Flowserve Valtek StarPac 1 Intelligent Control Systems User Manual

Valtek StarPac Intelligent Control Systems
GENERAL INFORMATION
The following instructions are designed to assist in unpacking, installing and performing maintenance as required on Valtek® StarPac® Intelligent Control Sys­tems. Product users and maintenance personnel should thoroughly review this bulletin prior to installing, operat­ing, or performing any maintenance on the valve.
More detailed installation, maintenance and opera­tion instructions are included in the StarPac manual; refer to it when more information is needed.
Separate Flowserve Installation, Operation and Main­tenance (IOM) manuals cover the valve (IOM 1 or IOM
27), actuator (IOM 2 or IOM 31) and positioner (IOM 45) portions of the system and other accessories. Refer to the appropriate instructions when this information is needed.
To avoid possible injury to personnel or dam-
age to valve parts, WARNING and CAUTION notes must be strictly adhered to. Modifying this product, substituting non-factory parts, or inferior parts, or using maintenance procedures other than outlined could drastically affect per­formance and be hazardous to personnel and equipment, and may void existing warranties.
WARNING: Standard industry safety practices must be adhered to when working on this, or any other, process control product. Specifically, personal protective and lifting devices must be used as warranted.
Unpacking
1. While unpacking the StarPac system, check the packing list against the materials received. Lists describing the system and accessories are in­cluded in each shipping container.
2. When lifting the system from the shipping con­tainer, position lifting straps to avoid damage to tubing and mounted accessories. Valves up through 6-inches may be lifted by the actuator lifting ring. On larger systems, lift unit using lifting straps or hooks through the yoke legs and outer end of body.
WARNING: When lifting a valve/actuator as­sembly with lifting straps, be aware the center of gravity may be above the lifting point. There­fore, support must be given to prevent the valve/actuator from rotating. Failure to do so can cause serious injury to personnel or dam­age to nearby equipment.
3. In the event of shipping damage, contact the ship­per immediately.
4. Should any problem arise, contact a Flowserve representative.
INSTALLATION Valve Installation
The StarPac Intelligent Control System valve is in­stalled in the same manner as a conventional control valve and according to industry standards. Refer to the appropriate valve installation, operation, maintenance instructions for proper installation procedures.
If the StarPac system is being installed in an insulated process line, do not place more than four inches of insulation around the StarPac pressure or temperature sensors; otherwise the sensors may not operate properly. In addition, NEVER insulate the StarPac electronics assembly or remote-mounted temperature/ pressure sensors (when used).
CAUTION: Do not insulate the StarPac electronics housing or remote-mounted pressure or tempera­ture sensors; otherwise excessive heat may build up and affect operation.
41-1Valtek No. 125694
Valtek StarPac
Valtek StarPac
Figure 1: Shielded Wire Diagram
Wiring and Grounding Guidelines
This section will help achieve a maximum 'noise-free' environment and performance with a StarPac unit.
Shielding Versus Grounding
All signals to the StarPac system should be in shielded cables. Shields must be tied to a ground at only one end of the cable to provide a place for environmental elec­trical noise to be removed from the cable. A ground wire unlike a shield is attached at both ends to provide a continuous path for electrical conductivity.
Grounding Screw
The green grounding screw by the user interface termi­nal block should be used to provide the unit with an adequate and reliable earth ground reference. This ground should be tied to the same ground as the electrical conduit. Additionally, the electrical conduit connecting to the StarPac unit should be earth grounded at both ends of its run. The green grounding screw
must not be used to terminate signal shield wires. 24VDC Power
The 24VDC connection points will work best with shielded twisted pair wire with the shield wire con­nected only at the source. The input power is isolated within the StarPac system and may be referenced to whatever level is necessary. The 24VDC power sup-
ply should not be connected to earth ground. RS-485 Communication
RS-485 wiring requires the use of a shielded twisted pair cable, which is grounded only at the source and not in the StarPac unit. (For maximum performance, wire should have a characteristic impedance of 120 ohms.) These signals are referenced to the StarPac internal system ground; hence this is the main fault path should
one of the isolation points fail. Therefore, care must be taken to ensure the RS-485 cable is wired correctly.
