Carrier 30GX125, 30GX080, 30GX115, 30GX150, 30GX136 Controls, Start-up, Operation, Service, And Troubleshooting

...
0 (0)
ECOLOGIC™ Air-Cooled and Fluid Cooled Chillers
Controls Start-Up, Operation,
Service, and Troubleshooting
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical components, and equipment location (roof, elevated structures, etc.). Only trained, qualified installers and service mechanics should in­stall, start up, and service this equipment.
When working on this equipment, observe precautions in the literature, and on tags, stickers, and labels attached to the equipment, and any other safety precautions that apply. Follow all safety codes. W ear safety glasses and work gloves. Use care in handling, rigging, and setting this equipment, and in han­dling all electrical components.
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation and ser­vice. There may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work is completed.
This unit uses a microprocessor-based electronic control system. Do not use jumpers or other tools to short out com­ponents, or to bypass or otherwise depart from recom­mended procedures. Any short-to-ground of the control board or accompanying wiring may destroy the electronic modules or electrical components.
To prevent potential damage to heat exchanger tubes always run fluid through heat exchangers when adding or removing refrigerant charge. Use appropriate brine solu­tions in cooler and condenser fluid loops to prevent the freezing of heat exchangers when the equipment is exposed to temperatures below 32 F (0° C).
DO NOT VENT refrigerant relief valves within a build­ing. Outlet from relief valves must be vented outdoors in accordance with the latest edition of ANSI/ASHRAE (American National Standards Institute/Ame rican Society of Heating, Refrigeration and Air Conditioning Engineers) 15 (Safety Code for Mechanical Refrigeration). The accu­mulation of refrigerant in an enclosed space can displace oxygen and cause asphyxiation. Provide adequate ventila­tion in enclosed or low overhead areas. Inhalation of high concentrations of vapor is harmful and may cause heart ir­regularities, unconsciousness or death. Misuse can be fatal. Vapor is heavier than air and reduces the amount of oxygen available for breathing. Product causes eye and skin irrita­tion. Decomposition products are hazardous.
30GX080-350
30HXA,HXC076-271
50/60 Hz
Series 3
DO NOT attempt to unbraze factory joints when servicing this equipment. Compressor oil is flammable and there is no way to detect how much oil may be in any of the refrig­erant lines. Cut lines with a tubing cutter as required when performing service. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to system. DO NOT re-use compressor oil.
CONTENTS
SAFETY CONSIDERATIONS GENERAL MAJOR SYSTEM COMPONENTS Processor Module (PSIO-1) DSIO-HV Relay Module Electronic Expansion Device Module Compressor Protection Module (CPM) PSIO-2 (8052) Module Keypad and Display Module
(Also Called HSIO-II) Control (LOR) Switch OPERATION D ATA Electronic Expansion Device (EXD)
• EXV OPERATION
• ECONOMIZER OPERATION
Oil Pumps Motor Cooling Back Pressure Valve (30GX and 30HXA only) Sensors Compressor Protection Module (CPM)
• OUTPUTS
• INPUTS
Wye-Delta vs Across-the-Line (XL)
Starting Option Capacity Control
• MINUTES LEFT FOR START
• MINUTES OFF TIME
• LOADING SEQUENCE
• CLOSE CONTROL
• LEAD/LAG DETERMINATION
• CAPACITY SEQUENCE DETERMINATION
• MINIMUM LOAD VALVE
• CAPACITY CONTROL OVERRIDES
Head Pressure Control
• GENERAL
• AIR-COOLED UNITS (30GX)
• WATER-COOLED UNITS (30HXC)
• CONDENSERLESS UNITS (30HXA)
• 09DK CONDENSING UNITS
• ADJUSTING PID ROUTINES
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2,3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-44
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
. . . . . . . . . . . . . . . . . . . . . . 1
. . . . . . . . . . . . . . . . . 3
. . . . . . . . . . . . . . . . . . . . . . 3
. . . . . . . . . . . . . . . . . . . . . . . . . . . 3
. . . . . . . . . . . . . 3
. . . . . . . . . . . 3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
. . . . . . . . . . . . . . . . . . . . . . . . . . . 3
. . . . . . . . . . . . . . 3
. . . . . 4
. . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . . . . . . 10
Page
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Ta b 5 c
PC 903 Catalog No. 533-095 Printed in U.S.A. Form 30G,H-5T Pg 1 8-99 Replaces: 30G,H-4T
CONTENTS (cont)
Page
Cooler and Condenser (30HXC) Pump Control
• COOLER PUMP CONTROL
• CONDENSER PUMP CONTROL
Cooler Heater Control Oil Heater Control Keypad and Display Module
(Also Called HSIO-II)
• ACCESSING FUNCTIONS
AND SUBFUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . 15
• AUTOMATIC DEFAULT DISPLAY . . . . . . . . . . . . . . 15
• STATUS FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . 19
• TEST FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
• HISTORY FUNCTION. . . . . . . . . . . . . . . . . . . . . . . . . 27
• SET POINT FUNCTION . . . . . . . . . . . . . . . . . . . . . . . 27
• SERVICE FUNCTION . . . . . . . . . . . . . . . . . . . . . . . . . 32
• SCHEDULE FUNCTION. . . . . . . . . . . . . . . . . . . . . . . 39
Temperature Reset
• EXTERNAL TEMPERATURE RESET
• EXTERNALLY POWERED RESET
• RETURN FLUID TEMPERATURE RESET
Demand Limit
• DEMAND LIMIT (Switch Controlled, 30GX Only)
• EXTERNALLY POWERED DEMAND LIMIT
• DEMAND LIMIT (CCN Loadshed Controlled)
TROUBLESHOOTING Checking Display Codes Unit Shutoff Complete Unit Stoppage Single Circuit Stoppage Restart Procedure
• POWER FAILURE EXTERNAL TO THE UNIT
Alarms and Alerts Compressor Alarm/Alert Circuit EXD Troubleshooting Procedure
• INSPECTING/OPENING ELECTRONIC EXPANSION VALVES
• INSPECTING/OPENING ECONOMIZERS
SERVICE Servicing Coolers and Condensers
• TUBE PLUGGING
• RETUBING
• TIGHTENING COOLER/CONDENSER HEAD BOLTS
Inspecting/Cleaning Heat Exchangers
•COOLERS
• CONDENSERS (30HX Only)
Water Treatment Condenser Coils (30GX Only)
• COIL CLEANING
Condenser Fans (30GX Only) Refrigerant Charging/Adding Charge Oil Charging/Low Oil Recharging Oil Filter Maintenance
• REPLACING THE EXTERNAL OIL FILTER
• REPLACING THE INTERNAL OIL FILTER
Compressor Changeout Sequence
• BURNOUT CLEAN-UP PROCEDURE
Moisture-Liquid Indicator Filter Drier Liquid Line Service Valve Thermistors
•LOCATION
• THERMISTOR REPLACEMENT
Pressure Transducers
• PRESSURE TRANSDUCER CALIBRATION
• TROUBLESHOOTING
Safety Devices
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
. . . . . . . . . . . . . . . . . . . . . . . . . . . 15
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
. . . . . . . . . . . . . . . . . . . . . . . . . . 15
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
. . . . . . . . . . . . . . . . . . . . . . . . . 45-54
. . . . . . . . . . . . . . . . . . . . . . . . 45
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
. . . . . . . . . . . . . . . . . . . . . . . . 45
. . . . . . . . . . . . . . . . . . . . . . . . . 45
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
. . . . . . . . . . . . . . . . . 46
. . . . . . . . . . . . . . . . 52
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54-68
. . . . . . . . . . . . . . 54
. . . . . . . . . . . 55
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
. . . . . . . . . . . . . . . . . . . 55
. . . . . . . . . . . . . . . . . . . . 56
. . . . . . . . . . . . 56
. . . . . . . . . . . . . . . . 57
. . . . . . . . . . . . . . . . . . . . . . . . . . . 58
. . . . . . . . . . . . . . 58
. . . . . . . . . . . . . . . . . . . . . . . . 60
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
. . . . . . . . . . . . . . . . . . . . . . . . 60
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
. . . . . . . . . . . . . . . . . . . . . . . . . . . 61
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
• COMPRESSOR PROTECTION
• OIL SEPARATOR HEATERS (30GX)
• COOLER PROTECTION
Relief Devices
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
• PRESSURE RELIEF VALVES
Control Modules
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
• PROCESSOR MODULE (PSIO-1), COMPRESSOR PROTECTION MODULE (CPM), HIGH VOLTAGE RELAY MODULE (DSIO-HV), AND EXV DRIVER MODULE (DSIO-EXV), 12/6 MODULE (PSIO-2)
• RED LED
• GREEN LED
• CONTROL MODULE BATTERY REPLACEMENT
Carrier Comfort Network (CCN) Interface
. . . . . . . . 66
• PROCESSOR MODULE (PSIO-1)
• HIGH VOLTAGE RELAY MODULE (DSIO-HV)
Replacing Defective Processor Module Winter Shutdown Preparation PRE-START-UP PROCEDURE System Check
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
START-UP AND OPERATION Actual Start-up Operating Sequence FIELD WIRING
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70-75
. . . . . . . . . . . . . . . . . . . 68
. . . . . . . . . . . . . . . . . . . . 69
. . . . . . . . . . . . . . . . . . . . . 69
. . . . . . . . . . 68
APPENDIX A
(Compressor Must Trip Amps)
. . . . . . . . . . . . . 76-80
APPENDIX B
(Capacity Loading Sequence) APPENDIX C (Available Accessories) APPENDIX D (Building Interface)
. . . . . . . . . . . . . . 81-85
. . . . . . . . . 86,87
. . . . . . . . . . . . . 88-92
APPENDIX E (Cooler and
Condenser Pressure Drop)
. . . . . . . . . . . . . . . . . 93-96
APPENDIX F
(Typical System Components) INDEX START-UP CHECKLIST
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
. . . . . . . . . . . . . . . . .CL-1 to CL-8
. . . . . . . . . . . . . 97,98
GENERAL
IMPORTANT: The 30GX,HX units use refrigerant R-134a. Compressor oil used with R-134a is Polyolester oil.
This publication contains Start-Up, Service, Controls, Oper­ation and Troubleshooting data for the 30GX080-350 and 30HXA,C076-271 screw chillers.
Circuits are identified as circuits A and B, and compressors are identified as A1 or A2 in circuit A, and B1 or B2 in circuit B.
The 30GX,HX Series chillers feature microprocessor-based electronic controls and electronic expansion devices (EXD) in each refrigeration circuit.
The control system cycles compressor loaders and/or com­pressors to mai ntain the se lected lea ving fluid te mperature s et point. The system automatically positions the EXD to maintain the specified refrigerant level in the cooler. The system also has capabilities to control a condenser water valve to maintain suit­able leaving-water temperature for the 30HXC unit. Safeties are continuously monitored to prevent the unit from operating under unsafe conditions. A scheduling function can be pro­grammed by the user to control the unit’s occupied and unoc­cupied schedules. The control also operates a test function and a manual control function that allows the operator to check out­put signals and ensure components are operable.
