Flowserve Valtek Position Pac User Manual

V altek Position Pac
GENERAL INFORMATION
The following instructions are designed to assist with installing, calibrating and troubleshooting the Valtek Position Pac™ valve position indicator. Product users and maintenance personnel should thoroughly review this bulletin in conjunction with the maintenance bulletin for the appropriate valve body and actuator being used.
To avoid possible injury to personnel or damage to valve parts, WARNING and CAUTION notes must be strictly adhered to. Modifying this prod­uct, substituting non-factory or inferior parts, or using maintenance procedures other than out­lined could drastically affect performance, be hazardous to personnel and equipment, and may void existing warranties.
OPERATION
Position Pac is a ‘package’ unit containing a potenti­ometer and transmitter, two or four limit switches, or a combination of a transmitter and two limit switches.
The position transmitter utilizes a potentiometer to measure the valve’s position and a transmitter circuit that sends a 4 to 20 mA electrical signal to a remote monitoring device. Position Pac will continuously trans­mit the position of a control valve as it modulates between the open and closed positions.
The limit switches in Position Pac can be independently set to indicate open, closed or any intermediate valve position.
Position Pac’s sealed construction provides protection
®
from the entry of water, dust and oil as defined by the National Electrical Manufacturers Association (NEMA) 1, 3, 3R, 4, 12 and 13. Position Pac is also explosion­proof, providing protection from flammable hydrocarbon atmospheres, metal dust, coal dust, and grain dust. It i s UL and CSA listed for Class I, Division 1, Groups B, C, D; Class II, Division 1, Groups E, F, G (See Table I). All electrical wiring should be installed per NEC articles 501-4 and 501-5.
WARNING: Keep hands, hair, clothing, etc. away from moving parts when operating the valve. Fail­ure to do so can cause serious injury.
INSTALLATION INSTRUCTIONS
The following instructions are designed to assist in the field installation of Position Pac units.
Valtek Linear Actuators
To install Position Pac on Valtek linear actuators, refer to Figures 1 and 2, and proceed as follows:
1. Remove the name plate from the yoke leg opposite from the stroke indicator plate.
2. Using the two tapped holes, attach the Position Pac mounting bracket to the yoke leg using two mounting bolts. When facing this yoke leg, the bracket will jog in towards the valve center and protrude to the left.
3. Remove the nut from the stem clamp bolting. Place the tripper bracket on the bolt so the ‘S’ shape ex­tends down. Replace the nut and tighten it firmly.
Valtek No. 62152
Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
29-1
Figure 1: Linear Application – Front View
(cover removed)
Table I: Model Configuration
ledoMnoitpircseD
2HT
ST2H
XT rettimsnartgolanA
2AT
2A sehctiwsTDPSowT 4A sehctiwsTDPSruoF
ST2A
sehctiwsTDPSdelaesyllacitem
TDPSdelaesyllacitemrehowT
hctiwslanimrethtiwsehctiws
owthtiwrettimsnartgolanA
sehctiwsTDPS
htiwsehctiwsTDPSowT
pirtslanimret
AMEN
4
-rehowthtiwrettimsnarTgolanA
2&1 )puorG(
ABCDEFG
Figure 2: Linear Application – Rear View
(cover removed)
aerAlacirtcelE
foorPnoisolpxE
noisiviDIssalC
2&1 )puorG(
noisiviDIIssalC
CELENEC
lavorppA
gnidneP
gnitaR
LUseYgnoL
LUseYgnoL
ASC/LUoNtrohS
LUoNgnoL LUoNtrohS
LUoNgnoL LUoNgnoL
delaeS
sehctiwS
gnisuoH
eziS
Table II: Linear Mounting Information
Actuator Valve Spud Kit Hole
Size Stroke Size No.* Set
(sq. in.) (inch) (inch) (Mounting)
25 0.5-1.0 2.00 37434 bottom of slot
1.5 2.00 37434 top of slot
50 0.5-2.5 2.62 37345 bottom holes
3.0 2.62 37345 top holes
100 1.0-3.5 2.62/2.88 37436 bottom holes
& larger 4.0 3.38 37630 top holes
4.0 4.75 71636 top holes
*Kit includes: bracket, arm, trip lever or stem clamp with trip lever nuts and bolts.