The RS-485 allows only a 7 to 12V common mode voltage differential between stations. Flowserve's Valtek RS-232 to RS-485 converter is not a grounded connection. PCs with internal RS-485 cards, on the other hand, are often grounded. If another ground communication device is on the network, a fault condi­tion will almost certainly exist due to transient and steady state differences in ground potential.
4 - 20 mA Command Input, Auxiliary Input, and Feedback Output
These signals are isolated, but shielded twisted pair wire should be used to reduce crosstalk from other signals. The shield should be connected only at the source.
4 - 20 mA I/P Output
This signal is not isolated from the StarPac internal system ground and will provide a fault path if the I/P or connecting wires become grounded. Shielded twisted pair wire should be used with the shield connected in I/P.
Discrete Inputs and Outputs
These signals are isolated, but because they are fre­quently used to switch high voltage (120VAC), they should be run in separate shielded wire paths away from the other StarPac signals.
AIB and RS-232 to RS-485 Converter Connection
When connecting a StarPac system to a communica­tion device, no shield or ground connections exist. Hence, the 24VDC power and RS-485 communication shield drain wires must be connected to a convenient ground near the AIB or converter.
41-2 Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
XL Positioner
Positioner Sensor Arm
User Access Terminal Cap
Actuator Pressure Sense Tubing
Electronics Housing
Actuator Pressure Gauges
I/P Module
Electrical Conduits
Thermocouple
Figure 2: StarPac Intelligent Control System Components
Wiring The StarPac System
All electrical connections must be done according to local and industry electrical codes. Flowserve recom­mends a shielded cable be used for the RS-485 com­mand signal wire (i.e., Belden 9841 or equivalent).
When connecting multiple StarPac systems, a parallel daisy-chain wiring pattern is used. Connect the StarPac branch lines to the main line, keeping branch lines as short as possible. The total length of wiring should not exceed 4,000 feet (1,200 meters) without the use of repeaters.
Avoid devices producing electrical 'noise' while installing the cable.
CAUTION: The following procedure should be performed on the bench or with the unit isolated so that unexpected valve stroking will not adversely affect the process.
WARNING: The following procedures may cause the valve to stroke, causing pressures and temperatures to vary from their norms. Notify appropriate personnel that the valve may stroke unexpectedly. Flowserve suggests that the system be isolated from the process, if installed in line.
Four StarPac system models are available: SP, SPJS SPJD and NT. The electronics model for a system is most easily identified by the face plate of the local display. If the black cover of the face plate has printed information with an 'ABC' table for the display para­meters, the system contains SP electronics package.
4/20 mA Electrical
Local Display
Process Pressure Sensors
Conduit
If the black cover of the face plate shows only the StarPac and Valtek logos, the system is an SPJS, SPJD, or NT unit. The SPJS and SPJD models are identical except that the SPJD version has two Modbus ports. To tell the difference, remove the cover on the user access terminal. If the user interface terminal block has 18 connections, the unit is a SPJS electronics package; if the terminal block has 20 connections, it is the SPJD or NT package.
resU
ledoM yalpsiDlacoL
ecafretnI
kcolB
PS ylnOciremuN slanimreT81 klaTratS
SJPS ciremunahplA slanimreT81 rofklaTratS
DJPS ciremunahplA slanimreT02 rofklaTratS
TN ciremunahplA slanimreT02 rofklaTratS
NOTE: StarTalk and StarTalk for Windows® interface software packages use different communication proto­cols and are not compatible. Contact a Flowserve repre­sentative for more information about upgrade options
To connect the wiring to the StarPac system, refer to Figures 1, 2, 3 and Table I, and proceed as follows.
1. Remove the StarPac user interface housing cover (small cap).
erawtfoS
swodniW
swodniW
swodniW
.
41-3Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Model SPJD, NT Model SP, SPJS
Figure 3: User Interface Terminal Pinouts
WARNING: Do not remove the electronic housing cover in flammable atmospheres; otherwise possible injury to personnel or equip­ment may occur.
