Flowserve Valtek Position Pac User Manual

V altek Position Pac
GENERAL INFORMATION
The following instructions are designed to assist with installing, calibrating and troubleshooting the Valtek Position Pac™ valve position indicator. Product users and maintenance personnel should thoroughly review this bulletin in conjunction with the maintenance bulletin for the appropriate valve body and actuator being used.
To avoid possible injury to personnel or damage to valve parts, WARNING and CAUTION notes must be strictly adhered to. Modifying this prod­uct, substituting non-factory or inferior parts, or using maintenance procedures other than out­lined could drastically affect performance, be hazardous to personnel and equipment, and may void existing warranties.
OPERATION
Position Pac is a ‘package’ unit containing a potenti­ometer and transmitter, two or four limit switches, or a combination of a transmitter and two limit switches.
The position transmitter utilizes a potentiometer to measure the valve’s position and a transmitter circuit that sends a 4 to 20 mA electrical signal to a remote monitoring device. Position Pac will continuously trans­mit the position of a control valve as it modulates between the open and closed positions.
The limit switches in Position Pac can be independently set to indicate open, closed or any intermediate valve position.
Position Pac’s sealed construction provides protection
®
from the entry of water, dust and oil as defined by the National Electrical Manufacturers Association (NEMA) 1, 3, 3R, 4, 12 and 13. Position Pac is also explosion­proof, providing protection from flammable hydrocarbon atmospheres, metal dust, coal dust, and grain dust. It i s UL and CSA listed for Class I, Division 1, Groups B, C, D; Class II, Division 1, Groups E, F, G (See Table I). All electrical wiring should be installed per NEC articles 501-4 and 501-5.
WARNING: Keep hands, hair, clothing, etc. away from moving parts when operating the valve. Fail­ure to do so can cause serious injury.
INSTALLATION INSTRUCTIONS
The following instructions are designed to assist in the field installation of Position Pac units.
Valtek Linear Actuators
To install Position Pac on Valtek linear actuators, refer to Figures 1 and 2, and proceed as follows:
1. Remove the name plate from the yoke leg opposite from the stroke indicator plate.
2. Using the two tapped holes, attach the Position Pac mounting bracket to the yoke leg using two mounting bolts. When facing this yoke leg, the bracket will jog in towards the valve center and protrude to the left.
3. Remove the nut from the stem clamp bolting. Place the tripper bracket on the bolt so the ‘S’ shape ex­tends down. Replace the nut and tighten it firmly.
Valtek No. 62152
Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
29-1
Figure 1: Linear Application – Front View
(cover removed)
Table I: Model Configuration
ledoMnoitpircseD
2HT
ST2H
XT rettimsnartgolanA
2AT
2A sehctiwsTDPSowT 4A sehctiwsTDPSruoF
ST2A
sehctiwsTDPSdelaesyllacitem
TDPSdelaesyllacitemrehowT
hctiwslanimrethtiwsehctiws
owthtiwrettimsnartgolanA
sehctiwsTDPS
htiwsehctiwsTDPSowT
pirtslanimret
AMEN
4
-rehowthtiwrettimsnarTgolanA
2&1 )puorG(
ABCDEFG
Figure 2: Linear Application – Rear View
(cover removed)
aerAlacirtcelE
foorPnoisolpxE
noisiviDIssalC
2&1 )puorG(
noisiviDIIssalC
CELENEC
lavorppA
gnidneP
gnitaR
LUseYgnoL
LUseYgnoL
ASC/LUoNtrohS
LUoNgnoL LUoNtrohS
LUoNgnoL LUoNgnoL
delaeS
sehctiwS
gnisuoH
eziS
Table II: Linear Mounting Information
Actuator Valve Spud Kit Hole
Size Stroke Size No.* Set
(sq. in.) (inch) (inch) (Mounting)
25 0.5-1.0 2.00 37434 bottom of slot
1.5 2.00 37434 top of slot
50 0.5-2.5 2.62 37345 bottom holes
3.0 2.62 37345 top holes
100 1.0-3.5 2.62/2.88 37436 bottom holes
& larger 4.0 3.38 37630 top holes
4.0 4.75 71636 top holes
*Kit includes: bracket, arm, trip lever or stem clamp with trip lever nuts and bolts.
4. Mount Position Pac to the bracket using the mount­ing holes as specified in Table II: Insert the lever onto the switch shaft. On larger actuators (size 50 and larger) that use the adjustable lever arm, adjust the length so that the center of the roller rests on the center of the tripper bracket. To preload the Position Pac’s restoring spring, be certain the control valve is in its minimum signal position. Loosen the lever arm clamp screw with a 0.14-inch ( 9/64) hex wrench, allowing the arm to turn on the shaft. While holding the arm in contact with the bottom of the tripper bracket and using a slotted screwdriver to rotate the switch shaft perform the following (all rotation direc­tion instructions are as viewed from the lever arm side of the Position Pac):
29-2 Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Figure 3: Rotary Application – Rear View
(cover removed; air-to-close valve)
Figure 4: Rotary Application – Front View
(cover removed; air-to-close valve)
For direct-acting, air-to-open actuators, rotate the shaft counter clockwise as far as it will go, then back off approximately 5 to 10 degrees. For direct-acting, air-to- close actuators, rotate the shaft counter clock­wise approximately 5 to 10 degrees.
For reverse-acting, air-to-open actuators, rotate the shaft counter clockwise approximately 5 to 10 de­grees. For reverse-acting, air-to-close actuators, rotate the shaft counter clockwise as far as possible, then back off approximately 5 to 10 degrees. With the slot in this position, tighten lever arm clamp screw tightly (until the teller tab will not move). With this pro­cedure completed, stroke valve to ensure spring is preloaded throughout the entire valve travel.
5. To make electrical connections, remove the housing cover.
WARNING: On explosion-proof installations, disconnect electrical power or be certain the area is safe from combustible atmospheres be­fore removing the housing cover.
(Refer to the specifications in Table IV for component electrical ratings.) Attach transmitter signal wiring to the transmitter terminal block, using caution to attach the positive and negative wires to the appropriate terminal.
CAUTION: Do not apply a voltage greater than 40 volts to the transmitter terminals or the circuit will be damaged.
Attach limit switch wiring to the COMM (common) and either NC (normally closed) or NO (normally open) terminals according to the needed signal.
6. To adjust the limit switches and/or position transmit­ter, remove the housing cover and refer to the
bration
WARNING: On explosion-proof installations, disconnect electrical power or be certain the area is safe from combustible atmospheres be­fore removing the housing cover.
7. Replace the housing cover.
8. Reinstall the name plate to the mounting bracket.
section in this document.
Cali-
NOTE: Name plate reinstallation is important for valve identification/servicing purposes.
Valtek Rotary Actuators
To install Position Pac on Valtek rotary actuators, refer to Figures 3 and 4, and proceed as follows:
1. Mount the bracket to the mounting pad on the back­side of the actuator using two 0.31-inch (5/16) mount­ing bolts.
2. Mount the Position Pac to the bracket using four
0.31-inch (5/16) mounting bolts and nuts.
3. Loosely mount the trip lever to the valve shaft within the yoke.
4. Attach the switch lever to the Position Pac shaft.
5. Connect the linkage assembly to both levers as shown in Figure 3.
6. Measure the approximate radius of the trip lever from the center of the valve shaft to the linkage assembly connection (not the end of the lever). Next, adjust the switch lever to approximately the same radius and tighten.
Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
29-3
Loading...
+ 5 hidden pages