C7089U1006, C7189U1005 and VisionPRO® IAQ Comfort Sys-
tems are factory-calibrated and require no field calibration.
Interstage Differential:
VisionPRO
®
IAQ Comfort Systems operate with droopless
control. Once the thermostat senses that 1st stage is running at 90% capacity, the thermostat energizes 2nd stage.
Mounting Means:
VisionPRO
®
IAQ Comfort System: Thermostat mounts directly
on the wall in the living space using mounting screws and
anchors provided. Fits a vertical or horizontal 2 x 4 in. junction box.
THM5421C1008 Equipment Interface Module (EIM) mounts on
HVAC equipment or on a wall in the equipment room.
C7089U1006 Outdoor Sensor: Mounts outside of living space
with mounting clip and screws provided.
C7189U1005 Remote Indoor Sensor: Mounts directly on the
wall using mounting screws and anchors provided.
Cover Plate:
32003796-001 Cover Plate is used to cover marks left on the
wall by the old thermostat.
Dimensions:
VisionPRO
®
IAQ Comfort System: see Fig. 1.
THM5421C1008: see Fig. 2
C7089U1006 Outdoor Sensor Mounting Clip: see Fig. 3.
32003796-001 Cover Plate: see Fig. 4.
C7189U1005 Remote Indoor Sensor: see Fig. 5.
Cycle Rates (at 50% Load):
Heating: Selectable 1 - 12 cycles per hour.
Cooling: Selectable 1 - 6 cycles per hour.
68-0287—12
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
WALLPLATE
3-3/8 (86)
THERMOSTAT
6 (152)
3-3/8 (86)
THERMOSTAT
AND WALLPLATE
4-9/16
(116)
1-3/8 (35)
M23539
1-1/2 (38)
M4488
Fig. 3. C7089U1006 Outdoor Sensor Mounting Clip
dimensions in in. (mm).
7-7/8 (200)
3-5/16 (84)
5-1/2
(140)
3-5/16
(84)
Fig. 1. VisionPRO® IAQ Comfort System
dimensions in in. (mm).
7-9/32
(185)
6-57/64
(175)
4-35/64
(116)
FRONT VIEWSIDE VIEW
1-21/64
(34)
M22139
Fig. 4. 32003796-001 Cover Plate dimensions in in. (mm).
M23544
Fig. 2. THM5421C1008 Equipment Interface Module
dimensions in in. (mm).
368-0287—1
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
2-9/32
(58)
1-1/2 (38)
M23522
FRONT VIEWSIDE VIEWFRONT VIEW (COVER OFF)
Fig. 5. C7189U1005 Remote Indoor Sensor dimensions in in. (mm).
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow the
instructions can damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions to make sure
the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After completing installation, use these instructions to
verify the product operation.
Selecting Location
Install the thermostat about 5 ft. (1.5m) above the floor in an area
with good air circulation at average temperature. See Fig. 6.
2-9/32
(58)
45/64
(18)
1-1/2 (38)
Do not install the thermostat where it can be affected by:
— Drafts or dead spots behind doors and in corners.
— Hot or cold air from ducts.
— Radiant heat from sun or appliances.
— Concealed pipes and chimneys.
— Unheated (uncooled) areas such as an outside wall behind
the thermostat.
Installing Wallplate
CAUTION
Electrical Hazard.
Can cause electrical shock or equipment damage.
Disconnect power before wiring.
The thermostat can be mounted horizontally on the wall or on a
4 in. x 2 in. (101.6 mm x 50.8 mm) wiring box.
NO
M19925
NO
NO
YES
5 FEET
[1.5 METERS]
Fig. 6. Selecting thermostat location.
68-0287—14
1. Position and level the wallplate (for appearance only).
2. Use a pencil to mark the mounting holes.
3. Remove the wallplate from the wall and, if drywall, drill
two 3/16-in. holes in the wall, as marked. For firmer
material such as plaster, drill two 7/32-in. holes. Gently
tap anchors (provided) into the drilled holes until flush
with the wall.
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
4. Position the wallplate over the holes, pulling wires
through the wiring opening. See Fig. 7.
5. Insert the mounting screws into the holes and tighten.
WALL
WIRES THROUGH WALL
AND WIRE SLOT
WALL ANCHORS (2)
MOUNTING
HOLES
M23541
MOUNTING
SCREWS (2)
M23543
Fig. 7. Mounting wallplate.
Installing Equipment Interface Module (EIM)
NOTE: It is normal for the LED to blink continuously during
startup, and while checking equipment status (Auto
Discover mode).
WALL ANCHOR
COMMUNICATION LED
DRILL 3/16 IN. HOLES
FOR DRYWALL. DRILL
7/32 IN. HOLES FOR
PLASTER
CAUTION
Electrical Hazard.
Can cause electrical shock or equipment damage.
Disconnect power before wiring.
The EIM can be mounted vertically on the HVAC equipment or
on a wall in the equipment room.
1. Position the EIM.
2. Use a pencil to mark the mounting holes.
3. Remove the wallplate from the wall and, if drywall, drill
two 3/16-in. holes in the wall, as marked. For firmer
material such as plaster, drill two 7/32-in. holes. Gently
tap anchors (provided) into the drilled holes until flush
with the wall.
4. Position the wallplate over the holes, pulling wires
through the wiring opening.
5. Insert the mounting screws into the holes and tighten.
See Fig. 8.
Communication LED
The EIM has an LED (see Fig. 8) that communicates the EIM
status as follows.
• LED blinks rapidly: Normal information transfer.
• LED blinks once: Incoming message to EIM.
• LED blinks continuously: Wiring problem. Check wiring to
terminals 1, 2, 3.
• LED always off: Wiring problem. Check wiring to terminals
1, 2, 3.
• LED always on: EIM may need replacement.
MOUNTING SCREW
M23484
Fig. 8. Mounting EIM.
WIRING
All wiring must comply with local electrical codes and
ordinances. See Fig. 10–20.
1. Select set of terminal identifications (Table 1) that corre-
sponds with system type.
2. Loosen the screws for the appropriate system type
selected; see Table 1. See Table 2 for terminal designation descriptions. Insert wires in the terminal block under
the loosened screw. See Fig. 9.
3. Securely tighten each screw.
4. Push excess wire back into the hole.
5. Plug the hole with nonflammable insulation to prevent
drafts from affecting the thermostat.
6. See Fig. 10–20 for typical wiring hookups.
Table 1. Selecting Terminal Identifications for System Type.
Wallplate Terminal
System Type
Identifications
Standard Heat/Cool Conventional10, 11
Standard Multistage
Conventional12
up to 3 Heat/2 Cool
Heat Pump with
Heat Pump13
Auxiliary Heat
Wiring Diagram
Reference
568-0287—1
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
M23541
Fig. 9. Inserting wires in terminal block.
NOTES:
1.When used in a single-transformer system, leave
the metal jumper wires in place between R and Rc,
and Rc and Rh. If used on a two-transformer system, remove metal jumper wire between Rc and Rh.
2.If thermostat is configured for a heat pump system
in the Installer Setup, configure changeover valve
for cool (O-factory setting) or heat (B).
For wiring to a W8835 Zone panel please refer to the product
data sheet included with the panel.
Auxiliary Heat (fossil fuel or electric) (Heat
Pump)
W3/AUX2Stage 3 Heating Relay (Conventional)
Auxiliary Heat (fossil fuel or electric) (Heat
Pump)
YStage 1 Compressor Relay
Y2Stage 2 Compressor Relay
GFan Relay
LHeat Pump Equipment Monitor
OUT1/OUT2Outdoor Temperature Sensor
IN1/IN2Remote Indoor Temperature Sensor
DATS1/DATS2Discharge Air Temperature Sensor
1
1
2
3
FACTORY INSTALLED
JUMPER BETWEEN R,
RC AND RH
WIRE TO TERMINALS ON THERMOSTAT.1
1
2
3
C
R
RC
RH
COMMUNICATION LED
COMMUNICATION
TERMINALS
24 VAC
CONV. HP
O/B
W1
AUX
W2
AUX2
W3
Y
Y
Y2
Y2
G
G
M23485
Fig. 10. Typical hookup of conventional single-stage heat
and cool system with single transformer
(1H/1C conventional).
OIL PRIMARY/
AQUASTAT
WIRE TO TERMINALS ON THERMOSTAT.1
1
1
2
3
FACTORY INSTALLED JUMPER BETWEEN R,
AND RC (REMOVE FACTORY INSTALLED
JUMPER BETWEEN RC AND RH
1
2
3
C
R
RC
RH
COMMUNICATION LED
COMMUNICATION
TERMINALS
24 VAC
CONV. HP
O/B
W1
AUX
W2
AUX2
W3
Y
Y
Y2
Y2
G
G
M23486
Fig. 11. Typical hookup of conventional single-stage heat
and cool system with oil primary (1H/1C conventional).
68-0287—16
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
KEY
= NORMALLY OPEN, DRY CONTACTS
= NORMALLY CLOSED, DRY CONTACTS
M23685
1
COMMUNICATION LED
1
1
2
3
FACTORY INSTALLED
JUMPER BETWEEN R,
RC AND RH
WIRE TO TERMINALS ON THERMOSTAT.
1
2
3
C
R
RC
RH
COMMUNICATION
TERMINALS
24 VAC
CONV. HP
W1
W2
W3
Y
Y2
G
O/B
AUX
AUX2
Y
Y2
G
HEAT 1 RELAY
HEAT 2 RELAY
HEAT 3 RELAY
COOL 1 RELAY
COOL 2 RELAY
FAN RELAY
M23487
Fig. 12. Typical hookup of conventional system with up to
three-stage heat and two-stage cool with one transformer
(3H/2C, 2H/2C, 2H/1C, 1H/2C, 1H/1C conventional).
1
1
2
3
FACTORY INSTALLED
JUMPER BETWEEN R,
RC AND RH
WIRE TO TERMINALS ON THERMOSTAT.
1
1
2
3
C
R
RC
RH
COMMUNICATION LED
COMMUNICATION
TERMINALS
24 VAC
CONV. HP
W1
W2
W3
Y
Y2
G
O/B
AUX
AUX2
Y
Y2
G
CHANGEOVER
AUX 1 (HEAT 3)
AUX 2 (HEAT 4)
COMP 1
COMP 2
FAN RELAY
M23488
Fig. 13. Typical hookup of heat pump system
(up to 4H/2C heat pump).
1
2
3
C
24 VAC
R
FIELD INSTALLED
JUMPER BETWEEN
R AND HUM 1
NON-POWERED
HUMIDIFIER
RC
RH
H1
U
M2
D1
H
M2
V1
N
T2
OR
M23489
1
2
3
C
24 VAC
R
RC
RH
POWERED
HUMIDIFIER
H1
U
M2
D1
H
M2
V1
N
T2
OR
M23490
Fig. 15. Typical hookup of powered humidifier.
1
2
3
C
24 VAC
R
RC
FIELD INSTALLED
JUMPER BETWEEN
R AND DHM 1
LOW SPEED
FAN
RH
H1
U
M2
D1
H
M2
V1
N
T2
OR
M23491
Fig. 16. Typical hookup of variable speed blower for
dehumidification in low speed (contacts normally closed).
NOTE: Connect DHM2 to low-speed fan terminal on air han-
dler for dehumidification with air conditioner and a
low-speed fan.
1
2
3
C
24 VAC
R
RC
RH
H1
U
M2
POWERED
DEHUMIDIFIER
D1
H
M2
V1
N
T2
OR
M23492
Fig. 17. Typical hookup of powered whole house
dehumidifier (contacts normally open).
Fig. 14. Typical hookup of non-powered humidifier.
768-0287—1
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
1
2
3
C
24 VAC
R
FIELD INSTALLED
JUMPER BETWEEN
R AND VNT 1
NON-POWERED
VENTILATOR
RC
RH
H1
U
M2
D1
H
M2
V1
N
T2
OR
M23493
Fig. 18. Typical hookup of fresh air damper.
NOTE: Use this hookup for ventilation using a fresh air
damper.
1
2
3
C
24 VAC
R
RC
RH
H1
U
M2
D1
H
OR
M2
POWERED
VENTILATOR
V1
N
T2
M23494
Fig. 19. Typical hookup of powered ventilation.
POWER THE THERMOSTAT
• 24 Vac common wire only to EIM or zone panel.
Wiring 24 Vac Common
• Single-Transformer System—Connect the common side of
the transformer to the C screw terminal of the EIM. Leave
the metal jumper wires in place between R, Rc, and RH.
• Two-Transformer System—Connect the common side of
the cooling transformer to the C screw terminal of the EIM.
Remove the metal jumper wire between Rc and Rh.