2. Connect the required wires to the terminal interface block and computer as described in Figure 3 and Table I. (The system must have 24 VDC power and signal cable for operation.)
NOTE: The StarPac system remembers the oper­ating mode setting (automatic or manual) from the last time the unit had power. When power to the system is turned on again, the unit will resume operation in the previous mode.
Normally the StarPac system arrives from the fac­tory set in the manual operating mode. This means a command signal will position the valve the same as a conventional control valve, providing a plug position proportional to the 4 - 20 mA signal.
To avoid upsetting the process because of im­proper operating mode selection:
Ensure that the system arrived from the factory with the proper operating mode setting in the shop prior to installation by connecting the air supply and command signal, then turning on the power and looking at the mode value on the local display, or;
Set the proper operating mode for the particular application in the shop prior to installation by select­ing the desired operating mode from the Tuning/ Tune screen in the StarTalk software, or;
Ensure that the block valves in the process line around the StarPac system are closed and the process is diverted around the unit.
3. Turn on the 24 VDC power to the unit, and verify that the StarPac system has been correctly wired by checking the following:
24 VDC power is at least 300 mA and between
21.6 and 27.0 VDC
Table I: User Interface Terminal Connections
Signal Positive Negative
Term.No. Term. No.
24 VDC power 1 2 Valve command signal 3 4 Primary RS-485 11 18
communication link (Port A) RS-485 communication 19 20
link (second / Port B) Auxiliary input (4 - 20 mA) 17 16 Analog output (4 - 20 mA) 9 10 Discrete input 1 – switch/ 13 12
solenoid monitoring (discrete
mode source input) Discrete input 2 – switch/ 15 14
solenoid monitoring Discrete output 1 5 6
(malfunction alarm contact) Discrete output 2 (special) 7 8
Polarity is correct
Local display is on; if not, check the power supply
or reset switch The StarPac local display should now be on, indi-
cating the following:
Valve stem position
Setpoint signal
Process flow value (gas or liquid)
Temperature of process
Upstream (P1) and downstream (P2) pressures
At this point the StarPac unit is installed and will operate as a conventional control valve receiving a 4 - 20 mA command signal from a DCS, or other device, and stroking the valve accordingly.
41-4 Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Before additional work can be done with the StarPac system (configured, calibrated and operation mode changed, etc.) a RS-485 communication cable must be connected to the unit and RS-485 communica­tion port on a computer with the StarTalk software. See the StarPac manual for more information.
4. Replace the StarPac user interface housing cover.
System Default Configurations
StarPac systems are shipped from the factory ready for installation and operation. Rarely do the units need to be reconfigured prior to operation. Table II lists the factory default communication/failure mode settings. If these settings are not correct for the equipment being used, proceed to the following sections.
Table II: Factory Default Mode Settings
Description Setting
Address 1 Parity odd Baud Rate 19,200 Modbus Communication RT U
Mode RS-485 Termination Installed
Resistor
Failure Mode Setting Pass through command
signal on loss of power
Figure 4: Dip Switch Blocks
Selecting Correct Baud Rate Setting
StarPac systems support baud rates of up 57,600 baud. However, both the StarPac system and StarTalk soft­ware are shipped from the factory set to 19,200 baud.
If the default baud rate setting needs to be changed, refer to Figures 4 and 5, Table IV and Changing Communica­tion Settings section, and make the necessary change.
Selecting Correct Address Setting
If the StarPac system is the only unit on the communi­cation network, the default address (1) is acceptable.
If multiple StarPac systems will be operating on the same communication network, each unit must have a unique address. Before changing the address, use the StarTalk software to determine what other devices are on the existing line. (Remember to include devices that may be temporarily off line.)
If the default address setting needs to be changed, refer to Figures 4 and 5, Table III and Changing Communica­tion Settings section, and make the necessary change.
Selecting Correct Modbus Transmission Mode
Two transmission modes exist in a Modbus system, ASCII and RTU (default). Use the ASCII mode when transmitting information through a device that uses ASCII control codes; for example, a modem. Use the RTU mode when connecting directly to both devices; for example, an RS-485 interface card wired directly to a StarPac system.
If the default Modbus transmission mode setting needs to be changed, refer to Figures 4 and 5, Table IV and Changing Communication Settings section, and make the necessary change.
Figure 5: Dip Switches with Labels
41-5Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Dipswitch
access slot
Table III: Address Dip Switch Settings
Switch no. on address block
12345678
1
1 Adds 2 to address value
1 Adds 4 to address value
1 Adds 8 to address value
1 Adds 16 to address value
1 Adds 32 to address value
1 = up = off 0 = down = on
Adds 1 to address value
1 Adds 64 to address value
1 Adds 128 to address value
Figure 6: Dip Switch Access
Selecting Proper RS-485 Termination Resistor Setting
A termination resistor must be installed on the two most remote devices on the network, counting the host com­puter as any other device.
(For example, a single StarPac system and the RS-485 driver in the host computer would each require the termination resistor to be installed. If four StarPac systems were on the network with a host computer, decide which of the two devices have the most com­bined cable length between them. These two devices should have the termination resistors installed. The termination resistors should be disabled in the devices not considered to be the most remote using the instruc­tions in the next section. Using more than two termina­tion resistors in a network can cause the RS-485 commu­nications to operate erratically or fail.)
If the RS-485 termination resistor needs to be changed, refer to Figure 5, Table IV and Changing Communication Settings section, and make the necessary change.
Changing Communications Settings
If the StarPac system communication settings (ad­dress, parity, baud rate, Modbus transmission mode, and RS-485 termination resistor) need to be changed; refer to Figures 4 and 5 and Table IV and proceed as follows.
WARNING: Never remove the StarPac electronics housing cover in explosive atmospheres; otherwise, nearby personnel and equipment could be injured.
CAUTION: Properly ground yourself before handling the sensitive StarPac electronics; otherwise unseen damage to components may occur.
1. If the StarPac system is installed in line, make sure that taking it and the valve off line will not adversely affect the process.
NOTE: Down means toward the circuit board; up means away from the circuit board.
2. Turn off the 24VDC power to the StarPac System.
3. Remove the large cover from the StarPac electron­ics housing. (See Figure 2.)
4. Make the required dip switch changes (address, parity, baud rate, and Modbus transmission mode) according to Tables III and IV. These switches are visible through the window cut in the lower side of the shroud. (See Figure 5.)
a. The first dip switch block (marked address)
defines the Modbus address of the StarPac system using binary coded decimal numbers (switch 1 = 1; 2 = 2; 3 = 4 ; 4 = 8; 5 = 16; 6 = 32; 7 = 64; 8 = 128). The switches that are up (off condition) define the address, refer to Table III. For example, set address 11 by putting switches 1, 2, and 4 (1 + 2 + 8 = 11) up (off condition) and 3, 5, 6, 7, and 8 down (on condition).
b. The second dip switch block sets the parity,
baud rate and Modbus transmission mode.
NOTE: This block also contains initialization and reset switches described later. Parity changes are also done by using the switches marked PRTOCL 1 and 2 as shown in Table IV.
c. Set the baud rate by using the switches marked
BAUD 1, 2, and 3 as shown in Table IV.
d. Set the Modbus transmission mode with the
switch marked EXPAN. When the switch is up (off), the transmission mode is RTU. When the switch is down (on), transmission mode is ASCII.
NOTE: If the StarPac unit has a dual communication port (model SPJD or NT), the single set of DIP switches configures both ports. All of the communi­cation parameters are the same including the address of two ports. The identical address settings should not conflict because separate ports are isolated and independent for use on different networks.
41-6 Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Table IV: Protocol Dip Switch Settings
Switch Label Description
Reset
Init
Protocol 1
Protocol 2
Baud 1
Baud 2
Baud 3
Expan
0 Reset (halt processor) 1 Normal Operation *
0 Initialize on Startup 1 Normal Startup
0 0 No Parity 1 0 Even Parity 0 1 No Parity 1 1 Odd Parity *
0 0 0 Invalid 1 0 0 1200 Baud Rate 0 1 0 2400 Baud Rate 1 1 0 9600 Baud Rate 0 0 1 19200 Baud Rate * 1 0 1 31250 Baud Rate 0 1 1 38400 Baud Rate 1 1 1 57600 Baud Rate
0 ASCII Trans. Mode 1 RTU Trans. Mode *
* default factory settings
5. The jumper for the termination resistor labeled TERM (see Figure 4) is located at the end of the protocol dip switch block. Place the jumper over both pins if the termination resistor is needed, and over one pin for storage if it is not.