4. Mount Position Pac to the bracket using the mount­ing holes as specified in Table II: Insert the lever onto the switch shaft. On larger actuators (size 50 and larger) that use the adjustable lever arm, adjust the length so that the center of the roller rests on the center of the tripper bracket. To preload the Position Pac’s restoring spring, be certain the control valve is in its minimum signal position. Loosen the lever arm clamp screw with a 0.14-inch ( 9/64) hex wrench, allowing the arm to turn on the shaft. While holding the arm in contact with the bottom of the tripper bracket and using a slotted screwdriver to rotate the switch shaft perform the following (all rotation direc­tion instructions are as viewed from the lever arm side of the Position Pac):
29-2 Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Figure 3: Rotary Application – Rear View
(cover removed; air-to-close valve)
Figure 4: Rotary Application – Front View
(cover removed; air-to-close valve)
For direct-acting, air-to-open actuators, rotate the shaft counter clockwise as far as it will go, then back off approximately 5 to 10 degrees. For direct-acting, air-to- close actuators, rotate the shaft counter clock­wise approximately 5 to 10 degrees.
For reverse-acting, air-to-open actuators, rotate the shaft counter clockwise approximately 5 to 10 de­grees. For reverse-acting, air-to-close actuators, rotate the shaft counter clockwise as far as possible, then back off approximately 5 to 10 degrees. With the slot in this position, tighten lever arm clamp screw tightly (until the teller tab will not move). With this pro­cedure completed, stroke valve to ensure spring is preloaded throughout the entire valve travel.
5. To make electrical connections, remove the housing cover.
WARNING: On explosion-proof installations, disconnect electrical power or be certain the area is safe from combustible atmospheres be­fore removing the housing cover.
(Refer to the specifications in Table IV for component electrical ratings.) Attach transmitter signal wiring to the transmitter terminal block, using caution to attach the positive and negative wires to the appropriate terminal.
CAUTION: Do not apply a voltage greater than 40 volts to the transmitter terminals or the circuit will be damaged.
Attach limit switch wiring to the COMM (common) and either NC (normally closed) or NO (normally open) terminals according to the needed signal.
6. To adjust the limit switches and/or position transmit­ter, remove the housing cover and refer to the
bration
WARNING: On explosion-proof installations, disconnect electrical power or be certain the area is safe from combustible atmospheres be­fore removing the housing cover.
7. Replace the housing cover.
8. Reinstall the name plate to the mounting bracket.
section in this document.
Cali-
NOTE: Name plate reinstallation is important for valve identification/servicing purposes.
Valtek Rotary Actuators
To install Position Pac on Valtek rotary actuators, refer to Figures 3 and 4, and proceed as follows:
1. Mount the bracket to the mounting pad on the back­side of the actuator using two 0.31-inch (5/16) mount­ing bolts.
2. Mount the Position Pac to the bracket using four
0.31-inch (5/16) mounting bolts and nuts.
3. Loosely mount the trip lever to the valve shaft within the yoke.
4. Attach the switch lever to the Position Pac shaft.
5. Connect the linkage assembly to both levers as shown in Figure 3.
6. Measure the approximate radius of the trip lever from the center of the valve shaft to the linkage assembly connection (not the end of the lever). Next, adjust the switch lever to approximately the same radius and tighten.
Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
29-3
Table III: Rotary Mounting Kits
Actuator Valve Shaft
Size Diameter Kit No.*
(sq. in.) (inches)
25 0.62 97556 25 0.75 97557 25 0.88 97558
50 0.62 97559 50 0.75 97560 50 0.88 97561 50 1.12 97562
100 0.88 97563 100 1.12 97564 100 1.50 97565 100 1.75 97566
*Kit includes: bracket, trip lever, switch lever, linkage assembly, nuts and bolts.
7. With the actuator at its minimum signal position, slide the trip lever along the shaft until the linkage assembly is parallel to the mounting bracket. At the same time, rotate the trip lever until it is at a 45­degree angle to the mounting bracket and pointing toward the top yoke bolt closest to the Position Pac. Tighten the trip lever on the shaft in this position.
