Modulens
EN
Gas fired floor-standing condensing boiler
AGC 10/15
AGC 15
AGC 25
AGC 35
User Guide
300026080-001-03
Contents
1 |
Introduction ................................................................................................ |
|
|
4 |
|
1.1 |
Symbols used ....................................................... |
4 |
|
|
|
1.1.1 |
Symbols used in the manual ................................... |
4 |
|
|
1.1.2 |
Symbols used on the equipment ............................. |
4 |
|
1.2 |
Abbreviations ........................................................ |
5 |
|
|
1.3 |
General |
.................................................................. |
5 |
|
|
1.3.1 |
Manufacturer’s liability ............................................. |
5 |
|
|
1.3.2 |
Installer’s liability ..................................................... |
6 |
|
|
1.3.3 |
User’s liability .......................................................... |
6 |
|
1.4 |
Certifications ......................................................... |
6 |
2 |
Safety instructions and recommendations .............................................. |
7 |
|||
|
2.1 |
Safety instructions ............................................... |
7 |
||
|
2.2 |
Recommendations ................................................ |
8 |
||
3 |
Description .................................................................................................. |
|
|
|
9 |
|
3.1 |
Operating principle ............................................... |
9 |
||
|
|
3.1.1 |
Gas/air setting ......................................................... |
9 |
|
|
|
3.1.2 |
Combustion ............................................................. |
9 |
|
|
3.2 |
Main parts ............................................................ |
10 |
||
|
3.3 |
Control panel ....................................................... |
11 |
||
|
|
3.3.1 |
Description of the keys .......................................... |
11 |
|
|
|
3.3.2 |
Description of the display ...................................... |
12 |
|
|
|
3.3.3 |
Browsing in the menus .......................................... |
15 |
|
4 |
Operating the appliance .......................................................................... |
|
|
|
16 |
|
4.1 |
Putting the appliance into operation ................ |
16 |
||
|
4.2 |
Reading out measured values ........................... |
16 |
||
|
4.3 |
Changing the settings ........................................ |
18 |
||
|
|
4.3.1 |
Setting the set point temperatures ........................ |
18 |
|
|
|
4.3.2 |
Selecting the operating mode ............................... |
19 |
|
|
|
4.3.3 |
Forcing domestic hot water production ................. |
20 |
|
|
|
4.3.4 |
Setting the contrast and lighting on the |
|
|
|
|
|
|
display ................................................................... |
20 |
|
|
4.3.5 |
Setting the time and date ...................................... |
21 |
|
|
|
4.3.6 |
Selecting a timer programme ................................ |
21 |
|
|
|
4.3.7 |
Customising a timer programme ........................... |
22 |
|
|
|
|
|
|
|
1 |
|
|
|
03/12/2013 - 300026080-001-03 |
|
|
|
|
Contents |
|
|
4.4 |
Installation shutdown |
.........................................24 |
4.5 |
Antifreeze protection .......................................... |
24 |
5 |
Checking and maintenance |
..................................................................... |
26 |
|
5.1 |
General instructions ........................................... |
26 |
|
5.2 |
Periodic checks .................................................. |
26 |
6 |
Troubleshooting ....................................................................................... |
|
28 |
|
6.1 ........................................................ |
Anti - hunting |
28 |
|
6.2 .................... |
Messages (Code type Bxx or Mxx) |
28 |
|
6.3 ........................... |
Faults (Code type Lxx or Dxx) |
30 |
7 |
Technical specifications .......................................................................... |
|
36 |
|
7.1 .................................... |
Technical specifications |
36 |
8 |
Energy savings ......................................................................................... |
|
38 |
|
8.1 ......................................... |
Energy - saving advice |
38 |
|
8.2 .............................................. |
Recommendations |
38 |
9 |
Warranty .................................................................................................... |
|
39 |
|
9.1 ................................................................ |
General |
39 |
|
9.2 ................................................... |
Warranty terms |
39 |
2 |
|
|
|
03/12/2013 - 300026080-001-03 |
|
|
3 |
|
|
|
03/12/2013 - 300026080-001-03 |
|
|
AGC 10/15 AGC 15 AGC 25 AGC 35 |
1. Introduction |
1Introduction
1.1Symbols used
1.1.1.Symbols used in the manual
In these instructions, various danger levels are employed to draw the user’s attention to particular information. In so doing, we wish to safeguard the user’s safety, obviate hazards and guarantee correct operation of the appliance.
DANGER
Risk of a dangerous situation causing serious physical injury.
WARNING
Risk of a dangerous situation causing slight physical injury.
CAUTION
Risk of material damage.
Signals important information.