NOTE: If the StarPac unit has a dual communica­tion port (model SPJD or NT) the termination resis­tor jumper for the second port is located 90 degrees clockwise from the jumper described above and can only be accessed by removing the white pro­tective plastic shroud from the electronics assem­bly. Note second port jumper only needs to be set according to requirements of the second network.
6. When the required communication settings have been made, replace the white shroud (if removed) and the large StarPac electronic housing cover.
Figure 7: Removing Board Stack
the power failure setting as described below. (Refer to Figures 2, 6, 7 and 8.)
WARNING: Never remove the StarPac cover in explosive atmospheres; otherwise potential injury may result to personnel and equipment.
CAUTION: Properly ground yourself before handling the StarPac electronics; otherwise the sensitive components may be damaged.
1. If the StarPac system is currently installed in-line, make sure that the StarPac system (including valve) can be taken off line in the current process.
2. Turn off the 24-volt power supply and disconnect the supply air to the StarPac valve.
3. Remove the large electronic housing cover from the StarPac unit.
Changing the Power Failure Setting
On loss of power, the StarPac is factory set to pass the command signal to the I/P (unless ordered otherwise). This configuration causes the system to assume a traditional control valve mode and respond to an external 4 - 20 mA command signal. During loss of power and if the application warrants, the StarPac system can be configured to fail using the fail-safe spring(s) inside the cylinder actuator. This is accomplished by changing
Figure 8: NT Failure Jumper Location
41-7Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Figure 9:
Shroud Retaining Screws / Local Display
4. Remove the white plastic protective shroud from the electronic assembly by removing the two screws from the display end of the assembly. For NT units, locate the jumper I/P Bypass at the edge of Analog board number 1. (Refer to Figure 8 and proceed to step 9.)
5. Next, for SP units only, remove the third screw that holds the board stack in place.
6. Carefully grasp the computer boards and gently pull them away from the housing.
7. Locate the jumper on the bottom board (shown in Figure 8), labeled J105. Remove the jumper from the two pins and reinsert it onto only one pin for storage if wanting the valve to fail immediately per the actuator fail-safe spring configuration. To reac­tivate the manual failure mode place the jumper over the two pins labeled J105.
8. Carefully reinstall the top four computer boards onto the assembly. Be certain the computer board connector pins are lined up and securely attached to the bottom board connector. Be certain the top boards are in line with the bottom board.
9. Replace the protective shroud, install and tighten the three computer board assembly retaining screws.
10. Replace the StarPac electronics assembly cover.
Resetting or Initializing the StarPac
The 'Reset' and 'Initialize' switches are the first two dip switches on the second switch block (see Figure 4). On rare occasions it may be necessary to reset or initialize
the embedded software program on the StarPac sys­tem to stop abnormal operation or clear persistent errors. This includes errors sometimes caused by brief power interruptions, or resetting the software after changing the EPROM.
The reset switch forces the StarPac system through the startup and diagnostics sequence that the system nor­mally goes through on system power up, and it initial­izes the program execution to the starting instruction. The startup sequence also checks internal CPU regis­ters and all of the volatile and nonvolatile RAM. While initializing the system the local display shows the ver­sion number of the EPROM currently installed in the system. The last thing done by a reset is to clear and initialize the watchdog timer on the CPU.
A reset can be done by powering the unit down for five seconds or more and reconnecting the power, or by resetting the system by pushing the 'Reset' switch down (on) for five seconds and then moving the switch back up (off).
NOTE: If the reset switch is left down (on) the CPU will be halted until the switch is moved up (off).
The 'Initialize' switch (no. 2 or labeled INIT on the PC board) resets some of the internal work registers to known values and resets the EPROM checksum. The switch also sets the command or setpoint source to receive a 4 - 20 mA analog signal. The 'Initialize' switch is only accessed by the CPU during a reset.
An initialization is done by setting the INIT switch down (on) and then resetting the CPU as described above. After an initialization the system is left in the calibration mode, which is an out of service mode, meaning that the system will not respond to normal commands. StarTalk software must be used to put the system back into an operating mode. The com­mand or setpoint source must also be reset to digital if that is the normal operating source.
If the INIT switch is left down (on), the system will startup in the calibration mode each time power is lost to the unit or the Reset switch is put in the on position. This feature can be beneficial if it is desired to manually reset the system after a power outage to ensure safe startup.
If the system must be reset using the dip switch as described above or initialized, refer to Figure 4 and proceed as follows:
1. Make sure that the StarPac system and valve can be taken off line without disrupt the process.
2. Remove the large cover from the StarPac elec­tronic housing.
WARNING: Never remove the StarPac cover in explosive atmospheres; otherwise potential injury may result to personnel and equipment.
41-8 Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
3. Perform the desired actions as described above to reset or initialize the system.
CAUTION: Properly ground yourself before handling the StarPac electronics; otherwise the sensitive components may be damaged.
4. Replace the StarPac electronic housing cover.
Reading Local Display
The local display on StarPac models SPJS, SPJD or NT displays two lines of information about the system and the process. The top line of the display has two func­tions: the left side is a description of the variable displayed on the second line. The right side of the top line has information on the current mode of operation MAN = manual, AUT= automatic, and CAL = calibrate (or out of service), OVR = over range, TRP = tripped.
Figure 10: Local RS-485 Connector
The second line of the local display shows process or valve information as configured using the StarTalk II software.
An 'A' flashing on the right side of the display indicates there currently is an alarm condition. An 'E' flashing indicates an error condition. Generally at this point, these problems are caused by one or more of the following three conditions:
1. Air supply is not turned on to system
2. The 4 - 20 mA signal is not turned on, or is not being received by system.
3. The system has just been initialized or is operating in the calibration mode. The alarm signal will cease when the system is reconfigured or set to the proper mode.
For more information, refer to StarPac manual section on alarms and errors.
Adjusting Display View
The StarPac alphanumeric local display has an adjust­ment to allow some changes to the display for optimum visibility.
WARNING: Never remove the StarPac cover in explosive atmospheres; otherwise potential injury may result to personnel and equipment.
CAUTION: Properly ground yourself before handling the StarPac electronics; otherwise the sensitive components may be damaged.
This adjustment is made by removing the plastic shroud and adjusting the blue trim potentiometer until the display is visible. Replace the plastic shroud, secure in place and replace the large StarPac electronic housing when done.
Table V: Hardware Specifications
Power Supply 24 VDC ±10%, 300 mA
maximum RS-485 length Up to 4000 feet (22-26 AWG) 4–20 mA input 232 ohms, 500 V isolation 4–20 mA up to 750 ohm load, 500 V
output drive isolation Output contact 1 amp at 110 VAC (for Division
rating II areas the ratings are reduced
to 24VDC resistive load: Groups
A & B- 230 mA; Group C- 590
mA; Group D- 800 mA) Discrete inputs 26.6 kohm, 75 V DC or AC
(peak-peak) rising, 22 V DC or
AC (peak-peak) falling with
180 V maximum.
Local RS-485 Connector
A local RS-485 connector is located on the user termi­nal block (Figure 9) to allow ease of direct field interfac­ing to the StarPac system. This connection is a parallel connection to the RS-485 port terminals (11, 18) on the user interface terminal block. On StarPac models SPJD and NT, this is connected only to Port B.
NOTE: The StarPac can only communicate to one master device on a communication port. When using the local interface, one of the RS-485 screw interface wires may need to be disconnected to prevent a conflict in communications.
A plug connector is available from the factory that will allow an interface cable to be established. (Request Part No. 83213.FOT from Flowserve Advanced Prod­uct Development Group.) The connectors crimp termi­nals are made for 22-26 AWG wire. Note the correct polarity of the terminals as shown in Figure 9.
41-9Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Loading...
+ 19 hidden pages