Connect the hot side of heating transformer to Rh and leave
the jumper wire between R and Rc and connect the hot side
of cooling transformer to R or Rc.
1. Locate and remove the tab labeled, Remove, in the
lower left corner on the thermostat back. See Fig. 21.
REMOVE
TAB
INSTALLATION
REMOVE DURING
INSTALLATION
REMOVE DURING
M19920
Fig. 21. Remove tab labeled, Remove, on thermostat back
Mount Thermostat to Wallplate
1. Align the terminal screw blocks with the pins on the back
of the thermostat. Push the thermostat straight onto the
wallplate until it snaps into place. See Fig. 22.
1
2
3
C
24 VAC
R
RC
FIELD INSTALLED
JUMPER BETWEEN
DHM 1 AND VNT 1
BLUE
YELLOW
DH90
GREEN
RED
WHITE
FRESH
AIR
DAMPER
RH
H1
U
M2
D1
H
M2
V1
N
T2
OR
M23495
Fig. 20. Hookup of Honeywell DH90 with fresh air intake for
ventilation.
68-0287—18
WALLPLATE
TERMINAL
SCREW
BLOCK
Fig. 22. Mount thermostat to wallplate.
PINS ON
BACK OF
THERMOSTAT
M23542
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
Locate and Mount C7089U1006 Outdoor
Temperature Sensor (Optional)
Mount the sensor where (see Fig. 23):
• cannot tamper with settings.
• there is good air circulation.
• it can measure true outdoor ambient temperature.
• surface is flat.
• wire distance between C7089U1006 and EIM is less than
200 feet.
Do not mount the sensor:
• in direct sunlight.
• where hot or cold air blows on the sensor. Discharge line
from an outdoor compressor unit, vent or fan causes
inaccurate temperature readings.
• where snow, ice or debris can cover it.
Use the following steps to mount the sensor:
1. Remove the sensor from the mounting clip.
2. Mark the area on the location selected for mounting the
sensor mounting clip.
3. Mount the clip.
IMPORTANT
Erratic temperature readings from a sensor can occur
as a result of any of the wiring practices described
below. Avoid these practices to assure correct operation. Use shielded cable to reduce interference if
rerouting sensor wiring is not possible.
— Be sure wires have a cable separate from the thermo-
stat cable.
— Do not route temperature sensor wiring with building
power wiring, next to control contactors or near light
dimming circuits, electric motors or welding
equipment.
— Avoid poor wiring connections.
— Avoid intermittent or missing building earth ground.
CAUTION
Electrical Shock Hazard.
Can cause electrical shock or equipment damage.
Disconnect power supply before connecting wiring.
Wiring must comply with applicable codes, ordinances and
regulations:
1. Wire C7089U1006 Outdoor Sensor to OUT1and OUT2
terminals on the EIM. If leadwire provided is not long
enough (60 in.), run a cable to a hole at C7089U1006
location.
a. Using color-coded, 18-gauge thermostat wire is
recommended. For example of general wiring of
C7089U1006, see Fig. 24.
b. Pigtail wiring can be used.
2. Mount C7089U1006 in its mounting clip.
3. Plug wiring hole using nonhardening caulk or putty.
M7514
Fig. 23. Typical locations for C7089U1006 Outdoor Sensor.
Wire C7089U1006 Outdoor Sensor
CAUTION
Electrical Interference (Noise) Hazard.
Can cause erratic system operation.
Keep wiring at least one foot away from large inductive
loads such as motors, line starters, lighting ballasts and
large power distribution panels.
Use shielded cable to reduce interference when
rerouting is not possible.
1
WIRING HOLE
C7089
1
USE APPROPRIATE MOUNTING MEANS FOR THE
TYPE OF STRUCTURE.
2
PLUG WIRING HOLE WITH NON-HARDENING CAULK
OR PUTTY.
THROUGH
STRUCTURE
2
M23525
Fig. 24. Wire C7089U1006 Outdoor Sensor to the EIM.
If an outdoor temperature sensor is installed, the thermostat
displays the outside temperature in the lower right corner of the
Home Screen.
968-0287—1
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
MON
UE
THUSASUN
O
de
Se
o
SCHED
HOLD
T
Insi
AUT
SYSTEM
HEAT
AM
SCHED HOLD CLOCK SCREEN MORE
t T
Following
Schedule
Outside
M22453
If thermostat is set to Auto Changeover System mode, press
the More key until the outside temperature is shown on the
screen.
TUEWEDTHUFRISATSUN
MON
YES
NO
NO
NO
5 FEET
(1.5 METERS)
Fig. 25. Typical location for C7189U1005 Indoor Sensor.
Wire C7189U1005 Indoor Sensor
CAUTION
Electrical Interference (Noise) Hazard.
Can cause erratic system operation.
Keep wiring at least one foot away from large inductive
loads such as motors, line starters, lighting ballasts and
large power distribution panels.
M4476
Outside
SCHED
HOLD
CLOCK SCREEN
DONE
WAKE
LEAVE RETURN SLEEP CANCEL
M22448
Locate and Mount C7189U1005 Remote
Indoor Temperature Sensor (Optional)
1. Choose a location (see Fig. 25) for mounting the sensor
on an inside wall about 5 ft (1.5m) above the floor.
2. Be sure wire distance between C7189U1005 and EIM is
less than 200 feet.
3. Make sure there is good air circulation at average tem-
perature at the chosen location. Avoid the following locations because they can introduce errors in sensor
measurements. See Fig. 25.
a. Hot areas caused by:
(a)Concealed pipes or ducts.
(b)Drafts from fireplaces or other heat sources.
(c)Convection or radiant heat from the sun or
electrical equipment.
b. Cold areas caused by:
(a)Concealed pipes or ducts.
(b)Drafts from windows and doors.
(c)Unheated areas on the other side of the wall
c. Dead air areas:
4. Mark the area on the wall selected for mounting the
C7189U1005 Sensor.
5. Run wire cable to a hole at the selected wall location.
Pull approximately three inches of wire through the
opening. Color-coded, 18-gauge thermostat wire is
recommended.
location.
(a)Behind doors, furniture and curtains.
(b)In corners and alcoves.
IMPORTANT
Erratic temperature readings from a sensor can occur
as a result of any of the wiring practices described
below. Avoid these practices to assure correct
operation.
— Be sure wires have a cable separate from the thermo-
stat cable.
— Do not route temperature sensor wiring with building
power wiring, next to control contactors or near light
dimming circuits, electric motors or welding equipment.
— Avoid poor wiring connections.
— Avoid intermittent or missing building earth ground.
CAUTION
Electrical Shock Hazard.
Can cause electrical shock or equipment damage.
Disconnect power supply before connecting wiring.
Wiring must comply with applicable codes, ordinances and
regulations.
1. Wire C7189U1005 Indoor Sensor to IN1and IN2 termi-
nals on the EIM. For an example of general wiring of
C7189U1005, see Fig. 26 to wire one sensor and Fig. 27
to wire multiple sensors.
2. Push excess wire back into the hole. Plug the hole using
nonhardening caulk, putty or insulation to prevent drafts
from affecting performance.
3. Remove C7189U1005 cover.
4. Mount C7189U1005 to the wall using the screws and
anchors provided.
5. Level the C7189U1005 for appearance only. Device
functions correctly even when not level.
6. Install C7189U1005 cover.
68-0287—110
L
MO
1 OUT
2 OUT
1 IN
2 IN
C7189
M23523
Fig. 26. Wiring a single C7189U1005 Indoor Sensor.
L
1 OUT
2 OUT
1 IN
2 IN
C7189C7189
C7189C7189
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
• The thermostat will display the temperature measured at
the sensor locations (internal thermostat sensor is
disabled). Sensors must be in square numbers (e.g., 4, 9,
16, and so on) and the displayed temperature will be an
average of the temperatures measured at each location.
• The thermostat will display a 50-50 average of the
temperature measured at the thermostat location and the
average of the temperatures measured at the remote indoor
sensor locations. In this case, the thermostat sensor still
carries a 50% weighting of the displayed temperature.
Install Discharge Air Temperature Sensor
(Optional):
Prior to installing Discharge Air Temperature Sensor (DATS)
refer to the installation instructions included with the product for
more information on placement and wiring.
When using a DATS with network zoning the DATS will monitor
the duct air temperature and communicate with the thermostat
and will disable the heating and/or cooling if installer set high or
low temperature limits are reached.
L
1 OUT
2 OUT
1 IN
2 IN
C7189C7189
C7189C7189C7189
C7189C7189
C7189
C7189
M23524
Fig. 27. Wiring Multiple C7189U1005 Sensors.
If a remote indoor temperature sensor is installed, the
thermostat has several options for displaying the current indoor
temperature. This is configured in ISU 340. The thermostat can
display either the temperature measured at the thermostat
location, the sensor location, or a 50-50 average of both.
ONE REMOTE INDOOR SENSOR INSTALLED (OPTIONAL)
If one remote indoor temperature sensor is used, based on
configuration during installer setup, either of the following
options are available:
When using a DATS with an Equipment Interface Module the
DATS is for testing only. When the installer is in any of the
Installer Tests pressing the “More” button will display the
temperature measured at the DATS. This allows the installer
to view the temperature of each stage of heating and or
cooling. The DATS will not be used for control and will not
disable heating or cooling based on duct air temperature.
Set Calendar and Time
Thermostat keeps current time and day for up to ten years
under normal use after the calendar is set.
When the thermostat is first powered, the display is ready to
set the calendar and time.
NOTE: Calendar can also be set in the Installer Setup.
1. Press the arrow keys to set the year, month and day.
2. Press the Done key.
SET CURRENT DAY
SET MONTH
MO
WEWETHTHFRFRSSAASU
OK TO PICK MULTIPLE DAYS SCREEN LOCKED
CHANGE FILTER UV LAMP
• The thermostat will display the temperature measured at
the sensor location (internal thermostat sensor is disabled).
• The thermostat will display a 50-50 average of the
temperature measured at the thermostat location and the
remote indoor sensor location.
If more than one remote indoor sensor is used, based on
configuration during installer setup, either of the following
options are available:
DONE
USE ARROWS TO SET YEAR AND TIME
M22424
3. Press the arrow keys to set the current time.
4. Press the Done Key.
1168-0287—1
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
E
MO
SA
SU
MO
USE ARROWS TO SET YEAR AND TIME
1. Press and release the System Key.
DON
M22425
INSTALLER SETUP
Auto Discover is available when the TH9421C thermostat is
connected to an EIM. The EIM communicates information to
the thermostat. Thermostat settings can be specified using the
up and down arrow keys on the screen or set to Auto Discover.
Using Auto Discover
Some Installer setups are defaulted to Auto Discover. If not
defaulted, the installer can change the option to Auto Discover,
however, it is always important that the installer verify that the
auto discovered values are correct for the system that is
present.
FAN
ON
Inside
AUTO
SYSTEM
EM HEAT
OFF
COOL
SCHED HOLD CLOCK
THU
Following
Schedule
A
M
Humidity
SCREEN
M23498
2. Press and hold the two blank keys on either side of the
center blank key for approximately five seconds until
screen changes.
TUWEWETHTHFRFRSSAASU
MO
OK TO PICK MULTIPLE DAYS SCREEN LOCKED
CHANGE FILTER UV LAMP
SYSTE
EM
HEAT
OFF
DONE
Inside
M
Set
Following
Schedule
Humidity
CANCEL
When using the thermostat with an equipment interface
module, Auto Discover will discover factory default settings
and will not receive communications as to proper system
settings. The equipment interface module is preprogrammed at
the factory as a one heat one cool product and the thermostat
will “auto discover” those settings. The equipment interface
module will be reprogrammed when the installer manually
changes the configuration in the installer set up. It is not
recommended to use Auto Discover with an equipment
interface module.
When using the VisionPRO® IAQ thermostat with a W8835
zone panel, configure the zone panel, using the DIP switches
on the panel, for the proper system settings. Enter the installer
setup on each thermostat and assign zone numbers, and
change the system settings (ISU 172–180) to Auto Discover
(E) then press the discover button on the zone panel. The zone
panel will then communicate those settings back to the
thermostats and the thermostats will automatically configure
the ISU settings in Auto Discover, again it is important to verify
that the auto discovered values are correct.
NOTE: When a VisionPRO® IAQ thermostat is being added
to an existing zoning system with T8635 Thermostats
the new VisionPRO® IAQ must be set up as the Zone
One Thermostat (master zone controller), and can
only be used with a W8835 zone panel.
Follow these steps to enter the Installer Setup:
M23499
3. Release the two blank keys when the screen on the ther-
mostat matches the screen below.
DONE
M22442
68-0287—112
4. See screen below to review how the thermostat keys are
DONE
MON
THUSASUN
A
used during Installer Setup. See Table 3–4 for the
Installer Setup Numbers and Settings.
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
ADVANCE TO NEXT
INSTALLER
SETUP
NUMBER
INSTALLER SETUP
CURRENT
SETTING
ISU
Parameter
Number
Installer Setup
Name
110Zone Number0
120
USU
130
USU
140
USU
150
USU
160
Date (Year
Upper)
Date (Year
Lower)
Date (Month)1-12Select number that represents current calendar
Date (Day)1-31Select number that represents current calendar
Schedule Options 4
USU
165
USU
Restore Energy
Star Schedule01
172System Selection 1
174Number of Cool/
Compressor
Stages
176Number of
180Fan Operation
190Reversing Valve
Conventional
Heat or Heat
Pump Aux Stages
Conventional
heat only
O/B
PRESS TO EXIT
INSTALLER SETUP
CHANGE THE
CURRENT
SETTING
M22443
5. Press the Done key to exit the Installer Setup screen.
Table 3. Installer Setup Menu.
(Factory Defaults Shown in Bold)Notes
Not zoned
1–9
Zone number
20
21
01-99Default = 06Select last two digits of current calendar year (2006 for
month.
Default = 06
date.
Default = 15
Seven-day programmable
0
2
3
E
0
1
2
E
0
1
2
3
E
0
1
2
E
0
1
Non-programmable
No
Yes
Conventional
Heat Pump
Heat Only No Fan
Auto Discover
none
1
2
Auto Discover
none
1
2
3
Auto Discover
Gas or oil furnace equipment controls fan in
heating
Electric furnace—thermostat controls fan in
heating
Equipment controls stage 1; thermostat controls
stage 2+
Auto Discover
Changeover valve—O/B terminal is energized
in cooling
Changeover valve—O/B terminal is energized in
heating
Settings
Select zone number.
Zone 0 = not zoned
Zone 1 = master zone controller
Zone 2–9 = satellite thermostat
Select first two digits of current calendar year (2006 for
example) - (2001-2178 available).
example) - (2001-2178 available).
Selection of a specific system setting will automatically
modify some default settings and/or hide other installer
setup options that follow.
Not shown if ISU172 = 3.
Conventional systems = number of cooling stages.
Heat Pump systems = number of compressor stages.
Conventional systems = number of heating stages
(maximum of 3).
Heat Pump systems = number of auxiliary heat
stages (maximum of 2).
Only shown if ISU172 = 1 (conventional system).
Use 0 for fossil fuel systems (equipment controls fan).
Use 1 for electric systems (thermostat controls fan).
Use 2 if stage 1 is radiant heating and stage 2+ is a hot
water fan coil.
Only shown if ISU172 = 2.
1368-0287—1
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
Table 3. Installer Setup Menu. (Continued)
ISU
Parameter
Number
200Back-up Heat
210External Fossil
220CPH for 1st
230CPH for 2nd
240CPH for 1st
250CPH for 2nd
260CPH for 3rd
280
USU
300Changeover0
310Deadband
320
USU
330
USU
340Indoor Temp
342Outdoor Temp
Installer Setup
Name
Source Applies to
both Aux and
EmHeat
Fuel Kit
Stage Cool/
Compressor
Stage Cool/
Compressor
Stage
Conventional
Heat or Auxiliary
Stage
Conventional
Heat or 2nd
Stage Auxiliary
Stage Heat
Continuous
Backlight
Temperature
Indication Scale01
Daylight Saving0
Sensor
Sensor
(Factory Defaults Shown in Bold)Notes
0
1
E
0
1
1-6E3—cph recommended for compressors
1-6E3—cph recommended for compressors
1-12E1—1 cph used for steam and gravity
1-12E1—1 cph used for steam and gravity
1-12E1—1 cph used for steam and gravity
0
1
1
21.5
32.0
42.5
53.0
63.5
74.0
84.5
95.0
1
2
0
1
2
0
1
E
Electric backup heat
Fossil fuel backup heat
Auto Discover
Thermostat controls backup heat
External Fossil Fuel kit controls backup heat
1, 2, 4, 5, 6—other cycle rate settings
Auto Discover
1, 2, 4, 5, 6—other cycle rate settings
Auto Discover
3—3 cph used for hot water system and high
efficiency (90% or better) furnaces
5—5 cph used for standard fossil fuel forced air
(less than 80% efficient) systems
9—9 cph used for electric furnaces
2, 4, 6, 7, 8, 10, 11, 12—other cycle rate settings
Auto Discover
3—3 cph for hot water systems and high efficiency
(90% or better) furnaces
5—5 cph for standard fossil fuel forced air (less
than 90% efficient) systems
9—9 cph used for electric furnaces or electric
auxiliary heat for heat pump systems
2, 4, 6, 7, 8, 10, 11, 12—other cycle rate settings
Auto Discover
3—3 cph for hot water systems and high efficiency
(90% or better) furnaces
5—5 cph for standard fossil fuel forced air (less
than 90% efficient) systems
9—9 cph used for electric furnaces or electric
auxiliary heat for heat pump systems
2, 4, 6, 7, 8, 10, 11, 12—other cycle rate settings
Auto Discover
Backlight not on continuously. Thermostat
backlight comes on with each key press.
Backlight is on continuously.
Manual
Auto
2°F 1.5°C
3°F 2.0°C
4°F 2.5°C
5°F 3.0°C
6°F 3.5°C
7°F 4.0°C
8°F 4.5°C
9°F 5.0°C
Note: degrees C is not same as degrees F
Fahrenheit temperature display
Celsius temperature display
Disabled
Enabled (US 1987)
Enabled (US 2007)
Thermostat location only
Remote indoor sensor(s) location(s) only
Average between thermostat and sensor locations
None
Yes
Auto Discover
Settings
Only shown if ISU172 = 2 and ISU176 = 1 or greater.
Only shown if ISU172 = 2 and ISU200 = 1.
Only shown if ISU174 = 2.
Only shown if ISU172 = 2 and ISU176 = 1 or higher.
Default varies based on types of heating.
Only shown if ISU176 = 2 or for Heat Pump systems
with 2 stages of Auxiliary Heat.
Default varies based on types of heating.
Only shown if ISU176 = 3.
Default varies based on types of heating.
If backlight is on continuously, it is low-intensity. Light
changes to full brightness after pressing any key.
Auto Changeover allows user to choose heat, cool, off
or auto. When set to Auto the thermostat will
automatically choose heat or cool based on room
temperature and heat/cool set points. Manual
changeover allows the user to manually toggle
between heat, cool and off.
Only shown if ISU300 = 0. The deadband indicates the
minimum number of degrees that are allowed between
the heat and cool settings when in auto changeover.
For example, if the deadband is set to 3°F and the cool
setpoint is 75°F the warmest heat setpoint allowed
would be 72°F.
Set to 0 in areas that do not follow daylight savings
time.
Indoor temperature sensors will display the
temperature at the sensor location or an average of
two indoor temperature sensors, not including the
temperature sensor in the thermostat. The
temperature sensor in the thermostat is disabled when
using remote indoor temperature sensor(s).
An outdoor temperature sensor is required for heat
pump compressor lockout (ISU350), heat pump
auxiliary lockout (ISU360), dual fuel heat pump
balance point (ISU360) and Humidification with Frost
Protection (ISU372).
68-0287—114
ISU
Parameter
Number
345Dual Fuel Heat
346Dual Fuel Heat
350Heat Pump
360Heat Pump
365Discharge Temp
366Zoning High
367Zoning Low
368Staging
369Staging
370Indoor Humidity
372Indoor
Installer Setup
Name
Pump Control01
Pump Upstage to
Furnace Timer
Balance Point
(also compressor
lockout)
Temperature
Off
Humidify with no Frost Protection
Humidify with Frost Protection
Auto Discover
Settings
See Dual Fuel Heat Pump control on page 22.
See Dual Fuel Heat Pump control on page 22.
Only shown for heat pump applications with an
outdoor temperature sensor present.
Only shown for heat pump applications with an
outdoor temperature sensor present.
Only Shown if ISU110 = 1 (Master Zone Controller)
and Discharge Temperature Sensor is available.
Only Shown if ISU110 = 1 (Master Zone Controller)
and Discharge Temperature Sensor is available.
Only Shown if ISU110 = 1 (Master Zone Controller)
and ISU174 = 2 or more. Must have Discharge
Temperature Sensor present.
Only Shown if ISU110 = 1 (Master Zone Controller)
and ISU176 = 2. Must have Discharge Temperature
Sensor present.
If there is a remote sensor installed and the setting is
either auto discover or “remote” the internal thermostat
humidity sensor is disabled. If set to “internal” the
internal thermostat sensor is presented on the screen.
If set to “disabled” the internal sensor and any remote
sensors are disabled, there will be no humidity
displayed and will have no humidification/
dehumidification control.
Shown only if ISU370 = 1, 2 or E.
1568-0287—1
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
Table 3. Installer Setup Menu. (Continued)
ISU
Parameter
Number
374Hum Fan Action 0
379Dehumidification
383Over-Cooling
384Dehumidification
390Southern
391Southern
392Southern
393Southern
394Southern
400Ventilation control 0
401Number of
402Total house
403Ventilation CFM 30-195 30–195 CFM in increments of 5
404Max ventilation
405Ventilation Fan
406Ventilation in
Installer Setup
Name
Control
Limit
Fan Action
Dehumidification
Away Mode
Dehumidification
Away Mode Fan
Setting
Dehumidification
Away Mode Low
Limit
Temperature
Setting
Dehumidification
Away
Temperature
Setting
Dehumidification
Away
Dehumidification
Setting
bedrooms
Sq. Ft.
percentage limit
Action
High Humidity01
(Factory Defaults Shown in Bold)Notes
1
2
3
0
1
3
10.5
21.0
31.5
0
1
0
1
0
1
2
70-8070°F–80°F
70-9970°F–99°F
55-7055%–70% relative humidity
1
2
1-61–6 bedrooms
10-501000–5000 sq. ft. in increments of 100
30-60
100
1
2
Humidify only while fan or heat is on
Humidify will force fan on
Humidify only when heat is on
Humidifier operates independent of fan
None
Dehumidify with Air Conditioning
Whole house Dehumidifier
1°F0.5°C
2°F1.0°C
3°F1.5°C
(Show 1/2 degree C)
System fan turns on with dehumidifier
Dehumidifier operates independent of system fan
No
Yes
Fan Auto
Fan On
Fan Circulate
Default = 76°F
Default = 85°F
Default = 65%
No ventilation
Ventilation on at all times
Ventilation on except during sleep period
Default = 2
Default = 1000 sq. ft.
Default = 160 CFM
30%–60%
Default = 50%
unlimited
Vent on will force fan on also
Vent will not force fan ON
Off
On
Settings
Setting 0 will run the humidifier only during a call for
heat or if the fan is running.
Setting 1 will force the fan to run if there is a call for
humidification.
Setting 2 will humidify only during a call for heat.
Setting 3 assumes the humidifier has it own internal
fan and will not require the system fan or heat to be
operating during a call for humidification.
Option 1 uses dehum terminal as a normally closed
relay to wire to a low-speed fan terminal.
Option 3 uses dehum terminal as a normally open
relay to wire to a whole-house dehumidifier.
Only shown if ISU379 = 1.
Only shown if ISU379 = 3.
Not shown if ISU379 = 0.
ISU 391-394 will only be shown if ISU390 = 1.
If ISU391 = 1 or 2 to help remove condensation from
the air handler and the A-coil, some humidity may be
re-introduced into the living space.
The air conditioner will be allowed to cool the living
space to this temperature to meet the humidity setting
that set in ISU394.
The A/C will maintain this temperature provided the
humidity setting is satisfied. This temperature setting
can not be set lower than the temperature set in ISU
392.
Set the desired humidity level to maintain within the
living space
If ISU300 = 0, ISU401-405 will not be shown.
The thermostat will determine if ventilation is meeting
ASHRAE standard 62.2. The display will show a P
above the setup number if the setting passes the
ASHRAE standard, or F if it does not. Best practice is
to move the setting down until F is displayed, then
move up one setting to the minimum passing value.
Only shown if ISU372 and ISU400 are not set to 0.
When set to On will use ventilation to remove humidity
when thermostat is in the heat mode.
68-0287—116
ISU
Parameter
Number
500
USU
502Furnace filter
510
USU
520
USU
530
USU
540
USU
580Min Compressor
600Heat Temp
610Cool Temp
640
USU
650Extended Fan on
660Extended Fan on
670
USU
680Temp Control
690Temp Control
Installer Setup
Name
Furnace Filter
Change
Reminder
reminder run time
equipment counts
Humidifier Pad
Replacement
Reminder
UV Lamp
Replacement
Reminder
Adaptive
Intelligent
Recovery
Number of
Periods
Off Time
Range Stops
Range Stops
Clock Format12
time Heat (Blower
Off Delay Heat)
time Cool (Blower
Off Delay Heat)
Keypad Lockout 0
Heat
Cool
Table 3. Installer Setup Menu. (Continued)
(Factory Defaults Shown in Bold)Notes
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
E
0
1
0
1
2
3
E
0
1
2
E
0
1
2
4
0
1
2
3
4
5
40-9040°F–90°F (Show 1/2 degree C)
60-9960°F–99°F (Show 1/2 degree C)
24
0
30
60
90
120
0
30
60
90
120
1
2
1
2
3
1
2
3
Disabled
10 R.T. Days
30 R.T. Days
60 R.T. Days
90 R.T. Days
120 R.T Days
180 R.T. Days
270 R.T. Days
365 R.T. Days
30 C Days
60 C Days
90 C Days
120 C Days
180 C Days
365 C Days
Auto Discover
Counts runtime Heat and Cool
Counts runtime Cool only
Disabled
90 C Days or 30 R.T. Days
180 C Days or 60 R.T. Days
365 C Days or 90 R.T. Days
Auto Discover
Disabled
365 Days
730 Days (2 years)
Auto Discover
Conventional
Adaptive
2 Periods
4 Periods
Off
1 minute
2 minutes
3 minutes
4 minutes
5 minutes
Default = 90°F
Default = 60°F
12 Hour
24 Hour
Off
30 seconds
60 seconds
90 seconds
120 seconds
Off
30 seconds
60 seconds
90 Seconds
120 Seconds
Unlocked
Partial Locked
Full Locked
Less Aggressive temp control (may cause temp
undershoot)
Standard (recommended)
More Aggressive temp control (may cause temp
overshoot)
Less Aggressive temp control (may cause temp
undershoot)
Standard (recommended)
More Aggressive temp control (may cause temp
overshoot)
Settings
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
Display will show Calendar Days if ISU372 = 0; Run
Time Days if ISU372 = 1 or 3.
See Temperature Recovery on page 31.
2 periods = Wake and Sleep.
4 periods = Wake, Leave, Return, and Sleep.
This can be used to remove condensation from A-coil;
however, could re-introduce humidity into the living
space.
1768-0287—1
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
DONE
Table 3. Installer Setup Menu. (Continued)
ISU
Parameter
Number
700Temperature
701Humidity Display
710Restore Factory
Installer Setup
Name
Display Offset-3-2
Offset
Defaults
(Factory Defaults Shown in Bold)Notes
-3°F -1.5°C
-2°F -1°C
-1
0
1
2
3
-5
-4
-3
-2
-1
0
1
2
3
4
5
0
1
-1°F -.5°C
0°F0. °C — (no difference in displayed
temperature and actual room temperature)
1°F.5°C
2°F1°C
3°F1.5°C
-5%
-4%
-3%
-2%
-1%
0%
1%
2%
3%
4%
5%
No
Yes
Settings
Restoring factory defaults will re-set installer setup and
programming.
INSTALLER SYSTEM TEST
Use the Installer System Test to test the heating, cooling and
fan (and emergency heat for heat pump systems).
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed during
Installer System Test
Avoid cycling compressor quickly.
How to Use the Installer System Test
The Installer Test is part of the Installer Setup Menu.
1. Enter the Installer System Test by entering the Installer
Setup.
2. Note that the test appears at the end of the Installer
Setup Numbers.
3. See Fig. 28 to review how the thermostat buttons are
used during the Installer System Test. See Table 6 for
available Installer System Tests.
4. If installed with a Discharge Air Temperature Sensor
(ISU365=1) press the “MORE” button to view the discharge temperature, and press Cancel to return to the
Installer test screen.
SYSTEM TEST
NUMBER
DONE KEY
EXITS INSTALLER
SYSTEM TEST
SYSTEM STATUS
NUMBER
UP ARROW KEY
ADVANCES TO
NEXT SYSTEM
TEST NUMBER
UP ARROW
TURNS THE
SYSTEM ON
DOWN ARROW
TURNS THE
SYSTEM OFF
M22428
Fig. 28. Review thermostat buttons used during Installer
System Test.
68-0287—118
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
Installer System Tests
Table 4. Installer System Test.
System Test NumberTest TypeISU ValueSystem Status Number and Description
Test 1Installer Test Cool0
1
2
Test 2Installer Test Fan0
1
Test 3Installer Test Heat0
1
2
3
4
Test 4Emergency Heat Test0
1
2
Test 5Installer Test Humidifier0
1
Test 6Installer Test Dehumidifier0
1
Test 7Installer Test Ventilator0
1
ErrDiagnostic Recall00-99See “Communication Error Codes” on page 34
Press the Next button to go to the beginning of the Installer Setup or press the Done button to exit the Installer System Test.
When VisionPRO® IAQ is used in a zoning system you must exit the installer test on one thermostat before entering the installer
test on another thermostat.
OPERATION
Thermostat Keys
SYSTEM
SELECTS EM.
HEAT/HEAT/OFF/COOL
FAN
SELECTS
ON/AUTO/CIRC
TUE
FAN
Inside
AUTO
SYSTEM
HEAT
COOL
SCHEDHOLD CLOCK SCREEN MORE
SCHED
ENTERS
SCHEDULING
MODE
HOLD
SETS A PERMANENT
HOLD AND ACTIVITIES
VACATION HOLD
AM
CLOCK
SETS THE
TIME
FORWARD
OR BACK
DOWN ARROW
LOWERS TEMPERATURE
SETTING
UP ARROW
RAISES
TEMPERATURE
SETTING
Set To
Following
Schedule
Humidity
MORE
SHOWS ADDITIONAL
ACCESSORY AND
MAINTENANCE
OPTIONS
SCREEN
LOCKS OUT THE
SCREEN TO ALLOW
FOR CLEANING
M23500
Thermostat Display
TUE
SHOWS CURRENT DAY
OF THE WEEK
FAN
SHOWS FAN
SETTING
TU
FAN
Inside
AUTO
SYSTEM
EM HEAT
HEAT
OFF
COOL
SCHEDHOLD CLOCK SCREEN MORE
SYSTEM
SHOWS
CURRENT
SYSTEM
POSITION
TIME
DISPLAY CURRENT
TIME OF DAY, HOLD
TIME REMAINING OR
NUMBER OF VACATION
DAYS REMAINING
INSIDE TEMPERATURE
SHOWS THE CURRENT INSIDE
TEMPERATURE
SET TO
TEMPERATURE
SHOWS THE
CURRENT SET
TEMPERATURE
Set To
Following
Schedule
A
M
Humidity
FOLLOWING
SCHEDULE
SHOWS THE
THERMOSTAT IS
FOLLOWING THE
PROGRAMMED
SCHEDULE
M23501
1968-0287—1
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
System and Fan Settings
System
The System key selections vary based on your heating and/or
cooling system type.
Heat — Thermostat controls the heating system.
Off — Both heating and cooling systems are off.
Cool — Thermostat controls the cooling system.
Auto — Thermostat automatically changes between heating
and cooling operation, depending on indoor temperature.
Em. Heat — Emergency heat cycles to maintain temperature.
Compressor is locked out and auxiliary heat turns on as
needed.
Fan
The Fan key selections vary based on the heating and/or
cooling system type.
On — Fan runs continuously. Use this setting for improved air
circulation or for more efficient central air cleaning.
Auto — fan follows the fan program schedule.
Circ — fan runs randomly approximately 35% of the time. Use
this setting for improved air circulation or for more efficient
central air cleaning when you do not want the fan running
continuously.
Control Humidification Level
The VisionPRO® IAQ Touchscreen Thermostat reads the
inside humidity level and allows for a humidification setting with
or without frost protection. Humidification will only take place
when the thermostat is in Heat mode or in Auto mode when the
previous call was a call for heating.
WITH FROST PROTECTION
Controlling humidification with frost protection requires an
outdoor temperature sensor. The Frost Index (scale 1–10) will
limit the amount of humidity added to the air based on outdoor
temperature, with 1=most dry and 10=most humid. This
prevents frost from accumulating on windows.
1. Press the More key until the inside humidity level set-
point is shown.
2. Use Up and Down arrow keys, located to the right of the
humidity setpoint, to set desired humidity level.
3. Press Done key.
Control Dehumidification Level
The VisionPRO® IAQ Touchscreen Thermostat reads the
inside humidity level and allows for a dehumidification setting,
and can be set to dehumidify using the air conditioner or a
whole house dehumidifier.
CURRENT
INDOOR
HUMIDITY
Inside
DONECANCEL
DEHUMIDIFIER
SETTING
(AUTO/OFF)
With Air Conditioner
The set range for dehumidification is 40 to 80%, and can be set
in 5% increments. The thermostat must be in Cool mode or
Auto mode when the previous call was a call for cooling.
Inside
DEHUMIDIFIER
Humidity
MORE
HUMIDITY SET
POINT
M23496
Inside
HUMIDIFIER
Humidity
MORE
DONE
CANCEL
M23518
WITHOUT FROST PROTECTION
The frost setpoint is not displayed, but a humidity setpoint can
still be set.
68-0287—120
DEHUMIDIFIER
DONECANCEL
M23514
Dehumidifying in this manner runs the air conditioner longer
than simply cooling the house would require, and can be set to
run 1, 2, or 3°F below the temperature setpoint. This feature is
called Dehumidification Droop Control.
NOTE: You must use this setting if:
—No powered, whole house dehumidifier is present,
and
—The system uses the air conditioner as the
dehumidifier.
DEHUMIDIFICATION DROOP CONTROL
In extremely high humidity conditions, the thermostat keeps
the air conditioner running (energizing Y/Y2 and G) for up to
3°F below the temperature setpoint. It does this while trying to
achieve the desired humidity setpoint and balancing that with
the temperature setpoint. The thermostat controls up to 3° F
below the temperature setting until either the humidity setpoint
is satisfied or conditions change.
With Whole House Dehumidifier
Controls humidity levels in the house by dehumidifying without
the use of the air conditioner. This setting requires a dedicated
unit for dehumidification. Dehumidification with a whole house
dehumidifier will take place when the thermostat is in the Cool,
Off, Auto, Heat or Em.Heat modes. If the system is installed
with a whole house humidifier, dehumidification with a whole
house dehumidifier will only take place when the thermostat is
in Cool, Off or Auto modes (Auto only if the previous call was a
call for cooling).
When controlling a whole-house dehumidifier the user can
toggle between auto (dehumidify when needed based on
setpoint and current humidity level) and off (see Fig. 29).
Inside
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
DONE
M23520
Ventilation occurs two ways:
AUTOMATIC
Uses installer setup to determine amount of ventilation
required based on house and equipment size. To disable
automatic ventilation, switch the ventilation setting to Off. The
user can still use the timer to request ventilation.
ON DEMAND
User can also set a vent timer that will circulate fresh air into
the home for a set period of time from 20 to 180 minutes in 20minute increments. The vent timer is enabled whether
ventilation is set to “Auto” or “Off.”
DEHUMIDIFIER
Humidity
MORE
DONECANCEL
M23515
Fig. 29. Display when controlling a whole-house
dehumidifier.
1. Press the More key until the inside humidity percent and
dehumidification setpoint are shown.
2. Use Up and Down arrow keys, located to the right of the
dehumidifier setpoint, to set desired humidity level for
dehumidification in the summer.
3. Press Done key.
Ventilation Control
Ventilation setup options include ISUs 400, 401, 402, 403, and
404. Combined, these will determine a percentage of
maximum ventilation limit. The thermostat will calculate
whether or not this level of ventilation meets ASHRAE
standard 62.2. If ASHRAE 62.2 is met a P will appear in the
display above the setup number. If ASHRAE 62.2 is not met an
F will appear in the display above the setup number.
Passing ASHRAE 62.2 is only applicable when vent is running.
For example, if installer has set to not vent during sleep period,
ASHRAE 62.2 would be met at all times except during sleep
period.
VENT
Minutes
MORE
DONECANCEL
M23519
VENTILATION IN HIGH HUMIDITY CONDITIONS (SETUP FUNCTION 0406)
If Ventilation Control is available (setup function 0400 set to 1
or 2), this allows the ventilation equipment to turn on if the
humidity rises approximately 10% above the RH setting in
heating mode to exhaust the extra humidity.
HEAT PUMP OPERATION
Heat Pump LED Indication
A red LED indication is located in the upper right corner of the
thermostat. It is only visible when lighted.
When the L terminal is wired to an equipment monitor, the LED
signals when a check or fail signal is sent to the thermostat
from the system. This is operational in the Heat, Off, Cool or
Auto positions.
2168-0287—1
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
Heat Pump Emergency Heat LED Indication
The thermostat uses a red LED indicator that lights when the
thermostat is in the Emergency Heat mode. The LED is located
in the upper right corner of the thermostat. It is visible only
when on.
Heat Pump Temperature Lockouts
Dual Fuel Heat Pump and Outdoor Temperature
Sensor
In this operation, there is no external fossil fuel kit (dual fuel kit)
installed; the thermostat controls this function.
1. Choose correct heat pump application in Installer Setup
Number 0172.
2. Choose Fossil Fuel Option as the backup heat source
in Installer Setup Number 0200.
3. Choose No External Fossil Fuel Kit Option is control-
ling back up heat in Installer Setup Number 0210.
4. Choose Outdoor Temperature Sensor for Heat Pump
Temperature Lockouts in Installer Setup Number 0342.
5. Choose appropriate Balance Point Temperature in
Installer Setup Number 0350.
Dual Fuel Heat Pump Control
Balance Point Only (ISU345 = 0)
NOTE: System must have an outdoor temperature sensor.
When the outdoor temperature is above the selected balance
point temperature, only the compressor operates and the fan
(G terminal) energizes when the thermostat calls for heat. See
Fig. 30. When the outdoor temperature is below the selected
balance point temperature, only the fossil fuel (auxiliary heat)
operates and the fan (G terminal) does not energize when the
thermostat calls for heat.
When the outdoor temperature is above the Auxiliary Heat
Lockout Temperature only the compressor operates; below the
balance point temperature (setup function 0360) only the fossil
fuel operates. Between the balance point temperature and
auxiliary heat lockout temperature the compressor will operate.
However, the fossil fuel will turn on if the room temperature
droops approximately 2°F below the temperature setting,
compressor will be disabled.
COMPRESSOR ONLY
50
35
OUTDOOR TEMPERATURE
COMPRESSOR+2 °F
DROOP UPSTAGE TO
FURNACE
FURNACE ONLY
AUX.
LOCKOUT
BALANCE
POINT
M23497
Fig. 31. Balance Point with Auxiliary Lockout Temperature.
AUXILIARY LOCKOUT FOR ELECTRIC HEAT BACKUP
Heat Pump systems with electric heat backup can select a
compressor lockout temperature (function 0350) and/or
auxiliary heat lockout temperature (function 0360). When the
outdoor temperature is below the compressor lockout
temperature, only the auxiliary heat operates. When the
outdoor temperature is between the compressor and auxiliary
lockout temperatures, both the compressor and auxiliary heat
can operate.
NOTE: System must have an outdoor temperature sensor.
Heat Pump with Electric Auxiliary (Backup) Heat and
Outdoor Temperature Sensor
1. Choose correct heat pump application in Installer Setup
Number 0172.
2. Choose Electric as Auxiliary (Backup) Heat Source in
Installer Setup Number 0200.
3. Choose Outdoor Temperature Sensor in Installer
Setup Number 0342.
4. Choose Compressor Lockout Temperature in Installer
Setup Number 0350.
5. Choose Auxiliary Lockout Temperature in Installer
Setup Number 0360.
Fig. 30. Dual Fuel Heat Pump Operation in Heat mode with
Balance Point Set.
Balance Point Plus 2° Droop (ISU345 = 1)
The fossil fuel will turn on when the outdoor temperature is
above the balance point if the room temperature droops
approximately 2 degrees below the temperature setting, and
the compressor will be disabled.
68-0287—122
NOTE: There is a 5°F deadband between the Compressor
and Auxiliary Heat Lockout Temperatures.
Operation in Heat Mode
When the outdoor temperature is below the Compressor
Lockout Temperature, only the Auxiliary Heat operates.
When the outdoor temperature is above the Auxiliary Lockout
Temperature, only the Compressor operates. See Fig. 32.
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
Operation in Emergency Heat Mode
COMPRESSOR ONLY
50
BOTH COMPRESSOR AND
AUXILIARY HEAT
35
AUXILIARY ONLY
OUTDOOR TEMPERATURE
AUXILIARY
LOCKOUT
TEMPERATURE
COMPRESSOR
LOCKOUT
TEMPERATURE
M19950
Fig. 32. Heat Pump Operation with Lockout
Temperatures Set.
When the outdoor temperature is between the two
temperatures, both the Compressor and Auxiliary Heat operate.
Table 5. Sequence of Operation for Conventional Systems.
System SettingFan SettingCall for ActionEnergize TerminalsScreen Message
OffAutoNoneNoneNone
Cool or AutoAutoNoneNoneNone
Cool or AutoAutoStage 1 CoolingY, GCool On
Cool or AutoAutoStage 1 and Stage 2 cooling
Heat or AutoAutoNoneNoneNone
Heat or AutoAutoStage 1 heating
Heat or AutoAutoStage 1 and Stage 2 heating
Heat or AutoAutoStage 1, Stage 2 and Stage 3 heating
a
G energizes only if Installer set up number 180 is set to Option 1 (Electric Heat).
b
If installer setup (ISU174) is configured for two stages of cooling.
c
If installer setup (ISU 176) is configured for two or more stages of heating.
d
If installer setup (ISU 176) is configured for three stages of heating.
e
G energizes only if Installer set up number 180 is set to Option 1 (Electric Heat) or 2 (Hot water coil).
Once the thermostat is placed into the Emergency Heat mode,
the compressor and auxiliary lockout features are turned off. In
the Emergency heat mode, the compressor is locked out. The
first stage of heat is whatever is connected to the AUX
terminal. The second stage of heat is connected to the AUX2.
terminal.
Operating Sequence
The thermostat energizes specific terminal(s), depending on
the demand for heating, cooling or fan. The thermostat screen
shows the time, inside temperature, system and fan selections.
Additional indicators are shown when the heating, cooling or
fan is energized. See Table 5 and 6 for specification
information.
b
, G
Y, Y 2
a
W1, G
W1, W2c, G
c
W1, W2
, W3d, G
e
e
Cool On
Heat On
Heat On
Heat On
Table 6. Sequence of Operation for Heat Pump Systems.
System Setting Fan SettingCall for ActionEnergize TerminalsScreen message
OffAutonone
Cool or AutoAutonone
Cool or AutoAutoStage 1 cooling
Cool or AutoAutoStage 1 and Stage 2 cooling
Heat or AutoAutonone
Heat or AutoAutoStage 1 heating
Heat or AutoAutoStage 1 and Stage 2 heating
Heat or AutoAutoStage 1, Stage 2 and Stage 3 heating
Heat or AutoAutoStage 1, Stage 2, Stage 3 and Stage 4 heating
Em.Heat
Em.Heat
Em.Heat
a
Configure O/B in Installer Setup. Based on last piece of equipment called (cooling = O or Heating = B).
b
Red LED is on. See LED indication section for more details (page 21).
c
If installer setup (ISU 174) is configured for 2 compressor stages.
d
If installer setup (ISU 176) is configured for one or more stages of Auxiliary Heat.
e
If installer setup (ISU 176) is configured for two stages of Auxiliary Heat.
f
If thermostat is controlling backup heat, see temperature lockout section (page 22).
b
b
b
AutoNone
AutoStage 1 Heating
AutoStage 1 and Stage 2 heating
a
O/B
a
O/B
Y, G, O/B
a
Y, Y 2c, G, O/B
a
O/B
Y, G, O/B
Y, Y 2
f
Y
Yf, Y2
O/B
AUX
AUX
a
c
, G, O/B
c,f
, Y2
, AUXd, G, O/B
c,f
, AUXd, AUX2e, G, O/B
a
d
, G, O/B
d
, AUX2e, G, O/B
a
a
a
a
a
None
None
Cool On
Cool On
None
Heat On
Heat On
Aux Heat On
a
Aux Heat On
None
Aux Heat On
Aux Heat On
2368-0287—1
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
Table 7. Indoor Air Quality Operation.
Last call
System SettingCall For Action
AutoHumidification
AutoDehumidification
AutoDehumidification
HUM1 and HUM2 Close
Nothing
Nothing
b
b
a
Nothing
DHM1 and DHM2 close
DHM1 and DHM2 opencYc and G
a
None
e
None
AutoVentilationVNT1 and VNT2 CloseVNT1 and VNT2 CloseNone
Heat or Em.HeatHumidificationHUM1 and HUM2 CloseNANone
d
Heat or Em.HeatDehumidification
VNT1 and VNT2 Close
NANone
Heat or Em.HeatVentilationVNT1 and VNT2 CloseNANone
CoolHumidificationNA
CoolDehumidificationNA
CoolDehumidificationNA
Nothing
a
DHM1 and DHM2 close
DHM1 and DHM2 open
None
e
None
cYc
and G
CoolVentilationNAVNT1 and VNT2 CloseNone
a
Humidification only operates in heating or when last call was for heating.
b
Dehumidification only operates in cooling or when last call was for cooling.
c
Must be set up in installer setup (ISU 379) for dehumidification with air conditioning.
d
Installer setup (ISU 406) must be setup for Ventilation in high humidity or nothing will happen.
e
Only with whole house dehumidifier.
Multi-Stage Heat and Cool Control
In a multi-stage system, while maintaining setpoint, several
factors affect when the next stage energizes, such as load
conditions, environmental conditions, P+I control, and home
insulation. The next stage energizes when the thermostat
senses the previous stage is running at 90% capacity. This
operation is droopless control.
User Setup
Follow these steps to enter the User Setup:
1. Press and release the System key.
TUE
CHANGE FILTER UV LAMP HUMIDIFIER PAD
Inside
SYSTEM
EM HEAT
OFF
COOL
DONECANCEL
Set To
Following
Schedule
Humidity
Energize
terminalsHeatCool
c
c
FAN
ON
Inside
AUTO
SYSTEM
EM HEAT
OFF
COOL
SCHED HOLD CLOCK
THU
Following
Schedule
A
M
Humidity
SCREEN
M23502
2. Press and hold the center blank key for approximately
five seconds until the screen changes.
68-0287—124
M23503
3. Release the center blank key when the screen on the
thermostat matches the screen below.
DONE
M22440
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
DONE
MON
THUSASUN
A
4. See the screen below to review how the thermostat keys
are used during the User Setup. See Table 8 for the User
Setup numbers and settings.
ADVANCE TO NEXT
USER SETUP
NUMBER
PRESS TO EXIT
USER SETUP
USER SETUP
CURRENT
SETTING
CHANGE THE
CURRENT
SETTING
M19922
5. Press the Done key to exit the User Setup screen.
Table 8. User Setup Menu.
User
Setup
120Date (Year
130Date (Year
140Date (Month)1-12 Select number that represents current
150Date (Day)1-31 Select number that represents current
160Schedule
165Restore Energy
280Continuous
320Temperature
330Daylight Saving 0
400Ventilation
User Setup
No.
NameSettings
Upper)
Lower)
Options
Star Schedule01NoYes
Backlight
Indication
Scale
control
20
21
01-99 Default = 06
calendar month.
Default = 06
calendar date.
Default = 15
40Seven-day programmable
Non-programmable
01Backlight not on continuously.
Thermostat backlight comes on with
each key press.
Backlight is on continuously.
01Fahrenheit temperature display
Celsius temperature display
Disabled
1
Enabled (US 1987)
2
Enabled (US 2007)
0
No ventilation
1
Ventilation on at all times
2
Ventilation on except during sleep
period
Table 8. User Setup Menu. (Continued)
User
Setup
500Furnace Filter
510Humidifier Pad
520UV Lamp
530Adaptive
540Number of
640Clock Format122412 Hour
670Keypad
No.
Change
Reminder
Replacement
Reminder
Replacement
Reminder
Intelligent
Recovery
Periods
Lockout
User Setup
NameSettings
Disabled
0
10 R.T. Days
1
30 R.T. Days
2
60 R.T. Days
3
90 R.T. Days
4
120 R.T Days
5
180 R.T. Days
6
270 R.T. Days
7
365 R.T. Days
8
30 C Days
9
60 C Days
10
90 C Days
11
120 C Days
12
180 C Days
13
365 C Days
14
Auto Discover
E
0
Disabled
1
90 C Days
2
180 C Days
3
365 C Days
E
Auto Discover
0
Disabled
1
365 Days
2
730 Days (2 years)
E
Auto Discover
01Conventional
Adaptive
242 Periods
4 Periods
24 Hour
0
Unlocked
1
Partial Locked
2
Full Locked
PROGRAMMING
Preprogrammed Energy Star Settings
Table 9 shows default program settings. Visit the Energy Star
web site at www.energystar.gov
resources on programmable touchscreen thermostats.