8. Adjust the linkage assembly until the switch lever is approximately the same angle as the trip lever and the linkage assembly is horizontal. To preload the Position Pac's restoring spring (used to remove backlash in the linkage), be certain the actuator is in its minimum signal position and perform the follow­ing using a slotted screw driver to rotate the switch shaft (all rotation direction instructions are as viewed from the lever arm side of the Position Pac):
For direct-acting, air-to-open actuators, rotate the shaft counter clockwise as far as it will go, then back off approximately 5 to 10 degrees. For direct-acting, air-to-close actuators, rotate the shaft clockwise approximately 5 degrees.
For reverse-acting, air-to-open actuators, rotate the shaft clockwise approximately 5 degrees. For re­verse-acting, air-to-close actuators, rotate the shaft counter clockwise as far as possible, then back off approximately 5 to 10 degrees.
With the slot in this position, tighten the lever arm clamp screw tightly (until the teller tab will not move).
9. If possible, stroke the valve; the linkage assembly should travel back and forth remaining horizontal.
10.To make electrical connections, remove the hous­ing cover. (Refer to the specifications in Table IV for the component electrical ratings.) Attach the trans­mitter signal wiring to the transmitter terminal block, using caution to attach the positive and negative wires to the appropriate terminal. Attach the limit switch signal wiring to COMM (common) and either
NC (normally closed) or NO (normally open) termi­nals according to the needed signal.
WARNING: On explosion-proof installations, disconnect electrical power or be certain the area is safe from combustible atmospheres be­fore removing the housing cover.
11.To adjust the limit switches and/or the position trans­mitter, remove the housing cover and refer to the
Calibration
12.Replace the housing cover.
section in this document.
CALIBRATION
When a Position Pac is installed in the field or a factory installed unit needs to have output signal adjustments made, refer to Figure 5 and proceed as follows:
Limit Switch
Position Pac limit switches are adjusted at the factory before shipment and should not require on-site adjust­ment. However, if the mechanical lever has shifted position, the unit may need readjustment. To readjust the limit switch, proceed as follows:
CAUTION: If the valve cannot be stroked without disturbing the process fluid, bypassing or remov­ing the valve from the line may be necessary before calibrating the Position Pac.
WARNING: Prior to removing the valve from the line, depressurize the line to atmospheric pressure, drain all process fluid and, if caustic or hazardous mate­rial are present, decontaminate the valve. Failure to do so can cause serious injury.
1. Stroke the valve to the closed position.
WARNING: Keep hands, hair, clothing, etc. away from moving parts when operating the valve. Failure to do so can cause serious injury.
2. Remove the housing cover from the Position Pac.
WARNING: On explosion-proof installations, disconnect electrical power or be certain the area is safe from combustible atmospheres be­fore removing the housing cover.
3. Lift the appropriate cam follower lever. Move the cam wheel axially to disengage the teeth on the wheel from the teeth on the shaft disc.
4. Turn the cam wheel to the desired position. Each notch on the cam wheel represents an operating point change of 70 20'.
5. When the cam wheel has been rotated to the desired location, slide the cam wheel to engage with the mating shaft disc. (For finer adjustment, use the setscrew in the cam follower.)
6. Release the cam follower lever.
7. Cycle the valve and check for proper adjustment. Readjust if necessary.
8. Replace the housing cover.
29-4 Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Transmitter terms block
Limit switch wiring terminal
Limit switch adjustment cams (not shown)
Transmitter span adjusting screw (pot)
Transmitter zero Adjusting Screw (pot)
Figure 5: Calibration Points
Position Transmitter
1. Remove the housing cover from the Position Pac.
WARNING: On explosion-proof installations, disconnect electrical power or be certain the area is safe from combustible atmospheres be­fore removing the housing cover.
2. Wire the Position Pac transmitter in series with a
12.5-40 VDC power supply and a milliamp meter.
NOTE: Instructions within parenthesis ( ) refer to older Position Pac models characterized by a white label.
CAUTION: Do not apply a voltage greater than 40 volts to transmitter terminals or the circuit will be damaged.
3. Be certain the CW/CCW Switch located next to the potentiometer (Direct/Reverse Switch located next to the wire terminal block) is set to provide the de­sired output signal action. In the CW (DIR) position, a clockwise rotation of the Position Pac shaft will cause the output signal to increase. In the CCW (REV) position, a counterclockwise stem rotation causes the signal to increase.
4. Stroke the valve to the closed position.
WARNING: Keep hands, hair, clothing, etc. away from moving parts when operating the valve. Failure to do so can cause serious injury.
Clockwise/counter­clockwise switch
5. Referring to Figure 5, adjust the ZERO adjusting screw with a small, straight end screw driver, until the meter reads 4 mA DC.
6. Stroke the valve to the open position.
7. Adjust the SPAN adjusting screw until the meter reads 20 mA DC.
8. Stroke valve to the closed position and recheck the meter for 4 mA DC. Some readjusting of the calibra­tion may be required. Repeat steps 4-8 until satis­fied.
9. If calibration is unsuccessful after following this pro­cedure, one of two problems may exist: (a) The ori­entation of the Position Pac stem may need to be adjusted. (b) The ZERO and SPAN potentiometers may be adjusted out of range.
NOTE: The electrical travel of the potentiometer is 340 (150) degrees. To operate properly, the poten-
tiometer wiper must stay within the center 185 de­grees of its 340 degree electrical range during the full stroke of the valve.
9a.To adjust, stroke the valve to its middle position.
Loosen the potentiometer collar nut. While measur­ing the voltage between pins 1 and 2 on the back of the potentiometer, rotate the potentiometer until the voltage is between 0.55 and 0.65 volts. Retighten the potentiometer being careful to keep the potenti­ometer oriented in the same position.
Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
29-5
9b.Set the ZERO and SPAN potentiometers to their
approximate middle position. This is accomplished by first turning each potentiometer clockwise 25 turns or until a click is either felt or heard. Then turn each potentiometer counterclockwise approxi­mately 12 complete turns. Repeat steps 2 through 8 to complete calibration.
10.Replace the housing cover.
REVERSING POSITION TRANSMITTER SIGNAL
The following instructions should be used when the sig­nal being transmitted from the position transmitter is either incorrect or needs to be reversed. Refer to Figure 5.
Figure 6: Wiring Diagram
1500
L
Max. Load Resistance, R ()
R = V - 12.5V
1250 1000
750 500 250
L max PS
20 mA
Operating
Region
0
0 10 20 30 40 50 60
Power Supply Voltage, V (volts)
PS
Figure 7: Power Supply Requirements
NOTE: Instructions within parenthesis ( ) refer to older
Position Pac models characterized by a white label.
1. Remove the housing cover.
WARNING: On explosion-proof installations, disconnect electrical power or be certain the area is safe from combustible atmospheres be­fore removing the housing cover.
2. Locate the switch next to the position transmitter’s wiring terminal. Move switch to the opposite posi­tion, CCW or CW (DIR or REV). Repeat steps 3-9 in the
Calibration
section for the position transmitter.
NOTE: The SPAN potentiometer will generally not need readjustment.
3. Replace the housing cover.
Table IV: Specifications
Analog Output
Power Supply Range 12.5 to 40 VDC (24V DC typical) Maximum Load Maximum Resistance (ohms) =
Resistance Supply Voltage - 12.5 (see Figure 3)
Current Signal Output 4-20 mA Span Adjustable from 5° to 100° of angular
Null 4 mA position may be set at any angular
Linearity ±1.0% full-scale* Repeatability ±0.25% full-scale Hysteresis ±1.0% full-scale Operating -40O to 185O F (-40O to 85O C)
Temperature Range Ambient Temperature For a 100O F (38O C) change in ambient
Range temperature, maximum zero shift is
Power Supply Output signal changes less than
rotation
position
±0.4% full scale, maximum span shift is ±0.7% full scale
0.05% when supply voltage is varied between 12.5 and 40 volts dc
Limit Switches
(SPDT) 20 amps, 125, 250, 480 VAC, ind. and UL/CSA Rating (L23) res. 1 Hp. 125 VAC; 2 Hp, 250 VAC, 0.5
amp. 125 VDC; 0.25 amp, 250 VDC res.
Mechanical
Input motion ±105O from the center; spring
* Linearity is ±1.0% for 90O rotary shaft input. When mounted to
linear travel valves, linearity is dependent on linkage design and stroke length. Typical linearity is ±1.5% full-scale on Valtek Mark One control valves.
loaded to return to the center
0.02
29-6 Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Rotary
Short Housing Long Housing
4.00 102
1.26 dia. max. 32
0.72 18
3.15 80
2.00 51
0.33 dia. thru (4) 8
1.57 40
0.25
Front Mounting
0.49 12
0.75 19
0.88 22
0.37 9
2.38 typ 60
0.80 20
1.00 25
4.09 max. 104
3.78 max. 96
3.86 dia. 98
0.75 - 14 NPT (5 full threads min.) (2)
Eight side mounting holes can be tapped 5/16 - 18-inch
Lever Actuators
6
4.04 103
0.74 19
0.83 21
0.39 10
1.50 38
0.88 22
0.37 9
Adjust
1.50 - 3.70 38 - 94
0.72 18
0.29 dia. 7
0.80 20
1.00
5.71 max. 145
3.78 max. 133
3.82 dia. 97
0.75 - 14 NPT
1.00 25
0.57
0.50
14
13
25
0.27 7
0.16 4
0.09
(5 full threads min.) (2)
0.16 4
0.31 8
2
Figure 8: Dimensions
Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
29-7
Troubleshooting
Failure Probable Cause Corrective Action
Operation erratic 1. Loose bracket bolting 1. Tighten bolting bracket to yoke leg or transfer and inconsistent case: readjust position transmitter and switches
2. Loose Position Pac mounting 2. Tighten mounting screws, readjust position screws transmitter and switches
3. Loose tripper bracket 3. Tighten tripper bracket or extended spline (linear actuator) or extended connector spline connector (rotary actuator)
4. Internal or electrical 4a. Ensure that terminal block connections are malfunction tight
4b. Check for foreign material in contact with printed
circuit board or components
4c. Check for components or wires broken loose
from printed circuit board
4d. Check that the switch is fully set in desired
position
Indicating 1. Incorrect adjustment 1. Refer to incorrect position
2. Internal or electrical 2a. Ensure that terminal block connections are
tight
2b. Check for foreign material in contact with printed
circuit board or components
2c. Check for components or wires broken loose
from printed circuit board
2d. Check that the switch is fully set in desired
position
Calibration
section, step 9
Flowserve Corporation has established industry leadership in the design and manufacture of its products. When properly selected, this Flowserve product is designed to perform its intended function safely during its useful life. However, the purchaser or user of Flowserve products should be aware that Flowserve products might be used in numerous applications under a wide variety of industrial service conditions. Although Flowserve can (and often does) provide general guidelines, it cannot provide specific data and warnings for all possible applications. The purchaser/user must therefore assume the ultimate responsibility for the proper sizing and selection, installation, operation and maintenance of Flowserve products. The purchaser/user should read and understand the Installation Operation Maintenance (IOM) instructions included with the product, and train its employees and contractors in the safe use of Flowserve products in connection with the specific application. While the information and specifications presented in this literature are believed to be accurate, they are supplied for informative purposes only and should not be considered certified or as a guarantee of satisfactory results by reliance thereon. Nothing contained herein is to be construed as a warranty or guarantee, express or implied, regarding any matter with respect to this product. Because Flowserve is continually improving and upgrading its product design, the specifications, dimensions and information contained herein are subject to change without notice. Should any question arise concerning these provisions, the purchaser/user should contact Flowserve Corporation at any of its worldwide operations or offices.
For more information, contact:
Flowserve and Valtek are registered trademarks of Flowserve Corporation.
29-8 Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
FCD VLAIM029-04 © 2000 Flowserve Corporation. Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
For more information about Flowserve, contact www.flowserve.com or call USA 972 443 6500
Regional Headquarters
1350 N. Mt. Springs Prkwy. Springville, UT 84663 Phone 801 489 8611 Facsimile 801 489 3719
12 Tuas Avenue 20 Republic of Signapore 638824 Phone (65) 862 3332 Facsimile (65) 862 4940
12, av. du Québec, B.P. 645 91965, Courtaboeuf Cedex, France Phone (33 1) 60 92 32 51 Facsimile (33 1) 60 92 32 99
Quick Response Centers
5114 Railroad Street Deer Park, TX 77536 USA Phone 281 479 9500 Facsimile 281 479 8511
104 Chelsea Parkway Boothwyn, PA 19061 USA Phone 610 497 8600 Facsimile 610 497 6680
1300 Parkway View Drive Pittsburgh, PA 15205 USA Phone 412 787 8803 Facsimile 412 787 1944
Loading...