¼Signals a referral to other instructions or other pages in the instructions.
1.1.2.Symbols used on the equipment
4Protective earthing
~Alternating current
Before installing and commissioning the device, read carefully the instruction manuals provided.
Dispose of the used products in an appropriate recovery and recycling structure.
This appliance must be connected to the protective earth.
D000241-C
03/12/2013 - 300026080-001-03 |
|
|
|
4 |
|
|
1. Introduction |
|
AGC 10/15 AGC 15 AGC 25 AGC 35 |
1 |
2 |
Caution: danger, live parts. |
|
|
Disconnect the mains power prior to any operations. |
M002628-A
1.2Abbreviations
43CE: Collective conduit for sealed boiler
4DHW: Domestic hot water
4Interscenario switch: Home automation switch that can be used to centralise and control several scenarios
4Hi: Lower heating value LHV (Nett)
4Hs: Higher heating value HHV (Gross)
4PPS: Polypropylene hardly inflammable
4PCU: Primary Control Unit - PCB for managing burner operation
4PSU: Parameter Storage Unit - Parameter storage for PCBs PCU and SU
4SCU: Secondary Control Unit - control panel PCB
4SU: Safety Unit - Safety PCB
43WV: 3-way valve
4HL: High Load - DHW tank with plate exchanger
4SL: Standard Load - DHW tank with coil
4SHL: Solar High Load - Solar DHW tank with plate exchanger
4SSL: Solar Standard Load - Solar DHW tank with coil
1.3General
1.3.1.Manufacturer’s liability
Our products are manufactured in compliance with the requirements of the various applicable European Directives. They are therefore
delivered with [marking and all relevant documentation.
In the interest of customers, we are continuously endeavouring to make improvements in product quality. All the specifications stated in this document are therefore subject to change without notice.
Our liability as the manufacturer may not be invoked in the following cases:
4Failure to abide by the instructions on using the appliance.
4Faulty or insufficient maintenance of the appliance.
4Failure to abide by the instructions on installing the appliance.
5 |
|
|
|
03/12/2013 - 300026080-001-03 |
|
|
AGC 10/15 AGC 15 AGC 25 AGC 35 |
1. Introduction |
1.3.2.Installer’s liability
The installer is responsible for the installation and inital start up of the appliance. The installer must respect the following instructions:
4Read and follow the instructions given in the manuals provided with the appliance.
4Carry out installation in compliance with the prevailing legislation and standards.
4Perform the initial start up and carry out any checks necessary.
4Explain the installation to the user.
4If a maintenance is necessary, warn the user of the obligation to check the appliance and maintain it in good working order.
4Give all the instruction manuals to the user.
1.3.3.User’s liability
To guarantee optimum operation of the appliance, the user must respect the following instructions:
4Read and follow the instructions given in the manuals provided with the appliance.
4Call on qualified professionals to carry out installation and initial start up.
4Get your installer to explain your installation to you.
4Have the required checks and services done.
4Keep the instruction manuals in good condition close to the appliance.
This appliance is not intended to be used by persons (including children) whose physcial, sensory or mental capacity is impaired or persons with no experience or knowledge, unless they have the benefit, through the intermediary of a person responsible for their safety, of supervision or prior instructions regarding use of the appliance. Care should be taken to ensure that children do not play with the appliance.
To prevent hazardous situations from arising, if the mains lead is damaged it must be replaced by the original manufacturer, the manufacturer’s dealer or another suitably skilled person.
1.4Certifications
CE identification no |
CE-0085CM0178 |
NOx classification |
5 (EN 297 pr A3, EN 483) |
Type of connection |
Chimney: B23, B33 |
|
Flue gas outlet: C13(x), C33(x), C43(x), C53, C83(x), |
|
C93(x) |
|
|
03/12/2013 - 300026080-001-03 |
|
|
|
6 |
|
|
2. Safety instructions and recommendations |
AGC 10/15 AGC 15 AGC 25 AGC 35 |
2Safety instructions and recommendations
2.1Safety instructions
DANGER
If you smell gas:
1. Do not use a naked flame, do not smoke, do not operate electrical contacts or switches ( doorbell, light, motor, lift, etc..).