Table 9. Energy Star Default Program Settings.
Schedule
PeriodTime
Wake6:00AM70°F (21°C)78°F (25.5°C) Auto
Leave8:00AM62°F (16.5°C) 85°F (29.5°C) Auto
Return6:00PM70°F (21°C)78°F (25.5°C) Auto
Sleep10:00PM 62°F (16.5°C) 82°F (28°C)Auto
for additional education and
Setpoints
Fan
SettingHeatCool
Program Heating and Cooling Schedule
Your thermostat can control up to four different schedule
periods per day:
Wake—Period when you awaken and want your home at a
comfortable temperature.
Leave—Period when you are away from home and want an
energy-saving temperature.
Return—Period when you return home and want your home
2568-0287—1
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
SCHED
HOLD
PM
back to a comfortable temperature.
Sleep—Period when you are asleep and want an energysaving temperature.
NOTE: Schedule times are in 15-minute intervals.
Edit Schedule
1. Press Sched key.
TUEWEDTHUFRISATSUN
MON
OK TO PICK MULTIPLE DAYS
FAN
ON
AUTO
CIRC
CANCEL
PERIOD
HEAT
FAN
Inside
AUTO
SYSTEM
HEAT
SCHEDHOLD CLOCK SCREEN
2. Press Edit key.
TUEWEDTHUFRISATSUN
MON
OK TO PICK MULTIPLE DAYS SCREEN LOCKED
FAN
Inside
AUTO
SYSTEM
EM HEAT
HEAT
OFF
COOL
AUTO
SCHED
DONE
EDIT
FRI
Set
AM
PM
Set To
CANCEL
PERIOD
AM
PM
HOLD
CLOCK SCREEN
WAKE
LEAVE RETURN SLEEP CANCEL
Following
Schedule
Humidity
Following
Schedule
M23504
HEAT
COOL
M22553
AM
DONEWAKE LEAVE RETURN SLEEP CANCEL
COOL
M19955
4. Press Wake key. Once pressed, Wake flashes to show it
is selected.
5. Press Up and Down keys to modify time and heat and
cool temperatures from this screen.
NOTE: The Fan setting can be programmed for On, Auto, or
Circ for each period selected. See Fan Schedule section for more information.
6. Press Leave key and repeat step 5.
7. Press Return key and repeat step 5.
8. Press Sleep key and repeat step 5.
9. When complete, press Done key. “Saving Changes”
appears on the screen to indicate changes are being
saved to the day(s) modified.
TUEWEDTHUFRI
MON
SAVING
CHANGES
3. It is OK to pick multiple days. Select any combination of
days to edit. These days are scheduled with the same
times and temperatures. Check marks appear next to
days selected.
68-0287—126
M19956
NOTE: To set a Program Schedule for the remaining days of
the week, repeat steps 1–9. Example: If Mon–Fri was
selected first, go back and repeat steps 1–9 for Sat
and Sun.
10. To exit schedule without saving changes, press Cancel
key any time.
Cancel a Schedule Period
1. Press Sched key.
2. Press Edit key.
3. Select the Day(s) of the week desired.
4. Press schedule period you want to cancel (Wake, Leave,
Return or Sleep). Once selected, the period flashes.
5. Press Cancel Period key.
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
SCHED
HOLD
PM
SCHED
HOLD
PM
TUEWEDTHUFRISATSUN
MON
OK TO PICK MULTIPLE DAYS SCREEN LOCKED
FAN
AUTO
SYSTEM
EM HEAT
HEAT
OFF
COOL
AUTO
DONE
Inside
SCHED
CANCEL
PERIOD
HOLD
WAKE
Set To
Following
Schedule
AM
PM
CLOCK SCREEN
LEAVE RETURN SLEEP CANCEL
HEAT
COOL
M22446
6. The time, temperature(s) and fan setting disappear. The
bar above the selected period is removed, indicating the
scheduled period was cancelled.
NOTE: To reinstate a schedule period, press arrow keys to
set desired time and temperatures.
TUEWEDTHUFRISATSUN
MON
OK TO PICK MULTIPLE DAYS
FAN
HEAT
COOL
DONEWAKE LEAVE RETURN SLEEP CANCEL
M19957
7. Press Done key.
Fan Schedule
Press Fan key while in the Scheduling Screen to program the
System Fan. Choices available from the Scheduling Screen:
Auto (default position)—fan runs with equipment.
Programmable for all schedule periods (Wake, Leave, Return
and Sleep).
On—fan runs continuously (programmable for all schedule
periods).
Circ—fan runs randomly for approximately 35% of schedule
period (programmable for all schedule periods).
TUEWEDTHUFRISATSUN
MON
OK TO PICK MULTIPLE DAYS SCREEN LOCKED
FAN
Inside
AUTO
SCHED
CANCEL
PERIOD
HOLD
WAKE
AM
PM
SYSTEM
EM HEAT
HEAT
OFF
COOL
AUTO
DONE
Set To
Following
Schedule
CLOCK SCREEN
LEAVE RETURN SLEEP CANCEL
HEAT
COOL
M22447
Fan Control
If the Fan program is scheduled, Auto is shown and any
programmable mode that is set; for example, if during Wake
period, Fan is set to Auto, only Auto is shown in the Fan area.
However, if during the Wake period, fan is scheduled to On,
both Auto and On are shown. Auto indicates fan is running its
schedule; On indicates Fan schedule is set to On.
THU
FAN
Inside
ON
AUTO
SYSTEM
HEAT
COOL
SCHEDHOLD CLOCK SCREEN
AM
Set
Following
Schedule
Humidity
M23505
Table 10. Fan Program Operation and Screen Status.
Fan
Fan
Setting
Fan
Program
Schedule
Call
for
Action
Energize
Ter min al
Status
shown on
Screen
AutoAutoNoneNoneAuto
AutoOnFanGAuto/On
Auto CircNoneNoneAuto/Circ
AutoCircFanGAuto/Circ
Manual Override of Fan Schedule
Auto—fan is automatically following the Fan schedule (choices
are Auto, On or Circulate).
On—overrides Fan schedule. Fan is continuously On.
Circ—overrides Fan schedule. Fan circulates randomly for
approximately 35% of time until the Auto position is selected.
Table 11. Manual Override of Fan Schedule Operation.
Screen
Fan
Fan
Setting
Schedule
Override
Setting
Call
for
Action
Energize
Ter min al
AutoOnFanGOn
Auto CircNoneNoneCirc
AutoCircFanGCirc
On
Auto
a
—— —
OnCircNone NoneCirc
OnCircFanGCirc
Circ
Auto
a
—— —
CircOnFanGOn
a
Auto Override resumes the Fan Program in each schedule
period (Wake, Leave, Return and Sleep)
Message
Under
Fan
Setting
2768-0287—1
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
OPERATE VISIONPRO® IAQ
Set Time
1. Press Clock.
2. Use arrows to set current time.
TUE
AM
DONECANCEL
M19958
3. Press Done key.
IMPORTANT
The current day of the week should already be set
correctly. If not, see Installer Setup to set the day.
Set Temperature Overrides
The thermostat has four temperature override options: Hold
Temperature Until, Permanent Hold, Vacation Hold, and
Southern Dehumidification Away Setting.
HOLD TEMPERATURE UNTIL (TEMPORARY HOLD)
Holds temperature temporarily until the next scheduled period
time or until the time the user sets.
1. Press Up or Down arrow next to the temperature you
want to adjust. “Hold Temperature Until” time appears on
the screen. The Hold Temperature Until time defaults to
the start time of the next scheduled period.
NOTE: The Time Up and Down arrows are shown for approx-
imately seven seconds. Pressing on the screen time
(where the Hold Temperature Until time is shown)
allows the arrows to reappear.
2. Press Up or Down arrow next to the Time key to set
desired time for the thermostat to resume schedule.
3. Press the Cancel or Sched key to cancel “Hold
Temperature Until” and resume schedule.
NOTE: Once “Hold Temperature Until” time is reached, the
thermostat shows “Following Schedule” on the screen
to indicate that “Temporary Hold” has ended.
PERMANENT HOLD
Permanent Hold changes the temperature setting until
Permanent Hold is cancelled.
1. Press Hold key. “Permanent Hold” appears on the
screen.
2. Press Up or Down arrow next to the temperature you
want to set during “Hold.”
TUE
FAN
Inside
AUTO
SYSTEM
COOL
Permanent
Hold
SCHEDHOLD CLOCK SCREEN
Set To
AM
Humidity
CANCEL
M23507
3. Press Cancel key to cancel “Permanent Hold” and
resume the schedule.
VACATION HOLD
Changes temperature setting for a designated number of days.
1. Press the Up and Down arrow keys to set the desired
temperature while away on vacation. Notice that “Hold
Temperature Until” time is shown on the screen. (This is
the time the Vacation Hold override expires after the
number of days ends.)
2. Press Hold key twice. Screen shows “Hold Temperature
Until” one day.
3. Press Up and Down arrow keys to change the number of
Days you desire thermostat to override the schedule.
NOTE: Days Up and Down arrows appear for approximately
seven seconds. Pressing just below Hold Temperature Until on the screen allows the Days Up and Down
arrows to reappear.
TUE
FAN
Inside
AUTO
SYSTEM
Hold Temperature
Until
COOL
SCHEDHOLD CLOCK SCREEN
68-0287—128
PM
Set
Humidity
CANCEL
M23506
FAN
Inside
AUTO
SYSTEM
Hold Temperature
HEAT
OFF
COOL
Until
SCHEDCLOCK SCREEN
THU
Set To
DAYS
Humidity
CANCEL
M23508
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
4. To cancel the Vacation Hold override early, press the
Cancel key.
NOTE: When the number of days of Vacation Hold expires,
the screen shows “Following Schedule” to indicate
that Vacation Hold has ended.
SOUTHERN DEHUMIDIFICATION AWAY SETTING
Southern Dehumidification Away Setting is an option that only
appears if ISU number 390 is set to yes. It can be used to
maintain the desired humidity level and temperature in the
living space while away for extended periods of time. See ISU
Numbers 390–394 for more information.
FRI
FAN
AUTO
SYSTEM
HEAT
COOL
Inside
Permanent
AM
Hold
Set To
DEHUMIDIFIER
MORE
CANCEL
M23521
1. Press Hold three times to enter the Southern Dehumidifi-
cation Away Setting.
2. These settings can only be changed in installer setup.
Clean Thermostat Screen
The thermostat has a touch screen interaction. Follow these
steps to clean the screen without making thermostat changes:
1. Press the Screen key. Thermostat locks out all touch
keys for 30 seconds to allow for cleaning.
4. Press the Done key to return to the Home Screen and
normal operation.
Screen Locks
TUE
FAN
Inside
AUTO
SYSTEM
COOL
SCHEDHOLD CLOCK SCREEN MORE
Partially Locked Screen
When partially locked, the screen indicates Screen Locked for
5 to 7 seconds whenever the user attempts to press a key that
is locked. Pressing a locked key, while Screen Locked is
shown, flashes “Screen Locked” on the screen.
In this mode, all keys are locked except the Temperature Up
and Down arrow keys:
— User can change temperature up or down but cannot
change schedule settings.
— Temporary temperature change lasts until next scheduled
period and that time shows on screen.
— To cancel temperature override and begin following
schedule, press Cancel key.
— To unlock screen, see Installer Setup section.
Fully Locked Screen
In this mode, all keys are locked and not functional. To unlock
screen, see Installer Setup section. The screen continuously
displays “Screen Locked.”
SCREEN LOCKED
Set
Following
Schedule
Humidity
M23509
OK TO
CLEAN
SCREEN
M19964
2. Use damp cloth slightly moistened with water or house-
hold glass cleaner to clean the screen.
3. Repeat the above steps, as necessary.
IMPORTANT
Do not spray any type of liquid directly on the thermostat itself. If using household glass cleaner, spray
cleaner on cloth. Then use a cloth to clean the thermostat screen.
Humidification Control
If you have a humidifier and outdoor temperature sensor, you
can use Frost Control to reduce window condensation.
1. Press MORE until the humidifier screen is displayed.
2. Press the Up or Down arrow to set the humidity and
Frost Control level. (Use a lower Frost Control level if
frost appears on windows. Use a higher setting if the air
is too dry.)
3. Press DONE to save and exit, or press CANCEL to exit
without saving changes.
NOTE: If you do not have an outdoor temperature sensor, the
Frost Control level will not be displayed.
Dehumidification Control
If installed to control a dehumidifier, the thermostat can activate
it as needed to reduce humidity.
2968-0287—1
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
MON
WED
THU
FRISSAA
HEAT
SCHED
HOLD
SCHED
HOLD
SCHED
HOLD
If you don’t have a dehumidifier, the thermostat activates the
air conditioner to reduce humidity (may cool as much as 3°F
lower than your temperature setting).
1. Press MORE until the dehumidifier screen is displayed.
2. Press the Up or Down arrow to set the desired humidity
level and operation (Auto or Off).
3. Press DONE to save and exit, or press CANCEL to exit
without saving changes.
Ventilation Control
You can ventilate your home at any time:
1. Press MORE until the ventilation screen is displayed.
2. Press the Up or Down arrow to set the ventilation timer.
You can set the timer to ventilate from 20 to 180 minutes,
in 20-minute increments. To turn off the ventilator, select
0.
3. Press DONE to save and exit, or press CANCEL to exit
without saving changes.
If programmed for auto-ventilation by the installer, the
thermostat will ventilate your home as needed.
Indoor Air Quality Reminders
Filter Change Reminder
The filter change reminder must be turned on from the Installer
Setup. Once expired, the screen flashes, “Change Filter” and a
Reset key appears. Press the Reset key to reset the change
reminder. The installer can configure the Filter Change
Reminder to display remaining run-time or calendar days.
1. Press the More key until the filter reminder appears on
the screen. This is the number of fan run-time or calendar days remaining on the filter reminder.
TUEWEDTHUFRISATSUN
MON
CHANGE FILTER UV LAMP HUMIDIFIER PAD
RESET
DAYS
SCHED
HOLD
CLOCK SCREEN MORE
DONE
WAKE
LEAVE RETURN SLEEPEDITCANCEL
M22449
2. Press the Edit key.
3. Use the Up and Down keys to change the number of run-
time or calendar days.
TUEWEDTHUFRISATSUN
MON
CHANGE FILTER UV LAMP HUMIDIFIER PAD
DAYS
TUEWED
MON
OK TO PICK MULTIPLE DAYS SCREEN LOCKED
CHANGEFILTER UV LAMP HUMIDIFIER PAD
FAN
Inside
AUTO
SYSTEM
RESET
HEAT
COOL
SCHEDHOLD CLOCK SCREEN MORE
THU
FRI
Set To
Following
Schedule
PM
Humidity
NOTE: When using run-time days, the days are counted as
fan run time, so anytime the fan is running, the
reminder is counting that time against the number of
days selected.
The remaining days can be viewed by pressing the More key;
the remaining days can be edited using the More key or from
the Installer Setup. To view or reset the reminder before it
expires, follow these steps using the More key:
SUN
M23511
SCHED
HOLD
CLOCK SCREEN
DONE
WAKE
LEAVE RETURN SLEEP CANCEL
M22450
4. Press the Done key to go back to the viewing screen.
TUEWEDTHUFRISATSUN
MON
CHANGE FILTER UV LAMP HUMIDIFIER PAD
RESET
DAYS
SCHED
HOLD
CLOCK SCREEN MORE
DONE
WAKE
LEAVE RETURN SLEEPEDITCANCEL
M22449
68-0287—130
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
SCHED
HOLD
SCHED
HOLD
SCHED
HOLD
5. Press the Reset key to activate the new number of days
selected in the previous screen.
TUEWEDTHUFRISATSUN
MON
CHANGE FILTER UV LAMP HUMIDIFIER PAD
RESET
DAYS
SCHED
HOLD
CLOCK SCREEN MORE
DONE
WAKE
LEAVE RETURN SLEEPEDITCANCEL
M22451
6. Press the Done key to return to the Home screen.
Humidifier Pad Reminder
The Humidifier Pad change reminder must be turned on from
the Installer Setup. Once expired, the screen flashes, “Change
Humidifier Pad” and a Reset key appears. Press the Reset key
to reset the change reminder.
The remaining calendar or run time days can be viewed by
pressing the More key. The remaining days can be edited
using the More key or from the Installer Setup.
TUEWEDTHUFRISASUN
MON
CHANGE FILTER UV LAMP HUMIDIFIER PAD
RESET
DAYS
NOTE: While the reminder is set according to calendar days,
the display shows the equivalent run time days.
TUEWEDTHUFRISASUN
MON
CHANGE FILTER UV LAMP HUMIDIFIER PAD
RESET
DAYS
SCHED
HOLD
CLOCK SCREEN MORE
DONE
WAKE
LEAVE RETURN SLEEPEDITCANCEL
M23517
The remaining days can be edited using the More key or from
the Installer Setup. To view or reset the reminder before it
expires, follow these steps using the More key:
1. Press the More key until the UV Lamp change reminder
appears on the screen. This is the number of run time
days remaining on the UV Lamp reminder.
2. Press the Edit key.
3. Use the Up and Down keys to change the number of cal-
endar days.
4. Press the Done key to go back to the viewing screen.
5. Press the Reset key to activate the new number of days
selected in the previous screen.
6. Press the Done key to return to the Home Screen.
Temperature Recovery
The thermostat feature, Adaptive Intelligent Recovery™,
eliminates all guesswork when setting the thermostat schedule.
Simply set the program schedule to the time that the comfort
temperature is desired. The thermostat then turns on the
heating or cooling at just the right time to have the home reach
the scheduled temperature at the scheduled time.
SCHED
HOLD
CLOCK SCREEN MORE
DONE
WAKE
LEAVE RETURN SLEEPEDITCANCEL
To view or reset the reminder before it expires, follow these
steps using the More key:
1.
Press the More key until the Humidifier Pad change
reminder appears on the screen. This is the number of
calendar days remaining on the Humidifier Pad reminder.
2. Press the Edit key.
3. Use the Up and Down keys to change the number of cal-
endar or run time days.
4. Press the Done key to go back to the viewing screen.
5. Press the Reset key to activate the new number of days
selected in the previous screen.
6. Press the Done key to return to the Home Screen.
UV Lamp Reminder
The UV Lamp change reminder must be turned on from the
Installer Setup. Once expired, the screen flashes, “Change UV
Lamp” and a Reset key appears. Press the Reset key to reset
the change reminder.
The remaining calendar days can be viewed by pressing the
More key.
M23516
For example—get up at 6:00 AM and want the temperature to
be 70°F. Set the Wake period for 6:00 AM and 70°F. The
thermostat then turns on the heat before 6:00 AM to raise the
temperature to 70°F by 6:00 AM.
The thermostat alerts that the heating or cooling system is
coming on before a scheduled time by showing “Recovery” on
the screen.
TUE
FAN
Inside
AUTO
SYSTEM
COOL
SCHEDHOLD CLOCK SCREEN MORE
3168-0287—1
PM
Set To
Following
Schedule
Recovery
Humidity
M23512
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
NOTE: It takes about a week for the thermostat to adjust to
local weather, the schedule, the construction of the
home and the heating and/or cooling system. Each
day it adjusts the next day’s recovery start time
accordingly.
P+I Control
The thermostat microprocessor-based control requires that the
user understands temperature control and thermostat
performance. A conventional mechanical or electronic
thermostat does not control temperature precisely at setpoint.
Typically there is an offset (droop) in the control point as the
system load changes. This is a phenomenon that most people
in the industry know and accept. Many factors contribute to
offset including switch differential, thermal lag, overshoot, cycle
rates and system load.
The thermostat microprocessor simultaneously gathers,
compares and computes data. Using this data, it controls a
wide variety of functions. The special proprietary algorithm
(program) in the thermostat eliminates the factors causing
offset. This makes temperature control more accurate than the
conventional mechanical or electronic thermostats. The
temperature control algorithm is called proportional plus
integral (P+I) control.
The thermostat sensor, located on the thermostat or remote,
senses the current space temperature. The proportional error
is calculated by comparing the sensed temperature to the
programmed setpoint. The deviation from the setpoint is the
proportional error.
The thermostat also determines integral error, which is a
deviation based on the length of error time. The sum of the two
errors is the (P+I) error. The cycle rate used to reach and
maintain the setpoint temperature is computed using the P+I.
The addition of the integral error is what differentiates the
thermostat from many other electronic and mechanical
thermostats. See Fig. 33.
THERMOSTAT
COOL SETPOINT
PROPORTIONAL COOL
CONTROL POINT
P+I CONTROL
POINT
P+I CONTROL POINT
TEMPERATURE
10050050100
PROPORTIONAL HEAT
CONTROL POINT
THERMOSTAT
HEAT SETPOINT
HEATING
PERCENT LOAD
COOLING
M4414
Minimum Off-Timer
The Thermostat has built-in compressor protection (minimumoff timer) that prevents the compressor from restarting too
early after a shutdown. The minimum-off timer is activated after
the compressor turns off.
If there is a call during the minimum-off timer, the thermostat
shows “Wait” in the display.
WED
FAN
Inside
AUTO
SYSTEM
HEAT
AM
COOL
SCHED HOLD CLOCK SCREEN MORE
PM
When the minimum-off timer expires, “Cool On” or “Heat On”a
appears in the display and the compressor and fan turn on.
_________
a
Heat Pumps only.
Inside Humidity Level
The humidity level in the home is shown in the lower right
corner of the Home Screen.
NOTE: If an outdoor temperature sensor is present, the out-
door temperature will be displayed in this location
rather than the indoor humidity. To see indoor humidity, display the humidity settings menu.
TUE
FAN
Inside
AUTO
SYSTEM
COOL
SCHED HOLD CLOCK SCREEN MORE
PM
Set To
Set
Wait
Following
Schedule
Humidity
Following
Schedule
Humidity
M23513
M23678
Fig. 33. Proportional temperature control versus P+ I
temperature control.
68-0287—132
If thermostat is set to Auto Changeover System mode, press
the More key until the humidity level is shown on the screen.
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
SCHED
HOLD
MON
UE
THUSASUN
O
de
Se
o
TUEWEDTHUFRISASUN
MON
Inside
SCHED
HOLD
CLOCK SCREEN
DONE
WAKE
LEAVE RETURN SLEEP CANCEL
M23679
C7089U1006 Outdoor Temperature Sensor
Operation
When installed with Thermostat Installer Setup Number 0342
set to 1, the outside temperature can be displayed on the
thermostat. See Fig. 34.
T
Insi
AUT
SYSTEM
HEAT
SCHED HOLD CLOCK SCREEN MORE
Fig. 34. Outside temperature reading on
VisionPRO
AM
®
The C7089U1006 Outdoor Sensor converts outdoor ambient
temperature to a resistance that the thermostat can interpret.
The C7089U1006 has a negative temperature coefficient
(NTC), which means that resistance decreases as the
temperature increases. See Table 12.
Checkout
Allow C7089U1006 Outdoor Sensor to absorb outdoor air for a
minimum of twenty minutes before taking a reading.
With an accurate thermometer (±1°F [0.5°C]) measure the
temperature at the sensor location, allowing time for the
thermometer to stabilize before reading.
To verify sensor resistance, remove one wire from one of the
C7089U1006 60-in. leadwires. Use an ohmmeter to measure
the resistance across the sensor. Then verify the sensor
accuracy with the temperature/resistance in Table 12.
Calibration
The C7089U1006 Outdoor Sensor is calibrated at the factory
and cannot be recalibrated in the field.
t T
Following
Schedule
Outside
M22453
IAQ Thermostat.
Table 12. Sensor Resistance at
Outdoor Temperature.
Outdoor
Temp erature
Ohms of
Resistance
Outdoor
Temp erature
Ohms of
Resistance°F°C°F°C
-20-28.91069265211.117136
-18-27.81009235412.216387
-16-26.7953105613.315675
-14-25.6900585814.414999
-12-24.4851246015.614356
-10-23.3804856216.713743
-8-22.2761376417.813161
-6-21.1720606618.912607
-4-20.0682376820.012081
-2-18.9646317021.111578
0-17.8612467222.211100
2-16.7580667423.310644
4-15.6550777624.410210
6-14.4533587825.69795
8-13.3495988026.79398
10-12.2470928227.89020
12-11.1447328428.98659
14-10.0425068630.08315
16-8.9403948831.17986
18-7.8384009032.27672
20-6.7365199233.37372
22-5.6347439434.47086
24-4.4330639635.66813
26-3.3314759836.76551
28-2.22997510037.86301
30-1.12855810238.96062
320.02721910440.05834
341.12594910641.15614
362.22474910842.25404
383.32361311043.35203
404.42253711244.45010
425.62151611445.64826
446.72054611646.74649
467.81962611847.84479
488.91875412048.94317
5010.017926—
C7189U1005 Remote Indoor Temperature
Sensor
Operation
When installed with Thermostat Installer Setup Number 0340
set to 1, the remote inside temperature is displayed on the
thermostat home screen as Inside Temperature. The
thermostat internal temperature sensor is not used. When
3368-0287—1
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
installed with Thermostat Installer Setup Number 340 set to 2,
the temperature displayed on the thermostat home screen as
Inside Temperature will be a 50/50 average between the
temperature sensed at the remote sensor location and the
temperature sensed at the thermostat location.
The C7189U1005 Wall Mount Temperature Sensor converts
room temperature to a resistance that the thermostat can
interpret.
The C7189U1005 has a negative temperature coefficient
(NTC), which means that resistance decreases as the
temperature increases. See Table 13.
The C7189U1005 can be used to provide one remote sensor
input (see Fig. 26) or as a temperature averaging network with
multiple C7189U1005 Sensors connected, as shown in Fig. 27.
Checkout
For best results, allow C7189U1005 Wall Mount Temperature
Sensor to absorb the air moving through the room for a
minimum of twenty minutes before taking a resistance
measurement.
With an accurate thermometer (±1°F [0.5°C]) measure the
temperature at the sensor location, allowing time for the
thermometer to stabilize before reading.
To verify sensor resistance, remove one wire from one of
C7189U1005 wiring terminals. Use an ohmmeter to measure
the resistance across the sensor. Then verify the sensor
accuracy with the temperature/resistance in Table 13.
Calibration
The C7189U1005 Wall Mount Temperature Sensor is
calibrated at the factory and cannot be recalibrated in the field.
Table 13. Sensor Resistance at Room Temperature.
Room
Temperature
404.4225377222.211100
425.6215167423.310644
446.7205467624.410210
467.8196267825.69795
488.9187548026.79398
5010.0179268227.89020
5211.1171368428.98659
5412.2163878630.08315
5613.3156758831.17986
5814.4149999032.27672
6015.6143569233.37372
6216.7137439434.47086
6417.8131619635.66813
6618.9126079836.76551
6820.01208110037.8 6301
7021.111578—
Ohms of
Resistance
Room
Temp erature
Ohms of
Resistance°F°C°F°C
COMMUNICATION ERROR CODES
VisionPRO® IAQ can alert the homeowner and installer to
problems with the HVAC equipment, thermostat, or equipment
interface module by using error codes. Please see Table 14 for
a list of error codes. When an error is active (the condition
causing the error is still present) it will be displayed in the time
field on the thermostat home screen. The home screen can
display up to 5 active errors. The time field will flash the time,
“Err,” and a list of up to 5 error codes, beginning with the most
critical, and repeat until the errors have been remedied.
A log of error codes can be viewed at the end of the installer
setup after the system tests. Active errors will be shown first.
The Error Log will log the last ten errors (active and inactive).
Pressing the reset button will clear all inactive errors from the
error log; active errors can not be cleared until the condition
has been remedied.
Table 14. VisionPRO® IAQ Error Codes.
Error CodeMeaning
027Faulty thermostat (must be replaced
036Duplicate UV timer
037Duplicate filter timer
038Duplicate humidifier pad timer
039Duplicate indoor humidity sensor
040Compressor should be running but it is not
050Duplicate outdoor temperature sensor
052Faulty post-coil air discharge sensor
053Faulty outdoor temperature sensor
054Faulty indoor humidity sensor
089Heating/cooling equipment is missing
090Data interface is continuously busy
091Thermostat is not receiving data from other
equipment
118Faulty discharge air temperature sensor
119Faulty temperature sensor
121Duplicate post-coil air discharge sensor
68-0287—134
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
TROUBLESHOOTING
Table 15. Troubleshooting.
SymptomPossible CauseAction
Display does not come onThermostat is not being poweredCheck if the thermostat is mounted and latched on the wall
plate. If not:
— Mount and latch the thermostat on the wallplate.
Check if the circuit breaker is tripped or the fuse is blown; if
it is:
— Reset the circuit Breaker or replace the fuse.
Check if the power switch at the equipment is in the off
position; if it is:
— Set to the on position.
Check for 24 Vac between terminals 2 and 3 at the
thermostat.
— Replace any broken wires if 24Vac is not present.
— Replace thermostat if 24Vas is present.
Check for 24 Vac between terminals R and C at the
Equipment interface module.
— If 24Vac is not present consult electrician.
— If 24 Vac is Present replace Equipment interface
module.
Temperature setting does not
change
Heating or cooling does not
come on and thermostat is not
calling for heat or cool.
Heating or cooling does not
come on and thermostat is
calling for heat or cool.
Heat does not turn on (“Heat On”
is solid in the display)
The upper and lower temperature
limits reached
Keypad is fully lockedCheck Installer Setup Number 670 to change keypad
Thermostat minimum off timer is
activated
System selection is not set to Heat
or Cool
Heating or cooling equipment is not
operating
Heating Equipment failureCheck for 24 Vac at the equipment on the secondary side
Loose or broken wire connection
between Equipment Interface
Module and heating equipment.
Communication is not being
completed
Check temperature setpoints.
Check installer setup Numbers 0600 and 610; modify as
needed.
locked options.
Wait up to 5 minutes for the system to respond (Wait is
displayed on the Thermostat home screen.
Set system selection to correct setting.
Check Wiring.
Check installer setup number 172 and verify the correct
system type is chosen.
Verify operation of equipment in system test mode.
of the transformer between power and common. If voltage
is not present check the heating equipment to find the
cause of the problem.
Check for 24 Vac between the heat terminal(s) on the
equipment interface Module and transformer common. If
present check heating equipment to find the cause of the
problem.
Check for 24 Vac between the heat terminal(s) on the
HVAC equipment and system transformer common. If
voltage is not present check for loose or broken wires
between the EIM and heating equipment.
End the call for heat at the thermostat then repeat the call
for heat. Check the communication LED on the EIM board.
— If the LED does not blink, check communication
wiring (wire between terminal 1 on both the EIM
and thermostat.
— If the LED does blinks correctly, check for 24 Vac
between heating terminals on the EIM and the sys-
tem common.
If 24 Vac is not present check the R to Rh connection on
the EIM, if the connection is good replace the EIM.
3568-0287—1
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
Table 15. Troubleshooting. (Continued)
SymptomPossible CauseAction
Cooling does not turn on (“Cool
Cooling Equipment failureCheck for 24 Vac at the equipment on the secondary side
On” is solid in the display)
Loose or broken wire connection
between Equipment Interface
Module and cooling equipment.
Communication is not being
completed
2nd stage heat or cool does not
energize
Stage configuration is not set
correctly to match the number of
selected stage
Terminals not connected properly at
EIM
“Err” appears in time field of
home screen on thermostat
Fan does not turn on in a call for
heat (electric furnace).
Heat pump puts out cool air in
the heat mode and warm air in
the cool mode.
Thermostat has detected an error
on the communication bus
Fan Control in Heating is set to Gas
or Oil Furnace (Setting 0180).
Changeover Valve (Installer Setup
Number 0190) is not configured to
match the changeover required by
the installed heat pump.
Both the heating and cooling
equipment are running at the
same time.
The heating equipment is not a heat
pump but the System Type (Installer
Setup Number 0172) is set to Heat
Pump.
Heating and cooling wires are
shorted together.
Heating equipment is running in
the cool mode.
Heating equipment is not a heat
pump but System Type (Installer
Setup Number 0172) is set to Heat
Pump.
Heating equipment does not turn
off and heat temperature setting
is set below room temperature
(Heat On is not in the display).
Cannot set the system setting to
Heat.
Heating equipment is not a heat
pump but System Type (Installer
Setup Number 0172) is set to Heat
Pump.
System Type (Installer Setup
Number 0172) is set to Cool Only.
of the transformer between power and common. If voltage
is not present check the cooling equipment to find the
cause of the problem.
Check for 24 Vac between the cool terminal(s) on the
equipment interface Module and transformer common. If
present check cooling equipment to find the cause of the
problem.
Check for 24 Vac between the cool terminal(s) on the
cooling equipment and system transformer common. If
voltage is not present check for loose or broken wires
between the EIM and cooling equipment.
End the call for cool at the thermostat then repeat the call
for cool. Check the communication LED on the EIM board.
— If the LED does not blink, check communication
wiring (wire between terminal 1 on both the EIM
and thermostat.
— If the LED does blinks correctly, check for 24 Vac
between heating terminals on the EIM and the sys-
tem common.
If 24 Vac is not present check the R to Rh connection on
the EIM, if the connection is good replace the EIM.
Set the stage configuration in installer setup for additional
stages of cool (ISU 174) or additional stages of heat (ISU
176).
Check that 24 Vac is present at W2/AUX and W3/AUX2 for
2nd and 3rd stages of conventional heating and for 3rd and
4th stages of heat pump heating. Also check that 24VAC is
present at Y2 for 2nd stage of cooling or 2nd stage heat in
heat pump applications.
Refer to error code section for more information.
Set Fan Control in Heating to Electric Furnace (Setting
0180).
Set Changeover Valve (Installer Setup Number 0190) to
match the changeover required by the installed heat pump.
Set System Type (Installer Setup Number 0172) to match
the installed heating and/or cooling equipment.
Separate the shorted heating and cooling wires.
Set System Type (Installer Setup Number 0172) to match
the installed heating and/or cooling equipment.
Set System Type (Installer Setup Number 0172) to match
the installed heating and/or cooling equipment.
Set System Type (Installer Setup Number 0172) to match
the installed heating and/or cooling equipment.
Cannot set the system setting to
Cool.
System Type (Installer Setup
Number 0172) is set to Heat Only or
Heat Only with Fan.
68-0287—136
Set System Type (Installer Setup Number 0172) to match
the installed heating and/or cooling equipment.
Table 15. Troubleshooting. (Continued)
SymptomPossible CauseAction
Heat On is not in the display.System setting is not set to Heat
and/or temperature setting is not set
above room temperature.
Cool On is not in the display.System setting is not set to Cool
and/or the temperature setting is
not set below room temperature.
Wait is in the display.Compressor minimum off timer is
active.
“Screen Locked” appears on the
screen and all or some of the
The keypad is fully or partially
locked.
keys do not respond.
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
Set the system setting to Heat and set the temperature
setting above the room temperature.
Set the system setting to Cool and set the temperature
setting below the room temperature.
Wait up to five minutes for the cooling or heating (heat
pump) equipment to turn on.
Check Installer Setup Number 0670 to change keypad
locked options.
3768-0287—1
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
COMPATIBILITY
Recommend the following products for use with the VisionPRO® IAQ.
Table 16. Humidifiers
HE440A1005—Powered Steam Humidifier with 13 gpd capacity
HE365A1006—Powered Bypass Flow-through humidifier with 18 gpd capacity
HE265A1007—Bypass Flow-through humidifier with 17 gpd capacity
HE225A1006—Bypass Flow-through humidifier with 12 gpd capacity
Table 17. Dehumidifier
DH90A1007—90 Pint Whole House Dehumidifier
Table 18. Ventilation
HR150B1005—heat recovery ventilator 150cfm with built in defrost
HR200B1005—heat recovery ventilator 200cfm with built in defrost
ER150B2006—energy recovery ventilator 150cfm with built in defrost
ER150C2004—energy recovery ventilator 150cfm with no defrost
ER200B2006—heat recovery ventilator 200cfm with built in defrost
ER200C2004—heat recovery ventilator 200cfm with no defrost
EARD5—5” round damper NC Power Open/Spring Close
EARD6—6” round damper NC Power Open/Spring Close
EARD7—7” round damper NC Power Open/Spring Close
EARD8—8” round damper NC Power Open/Spring Close
Following is a list of compatible communicating products.
Table 19. Communicating Products
THM5421C—Equipment Interface Module Universal up to 4H2C systems
T8635L1013*—3H3C communicating Thermostat
W8635A1006—Equipment Interface Module for 2H2C conventional systems
W8635B1004—Equipment Interface Module for 2H2C heat pump systems
W8735A1005—EnviraCOM Serial Port Adapter
W8735B1003—Telephone Access Module
W8735D1009—Telephone Access Module two Channel communicating
W8735D1017—Telephone Access Module four channel communicating
W8835A1004—Envirazone Zone Panel
C7835A1009—Communicating Discharge Air Sensor
W8703A1003—Damper Interface Module
L7224C1004—120VAC Electronic Aquastat
L7248—Aquastat
R7184—Oil Primary
* T8635L thermostats used with TH9421C thermostats must be used with a W8835A Zone Panel and the TH9421C must be the
Master Zone Controller (zone 1 thermostat)
Table 20. UV Lights
UV100E2009
UV100E1043
UV100E3007
68-0287—138
VISIONPRO® IAQ TOTAL HOME COMFORT SYSTEM
3968-0287—1
VISIONPRO
®
IAQ TOTAL HOME COMFORT SYSTEM
Automation and Control Solutions
Honeywell International Inc.Honeywell Limited-Honeywell Limitée