The control system consists of a processor module (PSIO-1), an EXD driver module (DSIO-EXV), a high voltage relay module on 30GX units (DSIO-HV), 2 six-pack relay boards, a keypad and display module (also called HSIO-II), 2 electronic expansion devices (EXDs), 1 compressor protec­tion module (CPM) per pair of compressors, a PSIO-2 module,
2
6 thermistors, and up to 10 transducers. A remote enhanced display is available as an accessory.
MAJOR SYSTEM COMPONENTS
Processor Module (PSIO-1) —
upgrade to the original PSIO (8088) module, with superior electrical noise immunity capability. It contains the operating software and controls the operation of the machine. It has 12 input channels and 6 output channels.
The PSIO-1 continuously monitors input/output channel in­formation received from all the modules and controls all output signals for all output channels. It also controls the relays on the six-pack relay board. The processor module also controls the EXD driver module, commanding it to open or close each EXD in order to maintain the proper cooler level. Information is transmitted between the processor module, CPM modules, the EXD driver module, and the HSIO-II standard display module through a 3-wire communications bus called COMM3. The remote enhanced display (accessory) is connected to the PSIO-1 module through a 3-wire communications bus, but uses a different communication bus called COMM1. The COMM1 bus is also used to communicate to other CCN (Carrier Comfort Network) devices when the unit is installed in a network application.
DSIO-HV Relay Module —
4 inputs and 8 outputs and is installed on 30GX units only. The module communicates the status of the inputs with the PSIO-1 module and operates the oil heater, outdoor fan, and minimum load control outputs.
Electronic Expansion Device Module —
electronic expansion device module has 4 inputs and 2 outputs. It receives signals from the PSIO-1 module and operates the electronic expansion devices. The electronic expansion device module also sends the PSIO-1 module the status of its 4 input channels.
Compressor Protection Module (CPM) —
compressor protection module monitors the high pressure switch status, running current, and motor temperature for each compressor. Each CPM controls up to 2 compressors. The CPM also controls the motor cooling solenoid, oil solenoid, and contactor outputs. A pre-punched configuration header for each compressor determines the must trip amps setting. Each CPM sends the PSIO-1 each compressor’s motor temperature, relay status, and running current as a percentage of the must trip amps value. The CPM als o communic ates any al arm con­ditions as the feedback value.
PSIO-2 (8052) Module —
put/output module only, as there is no unit software loaded in the module. This module has 12 input channels and 6 output channels.
This module is an
The DSIO-HV module has
The
The
This module is used as an in-
Keypad and Display Module (Also Called HSIO-II) —
keys, 4 operative keys, 12 numeric keys, and a 2-line 24-character alphanumeric LCD (liquid crystal display). Key usage is explained in the Accessing Functions and Subfunc­tions section on page 15.
Control (LOR) Switch —
fined by the position of the LOCAL/OFF/REMOTE (LOR) switch. This is a 3-positi on manual swit ch th at allow s th e chill­er to be put under the control of its own controls (LOCAL ), manually stopped (OFF), or controlled through a set of remote contacts (REMOTE). This switch i s different than the switch
This device consists of a keypad with 8 function
Control of the chiller is de-
that is used in the Flotronic™ II controls configuration. The CCN control is enabled through the H SIO-II. The switch al­lows unit operation as shown in T able 1.
In the LOCAL position, the c hiller i s allowed to ope rate and respond to the scheduling configuration, CCN configuration, and set point data. In the remote position, the unit operates sim­ilarly to the LOCAL position, except the remote contacts must be closed for the unit to operate.
Table 1 — Unit Mode from LOR Switch
and CCN State
SWITCH
POSITION
LOCAL
OFF
REMOTE
CCN — NR —
NOTE: If the unit is configured for a clock, then the unit is under clock control if it is in an ON mode.
REMOTE
CONTACTS
NR
NR NR NR LOCAL OFF
OPEN NR NR LOCAL OFF
CLOSED
LEGEND Carrier Comfort Network
Input Not Read by Processor
CCN
CONFIGURATION
DISABLE NR LOCAL ON
ENABLE
DISABLE NR LOCAL ON
ENABLE
CCN
STATE
RUN CCN ON
STOP CCN OFF
RUN CCN ON
STOP CCN OFF
UNIT
MODE
OPERATION DATA
Electronic Expansion Devi ce (EXD) —
processor controls the EXD through the EXD driver module . The EXD will either be an EXV (electronic expansion valve) or an economizer. Inside both these devices is a linear actuator step­per motor.
EXV OPERATION — High-pressure liquid refrigerant en­ters the valve through the bottom. A series of calibrated slots are located inside t he orifice assembly. As refrigerant passes through the orifice, the pressure drops and the refrigerant changes to a 2-phase condition (liquid and vapor). To control refrigerant flow for different operating conditions, the sleeve moves up and down over the orifice, thereby changing orifice size. The sleeve is moved by a linear stepper motor. The step­per motor moves in increments and is controlled directly by the processor module. As the stepper motor rotates, motion is transferred into linear movement by the lead screw. Through the stepper motor and lead screw, 1500 discrete steps of motion are obtained. The large number of steps and long stroke result in very accurate control of refrigerant flow.
Each circuit has a liquid level sensor mounted vertically in the top of the cooler shell. The level sensor consists of a small electric resistance heater and 3 thermi stors wire d in s eries , po­sitioned at different heights inside the body of the well. The heater is designed so that the thermistors read approximately 200 F (93.3 C) in dry air . As the refrigerant level ris es (falls) in the cooler, the resistance of the closes t thermistor(s) will in­crease (decrease) as it is cooled by the rising liquid refrigerant (heated by the heater). This large resistance difference allows the control to accurate ly maint ain a spe cified le vel.
The level sensor monitors the refrigerant liquid level in the cooler and sends this infor mation to the PSIO-1. At initia l start­up, the EXV position is at zero. After that, the microprocessor keeps accurate track of the valve position in order to use this in­formation as input for the other control functions. The proces­sor does this by initializing the EXVs at start-up. The processor sends out enough closing pulses to the valve to move it from fully open to fully closed, then resets the position counter to ze­ro. From this point on, until the next initialization, the proces­sor counts the total number of open and closed steps it has sent to each valve.
The micro-
3
ECONOMIZER OPERATION — Economizers are factory installed on 30GX105-350 units and 30HXA,C161-271 units. All other sizes use standard EXVs. The economizer improves both the chiller capacity and efficiency as well as providing compressor motor cooling. Inside the economizer are both a linear stepper motor (same as standard EXV motor) and a float valve. The stepper motor is controlled by the processor to maintain the desired liquid level in the cooler (as is done for chillers without economizers). The float valve maintains a liq­uid level in the bottom of the economizer.
Liquid refrigerant is supplied from the condenser through the end to the bottom of the economizer. A bubbler tube sup­plies a small amount of discharge gas to ensure that the float will be able to work properly. As the refrigerant passes through the EXD, its pr essure is reduced to an inter mediate level of about 75 psig (517 kPag). This pressure is maintained inside the economizer shell. Next, the refrigerant flows through the float valve where its pressure is further reduced to slightly above the pressure in the cooler.
The increase in performance is achieved when some of the refrigerant passing through the EXD flashes to vapor, further subcooling the liquid that is maintained at the bottom of the economizer. This increase in subcooling provides additional capacity. Also, since the additional power required to accom­plish this is minimal, the efficiency of the m achine improves. The vapor that flashes rises to the top of the economizer where it passes to the compressor and is used to provide motor cool­ing. After passing over the motor windings, the refrigerant reenters the cycle at an intermediate port i n the compression cycle.
Oil Pumps —
nally mounted prelubricating oil pump per circuit. This pump is operated as part of the start-up sequence. On 30GX units, the pumps are mounted to the base rails on the oil separator side of the unit. The pumps are mounted to a bracket on the condens­ers of 30HXC units and to the oil separator on 30HXA units.
When a circuit is required to start, the controls energize the oil pump first and read the oil pressure transducer reading. The pump is operated for a period of 20 seconds, after which the oil solenoid is energized to open the oil inlet valve at the compres­sor. The control again reads the pressure from the oil pressure transducer. If the pump has built up sufficient oil pressure, the compressor is allowed to start.
Once the compressor has started, the oil pump is turned off within 10 seconds. If the pump is not able to build up enough oil pressure, the pump is turned off. Within 3 seconds, the pump is re-energized and makes one additio nal attempt to build oil pressure. The control generates an alarm if the second at­tempt fails.
The oil pump is also used to supplement system pressure under certain operating conditions. The oil flow requirements of the compressor vary based on pressure differential across the compressor. The oi l pump is designed to provi de differential oil pressure during low pressure differential conditions. It is not designed to overcome high pressure drop across filters during high pressure differential conditions.
If the differential oil pressure (oil pressure – economizer pressure) for a compressor is less than 13 psi then the oil pump will be started. Just before the oil pump is started the control measures the pressure differential between the discharge pres­sure and oil pressure (oil system pressure drop). The oil system pressure drop is saved and used to determine when the oil pump should be shut off.
When the oil pump is operating, it is capable of increasing oil pressure from 0 psi to 50 psi depending on the oil flow
The 30GX,HX screw chillers use one exter-
requirements of the compressor. For example, if the compres­sor needs 2 gpm (high pressure differential condition) and the oil pump is capable of 1.2 gpm, there is no pressure rise and the oil flow will bypass the check valve and supply the 2 gpm to the compressor. If the compressor requires .75 gpm, the oil pump will increase pressure to satisfy the oil pressure require­ment.
The pump will continue to operate until the discharge pres­sure minus economizer pressure is greater then 17 psi plus the oil system pressure drop.
Example:
Discharge pressure 80 psi
Oil pressure 65 psi
Oil system pressure drop80 –65 = 15 psi
Economizer pressure 55 psi
Suction pressure 42 psi
Based on the above conditions the oil pump will be started because differential oil pressure equals 10 psi.
The oil pump will continue to operate until the discharge pressure minus economizer pressure (which equals 25) is greater than 17 plus 15 (oil system loss before pump was start­ed). The only way this can be satisfied is if the discharge pres­sure increases or the compressor unloads at which point the oil pump will be shut off.
Motor Cooling —
tures are controlled to a set point of 200 F (93.3 C). The control accomplishes this by cycling the motor cooling solenoid valve to allow liquid refrigerant to flow across the motor windings as needed. On units equipped with economizers, flash gas leaves the top of the economizer and continually flows to the motor windings. All refrigerant used for motor cooling re-enters the rotors through a port located midway along the compression cycle and is compressed to discharge pressure.
