The following instructions are designed to assist with
installing, calibrating and troubleshooting the Valtek
Position Pac™ valve position indicator. Product users
and maintenance personnel should thoroughly review
this bulletin in conjunction with the maintenance bulletin
for the appropriate valve body and actuator being used.
To avoid possible injury to personnel or damage
to valve parts, WARNING and CAUTION notes
must be strictly adhered to. Modifying this product, substituting non-factory or inferior parts, or
using maintenance procedures other than outlined could drastically affect performance, be
hazardous to personnel and equipment, and may
void existing warranties.
OPERATION
Position Pac is a ‘package’ unit containing a potentiometer and transmitter, two or four limit switches, or a
combination of a transmitter and two limit switches.
The position transmitter utilizes a potentiometer to
measure the valve’s position and a transmitter circuit
that sends a 4 to 20 mA electrical signal to a remote
monitoring device. Position Pac will continuously transmit the position of a control valve as it modulates
between the open and closed positions.
The limit switches in Position Pac can be independently
set to indicate open, closed or any intermediate valve
position.
Position Pac’s sealed construction provides protection
®
from the entry of water, dust and oil as defined by the
National Electrical Manufacturers Association (NEMA)
1, 3, 3R, 4, 12 and 13. Position Pac is also explosionproof, providing protection from flammable hydrocarbon
atmospheres, metal dust, coal dust, and grain dust. It i s
UL and CSA listed for Class I, Division 1, Groups B, C, D;
Class II, Division 1, Groups E, F, G (See Table I). All
electrical wiring should be installed per NEC articles
501-4 and 501-5.
WARNING: Keep hands, hair, clothing, etc. away
from moving parts when operating the valve. Failure to do so can cause serious injury.
INSTALLATION INSTRUCTIONS
The following instructions are designed to assist in the
field installation of Position Pac units.
Valtek Linear Actuators
To install Position Pac on Valtek linear actuators, refer
to Figures 1 and 2, and proceed as follows:
1. Remove the name plate from the yoke leg opposite
from the stroke indicator plate.
2. Using the two tapped holes, attach the Position Pac
mounting bracket to the yoke leg using two mounting
bolts. When facing this yoke leg, the bracket will jog
in towards the valve center and protrude to the left.
3. Remove the nut from the stem clamp bolting. Place
the tripper bracket on the bolt so the ‘S’ shape extends down. Replace the nut and tighten it firmly.
Valtek No. 62152
Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
29-1
Figure 1: Linear Application – Front View
(cover removed)
Table I: Model Configuration
ledoMnoitpircseD
2HT
ST2H
XTrettimsnartgolanA
2AT
2AsehctiwsTDPSowT
4AsehctiwsTDPSruoF
ST2A
sehctiwsTDPSdelaesyllacitem
TDPSdelaesyllacitemrehowT
hctiwslanimrethtiwsehctiws
owthtiwrettimsnartgolanA
sehctiwsTDPS
htiwsehctiwsTDPSowT
pirtslanimret
AMEN
4
-rehowthtiwrettimsnarTgolanA
2&1)puorG(
ABCDEFG
Figure 2: Linear Application – Rear View
(cover removed)
aerAlacirtcelE
foorPnoisolpxE
noisiviDIssalC
2&1)puorG(
noisiviDIIssalC
CELENEC
lavorppA
gnidneP
gnitaR
LUseYgnoL
LUseYgnoL
ASC/LUoNtrohS
LUoNgnoL
LUoNtrohS
LUoNgnoL
LUoNgnoL
delaeS
sehctiwS
gnisuoH
eziS
Table II: Linear Mounting Information
Actuator ValveSpudKitHole
SizeStrokeSize No.*Set
(sq. in.)(inch)(inch)(Mounting)
250.5-1.02.0037434 bottom of slot
1.52.0037434top of slot
500.5-2.52.6237345 bottom holes
3.02.6237345top holes
1001.0-3.5 2.62/2.88 37436 bottom holes
& larger4.03.3837630top holes
4.04.7571636top holes
*Kit includes: bracket, arm, trip lever or stem clamp with trip lever
nuts and bolts.
4. Mount Position Pac to the bracket using the mounting holes as specified in Table II: Insert the lever
onto the switch shaft. On larger actuators (size 50
and larger) that use the adjustable lever arm, adjust
the length so that the center of the roller rests on the
center of the tripper bracket. To preload the Position
Pac’s restoring spring, be certain the control valve is
in its minimum signal position. Loosen the lever arm
clamp screw with a 0.14-inch ( 9/64) hex wrench,
allowing the arm to turn on the shaft. While holding
the arm in contact with the bottom of the tripper
bracket and using a slotted screwdriver to rotate the
switch shaft perform the following (all rotation direction instructions are as viewed from the lever arm
side of the Position Pac):
29-2Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
Figure 3: Rotary Application – Rear View
(cover removed; air-to-close valve)
Figure 4: Rotary Application – Front View
(cover removed; air-to-close valve)
For direct-acting, air-to-open actuators, rotate the
shaft counter clockwise as far as it will go, then back
off approximately 5 to 10 degrees. For direct-acting,
air-to- close actuators, rotate the shaft counter clockwise approximately 5 to 10 degrees.
For reverse-acting, air-to-open actuators, rotate the
shaft counter clockwise approximately 5 to 10 degrees. For reverse-acting, air-to-close actuators,
rotate the shaft counter clockwise as far as possible,
then back off approximately 5 to 10 degrees. With the
slot in this position, tighten lever arm clamp screw
tightly (until the teller tab will not move). With this procedure completed, stroke valve to ensure spring is
preloaded throughout the entire valve travel.
5. To make electrical connections, remove the housing
cover.
WARNING: On explosion-proof installations,
disconnect electrical power or be certain the
area is safe from combustible atmospheres before removing the housing cover.
(Refer to the specifications in Table IV for component
electrical ratings.) Attach transmitter signal wiring to
the transmitter terminal block, using caution to attach
the positive and negative wires to the appropriate
terminal.
CAUTION: Do not apply a voltage greater than 40
volts to the transmitter terminals or the circuit
will be damaged.
Attach limit switch wiring to the ‘COMM’ (common)
and either ‘NC’ (normally closed) or ‘NO’ (normally
open) terminals according to the needed signal.
6. To adjust the limit switches and/or position transmitter, remove the housing cover and refer to the
bration
WARNING: On explosion-proof installations,
disconnect electrical power or be certain the
area is safe from combustible atmospheres before removing the housing cover.
7. Replace the housing cover.
8. Reinstall the name plate to the mounting bracket.
section in this document.
Cali-
NOTE: Name plate reinstallation is important for
valve identification/servicing purposes.
Valtek Rotary Actuators
To install Position Pac on Valtek rotary actuators, refer
to Figures 3 and 4, and proceed as follows:
1. Mount the bracket to the mounting pad on the backside of the actuator using two 0.31-inch (5/16) mounting bolts.
2. Mount the Position Pac to the bracket using four
0.31-inch (5/16) mounting bolts and nuts.
3. Loosely mount the trip lever to the valve shaft within
the yoke.
4. Attach the switch lever to the Position Pac shaft.
5. Connect the linkage assembly to both levers as
shown in Figure 3.
6. Measure the approximate radius of the trip lever from
the center of the valve shaft to the linkage assembly
connection (not the end of the lever). Next, adjust
the switch lever to approximately the same radius
and tighten.
Flowserve Corporation, Valtek Control Products, Tel. USA 801 489 8611
29-3
Loading...
+ 5 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.