T1000 Series
Thera-100
RADIATOR THERMOSTATS
PRODUCT DATA
Application
Design
The radiator thermostat consists of:
•Handwheel with lid, socket and red economy button
•Honeywell HW M30 x 1.5 connection and 11.5 mm closing dimension
•Sensor with support cage
•Wax sensor
•Spindle assembly
•Connection nut
Materials
•Handwheel socket and lid made of plastic, white to RAL9016
•Economy button made of red plastic
•Socket, support cage and spindle assembly made of plastic
•Sensor filled with wax
•Connection nut made of nickel-plated brass
A Radiator Thermostat is installed onto a Thermostatic Radiator Valve Body (TRV body). The combination of both, the Thermostatic Radiator Valve (TRV), controls the room temperature by adjusting the flow of hot water through a radiator.
TRVs are installed in water-based heating systems on the supply or, less commonly on the return connection of radiators.
Radiator thermostats of this type fulfill the European Standard EN 215 when used with certified Honeywell TRV bodies.
Honeywell radiator thermostats with Honeywell (HW) M30 x 1.5 connection are suitable for all TRV body and radiator inserts with M30 x 1.5 connection and 11.5 mm closing dimension.
Features
•Conforms with M30 x 1.5 connection to European standard EN 215
•Equipped with wax sensor
•Over-temperature protection
•Modern, ergonomical design with red economy button for optimal setting
•Compact size
Specifications
Thermostat connection M30 x 1.5
Setpoint range |
0 - - 1..6 |
Temperature range |
1...26°C (34...79°F) |
Closing dimension |
11.5 mm |
Function
Radiator thermostats of this type control the TRV body. The air passing around the sensor of the radiator thermostat causes the sensor to expand when the temperature rises. The expanding sensor closes the TRV accordingly. When the room temperature changes the TRV opens or closes proportionally. Only the amount of water required to maintain the room temperature set on the radiator thermostat is allowed to flow through the valve.
Honeywell y Subject to change |
EN0H-2018GE25 R0109 |
T1000 SERIES THERA-100
Dimensions and Ordering Information
ØD1
H
Fig. 1. Dimensions
Table 1. Dimensions
Type |
H closed |
H open |
ØD1 |
Thera-100 |
76.8 |
82.5 |
50 |
NOTE: All dimensions in mm unless stated otherwise.
Table 2. Available versions and OS-Nos (OS=Ordering Specification)
Type |
EN215 |
Connection |
OS-No. |
|
certification |
|
|
Thera-100 |
• |
M30 x 1.5 |
T1002W0 |
|
• |
M30 x 1.5 |
T1002W0GB |
EN215 Information
All radiator thermostats of this type with M30x1.5 connection in connection with certified Honeywell TRV bodies conform to the European Standard EN215.
Table 3. Comparison of radiator thermostats of this type specs and EN 215 requirements
|
Thera-100 |
EN215 |
|
with wax sensor |
requirements |
Min. setpoint temperature |
6°C (43°F) |
5...12°C (41...54°F) |
Max. setpoint temperature |
26°C (79°F) |
≤ 32°C (90°F) |
Hysteresis |
0.8 |
≤ 1.0K |
Influence of differential pressure |
0.7 |
≤ 1.0K |
Influence of static pressure |
0.8 |
≤ 1.0K |
Influence of heating medium |
0.7 |
≤ 1.5K |
Response time |
20 min. |
≤ 40 min. |
NOTE: All °C- and °F-values specified at ideal incident flow. This can differ from stated values depending on installation position and air flow.
NOTE: Influence of differential pressure depends on TRV body used.
Setpoint
Table 4. Setpoint temperature
Setpoint |
0 |
|
1 |
2 |
3 |
4 |
5 |
6 |
°C |
1 |
6 |
11 |
14 |
17 |
20 |
23 |
26 |
°F |
34 |
43 |
52 |
57 |
63 |
68 |
73 |
79 |
NOTE: All °C and °F-values approximate. Heating can freeze when radiator thermostats with zero-position are set at position '0'. Zero-position is also thermostatically controlled - when temperature falls the TRV may open.
EN0H-2018GE25 R0109 |
2 |