Compressor motor winding tempera-
Back Pressure Valve (30GX and 30HXA only) —
30GX units and mounted on the oil separator shell of 30HXA units. The valve’s function is to ensure that there is sufficient system differential pressure to allow for oil to be driven back to the compressor. A small copper line (economizer pressure) is connected to the top of the valve, which contains an internal spring that closes a piston if the pressure in the oil separator is not at least 15 psig greater than the economizer pressure.
Sensors —
Flotronic™ II chiller control system) gathers information from sensors to control the operation of the chiller. The units use up to 10 standard pressure transducers, up to 8 standard ther­mistors (including 4 motor temperature thermistors), and 2 liq­uid level thermistors to monitor and control system operation. The sensors are listed in Table 2.
Compressor Protection Module (CPM) —
CPM controls up to 2 compressors. The CPM provides the fol­lowing functions:
• compressor main contactor control|
• Wye-Delta contactor transition
• compressor ground current protection
• motor temperature reading
• high-pressure protection
• reverse rotation protection
• current imbalance protection
• compressor oil solenoid control
• motor cooling solenoid contro l
• sensor bus communications
• starting and running overcurrent protection
This valve is located on the oil separator outlet on
The 30GX,HX control system (based on the
One
4
The CPM has the following 4 output relays and 4 inputs:
OUTPUTS:
• compressor contactor
• compressor oil solenoid
• compressor motor cooling soleno id
• Wye-Delta transition relay INPUTS:
• motor temperature
• three-phase current
• high-pressure switch A diagram of the CPM board is (HN67LM101) shown in
Fig. 1. One CPM board is installed on 30GX080-176 and 30HXA,C076-186 units, and 2 CPM boards are installed on 30GX205-350 and 30HXA,C206-271 units. The address for
switches 3 and 4. For CPM1 (compressors A1 and B1), both DIP switches should be set to 0. For CPM2 (compressor A2, for 30GX205-265 and 30HXA,C206-271 units only and com­pressors A2 and B2 for 30GX281-350 only), both switches should be set to 1. See Table 3 for CPM board connections. The CPM has a reset button located between the DIP switch and the J10 connector. Pressing the reset button on the CPM will clear any current CPM alarms, but will not turn off any outputs from the CPM. Pressing the reset button on the CPM will NOT cause the board to go through initialization. Initial­ization period only occurs during power-up and lasts for ap­proximately 2 minutes. Each compressor’s MTA (must trip amps) setting is communicated to the PSIO-1 during the initial­ization period. Switches 1 and 2 should be set to 0. See Table 4 for DIP switch settings.
each CPM board is set using DIP (dual in-line package)
Table 2 — Thermistor and Transducer Locations
Sensor Description Location Connection Terminals T1 T2 Motor Temp A1 Motor Temp A2* Motor Temp B1 Motor Temp B2† T5 T6 LL-A (T3) LL-B (T4) T7 (optiona l)* * STP (optional)** T8 (optiona l)* * T9 (optiona l)* *
Sensor Description Location Connection Terminals DPT-A SPT-A EPT-A OPT-A1 OPT-A2* DPT-B SPT-B EPT-B OPT-B1 OPT-B2†
*30HX206-271 and 30GX205-265 only. †Sensors are available as accessories for field installation.
Cooler Leaving Fluid Temp Cooler Head Leaving Fluid Side PSIO-2, J7 pins 2,3 Cooler Entering Fluid Temp Cooler Head Entering Fluid Side PSIO-2, J7 pins 5,6 Motor Temperature A1 Compressor A1 Junction Box CPM1, plug J5 Motor Temperature A2 Compressor A2 Junction Box CPM2, plug J5 Motor Temperature B1 Compressor B1 Junction Box CPM1, plug J9 Motor Temperature B2 Compressor B2 Junction Box CPM1, plug J9 Discharge Gas Temp A Top of Oil Separator Circuit A PSIO-2, J7 pins 8,9 Discharge Gas Temp B Top of Oil Separator Circuit B PSIO-2, J7 pins 11,12 Liquid Level Circuit A Top of Cooler Circuit A PSIO-1, J7 pins 5,6 Liquid Level Circuit B Top of Cooler Circuit B PSIO-1, J7 pins 8,9 Outdoor Air Thermistor Outside Air Stream PSIO-2, J7 pins 20,21 Space Temperature Conditioned Space PSIO-2, J7 pins 23,24 Condenser Entering Water Thermistor Condenser Entering Fluid Line PSIO-2, J7 pins 14,15 Condenser Leaving Water Thermistor Condenser Leaving Fluid Line PSIO-2, J7 pins 17,18
Discharge Pressure Circuit A Top of Condenser Separator Circuit A PSIO-1, J7 pin 22 Suction Pressure Circuit A Top of Cooler Circuit A PSIO-1, J7 pin 19 Economizer Pressure Circuit A Economizer Line Entering Comp A PSIO-1, J7 pin 10 Oil Pressure Compressor A1 Compres sor A1 Oil Connection PS IO-1, J7 pin 25 Oil Pressure Compressor A2 Compres sor A2 Oil Connection PS IO-1, J7 pin 1 Discharge Pressure Circuit B Top of Oil Separator Circuit B PSIO-1, J7 pin 16 Suction Pressure Circuit B Top of Cooler Circuit B PSIO-1, J7 pin 31 Economizer Pressure Circuit B Economizer Line Entering Comp B PSIO-1, J7 pin 13 Oil Pressure Compressor B1 Compres sor B1 Oil Connection PS IO-1, J7 pin 28 Oil Pressure Compressor B2 Compres sor B1 Oil Connection PS IO-1, J7 pin 16
THERMISTORS
PRESSURE TRANSDUCERS
Table 3 — Compressor Protection Module
(CPM) Plug Connections
CPM PLUG DESCRIPTION
J1
J2, J6 J3, J7 J4, J8
J5, J9
J10, J11
NOTE: Plugs J2-J5 are for compressors A1 (CPM1) or A2 (CPM2). Plugs J6-J9 are for compressor B1 (CPM1) or B2 (CPM2).
24-vac Power Input Compressor Contactor(s) High Pressure Switch, Oil and Motor Cooling
Solenoids Current Sensor Input Compressor Motor Temperature Input Communication Connections
30GX080-176 30HXA076-186 30HXC076-186
30GX205-350 30HXA206-271 30HXC206-271
5
Table 4 — CPM Address DIP Switch Settings:
UNIT
CPM1 CPM2
1234 1 2 3 4
0000————
0000 0 0 1 1
To verify proper must trip amps header configuration, press
and use the up arrow key on the HSIO to locate the must trip amp values. Press the reset button on the control pan­el to update these values. See Appendix A. If the values do not match those in Appendix A, verify that the configuration head­ers have been properly punched out.
The CPM communicates on the COMM3 communic ation bus to the PSIO-1 module. Proper operation of the CPM board can be verified by observing the 2 LEDs (light-emitting diodes) located on the board. The red LED blinks at a rate of once ev­ery 1 to 2 seconds. This indicates that the module is powered and operating correctly. The green LED blinks when the mod­ule is satisfactorily communicating with the PSIO-1 module. The CPM communicates the status of its inputs and outputs, and reports 15 different alarm conditions to the PSIO-1. The alarms are listed in Table 5.
The CPM module has many features that are specifically designed to protect the compressor, including reverse rota­tion protection. Do not attempt to bypass or alter any of the factory wiring. Any compressor operation in the reverse direction will result in a compressor failure that will require compressor replacement.
The PSIO-1 will generate an alert when it receives an alarm input from the CPM. The alert will be generated in a y.xx for­mat, where “y” refers to the compre ssor and “xx” to the alarm value in Table 5 (decimal point removed). For example, the HSIO might display Alarm 1.75 for a contactor failure occur­ring on compressor A1. Similarly, the display would read 5.85 for a motor overtemperature condition on compressor B1. Alerts for compressors A2 and B2 (if present) would be gener­ated as “2.xx” and “6.xx,” respectively. Alarm codes 3 and 4 would not be used. Ending zeros are not displayed.
The high-pressure switch is wired in series with the relay coils of the 8 relays on the CPM. If this switch opens during operation, all relays on the CPM are deenergized and the com­pressor is stopped. The failure is reported to the PSIO-1 and the processor module locks off the compressor from restarting un­til the alarm is manually reset.
1
0
SW1
LEGEND
LED — MTA —
NOTES:
1. The red LED blinks continuously when the module is operating properly.
2. The green LED blinks continuously when communi­cating properly with PSIO-1.
3. On all plugs, pin 1 is identified by a “●.’’
1
0
SW2
Light-Emitting Diode Must Trip Amps
1
00
SW3 SW4
1
COMP 2 MTA HEADER
DIP SWITCH
RESET BUTTON
J1
J10
J11
3 2 1
3 2 1
3 2 1
1 2 3 4
8
8
GREEN LED
12
3
RED LED
5
4
5
4
1
COMP 1 MTA HEADER
1
2
3
1
J7
J6
1
J9
J8
J4
J5
J2
J3
2 3
1 2
3
1 2 3 4
1 2 3 4
1 2
3
1 2 3
Fig. 1 — Compressor Protection Module (HN67LM101)
6
Table 5 — Compressor Protection Module
Feedback Codes
High Pressure Switch Trip 1.0 No Motor Current 2.0 Current Imbalance Alarm 10% 2.5 Current Imbalance Warning 10% 2.7 Current Imbalance 25% 3.0 Single Phase Current Loss 3.5 High Motor Current 4.0 Ground Fault 5.0 Contactor Failure 7.5 Current Phase Reversal 8.0 Motor Overtemperature 8.5 Open Thermistor 9.0 Configuration Header Fault 9.5 Shorted Thermistor 10.0 No Error 0
ALARM CONDITION VALUE
Wye-Delta vs Across-the-Line (XL) Starting Option —
208/230-3-60 or 230-3-50 (5 or 8 at Position 12 in model num­ber) are supplied with factory installed Wye-Delta starters. All other voltage options can be ordered with either Wye-Delta or XL starting options. The XL starting method is the most cost effective and simply starts the compressor motor in a Delta configuration (the motors are designed for continuous opera­tion in this configuration) using a single contactor. See Fig. 2. This is the simplest starting method to use and is ideal where starting current does not require limiting.
Where current limitations exist, the Wye-Delta option may be used. See Fig. 3. This option uses a factory-installed starter assembly for each compressor, which consists of 3 contactors labelled 1M, 2M, and S. As the compressor is started, the CPM module energizes contactors 1M and S, which connects and energizes the motor windings in a Wye configuration. The starting current required will be approximately 60% less than that required for an XL start due to the higher impedance of the motor windings when W ye connected. The compressor will at­tain about 100% of its normal operating speed (approximately 3 to 5 seconds) before the CPM module deenergizes the S con­tactor and energizes the 2M contactor, switching the compres­sor windings to a Delta wiring configuration. The S and 2M contactors in the starter assembly are both mechanic ally and electrically interlocked so that they will not both be energized at the same time.
Do not alter the factory-installed power wiring from the control box terminal block to the compressor junction block.
Doing so will cause permanent damage t o the compress or and will require that the compressor be replaced.
Capacity Control —
pressors, loaders, and minimum load control valves to maintain the user-configured leaving chilled fluid temperature set point. Entering fluid temperature is used by the microprocessor to de­termine the temperature drop across the cooler and is used in determining the optimum time to add or subtract capacity stag­es. The chilled fluid temperature set point can be automatically reset by the return temperature reset or space and outdoor-air temperature reset features. It can also be reset from an ext ernal 4 to 20 mA signal (requires field-supplied 500-ohm, sistor), or from a network signal.
The capacity control algorithm runs every 30 seconds. The algorithm attempts to maint a in the Control Point at the desired set point. Each time it runs, the control reads the e ntering and leaving fluid temperatures. The control determines the rate at which conditions are changing and calculates 2 variables based
All 30GX,HX chillers operating at voltages of
The control system cycles com-
1
/2 watt re-
on these conditions. Next, a capacity ratio (Load/Unload Factor under ) is calculated using the 2 variables to deter­mine whether or not to make any changes to the current stages of capacity. This ratio value ranges from –100 to + 100%. If the next stage of capacity is a compressor, the control start s (stops) a compressor when the ratio reaches + 100% (–100%). If the next stage of capacity is a loader, the control energizes (deener­gizes) a loader when the ratio reaches + 60% (–60%). Loaders are allowed to cycle faster than com pressors, to minimize the number of starts and stops on each compressor. A delay of 90 seconds occurs after each capacity step change.
MINUTES LEFT FOR START — This value is displayed in the Status subfunction and represents the amount of time to elapse before the unit is started. This value can be zero without the machine running in many situations. This can include being unoccupied, LOR switch in the OFF position, CCN not allowing unit to start, Demand Limit in effect, no call for cool­ing due to no load, and alarm or alert conditions present. If the machine should be running and none of the above are true, a minimum off time may be in effect. The machine should start normally once the time limit has expired.
MINUTES OFF TIME ( ) — This user configurable time period is used by the control to determine how long unit operation is delayed after power is applied/restored to the unit. It is also used to delay compressor restarts after the unit has shut off its lowest stage of capacity. Typically, this time period is configured when multiple machines are located on a single site. For example, this gives the user the ability t o prevent all the units from restarting at once afte r a power fa ilure. A val ue of zero for this variable does not mean that the unit should be running.
LOADING SEQUENCE — The 30GX,HX compressor effi­ciency is greatest at full load. Therefore, the following sequence list applies to capacity control.
1. The next compressor is not started until all others are run­ning at 100%.
2. The second unloading stage is only used during initial capacity staging of the unit at start-up.
3. Whenever a compressor is started i n a c ircuit , th e loaders in the circuit are deenergized for 15 seconds before the com­pressor is started. The loaders are energized 90 seconds after the compressor is started.
CLOSE CONTROL ( ) — When configured for Close Control, the control is allowed to use any loading/capacity con­trol devices required to maintain better leaving fluid tempera­ture regulation. All stages of unloading are available. See Appendix B for an example.
LEAD/LAG DETERMINATION ( ) — This is a con­figurable choice and is factory set to be automatic. The value can be changed to Circuit A or Circuit B leading, as desired. Set at automatic, the control will sum the current number of logged circuit starts and one-quarter of the current operating hours for each circuit. The circuit with the lowest sum is started first. Changes to which circuit is the lead circuit and which is the lag are made when shutting off compressors.
On 30HX206-271 and 30GX205-350 units set for staged loading, the control fully loads the lead circuit before starting the lag circuit and unloads the lag circuit first. When these units are set for equal loading, the control maintains nearly equal capacities in each circuit when the chiller is loading and unloading.
7
TERMINAL BLOCK
21
22
23
COMPRESSOR CONTACTOR
1
2
3
L1
L2
L3
T1
1
2
T1
3
T3
JUMPER BARS
COMPRESSOR JUNCTION BOX
1
2
3
Fig. 2 — Across-the Line (XL) Compressor Wiring
6
4
5
TERMINAL BLOCK
21
22
23
1
2
3
COMPRESSOR STARTER ASSEMBLY
L1
L2
L3
L1
L2
L3
L1
L2
L3
1M
2M
S
Fig. 3 — Wye-Delta Compressor Wiring
CAPACITY SEQUENCE DETERMINATION ( ) — This is configurable as equal circuit loading or staged circuit loading with the default set at staged. The control determines the order in which the steps of capacity for each circuit are changed. This control choice does NOT have any impact on machines with only 2 compressors.
MINIMUM LOAD VALVE ( ) — When this option is installed and configured, the first stage of capacity is altered by energizing the Minimum Load valve relay. Once the control requires more capacity, the minimum load valve is deenergized and normal capacity staging resumes with loaders and com­pressors. Similarly, the Minimum Load valve relay will be energized for the last stage of capacity to be used before t he circuit is shut down.
Configure Unit for Minimum Load Control
— The chiller must be configured for minimum load control operation. This may be done using the unit keypad (HSIO-2). Set the LOCAL/ OFF/REMOTE (LOR) switch in the OFF position.
COMPRESSOR JUNCTION BOX
T2
T3
T1
T3
T1
T1
T2
T3
T2
1
2
3
21
1
2
22
23
3
6
4
6
4
5
5
1. Press on the keypad.
2. Press the down arrow until the display reads: MIN. LOAD V AL V E SELECT DISABLE
3. T o enable the minimum load valve feature, press
ENTER
.
4. The display may read as follows. (If not, skip to Step 7.) P ASSWORD PROTECTED FUNCTION ENTER P ASSWORD
5. Press .
ENTER
6. The HSIO-2 again displays the following: MIN. LOAD V AL V E SELECT DISABLE
7. Press . The display changes to:
ENTER
MIN. LOAD V AL V E SELECT ENABLE
8
The chiller is now configured for minimum load valve
control. Test Minimum Load Relay Outputs
— After the unit is re­configured, test the operation of the relay and solenoid valve using the Quick Test software function. Test Circuit A as fol­lows (the LOCAL/OFF/REMOTE (LOR) switch must be in the OFF position):
1. Press on the HSIO-2 keypad.
2. Press the down arrow until the display reads:
MIN. LOAD V AL VE A RELA Y IS OFF
3. Press .
ENTER
4. The display may read as follows. (If not, skip to Step 7.)
P ASSWORD PROTECTED FUNCTION ENTER P ASSWORD
5. Press .
ENTER
6. The HSIO-2 again displays the following:
MIN. LOAD V AL VE A RELA Y IS OFF
7. Press to energize the relay. The display reads:
ENTER
MIN. LOAD V AL VE A RELA Y IS ON An audible click will be heard. Verify that the solenoid valve for Circuit A is energized.
8. Press to turn off the minimum load valve relay for
ENTER
Circuit A.
To check the operation of the solenoid valve on Circuit B, follow the same procedure as the preceding, but enter in Step 1, instead of . The display screens will be fo r Circuit B instead of A.
Adjust Setting of Minimum Load Ball Valve
— The mini­mum load ball valve must be adjusted to suit the application. Calibrate one circuit at a time as follows:
1. Adjust the ball valve so that it is approximately half open.
2. Operate the chiller in Manual Control mode, with one circuit
operating, and all compressor loaders deenergized. See Man­ual Control Mode section on page 32 for further information.
3. Record the cooler T (the difference between cooler enter-
ing fluid temperature and cooler leaving fluid temperature) at this fully unloaded condition.
4. Use the Manual Control feature to enable the minimum load
valve for the circuit that is operating.
5. Observe and record the cooler T with the minimum load
valve energized.
6. Adjust the minimum load ball valve until the cooler temper-
ature difference reading from Step 5 is equal to half of the temperature difference reading from Step 3.
7. Open the ball valve to decrease the temperature difference or
close the ball valve to increase the temperature difference (T). When the valve is adjusted correctly, the difference between cooler entering and leaving fluid temperatures when the minimum load control is energized must be at least half of the temperature difference when the minimum load control is deenergized. For example, if the difference between the cooler entering and leaving water temperature is 3° F with the valve deenergized, then the difference between cooler entering and leaving water temperature must be at least 1.5° F with the valve energized.
Once the outputs have been tested and the ball valve ad­justed, the installation is complete. Disable manual control and return chiller to desired operational status.
CAPACITY CONTROL OVERRIDES — The following overrides will modify the normal operation of the routine.
Deadband Multiplier
— The user configurable Deadband Multiplier ( ) has a default value of 1.0. The range is from 1.0 to 4.0. When set to other than 1.0, this factor is ap­plied to the capacity Load/Unload Factor. The larger this value is set, the longer the control will delay between adding or re­moving stages of capacity. Figure 4 shows how compressor starts can be reduced over time if the leaving water temperature is allowed to drift a larger amount above and below the set point. This value should be set in the range of 3.0 to 4.0 for sys­tems with small loop volumes.
First Stage Override
— If the current capacity stage is zero, the control will modify the routine with a 1.2 factor on adding the first stage to reduce cycling. This factor is also applied when the control is attempting to remove the last stage of capacity.
Slow Change Override
— The control prevents the capacity stages from being changed when the leaving fluid temperature is close to the set point (within an adjustable deadband) and moving towards the set point.
Ramp Loading
( ) — Limits the rate of change of leav­ing fluid temperature. If the unit is in a Cooling mode and con­figured for Ramp Loading, the control makes 2 comparisons before deciding to change stages of capacity. The control calcu­lates a temperature difference betw een the control point and leaving fluid temperature. If the difference is greater tha n 4° F (2.2° C) and the rate of change (°F or °C per minute) is more than the configured Cooling Ramp Loading value ( ), the control does not allow any changes to the current stage of capacity.
Low Entering Fluid Temperature Unloading
— When the entering fluid temperature is below the control point, the con­trol will attempt to remove 25% of the current stages being used. If exactly 25% cannot be removed, the control removes an amount greater than 25%, but no more than necessary. The lowest stage will not be removed.
Low Discharge Superheat
— If a circuit’s discharge superheat
is less than 15° F (8.3° C), the control does not increase the cur­rent capacity stage. If the discharge superheat is le ss than 5° F (2.8° C) and decreasing, the circuit is unloaded every 30 sec­onds until the superheat is greater than 5° F (2.8° C). The final capacity stage is not unloaded unless an alarm condition exists. This override is ignored for the first 3 minutes after a compres­sor is started.
Low Saturated Suction Temperature
— To avoid freezing the cooler, the control will compare the cir cuit Saturated Suction temperature with a pre determined freeze point. If the cooler fluid selected is water, the freeze point is 28 F (–2.2 C). If the cooler fluid selected is bri ne, the freeze poi nt is 8° F (4.4 ° C) below the cooling set point (lower of 2 cooling set points for dual configuration). If the saturated suction temperature is below the freeze point, the unit capacity is not allowed to increase.
For brine applications, the freeze point (Brine Freeze Point) can be entered by pressing and scrolling 12 items down. The cont rol will use the B rine Freeze Point va lue less 6° F (3.3° C) as the freeze point to compare with the Saturated Suction temperature. The default for t he Brine Freez e Point is 34 F (1.1 C) which means the control will use 28 F (–2.2 C) as the freeze point. The brine freeze point is adjustable from –15 F to 34 F (–26.1 to 1.1 C).
9
For water [brine] circuits, if t he Sat urat ed Suct ion tempera ­ture falls below 34 F (1.1 C) [th e Brine F reeze Poi nt], the unit capacity will not increase. If the Saturated Suction temperature falls below 28 F (–2.2 C), [the Brine Freeze Point minus 6° F (3.3° C)], for 90 seconds, all loaders in the circuit are turned off. If this condition continues for a total of 3 minutes, the cir­cuit will alarm and shut down.
High Condensing Temperature Unloading
— Every 10 sec­onds the control checks for the conditions below. Loaders will be cycled as needed to control the saturated condensing tem­perature below the configured maximum condensing tempera­ture. Configured maximums are 154 F (67.8 C) for 30GX, 152 F (66.7 C) for 30HXA, and 122 F (50 C) for 30HXC units. If a circuit’s saturated condensing temperature is more than 12° F (6.7° C) below the maximum condensing temperature, the circuit capacity is not allowed to increase. If the saturated condensing temperature is more than 2° F (1.1° C) above the maximum condensing temperature for 60 seconds, a loader is turned off. If the saturated condensing temperature rises to more than 5° F (2.8° C) above the maximum condensing tem­perature during the 60 seconds, a loader is turned off immedi­ately. If all the loaders were already off, the compressor is shut down and an alarm is generated.
MOP (Maximum Operating Pressure) Override
— The con­trol monitors saturated condensing and suction temperature for each circuit as well as differential oil pressure. Based on a con­figurable maximum operating set point (saturated suction tem­perature), set maximum condensing temperature, and mini­mum differential oil pressure, the control may reduce the num­ber of capacity stages being used and/or may lower the EXD position when system pressures approach the set parameters.
Head Pressure Control
GENERAL — The microprocessor controls the condenser fans (30GX) or water val v e (30HX C ) to maintain the saturated condensing temperature to a configurable set point. The 30HXA condenserless units with a 09DK condenser use a combination of factory-supplied fan cycling pressure switches (shipped in the 30HXA control box), temperature switches, and an accessory Motormaster 50DJ902811) or Motormaster III (part no. 30GT910-079) con­trol to control head pressure independent of 30HXA unit con­trol. The fans are staged or speed varied (30GX) or water valve controlled (30HXC) based on each circuit’s saturated condens­ing temperature and compressor status. Water cooled units (30HXC) operating at less than 70 F (21.1 C) for entering con­denser water require the use of head pressure control.
The chiller must be field configured for the options shown
in T able 6. Fan stage settings are shown in Table 7.
®
(part no. 50DJ902801 or
AIR-COOLED UNITS (30GX) — See Fig. 5 for condenser fan locations.
Without Motormaster® Control
— The first stage of fans are turned on based on compressor status or a Head Pressure Set Point based on Saturated Condensing Temperature (SCT). Additional fan stages are added when the SCT exceeds the Head Pressure Set Point. The Head Pressure Se t Point is con­figurable in the Set Point subfunction. The default is 113 F (45 C). Once a fan stage has been added, the software tempo­rarily modifies the head pressure set point by adding 15° F (8.3° C) for 35 seconds. A fan stage will be removed when the Saturated Condensing Temperature has been less than the Head Pressure Set Point minus 35 F (19.4 C) for 2 minutes. The control uses the higher of the 2 Saturated Condensing Temperature values for 30GX080-150 and 160 units. For the 30GX151 and 161-350 units, each circuit’s fan stages are inde­pendently controlled based on the circuit Saturated Condens­ing Temperature. Refer to Table 7 for condenser fan control information. See Fig. 6A.
With Motormaster Control
— For low-ambient operation, the lead fan in each circuit can be equipped with the optional or accessory Motormaster III head pressure controller. If factory installed, the controller will be configured for 4 to 20 mA con­trol. With the Motormaster III option enabled, the PSIO-1 module calculates the required output based on Saturated Con­densing temperature, Head Pressure set point, and a PID (pro­portional integral derivative) loop calculation. This 4 to 20 mA output is driven through the PSIO-2 module. Proportional, Integral, and Derivative gain parameters for air cooled controls are adjustable and can be found in the Service subfunction. Checkout and adjustment of the PID loop should only be performed by certified Carrier Comfort Network technicians. To obtain this accessory for field installation, order by part number 30GX-900---012 for a single controller package (30GX080-150 and 160). Order part number 30GX-900---014 for a dual controller package (30GX151 and 161-350). These packages contain all the hardware required to install the acces­sory . See Fig. 6B.
The control will use the higher of the 2 Saturated Condens­ing Temperature values for 30GX080-150 and 160 units. For the 30GX151 and 161-350 units, each circuit’s fan stages are independently controlled based on the circuit Saturated Con­densing Temperature. Refer to Table 8 for condenser fan stag­ing information.
47
8
7
LWT (C)
6
5
LEGEND
LWT —
Leaving Water Temperature
46 45 44
43
LWT (F)
42 41
0 200 400 600 800 1000
STANDARD DEADBAND
DEADBAND EXAMPLE
TIME (SECONDS)
Fig. 4 — Deadband Multiplier
10
2 STARTS
3 STARTS
MODIFIED DEADBAND
Table 6 — Field Configured Chiller Options
UNIT CONFIGURATION OPTION DESCRIPTION HSIO LOCATION FACTORY CONFIGURED?
Fan Staging Select Air cooled staging method Yes. See Table 7
30GX
30HXC
Motormaster® Control Select Applies to air cooled units only
Water Valve Type Applies to water cooled unit only
Set to 1 to enable (Motormaster only)
Set to 1 = 4 to 20 mA, 2 = 2 to 10 V,
Yes. 0 = None
Yes. 0 = None
3 = 20 to 4 mA, 4 = 10 to 2 V
Table 7 — Fan Staging Settings for Air Cooled (30GX) Units
UNIT 30GX DESCRIPTION OPTION NUMBER HSIO DISPLAY
080-105 106-125
136, 150, 160
151, 161, 175,
205, 225
176
206, 226, 250
251-350
LEGEND
SCT —
Saturated Condensing Temperature
1st stage compressor status and SCT set point 2nd stage common control based on highest SCT
1st stage compressor status and SCT set point 2nd and 3rd stage common control based on highest SCT
1st stage compressor status and SCT set point 2nd through 4th stage common control based on highest SCT
1st stage each circuit, compressor status 2nd stage Circuit B independent 2nd and 3rd stage Circuit A independent
1st stage each circuit, compressor status 2nd and 3rd stage each circuit independent
1st stage each circuit, compressor status 2nd stage Circuit B independent 2nd, 3rd and 4th stage Circuit A independent
1st stage each circuit, compressor status 2nd, 3rd and 4th stage each circuit independent
12 Com_1cmp 14 Com_2cmp 16 Com_3cmp
7 A2B1_stg
3 Ind_2stg
9 A3B2_cmp
5 Ind_3stg
WATER-COOLED UNITS (30HXC) — The 30HXC chillers can be configured to control direct or reverse-acting water valves that are controlled by a 4 to 20 mA signal. A 2 to10 vdc signal can be used by installing a 500-ohm
1
/2 watt resistor across the 2 output terminals of the 4 to 20 mA signal. The 4 to 20 mA control scheme reads the saturated condensing temper­ature and uses a PID (proportional integral deriative) loop to control the head pressure. Proportional, Integral and Derivative gain parameters for the water cooled controls are adjustable and can be found in the Service subfunction. Checkout and adjustment of the PID loop should only be performed by certi­fied Carrier Comfort Network technicians.
CONDENSERLESS UNITS (30HXA) — The remote con­denser fans are controlled by 2 relays with the 30HXA control box. See Field Wiring section on page 73 for wiring details. The 30HXA control must be configured to turn the 09DK fans on and/or off. To set the 30HXA control for this configuration Unit T ype under must be changed to 3 (Split System). Next, under , Head Pressure Control Type must be changed to 1 (Air Cooled), and Condenser Pump control must be set to 0 (Not Controlled).
The 30HXA control does not support a 4 to 20 mA or a 2 to 10 vdc output for fan speed control. Instead, head pressure con­trol is accomplished with fan cycling pressure switches (09DK054-094), temperature switches (09DK044, 074-094) and Motormaster control. Motormaster and Motormaster III control is used with temperature sensor input to control con­denser fan speed. See accessory installation instructions for further information.
09DK CONDENSING UNITS 09DK044 Units
— The 09DK044 units have accessory provi­sion for fully automatic intermediate-season head pressure control through condenser fan cycling. Fan number 2 and 3 cycling is controlled by outdoor-air temperature through air temperature switches (ATS) 1 and 2.
The air temperature switches are located in the low er divid­er panel underneath the coil header. The sensing element is ex­posed to air entering the no. 1 fan compartment through a hole in the panel. Fan no. 1 is non-cycling.
The air temperature switch controls the fans as shown in Table 9.
09DK054-094
— The capacity of an air-cooled condenser in­creases with increased temperature difference (defined as satu­rated condenser temperature minus entering outdoor-air tem­perature) and decreases with decreased temperature difference. A drop in entering outdoor-air temperature results in a lower saturated condensing temperature. When outdoor-air tempera­ture drops below the minimum temperature for standard units, additional head pressure control is required.
Model 09DK units have fully automatic intermediate­season head pressure control through condenser fan cycling using electromechanical fan cycling controls. Standard head pressure controls regulate the 100 and 50/50% condenser capacity applications. Head pressure can also be controlled by fan cycling controls supplemented by the accessory Motormaster III solid-state head pressure control. See Motor­master
III installation instructions for more information.
In the standard control scheme, fans 1 and 2 are on when there is a call for cooling from the respective coil circuits. Fans 1 and 2 are non-cycling. On 054 and 064 units, fans 3 and 4 are controlled by using a fan cycling pressure switch on each of the primary coil circuits in response to condensing pressure. On 074-094 units, fans 3 and 4 are controlled using a fan cycling pressure switch in each of the primary coil circuits in response to condensing pressure. Fans 5 and 6 are controlled by using two air temperature switches, which respond to the outdoor ambient temperature. The air temperature swit ches are locat ed on the control box shelf.
11
Table 8 — 30GX080-350 Condenser Fan Staging (PSIO-1 Controlled)
30GX UNIT SIZE FAN TYPE FAN CONTACTOR FANS CONTROLLED FAN RELAY NO.*
080-105
106-125
136, 150, 160
151, 161, 175, 205, 225
176
206, 226, 250
251, 265
281-350
LEGEND
Comp. — FC
*Fan Relay number displayed when using
Compressor Fan Contactor
Standard
High Static
Standard
High Static
Standard
High Static
Standard
High Static
Standard
High Static
Standard
High Static
Standard
High Static
Standard
High Static
to test fans.
FC-1 1, 2 5
FC-2 3, 4 1 FC-1, 1A 1, 2 5 FC-2, 2A 3, 4 1
FC-1 1, 2 5
FC-2 3, 4 1
FC-3 5, 6 2 FC-1, 1A 1, 2 5 FC-2, 2A 3, 4 1 FC-3, 3A 5, 6 2
FC-1 1, 2 5
FC-2 3, 4 1
FC-3 5, 6 2
FC-4 7, 8 2 FC-1, 1A 1, 2 5 FC-2, 2A 3, 4 1 FC-3, 3A 5, 6 2 FC-4, 4A 7, 8 2
FC-1 1, 2 Comp. B1 contactor†
FC-2 3, 4 3
FC-3 5, 6 2
FC-4 7, 8 Comp. A1/A2 contactor†
FC-5 9, 10 1 FC-1, 1A 1, 2 Comp. B1 contactor† FC-2, 2A 3, 4 3 FC-3, 3A 5, 6 2 FC-4, 4A 7, 8 Comp. A1/A2 contactor† FC-5, 5A 9, 10 1
FC-1 1, 2 Comp. B1 contactor†
FC-2 3, 4 3
FC-3 5, 6 4
FC-4 7, 8 Comp. A1 contactor†
FC-5 9, 10 1
FC-6 11, 12 2 FC-1, 1A 1, 2 Comp. B1 contactor† FC-2, 2A 3, 4 3 FC-3, 3A 5, 6 4 FC-4, 4A 7, 8 Comp. A1 contactor† FC-5, 5A 9, 10 1 FC-6, 6A 11, 12 2
FC-1 1, 2 Comp. B1 contactor†
FC-2 3, 4 3
FC-3 5, 6 1
FC-4 7, 8 Comp. A1/A2 contactor†
FC-5 9, 10 2
FC-6 11, 12 2 FC-1, 1A 1, 2 Comp. B1 contactor† FC-2, 2A 3, 4 3 FC-3, 3A 5, 6 1 FC-4, 4A 7, 8 Comp. A1/A2 contactor† FC-5, 5A 9, 10 2 FC-6, 6A 11, 12 2
FC-1 2, 4 1
FC-2 6, 8 2
FC-3 1 Comp. B1 contactor†
FC-4 3 3
FC-5 5, 7 4
FC-6 9, 10 Comp. A1/A2 contactor†
FC-7 11, 12 2
FC-8 13, 14 2 FC-1, 1A 2, 4 1 FC-2, 2A 6, 8 2
FC-3 1 Comp. B1 contactor†
FC-4 3 3 FC-5, 5A 5, 7 4 FC-6, 6A 9, 10 Comp. A1/A2 contactor† FC-7, 7A 11, 12 2 FC-8, 8A 13, 14 2
FC-1 1, 2 Comp. B1/B2 contactor†
FC-2 3, 4 3
FC-3 5, 6 4
FC-4 7, 8 4
FC-5 9, 10 1
FC-6 11, 12 Comp. A1/A2 contactor†
FC-7 13, 14 2
FC-8 15, 16 2 FC-1, 1A 1, 2 Comp. B1/B2 contactor† FC-2, 2A 3, 4 3 FC-3, 3A 5, 6 4 FC-4, 4A 7, 8 4 FC-5, 5A 9, 10 1 FC-6, 6A 11, 12 Comp. A1/A2 contactor† FC-7, 7A 13, 14 2 FC-8, 8A 15, 16 2
†Proper rotation of these fans to be checked when compressor(s) is running. See Fig. 5 for
condenser fan locations when viewing from the control box end.
NOTE: For 30GX151, 161-350 units, fan relays 1 and 2 energize Circuit A fans. Fan relays 3 and 4 energize Circuit B fans.
12
Table 9 — Air Temperature Switch Control
(09DK044 Units)
FAN FAN SWITCH TEMPERATURE
ON
FAN 2
OFF
ON
FAN 3
OFF
Above 65 ± 3 F (18.3 ± 1.7 C) Between 55 and 65 F (12.8 and 18.3 C)
and temperature falling Below 55 ± 3 F (12.8 ± 1.7 C) Between 55 and 65 F (12.8 and 18.3 C)
and temperature rising Above 80 ± 3 F (26.7 ± 1.7 C) Between 70 and 80 F (21.1 and 26.7 C)
and temperature falling Below 70 ± 3 F (21.1 ± 1.7 C) Between 70 and 80 F (21.1 and 26.7 C)
and temperature rising
The fan cycling pressure switch controls the fans as follows:
Fans 3 and 4 are on above 185 ± 10 psig (1276 ± 69 kPa) and off below 97 ± 10 psig (669 ± 69 kPa). If pressure is rising be­tween 97 psig (669 kPa) and 185 psig (1276 kPa), fans 3 and 4 are off. If pressure is falling from 185 psig (1276 kPa) to 97 psig (669 kPa) fans 3 and 4 are on.
30GX080-105 30GX106-125 30GX136,150,160
4
2
CONTROL BOX END
2
4
The 09DK054-094 condensers are supplied with fan cy­cling pressure switches suitable for use with R-22 refrigerant. Fan cycling pressure switches that are compatible with R-134a refrigerant pressures are shipped with the 30HXA chillers. These fan cycling pressure switches must be installed in place of the 09DK factory-installed switches before charging to en­sure proper head pressure control.
The air temperature switch controls th e fans as foll ows: On the 074-094 condensers, below 70
±
3 F (21.1 ± 1.7 C) outdoor ambient, fans 5 and 6 are off; above 80 ± 3 F (26.7 ± 1.7 C) fans 5 and 6 are on. Between 70 F (21.1 C) and 80 F (26.7 C), whether fans 5 and 6 are on or off depends on whether temper­ature is rising or falling. If the temperature is rising from 70 F (21.1 C) to 80 F (26.7 C), fans 5 and 6 are off. If the tempera­ture is falling from 80 F (26.7 C) to 70 F (21.1 C), fans 5 and 6 are on.
6
CONTROL BOX END
24 6 8
CONTROL BOX END
1
10
9
CONTROL BOX END
3
1
3
5
13 5 7
30GX151,161,175,205,225 30GX176
8
7
6
5
4
3
2
CONTROL BOX END
1
12
7911
30GX206,226,250 30GX251,265
10
3
1
2
4
5
7
8
6
11
9
12
10
12
14
13
9
11
30GX281-350
10
16
12
14
8
6
4
2
6810
4
2
CONTROL BOX END
3
5
8
6
5
7
1
4
2
CONTROL BOX END
1
3
15
13
9
11
5
7
1
3
Fig. 5 — 30GX Condenser Fan Locations
13
CONTROL BOX END
30GX UNITS — MOTORMASTER III CONTROL NOT INSTALLED
LEGEND
Saturated Condensing Temper ature
SCT —
Fig. 6A — 30GX Head Pressure Control Without Motormaster
30GX UNITS — MOTORMASTER III CONTROL INSTALLED
READ CIRCUIT SATURATED CONDENSING TEMPERATURE AND CURRENT FAN STAGE
IS SCT GREATER THAN HEAD PRESSURE SET POINT PLUS 15°F (8.3°C)?
YES
INCREASE CURRENT FAN STAGE BY ONE
NO
Fig. 6B — 30GX Head Pressure Control Without Motormaster III Control
ADJUSTING PID ROUTINES — The 30GX and 30HXC head pressure control routines use PID (proportional integral derivative) loops to maintain a user-configurable head pressure set point. Gain defaul t values are located in the Service func­tion. See page 32. The current values can be read under
from the HSIO. The control calculates a new fan speed (30GX) or water valve position (30HXC) every 5 sec­onds based on these gain values and an error term equal to sat­urated condensing temperature minus head pressure set point. If the control routine is not responding fast enough to large changes (circuit starting, for example), increase the propor­tional term.
When the routine is making too great a change to valve po­sition or fan speed, decrease the proportional term. To mini­mize hunting, keep the integral term positive and as low as pos­sible. This value is used to control “droop,” which is common in master/submaster control schemes. The default for the deriv­ative term is zero. The value should not need to be changed.
Cooler and Condenser (30HXC) Pump Con­trol —
cooler and condenser (30HXC) pump control. Inputs for a
The 30GX and 30HX chillers can be configured for
®
III Control
CALCULATE NEW PID VALUE. DOES OUTPUT REQUIRE MORE FANS?
YES
INCREASE CURRENT FAN STAGE BY ONE
OUTPUT NEW mA SIGNAL TO CONTROLLER
NO
DOES PID OUTPUT REQUIRE LESS FANS?
YES
DECREASE CURRENT FAN STAGE BY ONE
NO
cooler flow switch or interlock and condenser flow switch are also provided.
COOLER PUMP CONTROL — Proper configuration of the cooler pump control and cooler pump interlock is required to prevent possible cooler freeze-up. The cooler pump interlock should always be enabled. This prevents the chiller from oper­ating unless chilled water flow is detected. See page 73 of the Field Wiring section for proper connection of the chilled water flow switch and cooler pump interlock.
The factory default setting for cooler pump control is “0” (not controlled). It is recommended for 30GX packaged air­cooled chillers that the cooler pump control be utilized unless the chilled water pump runs continuously or the chilled water system contains a suitable anti-freeze solution. The cooler pump relay is energized when the chiller enters an occupied mode. In the event a freeze protection alarm is generated t he cooler pump relay is also energized. If the cooler heater is being used and has been on for more than 15 minutes during saturated suction freeze protection, the cooler pump relay is energized.
When the cooler pump control is set to “0” and the cooler pump interlock is set to “1” an alarm 53 will be generated if flow is not proven within one minute after the unit is enabled and in an occupied mode.
14
When the cooler pump control is set to “1” and the cooler
CLEAR
ENTER
1
2
3
4
5
6
7
8
9
0
.
-
STAT
SET
SCHD
EXPN EDIT
SRVC
HIST
ALGO
TEST ALRM
TWENTY-FOUR CHARACTER TWO-LINE LCD DISPLAY
LEGEND
LCD —
Liquid Crystal Display
Fig. 7 — Keypad and Display Module
pump interlock is set to “1” an alarm 53 will be generated if flow is not proven within one minute after the cooler pump re­lay is energized. An alarm 55 will be generated if the interlock contacts remain closed when the cooler pump relay is off. In ei­ther cooler pump control configuration, alarm 54 will be gener­ated whenever the cooler pump interlock is open for at least 5 seconds during operation.
CONDENSER PUMP CONTROL ( ) — Factory de­faults for both condenser pump control and condenser flow switch are set to “Not Controlled” and “Disabled,” respec­tively. The condenser pump can be controlled in one of two ways: In the first method, the pump can be controlled like the cooler pump — it is turned on whenever the machine is in the on state and turned off otherwise (set to “1” using the Service function). The second method of control is to turn the pump on when the fir st compresso r is started and off when the last com­pressor is turned off (set to “2” using the Service function). With the flow switched enabled, the control checks the status of the input one minute after starting the pump. An alarm 49 is generated if the flow switch input is not closed.
Cooler Heater Control —
Accessory cooler heaters can be ordered for the 30GX chillers. If installed and e nabled, these heaters are turned on only when the machine is in the off state and the chiller is in a saturated suction temperature freeze condition.
Oil Heater Control —
Standard feature that controls oil temperature based on Saturated Condensing Temperature (SCT). Heaters turn on at <105 F (40.6 C) SCT, and turn off at >110 F (43.3 C) SCT.
Keypad and Display Module (Also Called HSIO-II) —
cate with the processor. It is used to enter configurations and set points and to read data, perform tests, and set schedules. The device consists of a keypad with 7 function keys, 5 opera­tive keys, 12 numeric keys (0 to 9, •, and -), and a 2-line, 24-character alphanumeric liquid crystal display . See Fig. 7.
ACCESSING FUNCTIONS AND SUBFUNCTIONS — Table 10 shows a brief description of the keypad buttons. Table 11A shows the 6 functions (identified by name) and the subfunctions (identified by number). Table 11B shows the 6 functions (identified by name) and the subfunctions (identi­fied by number) when using the optional remote enhanced dis­play controller. Table 12 shows a brief example on how to access subfunctions.
NOTE: It is not necessary to use the through every item in a subfunction. For example, if you wanted to read the oil pressure for the A1 compressor, press , then
procedure to view an item near the bottom of a subfunction. To view Condenser Pump Flow Switch status, press ,
, and . This procedure is available in all functions
except the TEST function. AUTOMATIC DEF AULT DISPLAY — When the keypad has
not been used for 10 minutes, the display automatically switches to the rota tin g a uto ma ti c defa u lt d isp la y. This display contains the 5 parts shown below .
Entering Fluid T emp
Leaving Fluid T emp
Percent Total Capacity
This module allows the operator to communi-
press to go directly to A1 Oil Pre ssure. Use a similar
xx.x° F xx.x° F
xxx.x%
Table 10 — Keypad and Display Module Usage
FUNCTION
KEYS
OPERATIVE
KEYS
CLEAR
ENTER
STATUS — For displaying diagnostic codes and current operating information about the machine.
HISTORY — For displaying run time, cycles, and previous alarms.
SERVICE — For entering specific unit configur ation information and enabling manual control function.
SCHEDULE — For entering occupied/unoccupied schedules for unit operation.
ALGORITHM — Not used. SET POINT — For entering operating set points
and daytime information. TEST — For testing operating of the analog and
discrete outputs.
EXPAND — For displaying a non-abbreviated expansion of the display.
CLEAR — For clearing the screen of all displays. UP ARROW — For returning to previous display
position. DOWN ARROW — For advancing to next display
position. ENTER — For entering data.
USE
USE
T ota l Num ber of A larm s
xx
MODES : MODE_TBL Current active modes
All functions are made up of a group of subfunctions. To en­ter a subfunction, first press the subfunction number desired. Then press the function key in which the subfunction resides. To move within that subfunction, press the up or down arrow keys. Another subfunction may be entered at any time by pressing the subfunction number, then the function key. De­pending on system type and configuration, all displays may not be shown.
15
SUBFUNCTION NO.
Table 11A — HSIO Functions and Subfunctions
FUNCTIONS
Status Test Schedule Service History Set Point
1
2
3
4
5
6
7
8
9
10
11
Alarm Display Circuit A
General Pa r ameters Circuit B
Circuit A Analog Values
Circuit A Discrete Inputs/ Outputs Table
Circuit B Analog Values
Circuit B Discrete Inputs/ Outputs Table Unit Analog Parameters Miscellaneous Inputs/Outputs Operating Modes Holiday 06
Capacity Control Holiday 07
Dual Chiller Holiday 08
®
Ice Build Occupancy Schedule
Local/Normal Occupancy Schedule Remote CCN Occupancy Schedule
Holiday 01 Configuration
Configuration
Configuration
Configuration
Configuration
Configuration
Configuration
Configuration*
Discrete Outputs
Discrete Outputs
Unit Discrete Outputs
Valves and Motormaster Control
—Holiday 02
—Holiday 03
—Holiday 04
—Holiday 05
Factory Configuration
Options Configuration1
Options Configuration 2
Reset/Demand Limit Configuration
Machine Configuration Codes
———
Transducer Calibration
Manual Control
Master /Slave Configuration
———
———
Operating Hours Set Point s
Alarm History English/Metric
Bus Address
Time/Date
Configuration
CCN
Enable/Disable
——
——
*Subfunctions through are for configuring Holidays 09 through 30.
16
Table 11B — Functions and Subfunctions Cross-Reference for the
Optional Remote Enhanced Display Controller
The optional Remote Enhanced Display controller cross reference table below can be used as a guide to access the same information outlined in the HSIO functions and subfunctions table (see Table 11A). For example, in Table 11A, the alarm history is accessed through the HSIO by pressing 2 and the History button on the keypad (see Table 10). The Remote En­hanced Display cross reference table lists the menu item from
the Remote Enhanced Display which contains the alarm histo­ry information. In another example, from Table 11A, pressing 3 and the Status button on the HSIO keypad will access the cir­cuit A analog values. In the table below, the circuit A analog values are accessed by selecting STATUS CIRCA_AN from the appropriate Remote Enhanced Display menu.
HSIO SUBFUNCTION
NO.
1
2
3
4
5
6
7
8
9
10
11
HSIO FUNCTION KEY
Status Test Schedule Service History Set Point
STATUS A_UNIT_1
STATUS A_UNIT_1
STATUS CIRCA_AN
STATUS CIRA_DIO
STATUS CIRCB_AN
STATUS CIRB_DIO
STATUS UNIT_2
STATUS UNIT_3
STATUS MODE_TBL
SERVICE CONTROL ALGORITHM STATUS LOADFACT
SERVICE CONTROL ALGORITHM STATUS LEADLAG
SERVICE CONTROL TEST
SERVI C E CONTROL TEST
SERVI C E CONTROL TEST
SERVI C E CONTROL TEST
SCHEDULE OCCPC01S
SCHEDULE OCCPC02S
SCHEDULE OCCPC65S
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_01
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_02
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_03
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_04
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_05
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_06
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_07
SERVICE EQUIPMENT CONFIGURATION HOLIDAY,HOLDY_08*
SERVICE EQUIPMENT CONFIGURATION
SERVICE EQUIPMENT CONFIGURATION OPTIONS1
SERVICE EQUIPMENT CONFIGURATION OPTIONS2
SERVICE EQUIPMENT CONFIGURATION RESETCON
SERVICE EQUIPMENT CONFIGURATION CONCODES
SERVICE EQUIPMENT CONFIGURATION EXV TESTS
SERVICE EQUIPMENT SERVICE CALIBRTE
SERVICE EQUIPMENT SERVICE MAN_CTRL
SERVICE EQUIPMENT CONFIGURATION MSTR_SL V
———
———
SERVIC E EQUIPMENT CONFIGURATION STRTHOUR
SERVIC E ALARM HISTORY
——
——
——
——
SETPOINT
SERVICE LID CONFIGURATION
SERVICE CONTROLLER IDENTIFICATION
SERVICE EQUIPMENT SERVICE TIME AND DATE
STATUS A_UNIT_1
*Subfunctions through are for configuring Holidays 09 through 30
NOTE: The optional Remote Enhanced Display controller uses the same password (1111) as the HSIO.
, and are also found under Service, Equipment Configuration.
17
Table 12 — Accessing Functions and Subfunctions
OPERATION KEYPAD ENTRY DISPLAY RESPONSE
To access a function, press subfunction no. and function name key. Display shows sub­function group.
To move to other elements, scroll up or down using arrow keys.
When the last element in a subfunction has been displayed, the first element is repeated.
To move to next subfunction it is not necessary to use subfunction number. Press function name key to advance display through all subfunctions within a function and then back to the first.
Circuit A Discrete Outputs Loader A1
Relay is OFF Loader A2
Relay is OFF Minimum Load Valve A
Relay is OFF Circuit A Oil Heater
Relay is OFF A1 Mtr. Cooling Solenoid
Relay is OFF A2 Mtr. Cooling Solenoid
Relay is OFF Circuit A Oil Pump
Relay is OFF Oil Solenoid A1
Relay is OFF Oil Solenoid A2
Relay is OFF Loader A1
Relay is OFF Circuit B Discrete Outputs Unit Discrete Outputs Valves and Motor Master Circuit A Discrete Outputs
To move to another function, either depress function name key for desired function (display shows the first subfunction), or Access a specific sub­function by using the sub­function number and the function name key.
Alarms : xx Reset Alarms : 1 <ENTER>
CIR. A DISCRETE OUTPUTS
18
ST ATUS FUNCTION — This function shows the rotating dis­play, current status of alarm and alert (diagnostic) codes, capacity stages, operating modes, chilled water set point, all measured system temperatures and pressures, analog inputs, and switch inputs. Refer to Table 13 for a complete description of the function.
Alarms/Alerts
— Alarms and alerts are mess ages that one or more faults have been detected. The alarms and alerts indicat e failures that cause the unit to shut down, terminate an option (such as reset) or result in the use of a default value such as a set point. Refer to the Troubleshooting section for more information.
Up to 10 alarms/alerts can be stored at once. To view them, press . The control will display the current total num­ber of alarms/alerts. Use the arrow keys to scroll through the list. Press the key when needed to view the full description of an alarm or alert. Press to clear all the alarms. Se e
ENTER
T able 14.
IMPORTANT: Do not clear the alarms without first
reviewing the full list and investigating and correcting
the cause of t he a lar ms .
When an alarm or alert is s tored in the display and the ma­chine automatically resets, the al arm/alert is deleted. Codes for safeties which do not automatically reset are not deleted until the problem is corrected and the machine is reset. To clear manual reset alarms from the CPM modules, the reset button on the HSIO bracket must be pressed. Next, switch the LOR switch to OFF and back to Local or Remote position (default alarm clearing method). Press and then to
ENTER
clear the alarm from the PSIO if the default LOR reset function has been disabled.
General Parameters
— General operating parameters are dis­played including control mode, run status, CCN status, and the 5 most current alarms. Press to display these and the other values as shown in T able 13.
Circuit A and B Analog and Discrete Information
— Cir­cuit A Analog Values can be vie wed by pre ssing and scrolling down to see current system operating conditions such as pressures and temperatures. Pressing will bring up Circuit A Discrete Inputs and Outputs. Scroll down to view the On/Off status of the compressor(s), loaders, solenoids, and pumps. Oil switch and feedback inputs are also displayed. Press and to view the identical ana log val­ues and discrete inputs and outputs for Circuit B. See Table 13 for a complete display.
Unit Analog Parameters and Temperature Reset
— Press
and scroll down to display the unit entering and leav­ing fluid temperatures as well as the temperature reset signal and calculated values.
Miscellaneous Inputs and Outputs
— Pressing and scrolling down will reveal the On/Off status of the condenser fans (30GX only). Also found here are the Demand Limit set­tings, pump relay and switch status, and miscellaneous items such as Heat/Cool and Dual Set Point switch positions. See Ta­ble 13 for a complete list.
— The operating modes are displayed to indicate the
Modes operating status of the unit at a given time. See Table 15 for a complete list of all mode s.
To enter the MODES subfunction, press and use the key to view all current modes of operation. See Table 16.
Capacity Control
— Pressing , this subfunction displays the load/unload factor, control point, and leaving wa­ter temperature. Scrolling down will also reveal the liquid level sensor values in degrees format.
Dual Chiller
— Pressing will access the dual chiller control status. This subfunction will display whether or not the chiller is operating as a Master or Slave, any alarm con­ditions present for dual chiller control, and lead/lag information for changeover. Dual chiller control is configured under
.
19
Table 13 — Status Function and Subfunction Directory
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 Alarms
Alarms : xx Reset Alarms : 1 <ENTER>
All current alarms are displayed
Use as needed
2 General Parameters
3 Circuit A Analog Values
See Legend on page 25.
GENERAL PARAMETERS Control Mode Run Status
Off/On Occupied ?
Yes/ No CCN Enable
Off/On CCN Chiller Start/Stop
Start/Stop Alarm State
Normal/Alarm Current Alarm 1
x.xx Current Alarm 2
x.xx Current Alarm 3
x.xx Current Alarm 4
x.xx Current Alarm 5
x.xx Active Demand Limit
xxx.x% Percent Total Capacity
xxx.x% Water/Brine Setpoint
xx.x dF Control Point
xx.x dF Entering Fluid Temperature
xx.x dF Leaving Fluid Temperature
xx.x dF Emergency Stop
Emstop Minutes Left for Start
xx min Heat-Cool Status
Heat/Cool CIRCUIT A ANALOG VALUES Total Capacity
xxx.x% Available Capacity
xxx.x% Discharge Pressure
xxx.x PSI Suction Pressure
xxx.x PSI A1 Oil Pressure Diff.
xxx.x PSI A2 Oil Pressure Diff.
xxx.x PSI A1 Oil Pressure
xxx.x PSI A2 Oil Pressure
xxx.x PSI Discharge Gas Temperature
xxx.x dF A1 Motor Temperature
xxx.x dF A2 Motor Temperature
xxx.x dF
Displays LOCAL ON/OFF or CCN ON/OFF
Force/clear value with HSIO or CCN device. Must be ON for CCN clock control.
Percentage of total circuit capacity currently in use.
Percentage of Total Capacity value not in an alarm or fault condition.
20
Table 13 — Status Function and Subfunction Directory (cont)
3 Circuit A Analog Values (cont) SAT Condensing Temp
4 Circuit A Discrete Inputs/Outputs
5 Circuit B Analog Values
SUBFUNCTION KEYPAD ENTR Y DISPLAY COMMENT
xxx.x dF Saturated Suction Temp
xxx.x dF EXV Percent Open
xxx.x% Motormaster Speed
xxx.x% Water Valve Position
xxx.x% Cooler Level Indicator
x.xx CPM A1 Feedback
x.x Volts CPM A2 Feedback
x.x Volts Circuit A Econ Pressure
xxx.x PSI CIR. A DISCRETE OUTPUTS Compressor A1
Off/On Compressor A2
Off/On Loader A1
Off/On Loader A2
Off/On Minimum Load Valve A
Off/On Circuit A Oil Heater
Off/On A1 Mtr Cooling Solenoid
Off/On A2 Mtr Cooling Solenoid
Off/On Circuit A Oil Pump
Off/On Oil Solenoid A1
Off/On Oil Solenoid A2
Off/On CIR. A DISCRETE INPUTS
Circuit A Oil Switch Open/Close
Compressor A1 Feedback Off/On
Compressor A2 Feedback Off/On
CIRCUIT A ANALOG VALUES Total Capacity
xxx.x% Available Capacity
xxx.x% Discharge Pressure
xxx.x PSI Suction Pressure
xxx.x PSI B1 Oil Pressure Diff.
xxx.x PSI B2 Oil Pressure Diff.
xxx.x PSI B1 Oil Pressure
xxx.x PSI B2 Oil Pressure
xxx.x PSI Discharge Gas Temperature
xxx.x dF
See Table 5. See Table 5.
Percentage of total circuit capacity currently in use.
Percentage of To tal Capacity value not in an alarm or fa ult condition.
21
5 Circuit B Analog Values (cont)
SUBFUNCTION KEYPAD ENTR Y DISPLAY COMMENT
6 Circuit B Discrete Inputs/Outputs
7 Unit Analog Parameters
Table 13 — Status Function and Subfunction Directory (cont)
B1 Motor Temperature xxx.x dF
B2 Motor Temperature xxx.x dF
SAT Condensing Temp xxx.x dF
Saturated Suction Temp xxx.x dF
EXV Percent Open xxx.x%
Motormaster Speed xxx.x%
Water Valve Position xxx.x%
Cooler Level Indicator x.xx
CPM B1 Feedback x.x Volts
CPM B2 Feedback x.x Volts
Circuit B Econ Pressure xxx.x PSI
CIR. B DISCRETE OUTPUTS Compressor B1
Off/On Compressor B2
Off/On Loader B1
Off/On Loader B2
Off/On Minimum Load Valve B
Off/On Circuit B Oil Heater
Off/On B1 Mtr Cooling Solenoid
Off/On B2 Mtr Cooling Solenoid
Off/On Circuit B Oil Pump
Off/On Oil Solenoid B1
Off/On Oil Solenoid B2
Off/On CIR. B DISCRETE INPUTS
Circuit B Oil Switch Open/Close
Compressor B1 Feedback Off/On
Compressor B2 Feedback Off/On
UNITS ANALOG PARAMETERS Cooling Entering Fluid
xx.x dF Cooling Leaving Fluid
xx.x dF Condenser Entering Fluid
xx.x dF Condenser Leaving Fluid
xx.x dF Reclaim Entering Fluid
xx.x dF Reclaim Leaving Fluid
xx.x dF 5 Volt Supply
x.x Volts
See Table 5. See Table 5.
See Legend on page 25.
22
7 Unit Analog Parameters (cont)
SUBFUNCTION KEYPAD ENTR Y DISPLAY COMMENT
8 Misc. Inputs/Outputs
9 Operating Modes
Table 13 — Status Function and Subfunction Directory (cont)
TEMPERATURE RESET 4-20 mA Reset Signal
xx.x mA Return Reset Signal
xx.x dF External Reset Signa l
xx.x dF Outdoor Air Temp
xx.x dF Calculated Reset
xx.x dF MISC INPUTS/OUTPUTS
FAN_1 Off/On
FAN_2 Off/On
FAN_3 Off/On
FAN_4 Off/On
FAN_5 Off/On
FAN_6 Off/On
DEMAND LIMIT 4-20 mA Demand Signal
x.xx mA Demand Switch 1
Off/On Demand Switch 2
Off/On CCN Loadshed Signal
Normal/Alarm Max Allowable CAP
xxx.x% PUMPS
Cooler Pump Relay Off/On
Cooler Pump Flow Switch Off/On
Condenser Pump Relay Off/On
Condenser Pump Flow Switch Off/On
MISCELLANEOUS Ice Valve
Off/On Ice Build Complete
Yes/N o Heat/Cool Switch
Heat/Cool Dual Set point Switch
Off/On Cooler Heater
Off/On Options Temperature 1
xx.x dF Options Temperature 2
xx.x dF MODES :MODE_TBL
mode name ON/OFF LOCAL OFF
CCN OFF
Not Used Not Used
Only active modes displayed Scroll with down arrow key to display
23
9 Operating Modes (cont)
SUBFUNCTION KEYPAD ENTR Y DISPLAY COMMENT
Table 13 — Status Function and Subfunction Directory (cont)
CLOCK OFF LOCAL ON CCN ON CLOCK ON DUAL SP ACTIVE (1st SP) DUAL SP ACTIVE (2nd SP) TEMPERATURE RESET
ACTIVE DEMAND LIMIT ACTIVE
LOAD LIMIT ACTIVE LOW SOURCE TEMP PROTECT RAMP LOADING ACTIVE TIMED OVERRIDE ACTIVE LOW COOLER SUCTION TEMP WSM CONTROLLING SLOW CHANGE OVERRIDE OFF TO ON DELA Y ACTIVE FSM CONTROLLING 2 CHILLR LEAD LAG ACTIVE 2 CHILLR LL COMM FAILURE CIR A LOW DISCHG SUPERHT CIR B LOW DISCHG SUPERHT CIR A HIGH SDT CIR B HIGH SDT
10 Capacity Control
See Legend on page 25.
CAPACITY CONTROL Load/Unload Factor
xxx.x% Control Point
xx.x dF Leaving Water Temp
xx.x dF MISC. INDICATORS
Liquid Lvl Sensor Cir. A xx.x dF
Liquid Lvl Sensor Cir. B xx.x dF
24
11 Dual Chiller
Table 13 — Status Function and Subfunction Directory (cont)
SUBFUNCTION KEYPAD ENTR Y DISPLAY COMMENT
DUAL CHILLER Unit Master/Slave
0 / 1 / 2 Master / Slave Ctrl Active
Yes / N o Lead Chiller
1 / 2
0 = Neither 1 = Master 2 = Slave
1 = Master 2 = Slave
0 = Chiller OFF 1 = Valid Run State in CCN Mode 3 = Chiller in Local Mode 5 = Shutdown on Alarm 6 = Communications Failure
Yes if Lead / Lag Balance Enabled 1 = Master / S lave Have Same Address
2 = Master / Slave Communication Failure 3 = Chiller in Local Mode 4 = Slave Shutdown on Alarm(s) 5 = Master Configured for Heating 6 = No Slave Configured
CCN — Carrier Comfort Network CPM — Compressor Protection Module dF — Degrees Fahrenheit EXV — Electronic Expansion Valve FSM — Flotronic™ System Manager LL — Lead/Lag MTA — Must Trip Amps SAT — Saturated SDT — Saturated Discharge Temperature SP —Set Point WSM — Water System Manager
LEGEND
Slave Chiller State 0 / 1 / 3 / 5 / 6
Slave Chiller Total Cap xxx.x%
Lead / Lag Changeover Master / Slave Error
1 / 2 / 3 / 4 / 5 / 6
Table 14 — