Flowserve Logix 3000MD Series, Logix 3200MD, Logix 3400MD Technical Bulletin

Page 1
TECHNICAL BULLETIN
Logix 3000MD Series
Digital Positioner
Experience In Motion
Page 2
Logix 3200IQ Digital Positioner FCD LGENTB0059-01 – 10/09
Superior Performance and Reliability
Introducing the Flowserve Logix™ 3000MD Series Digital Positioner
The Logix 3000MD series positioners offer valve status updates at a glance using the highly visible LEDs. Users can easily determine if a valve or actuator is functioning properly, and quickly diagnose any problems using the smart LED blink codes. This means that maintenance personnel can provide a visual check of the valve status without having to remove the cover or connect a HART handheld device or maintenance PC/laptop.
Inside the Logix 3200MD
Figure 1 – Logix 3200MD Controls
No Exposed Electronics
DIP Switches for Fast and Easy Setup
All Blink
2
Codes Listed
Large QUICK-CAL Button
Jog Buttons
Gain Selector Switch
Page 3
Logix 3000MD Series Digital Positioner FCD LGENTB0059-01 – 10/09
Sensor
-
+
+
+
+
Summer
Integration
I
Offset
Loop
Inner
+
-
Gmult
Pmin
Pmax
Deviation
F
OUNDATION
Fieldbus
Signal
Command In
(AO Block)
F
OUNDATION
Fieldbus
Transducer
Block
CONTROL
COMMAND
Output
D/A
Percentage
Algorithm
Control
Supply
Air
Control
Spool
Loop
Inner
ATO
Tubed
Sensor
Position
Stem
Voltage
Valve
Piezo
MPC
Soft Limits
Characterization
Linear Mode
Output
Inner-Loop
OR
Command In
(Digital Mode)
4-20
M
A
(A
NALOG
MODE
)
Input
Signal
A
NALOG
D
IGITAL
Logix 3200MD
Logix 3400MD
O O
Stem
Position
Sensor
Piezo Valve
Output 2
Output 1
Hall Effect Sensor
Flame Arrestor
Exhaust
Spool Valve
Flame Arrestor
Pressure Sensor Board
Air Supply
Main PCB
Regulator
Filter
Flame Arrestor
Digital Position Algorithm
LED Display
FF/HART Input Signal
The Logix 3000MD Series Digital Positioner - How It Works
Logix 3000MD Positioner Overview
Figure 1: System Positioning Algorithm for Logix 3400MDDigital Positioners
Figure 1: Logix 3000 Series Digital Positioners Schematic (air-to-open configuration)
Tu n i n g
Unlike other positioners that have only one set gains to set the response of the positioner, the Logix 3200MD positioner uses a multi-variable variable gain tuning algorithm. This allows the positioner to make large step changes with minimal overshoot, while achieving the resolution to respond to very small step changes.
The Auto Tune procedure cycles the actuator to produce a measured response and selects those gain values that provide appropriate actuator performance. The Auto Tune function includes a gain modifier selector that can be used to increase or decrease the calculated gain in order to achieve optimal performance.
By setting the Auto Tune on/off DIP switch, the tuning mode can be changed from auto to manual. The Logix 3000MD Series positioners provide several preset gain settings with a locally adjustable gain set selector directly from the user interface on the positioner. If custom settings are desired, tuning sets can be modified with a handheld or ValveSight, to accomodate a wide range of actuator sizes and types.
3
Page 4
Logix 3200IQ Digital Positioner FCD LGENTB0059-01 – 10/09
The Logix 3400MD for Fo u n d a t i o n Fieldbus Applications
Complete local configuration, on any valve/actuator and local.
FF Simulate – Run a control strategy without process
FF Write Protect – Locks out unauthorized writes to NVRAM
36 status and alert and messages displayed locally via three easy-to-read LEDs
Logix 3400MD Features
RFI/EMI Immunity
FISCO Compliant, User Interface
Polarity Insensitive UI (Potted UI)
AO Block (30mS)
PID Block (6 PID Equations) (90mS)
2 DI Block (20mS)
1 DO Block (30mS)
1 IS Block (50mS)
1 OS Block (50mS)
LAS (Link Master Device)
Auto Tune (Positioner Per formance)
High Friction Stabilit y
FF Code Download
Flash Ram (Local Positioner Embedded Code Upgrade)
Local Valve Signature Storage
Local Calibration and Setup (While in OOS)
24/7 Local Fault Monitoring
Local Adjustable Gain
Wizard/Method for On-line Commissioning
4
F
o u n d a t i o n Fieldbus made easy.
(In OOS) Calibrate stroke and adjust tuning without entering the Transducer Block —Updates the Block when complete.
Logix 3400MD Features
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
Local Jog Buttons to Adjust 100% Command Position (While in OOS)
Linkable Position feedback (AO Read Back)
Four Response Cur ves (Linear, =%, QO, and Custom) Locally Activated, or Through FF
Multiple View Objects in Transducer Block
Honeywell PKS Partner with FDM
Methods Setup Wizard
DTM Available
Yokogawa VIP Partner & PRM supported
Honeywell PKS Advantage Partner
Flowserve is a Honeywell Partner, with Flowserve DTM support pending in the ExperionDCS Field Device Manager. Please contact your Honeywell representative for details.
P
P
P
P
P
P
P
P
¸
Page 5
Logix 3000MD Series Digital Positioner FCD LGENTB0059-01 – 10/09
The Logix 3200MD for HART Applications
Complete local configuration, just like the Logix 3400MD, but HART protocol
• Local status and alert messages
• Tuning (Auto Tune function and manual adjustment)
• Jog buttons to manually adjust 100% position
• Easy-to-install 4-20 mA analog feedback card option
Simple plug-in AO card, automatically zero and spans position feedback during Quick Cal
Logix 3200MD Features
RFI/EMI Immunity
Auto Tune (Positioner Performance)
High Friction Stability Tuning
Integral 4-20 mA Feedback Option
Flash RAM (Local Positioner Embedded Code Upgrade)
Local Valve Signature Storage
Local Calibration and Setup
24/7 Local Fault Monitoring
Local Adjustable Gain
Three Response Curves (Linear, =% and custom)
Local Jog Buttons to Adjust 100% Command Position
Valve Signature Diag. “Valve Analysis” AMS
®
SnapOn
Application
AMS Device Manager
DTM Available
Yokogawa VIP Partner
Honeywell PKS Partner with Honeywell HART FDM
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
ValveSight Dashboard for Logix 3200MD or 3400MD Advanced DTM and Pro diagnostics
5
Page 6
Logix 3200IQ Digital Positioner FCD LGENTB0059-01 – 10/09
GAIN
C
B
A
DF
E
G
H
The Logix 3000MD Series Positioners – no software or hand­held device required... easy as 1, 2, 3
With the Logix 3400MD, function blocks are no longer
required to set up, configure and perform a simple stroke
calibration. The 3400MD can be set up with 9-32 VDC supply
and 45 psi (min.) air supply on any valve/actuator platform.
Calibration, configuration and tuning parameters from the local interface will be automatically updated in the Transducer Block on the Logix 3400MD. Local setup and calibration that does not require a link to a host controller, PC or hand-held device, as well as local validation that setup is correct, make any F and straightforward.
When the 3400MD is in OOS (Out Of Service mode), the local interface shown to the right is accessible and setup can be carried out through the following steps:
Common Configuration Steps
1. Make sure the mechanical linkage, air tubing and actuator mounting are correct.
2. Set the configuration switches to the desired operation of the valve/actuator.
3. Set the quick calibration switch to Jog or Auto. In Jog, the 100% position can be manually adjusted using the yellow up
and down buttons after Re-Cal is pressed. In Auto, the positioner finds the 100% position and calibration is complete. LED blink codes will guide the user through the process. Four green blinks (GGGG) or (GGGY) at the end of the sequence confirm that the calibration was successful.
4. If needed, the GAIN switch located to the right of the jog buttons will speed up or slow down the positioner’s response to command changes. With the Auto Tune configuration switch set to “On”, the positioner’s algorithm will select a gain with no over-shoot. The ‘E” position of the rotary GAIN dial indicates “neutral” with respect to gain adjustment. Turning clockwise from E to H and will speed up the response. Tuning counter-clockwise from E will slow it down, with A being the slowest response.
6
o u n d a t i o n Fieldbus™ installation easy
The Logix 3200MD can be set up with 10 VDC milliamp
current supply current and 45 psi (min.) air supply on any
valve/actuator platform.
Calibration, configuration and tuning parameters from the local interface will be automatically updated in the HART registers on the Logix 3200MD. Local setup and calibration that does not require a link to a host controller, PC or hand­held device, and local validation that setup is correct make any HART™ installation easy and straightforward.
With the Logix 3200MD, the local interface shown to the right can be used to set up the unit in seconds through the following steps:
Page 7
Logix 3000MD Series Digital Positioner FCD LGENTB0059-01 – 10/09
Time is Money
Shorter commissioning time gets you up and running, making money faster
Logix 3000MD Series
BONUS
Plant commission schedule
Other digital
positioners
Time to Startup and Commission
3000MD Series Facts
The local interface in the 3000MD series positioners and the two way communication capability allows the user to quickly commission loops.
3400
• Three versions: Basic, Advanced (Advanced includes
pressure sensors), and Pro (Pro includes pressure sensors and full featured valve diagnostics)
• ITK - CFF 4.6, 5.0
• DD available at www.fieldbus.org or www.flowserve.com
• Stores a valve signature onboard in NVRAM
Linkable Position Feedback as part of the AO Function block.
Contains: AO, PID, 2-DI, DO, OS, IS function blocks.
• Onboard temperature sensor to measure local positioner
ambient
• Stroke speed limiter (configurable in transducer block)
• Stainless steel version available
DTM Available
3200
• Three versions: Basic, Advanced (Advanced includes
pressures), Pro (Pro includes pressure sensors and full featured valve diagnostics)
• HART Command 1, 3, 9, 33 & 48
• Burst Mode available to continuously transmit
• Position command analog loop current
• Final value of command after characterization
• Supply pressure (advanced), Temperature (basic)
• Stem position in percent
• Onboard temperature sensor to measure local positioner
ambient
• Stroke speed limiter (configurable through HART)
• Stainless steel version available
• Enhanced Device Description for advanced signature
diagnostics
• Step test, friction test, HRL, data logger
DTM Available
7
Page 8
Logix 3200IQ Digital Positioner FCD LGENTB0059-01 – 10/09
There’s a Flowserve Expert Inside - ValveSight FDT/DTM Technology
Fl o w s e r v e s va l v e si g h t DtM s o F t w a r e h e l p s M a n a g e F i e l D D e v i c e s
b y c o M b i ni n g t h e F e a t u r e s o F F i e l D n e t w o r k h a r D w a r e a n D t h e
h
a r t (3200MD) o r Fo u n D a t i o n Fi e l D b u s (3400MD) c o M M u n i c a t i o n p r o t o c o l s u s i n g FDt/DtM t e c h n o l o g y w i t h t h e lo g i x 3000MD s e r i e s p o s i t i o n e r s . va l v e si g h t is a c o M p l e t e s o F t w a r e p a c k a g e , F e a t u r i n g a u n i q u e a n D e a s y t o u n D e r s t a n D h e a l t h s t a t u s o F t h e D e v i c e t h a t s h o w s n o t o n l y p r o b l e M s , b u t t h e M a g n i t u D e o F D e v e l o p i n g p r o b l e M s a s w e l l .
v
a l v e si g h t a l s o h a s c o n F i g u r a t i o n a n D c a l i b r a t i o n s c r e e n s t o F u l l y s u p p o r t t h e lo g i x 3000MD p o s i t i o n e r F a M i l y . aD D i t i o n a l l y , t h e u s e r c a n a c c e s s c u s t o M i z e D r e p o r t s F o r a l l c o n F i g u r a t i o n , c a l i b r a t i o n a n D e v e n t D a t a . Fl o w s e r v e s va l v e si g h t DtM o p e n s t h e w i n D o w t o t h e D e v i c e a n D a l l o w s i M M e D i a t e v i e w s w i t h l i v e F e e D b a c k o n a l l a c t i v e D e v i c e s e n s o r s i n c l u D i n g v a l v e s t e M p o s i t i o n , c o n t r o l s i g n a l , F r i c t i o n , r e s p o n s e t i M e a n D o t h e r i M p o r t a n t s y s t e M M e t r i c s .
ValveSight DTM software enables communication between the software and field device networks using the HART or FF protocol and provides access to the 24/7 diagnostic information from field devices. Using FDT/DTM technology maintenance personnel can access any Logix 3000MD series positioner on the network from a single workstation. Additionally, the software has capability to store configuration and calibration history and view event logs for each digital positioner accessible through the network.
21-Po i n T ch a r a c T E r i z a T i o n cu r v E
With ValveSight DTM software, the user can adjust a 21-point characterization curve to change the response of the posi­tioner in order to meet the process requirements. The output of each control point is independent, allowing the user to create a custom curve with very high resolution. This custom­ized curve can be saved in the memory of the Logix 3000MD positioners, and either activated or overridden with a simple on-board selector switch.
si g n a T u r E s
The Logix 3000MD positioners are designed to assure that data is easily gathered, stored and compared to historical valve data so the user can determine the performance of critical valves.
With ValveSight DTM software a user-defined signature ramp or step response test can be generated with a Logix 3000MD positioner. Signatures can be saved and cataloged (and later retrieved) for comparison with a more recent signature.
A special partial stroke signature function wil automatically test the valve/actuator and give a pass/fail indication.
Di a g n o s T i c En g i n E
Users can now obtain a new level of detailed real time diag­nostic information with ValveSight DTM software. ValveSight features an “Expert Inside’ performing real time on-line diagnostics 24 hours a day, 7 days a week. The diagnostic assessment of the ‘expert inside’ is instantly displayed on the local interface and through the ValveSight DTM software. The ‘health bars’ in the Dashboard view instantly indicate any developing issues and quickly direct the user to the implica­tions and solutions for each problem. The system automati­cally prioritizes alarms to direct the user to the root cause.
co n f i g u r a T i o n Ma n a g E M E n T
ValveSight DTM software also allows the user to easily upload a configuration from the positioner. This means that a new replacement positioner can be identically configured with the simple click of a mouse once the correct configuration has been identified. ValveSight enables users to edit individual configurations and print a positioner configuration report.
Po s i T i o n E r PE r f o r M a n c E
Static performance and accuracy measures such as hysteresis, deadband, linearity, and repeatability can be obtained with the Logix 3000MD positioners. These values can be graphically depicted, stored and later retrieved for comparative analysis.
8
Page 9
Logix 3000MD Series Digital Positioner FCD LGENTB0059-01 – 10/09
Logix 3000MD Series Features List for ValveSight DTM
Va l V e Si g h t dtM lo g i x 3200Md Po S i t i o n e r S lo g i x 3400Md Po S i t i o n e r S
Dashboard
V e r V i e w
All-Alarm Annunciator
o
Configuration Management
Local Interface Control
Position Cutoff
Soft Limits
Custom Stroke Characterization
Counters and Travel Settings
co n F i g u r a t i o n
Command Deviation Settings
Custom Units of Measure
All-Variable Editor
Analog Output Calibration
Analog Input Calibration
Stroke Calibration
ca l i B r a t i o n
Pressure and Friction Calibration
Ramp Test
Step Test
HDRL Test
i a g n o S t i c S
oF F -li n e
d
Data Logger
Supply Pressure
Friction
Actuation Ratio
Pneumatic Leak
Long-Term Trends
Partial Stroke Test
Valve Health View
on-li n e di a g n o S t i c S
Positioner Health View
Actuator Health View
Control Health View
ao
Pid
do
di
u n c t i o n Bl o c k S
oS
F
Fo u n d a t i o n Fi e l d B u S
1. Limited Function. No health information.
2. Limited function. No friction or forc e monitoring.
3. Limited function. No pressur e monitoring or information.
4. DCS Function
iS
a S i c
B
Va l V e Si g h t
P
1
d V a n c e d
a
Va l V e Si g h t
P P
P P P
lo g i x
o g i x
l
3200Md
1,3
2,3
P
P
1
2
3210Md
o g i x
l
3220Md
P P
P P
o g i x
l
o g i x
l
3400Md
1,3
2,3
3410 Md
P
1
P
2
P P P P P P P P
P P P P P P P P
P P P P P P P P
P P P P P P P P
P P P P P P P P
P P P P P P P P
P P P P P P P P
P P P
P P P
3
3
P P
P P P P P P P P
P P P P P
P P P P P
P P P P P P P P
P P P
P P P
P P P
3
3
P P P
P P P
P P
2
2
3
3
P P
P P
P P P P P P P
P P
3
P P
P P P P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
o g i x
l
3420Md
P
P
P
4
9
Page 10
Logix 3200IQ Digital Positioner FCD LGENTB0059-01 – 10/09
The Logix 3000MD Positioner Specifications
Specifications for Logix 3400MD
Table I: Electrical Specifications
Power Supply
IS Fisco compliant
Communications FF Protocol ITK 4.6x, 5.0
Operating Current 23 mA
Maximum Voltage 36.0 VDC
Two-wire, 9-32 VDC
FF compatible
Table III: Physical Specifications
Housing Material
Soft Goods Buna-N / Florosilicone
Weight
Cast, powder-painted aluminum or stainless steel
8.3 pounds (3.9 kg) aluminum
20.5 pounds (9.3 kg) stainless steel
Table II: Environmental Conditions
Operating Temperature
Range
Transport and Storage
Temperature Range
Operating Humidity 0 - 100% non-condensing
Note: The air supply must conform to ISA Standard ISA 7.0.01 (a
dew point at least 18 degrees Fahrenheit below ambient tempera-
ture, particle size below five microns—one micron recom-
mended—and oil content not to exceed one part per million).
Standard
-40° to 176°F (-40° to 80°C)
Specifications for Logix 3200MD
Table I: Electrical Specifications
Power Supply
Compliance Voltage 10.0 VDC @ 20 mA
Effective Resistance
Communications HART Protocol ITK 5,6
Minimum Operating
Current
Maximum Voltage 30.0 VDC
Table II: Environmental Conditions
Operating Temperature
Range
Transport and Storage
Temperature Range
Operating Humidity 0 - 100% non-condensing
Note: The air supply must conform to ISA Standard ISA 7.0.01
(a dew point at least 18 degrees Fahrenheit below ambient
temperature, particle size below five microns—one micron recom-
mended—and oil content not to exceed one part per million).
10
Two-wire, 4-20 mA
10.0 to 30.0 VDC
495 Ω @ 20 mA Typical
Add 20 Ω when HART communication active
3.6 mA without AO board
3.7 mA with AO board
Standard
Low
-40° to 176°F (-40° to 80°C)
-40° to 176°F
(-40° to 80°C)
-4° to 176°F
(-20° to 80°C)
-40° to 176°F
(-40° to 80°C)
Table IV: Positioner Specifications
Deadband <0.1% full scale
Repeatability <0.05% full scale
Linearity <0.5% (rotar y), <0.8%, (sliding stem) full scale
3
Air Consumption <0.3 SCFM (0.5 Nm
Air Supply 30-150 psig (ISA 7.0.0.1 compliant)
Air Delivery 12 SCFM @ 60 psi (0.27 Cv)
/hr) @ 60 psi (4 bar)
Table III: Physical Specifications
Housing Material
Soft Goods Buna-N / Florosilicone
Weight
Cast, powder-painted aluminum or stainless steel
8.3 pounds (3.9 kg) aluminum
20.5 pounds (9.3 kg) stainless steel
Table IV: Positioner Specifications
Deadband <0.1% full scale
Repeatability <0.05% full scale
Linearity <0.5% (rotar y), <0.8%, (sliding stem) full scale
3
Air Consumption <0.3 SCFM (0.5 Nm
Air Supply 30-150 psig (ISA 7.0.0.1 compliant)
Air Delivery 12 SCFM @ 60 psi (0.27 Cv)
/hr) @ 60 psi (4 bar)
Page 11
Logix 3000MD Series Digital Positioner FCD LGENTB0059-01 – 10/09
The Logix 3000MD E.O.M. Mounting Kits
Brand Model Size Mounting Kit
30 213 905
34
40
50
657 & 667
60
Fisher
1250
1052 33 171549 Rotary
65 7-8 40 173798
Neles
Slid-Std 173567
Foxboro
VS T-VA3 R 17-in. dia. 173798
VSL-VA1D 12-in. dia. 173798
Honeywell
71 Domotor
Masoneilan (Linear Actuators)
Linear 178258
37
38
88
47 B 173361
48 B 173361
“D”
Domotor
71-2057AB- D 176179
71-40413BD 176251
70 171518 4" stroke
80 171519
225
675
RC 171512
RD 178258
9
11
13 171720
18 173382
24 173896
11 173235
13 173234
15 186070
18 173382*
24 173896
25 173325
50 173335
100 173336
6 171722
16 173827
200 175141
141410
171516
171517 2" stroke
171516
171517 2" stroke
0.5" – 1.5" stroke
0.5" – 1.5" stroke
0.5" – 1.5" stroke
173371450
171721
Brand Model Size Mounting Kit
(Rotary
Actuators)
Masoneilan
Valtek Troope r 166636
Automax
Vangard 37/64 175128
Air-Tor que AT Series AT0 – AT6
Automax
Bettis
EL-O­Matic
Hytork XL Series XL45 – XL4580
Unitorq M Series M20 – M2958
Worcester 39 Series 2539 - 4239
*Adjustable mounting kit 173798 may be needed if handwheels are used.
N Series N250.300
R Series R2 – R5
G Series
E Series E25 – E350
P Series P35 – P4000
NAMUR Accessory Mounting Kit Part Numbers
Bracket Option Description
28 20 mm pinion x 80 mm bolt spacing
28 38 mm pinion x 80 mm bolt spacing
313 30 mm pinion x 80 mm bolt spacing
513 50 mm pinion x 130 mm bolt spacing
Bolt Option Description
A 10-24 UNC bolting
B 10-32 UNF bolting
L M5-.8 metric bolting
Example: NK313A, NAMUR Accessory Mounting Kit with 30 mm pinion x 80 mm bolt spacing and 10-24 UNC bolting.
Pl E a s E c o n T a c T y o u r fl o w s E r v E r E P r E s E n T a T i v E f o r a D D i -
T i o n a l M o u n T i n g k i T a v a i l a bi l i T y.
33 B 173298
4
35
7
70 10 17 329 8
R314 14118 0 HD
SN A115 NK313A
SNA
Series
RPC
Series
SNA3 – SNA2000
RP – TPC11000
G2009-M11
– G3020-M11
1732986
Consult factor y
0.75"
– 1.50"
Std
11
Page 12














 


$VTUPNFSDPOEVJUQPSUT /15UISFBE .PQUJPOBM
4VQQMZ0VUQVUBOE 0VUQVUQPSUT /15UISFBE
-&%*OEJDBUPST
.BJO$PWFS
$VTUPNFS *OUFSGBDF $PWFS
4QPPM7BMWF$PWFSBOE7FOU
%SJWFS$PWFS






4RVBSF




 
 
 
 
'PMMPXFSBSNMJNJU
JT¡GSPNQPTJUJPO
TIPXONBYJNVN
3000MD Series dimensions
NOTE: Dimensions in inches (mm)
Logix 3200IQ Digital Positioner FCD LGENTB0059-01 – 10/09
12
Page 13
Logix 3000MD Series Digital Positioner FCD LGENTB0059-01 – 10/09
How to order
Selection Code Example
3
Protocol
HART 2 Foundation Fieldbus 4 Standard (No Sensors) 0
Diagnostics
Advanced (With Sensors) 1 Pro Diagnostics (with sensors and full ValveSight dianostics) 2 Aluminum, White Paint (Valtek) 0 Stainless Steel, No Paint (Valtek) 1
Material
Aluminum, Black Paint (Automax) 2 Aluminum, Food-Grade White Paint (Automax) 3 Aluminum, Black Paint (Accord) 4 Aluminum, Food-Grade White Paint (Accord) 5
Design Version
Nonincendive Ex nL nA IIC, ATEX II 3 G, T4amb -40
0
C; Intrinsically Safe Ex ia IIC, T4 Tamb -400C to +850C, T5 Tamb -400C to +550C; Ex
+55 ia D 20, T950C -400C to +800C (CENELEC)
0
C to +850C, T5 Tamb -400C to
04
(3400MD)
INMETRO BR-EX ia IIC T4/T5; BR-Ex d IIB+H2 T5 (South America) 06 Explosionproof Ex d IIB + H
(GOST GGTN Ex d IIB+H2)
, Ex tD A21 T950C, ATEX II 2 G (CENELEC)
2
07
(3400MD)
Explosionproof Class I, Div 1, Groups B, C, D Intrinsically Safe Class I,
Certifications
Div 1, Groups A through G (FM, CSA) FM Nonincendive. CSA Class I, Div 2, Class I, Zone 1, Group IIB + H Group IIC (CSA Only)
and Exia Class 1, Zone 0,
2
General Purpose 14
0
Intrinsically Safe Ex ia IIC, T4 Tamb -40
0
C -400C to +800C, ATEX II 1 G D (CENELEC) (GOST GGTN Ex i Intrinsically Safe IIC)
T95
C to +850C, T5 Tamb -400C to +550C; Ex ia D 20,
10
15
(3400MD) IECEx Explosionproof 16 IECEx Intrinsically Safe 21 ATE X:
Explosion Proof: II2G Ex d IIB+H Intrinsically Save: II1G Ex ia IIC, T4 T II1D Ex iaD 20 T950C -400C to + 800C Nonincendive: II3G Ex nL nA IIC, T4 T II3D Ex tD A22 T950C -400C to + 800C
T5; II2D Ex tD A21 T
2
-400C to +850C, T5 T
amb
-400C to +850C, T5 T
amb
-400C to +800C
amb
-400C to +550C
amb
-400C to +550C
amb
28
(3200MD)
KO SHA*
Shaft
Conduit Connections
DD 316 Stainless Steel Shaft (Valtek Standard) D6
NAMUR 316 Stainless Steel (VDI/ VDE 3845) N6
½" NPT E M20 M Four-way (Double-Acting) 04
Action
Three-way (Single-Acting) 03 Four-way Vented (Double-Acting) 4V Three-way Vented (Single-Acting) 3V
Temperatu re Low Temperature (-40°F to 176°F; -40°C to 80°C) 40
OG OS KG KS
Gauges
SS with brass internals, psi (bar/kPa) (Valtek Standard) SS with SS internals, psi (bar/kPa) SS with brass internals, psi (kg/cm2 ) SS with SS internals, psi (kg/cm2 ) KS
No Gauges U
OO
RM
SF
Special Options
No special options 4-20 mA Position Feedback OF
Remote Mount Feedback (Only Available with Cer ti cation Option 14)
Fail Option Feedback*
For each category, select the code for one of the options.
* Contact factory before specifying this option
3
4
1
0
MD
14
D6
M
4V
40
KS
OF
13
Page 14
Logix 3200IQ Digital Positioner FCD LGENTB0059-01 – 10/09
®
Logix 3400MD Hazardous Area Certifications
Notified Body
Certification
Option
Approval Entity Parameters Temperature Code
Explosionproof: Class I, Div 1, Groups B,C,D
-01
-02
-02
Dust Ignition Proof: Class II, III, Div 1, Groups EFG
(See Warning No. 1, 2)
Intrinsically Safe: Class I, II, III, Div 1, Groups A,B,C,D Class 1, Zone 0, AEx ia IIC
(See Warning No. 2,3)
Non-Incendive: Class I, II, III, Div 2, Groups A,B,C,D
(See Warning No. 2)
Not Applicable T6 T
Enti ty Fisc o Para meters P aramete rs Ui = 24 Vd c Ui = 17.5 Vdc
Ii = 25 0mA Ii = 380mA
Pi = 1.2 W Pi = 5. 32W Ci = 3300pF Ci = 3300 pF Li = 10mH L i = 10mH
(refer to control drawing No. 23 4401)
Install per NEC Article 501-4 when barriers are
not used. Explosionproof: Class I, Div 1, Groups B,C,D
-01
Class II, Div 1, Groups E,F,G Class III Ex d IIB+H2
(See Warning No. 2)
Not Applicable -20º ≤ Ta ≤ +55ºC
Explosionproof (Flameproof): II 2 GD
ATE X
-07
-04 or -15
Ex d IIB + H Ex tD A21 T95ºC
2
Intrinsically Safe: II 1 G Ex ia IIC
(See Warning No. 1, 2)
(See Warning No. 2, 3)
Not Required
Ui = 30 Volts
Ii = 100mA
Pi = 800mW
Ci = 30 nF
Li = 0
Co = 36 nF Non-Incendive:
-04
II 3 G Ex nL nA IIC
Not Required
(See Warning No. 2)
Explostionproof (Flameproof): 1Ex d IIBT5/H
Intrinisically Safe: 0Ex ia IICT4X
X
2
(See Warning No. 1,2)
Not Required
Ui = 24 Vdc
Ii = 250mA
Pi = 1.2W
GOST
Ci = 330 pF
Li = 10 mH
IECEx
-21
Intrinsically Safe: Ex ia IIC
(See Warning No. 2, 3)
Ui = 24 Vdc
Ii = 250mA
Pi = 01.2W
Ci = 330 pF
Li = 10 mH Explosionproof (Flameproof):
-06
-06 or -22
BR-Ex d IIB + H
Intrinsically Safe: BR- Ex ia IIC
2
(See War ning No. 1, 2)
(See Warning No. 2, 3)
Not Required
Ui = 24 Vdc
Ii = 250mA
Pi = 1.2W
Ci = 3300 mF
Li = 10 mF
GOST R GOST K, GOST K GGTN
WARNINGS:
1. In order to maintain the explosionproof certifications do not remove or loosen covers during operation.
2. To avoid the possibility of static discharge clean only with a damp cloth. The positioner must be connected to suitable rated intrinsically safe equipment, and must be installed in accordance with intrinsically safe installation
3.
standards.
14
≤ = 60ºC
amb
T4 T
≤ = 60ºC NEMA
amb
T6 T
-200 to 600 C
amb
T5 (T =-40ºC to +
80ºC)
T4 (T
-40ºC to + 85ºC)
amb
T5 (T
-40ºC to + 55ºC)
amb
T4 T
-40ºC to + 85ºC)
amb
-40ºC to + 55ºC)
T5 T
amb
T5 (-500C ≤Ta ≤ +550C)
T4 (T
-500C to + 600C)
amb
T4 (T
-20ºC to + 60ºC)
amb
T5 (-40ºC≤ Ta ≤ + 55ºC)
T5 (-40ºC≤ Ta ≤ + 55ºC)
T4 (-40ºC≤ Ta ≤ + 85ºC)
Enclosure
Rating
NEMA
4X
4X
NEMA
4X
Type
4X
IP65
IP65
IP65
IP65
IP65
IP65
IP65
IP65
Page 15
Logix 3000MD Series Digital Positioner FCD LGENTB0059-01 – 10/09
®
Logix 3200MD Hazardous Area Certifications
Notified Body
ATE X
IECEx
GOST
Certification
Option
-10
-10
-10
-10
10
10
-28
-28
-28
-16
-21
-06
-06
Approval Entity Parameters Temperature Code
Explosionproof: Class I, Div 1, Groups B,C,D Dust Ignition Proof: Class II, III, Div 1, Groups EFG (See Warning No. 1, 2) Intrinsically Safe: Class I, II, III, Div 1, Groups A,B,C,D Class 1, Zone 0, AEx ia IIC
(See Warning No. 2,3)
Non-Incendive: Class I, Div 2, Groups A,B,C,D
(See Warning No. 2)
Explosionproof: Class I, Div 1, Groups B,C,D Class II, Div 1, Groups E,F,G Class III
(See Warning No. 1, 2)
Intrinsically Safe: Class I, II, III, Div 1, Groups A,B,C,D
(See Warning No. 2, 3)
Non-Incendive: Class I, II, Div 2, Groups A,B,C,D
(See Warning No. 2)
Explosionproof (Flameproof): II 2 GD Ex d IIB + H Ex tD A21 T95ºC
2
(See Warning No. 1, 2)
Intrinsically Safe: II 1 G D Ex ia IIC Ex iaD 20 T95
0
C
(See Warning No. 2, 3)
Non-Incendive: II 3 G Ex nL nA IIC Ex tD A22 T95
0
C
(See Warning No. 2)
Explosionproof (Flameproof): Ex d IIB + H
2
(See Warning No. 1, 2)
Intrinsically Safe: Ex ia IIC
(See Warning No. 2, 3)
Explosionproof (Flameproof): 1Ex d IIBT5/H2X
(See Warning No. 1,2)
Intrinisically Safe: 0Ex ia IICT4X 0Ex ia IICT5X
(See Warning No 2,3)
Explosionproof (Flameproof): BR-Ex d IIB + H
2
(See War ning No. 1, 2)
Intrinsically Safe: BR- Ex ia IIC
(See Warning No. 2, 3)
T4 T T5 T
T4 T T5 T
≤ = 60ºC
amb
≤ = 85ºC
amb
≤ = 55ºC
amb
≤ = 85ºC
amb
≤ = 55ºC
amb
Not Applicable T6 T
Vmax = 30 Volts Imax = 100mA
Pmax = 800mW
Ci = 30 nF
Li = 0 (refer to control drawing No.
1987 36)
Install per NEC Article 501-4 when barriers are not used.
Not Applicable -25º ≤ Ta ≤ +40ºC
Vmax = 30 Volts Imax = 100mA
Pmax = 800mW
Ci = 30 nF
Li = 0 (refer to control drawing No.
1987 36)
Not Required T4 T
T4 T
≤ = 80ºC
amb
≤ = 80ºC
amb
Not Required T5 (T = -40ºC to + 80ºC) IP65
Ui = 30 Volts Ii = 100mA
Pi = 800mW
Ci = 30 nF Li = 0 Co = 36 nF
Not Required
Not Required
Ui = 30 Vdc Ii = 100mA
Pi = 0.8W
Ci = 30 nF Li = 0
Not Required
T4 (T
-40ºC to + 85ºC)
amb
T5 (T
-40ºC to + 55ºC)
amb
(Ta = -400C to + 800C)
T4 T
(-40ºC to + 85ºC)
amb
T5 T
(-40ºC to + 55ºC)
amb
(Ta = -400C to + 800C)
T5 (T
-20ºC to + 55ºC)
amb
T5 (T
-40ºC to + 80ºC)
amb
T4 (T
-40ºC to + 85ºC)
amb
T5 (-500C ≤Ta ≤ +550C)
Ui = 30 Volts Ii = 100mA
T4 (T
Pi = 800mW
Ci = 30 nF
-500C to + 600C)
amb
Li = 0
Not Required
Ui = 30 Vdc Ii = 100mA
Pi = 800mW
Ci = 30 nF Li = 0 Co = 36 nF
T5 (-40ºC ≤ Ta ≤ + 80ºC)
T5 (-40ºC ≤ Ta ≤ + 55ºC)
T4 (-40ºC ≤ Ta ≤ + 85ºC)
Enclosure
Rating
NEMA
4X
NEMA
4X
NEMA
4X
Type
4X
Type
4X
Type
4X
IP65
IP65
IP65
IP65
IP65
IP65
IP65
IP65
15
Page 16
FCD LGENTB0059-01 10/09 Printed in USA.
Flowserve Headquarters
5215 N. O’Connor Blvd., Suite 2300 Irving, TX 75039 Telephone: 972 443 6500
Control Valve Manufacturing
1350 Mountain Springs Parkway
Springville, UT 84663-3004 USA Telephone: 1 801 489 8611 Fax: 1 801 489 3719
Singapore
12 Tuas Ave. 20, 638824
Republic of Singapore
Telephone: +65 862 3332 Fax: +65 862 4940
Austria
Kasernengasse 6 Villach Austria 9500
Telephone: +43 0 4242 41181 0 Fax: +43 0 4242 41181 50
To find your local Flowserve representative:
For more information about Flowserve Corporation, visit
www.flowserve.com or call USA 1 800 225 6989
Flowserve Corporation has established industr y leadership in the design and manufacture of its products. When properly selected, this Flowserve product is designed to per form its intended function safely during its useful life. However, the purchaser or user of Flowser ve products should be aware that Flowserve products might be used in numerous applications under a wide variety of industrial service conditions. Although Flowserve can (and often does) provide general guidelines, it cannot provide specific data and warnings for all possible applications. The purchaser/user must therefore assume the ultimate responsibility for the proper sizing and selection, installation, operation, and maintenance of Flowserve products. The purchaser/user should read and understand the Installation Operation Maintenance (IOM) instructions included with the product, and train its employees and contractors in the safe use of Flowserve products in connection with the specific application.
While the information and specifications contained in this literature are believed to be accurate, they are supplied for informative purposes only and should not be considered certified or as a guarantee of satisfactory results by reliance thereon. Nothing contained herein is to be construed as a warranty or guarantee, express or implied, regarding any matter with respect to this product. Because Flowserve is continually improving and upgrading its product design, the specifications, dimensions and information contained herein are subject to change without notice. Should any question arise concerning these provisions, the purchaser/user should contact Flowserve Corporation at any one of its worldwide operations or offices.
© 2006 Flowserve Corporation, Ir ving, Texas, USA. Flowserve is a registered trademark of Flowserve Corporation.