2. Shut off the gas supply.
3. Open the windows.
4. Evacuate the premises.
5. Call your fitter.
DANGER
If you smell flue gases:
1. Switch the appliance off.
2. Open the windows.
3. Evacuate the premises.
4. Call your fitter.
WARNING
Depending on the settings of the appliance:
4 Thetemperatureofthefluegasconduitsmayexceed 60°C.
4 The temperature of the radiators may reach 85°C.
4 Thetemperatureofthedomestichotwatermayreach 65°C.
CAUTION
Do not neglect to service the appliance:
4 For completely safe and optimum operation, you must have your boiler regularly serviced by an approved installer.
7 |
|
|
|
03/12/2013 - 300026080-001-03 |
|
|
AGC 10/15 AGC 15 AGC 25 AGC 35 |
2. Safety instructions and recommendations |
2.2Recommendations
WARNING
Only qualified professionals are authorised to work on the appliance and the installation.
4Regularly check the water pressure in the installation (minimum pressure 0.8 bar, recommended pressure between 0.08 and 1.5 bar).
4Keep the appliance accessible at all times.
4Never remove or cover labels and rating plates affixed to the appliance.Labelsandratingplatesmustbelegiblethroughoutthe entire lifetime of the appliance.
4The appliance should be on Summer or Antrifreeze mode rather than switched off to guarantee the following functions:
-Anti blocking of pumps
-Antifreeze protection
03/12/2013 - 300026080-001-03 |
|
|
|
8 |
|
|
3. Description |
AGC 10/15 AGC 15 AGC 25 AGC 35 |
3Description
3.1Operating principle
3.1.1.Gas/air setting
Air is sucked in by the fan and the gas injected into the venturi attachedtothefaninlet.Thefanrotationspeedmodulatesandadapts tothermalenergyrequirementsthankstothetemperaturesmeasured bythevarioussensors.Thegasandairaremixedintheventuri,which enables operation at a constant ratio. The noise of the venturi is absorbed by a silencer attached to its inlet. The gas/air mixture is carried to the burner in the top of the exchanger, guided by the premix channel.
3.1.2.Combustion
The burner heats the heating water circulating in the heat exchanger. At a return temperature lower than around 55°C, the flue gases cool down to a temperature lower than the dew point, thus causing the condensation of the water vapour contained in the flue gases in the lower section of the heat exchanger. The heat released duringthiscondensationprocess(thelatentheatorcondensingheat) isalsotransferredtotheheatingwater.Thecooledcombustiongases are evacuated via the combustion gas outlet flue. The condensation water is evacuated via a siphon.
9 |
|
|
|
03/12/2013 - 300026080-001-03 |
|
|
AGC 10/15 AGC 15 AGC 25 AGC 35 |
3. Description |
3.2Main parts
|
|
|
1 |
Flue gas discharge pipe |
|
|
|
2 |
Flue gas measuring point |
|
|
|
3 |
Heat exchanger |
5 |
|
|
4 |
Ignition/ionization electrode |
|
|
5 |
Box for the control PCBs |
|
|
|
|
||
|
|
|
6 |
Control panel |
6 |
|
|
7 |
Command module |
|
|
|
8 |
Water pressure sensor |
7 |
|
|
9 |
Circulation pump |
|
|
|
||
|
|
|
10 |
Hydroblock |
|
|
|
11 |
3-way valve |
|
|
|
12 |
Safety valve |
|
8 |
|
13 |
Casing |
|
|
|
||
|
|
C003072-C |
14 |
Expansion vessel |
|
|
|
15 |
Combined venturi and gas valve unit |
|
|
|
16 |
Fan |
|
|
|
17 |
Air intake silencer |
|
|
|
18 |
Mixer pipe |
|
|
|
19 |
Automatic air vent |
03/12/2013 - 300026080-001-03 |
|
|
|
10 |
|
|
3. Description |
AGC 10/15 AGC 15 AGC 25 AGC 35 |
3.3Control panel
3.3.1.Description of the keys
|
|
|
|
|
|
|
|
|
|
|
|
|
A000866-A |
|
0 |
2 |
4 |
6 |
8 |
10 |
12 |
14 |
16 |
18 |
20 |
22 |
24 |
A |
|
|
|
|
|
|
|
|
|
|
|
|
|
B |
BAR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
pb AUTOxc g m rjM |
|
|
|
|||||||||
C |
( |
|
|
' STD |
|
|
|
t |
|
|
|
||
|
|
|
|
|
|
|
|
|
|||||
|
D |
|
|
|
|
E |
|
|
|
|
|
|
F |
ATemperature setting key (heating, DHW, swimming pool)
B |
Operating mode selection key |
CDHW override key
DKey to access the parameters reserved for the installer
EKeysonwhichthefunctionvariesasandwhenselections are made
FRotary setting button:
4 Turn the rotary button to scroll through the menus or modify a value
4 Press the rotary button to access the selected menu or confirm a value modification
11 |
|
|
|
03/12/2013 - 300026080-001-03 |
|
|
AGC 10/15 AGC 15 AGC 25 AGC 35 |
3. Description |
3.3.2.Description of the display
n Key functions
|
|
|
|
|
|
|
|
|
|
|
|
|
|
> |
|
0 |
2 |
4 |
6 |
8 |
10 |
12 |
14 |
16 |
18 |
20 |
22 |
24 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
( |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
’ |
BAR |
r |
|
|
|
|
|
|
|
|
|
|
|
|
? |
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
pb AUTOxc g m rjL |
|
|
A |
f |
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
- |
|
|
( |
|
|
' STD |
|
|
|
t |
|
|
C002696 |
STD |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
b |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
v |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
j |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ESC |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
t |
Access to the various menus
Used to scroll through the menus
Used to scroll through the parameters
The symbol is displayed when help is available
Used to display the curve of the parameter selected
Reset of the time programmes
Selection of comfort mode or selection of the days to be programmed
Selection of reduced mode or deselection of the days to be programmed
Back to the previous level
Back to the previous level without saving the modifications made
Manual reset
n Flame output level
0 |
2 |
4 |
6 |
8 |
10 |
12 |
14 |
16 |
18 |
20 |
22 |
24 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
C002705-A |
BAR |
|
|
|
|
|
|
|
|
|
|
|
|
|
pb AUTOxc g m |
rjM |
|
|
|
-A |
||||||||
|
|
C002701-B |
C002704 |
||||||||||
|
|
|
|
|
STD |
|
|
|
t |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
C002703-A |
The whole symbol flashes: The burner starts up but the flame is not yet present
Part of the symbol flashes: Output is increasing
Steady symbol: The required output has been reached
Part of the symbol flashes: Output is dropping
C002702-A
03/12/2013 - 300026080-001-03 |
|
|
|
12 |
|
|
3. Description |
AGC 10/15 AGC 15 AGC 25 AGC 35 |
n Solar (If connected)
|
|
|
|
|
|
|
|
|
|
|
|
|
u |
0 |
2 |
4 |
6 |
8 |
10 |
12 |
14 |
16 |
18 |
20 |
22 |
24 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
L000200-A |
|
|
|
|
|
|
|
|
|
|
|
|
|
-A |
BAR |
|
|
|
|
|
|
|
|
|
|
|
|
L000201 |
pb AUTOxc g m |
rjM |
|
|
|
|||||||||
|
|
-A |
|
||||||||||
|
|
|
|
|
STD |
|
|
|
t |
|
|
L000197 |
L000198-A |
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
L000199-A |
The solar load pump is running
The top part of the tank is reheated to the tank set point
The entire tank is reheated to the tank set point
The entire tank is reheated to the solar tank set point
The tank is not loaded - Presence of the solar control system
n Operating modes
|
|
|
|
|
|
|
|
|
|
|
|
p |
0 |
2 |
4 |
6 |
8 |
10 |
12 |
14 |
16 |
18 |
20 |
22 |
24 |
|
|
|
|
|
|
|
|
|
|
|
|
b |
BAR |
|
|
|
|
|
|
|
|
|
|
|
|
pb AUTOxc g m rjM |
|
|
B |
|||||||||
|
|
|
|
|
STD |
|
|
|
t |
|
|
C002697- |
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
AUTO |
0 |
2 |
4 |
6 |
8 |
10 |
12 |
14 |
16 |
18 |
20 |
22 |
24 |
|
|
|
|
|
|
|
|
|
|
|
|
x |
BAR |
|
|
|
|
|
|
|
|
|
|
|
|
pb AUTOxc g m rjM |
|
|
B |
|||||||||
|
|
|
|
|
STD |
|
|
|
t |
|
|
C002698- |
|
|
|
|
|
|
|
|
|
|
m |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
g |
|
|
|
|
|
|
|
|
|
|
|
|
m |
Summer mode: The heating is off. Domestic hot water continues to be produced
WINTER mode: Heating and domestic hot water working
Operation in automatic mode according to the timer programme
Comfort mode: The symbol is displayed when a DAY override (comfort) is activated
4Flashing symbol: Temporary override
4Steady symbol: Permanent override
Reduced mode: The symbol is displayed when a NIGHT override (reduced) is activated
4Flashing symbol: Temporary override
4Steady symbol: Permanent override
Holidaymode:ThesymbolisdisplayedwhenaHOLIDAY override (antifreeze) is activated
4Flashing symbol: Holiday mode programmed
4Steady symbol: Holiday mode active
Manual mode: The boiler operates with the displayed set point. All of the pumps operate. The 3-way valves are not controlled.
13 |
|
|
|
03/12/2013 - 300026080-001-03 |
|
|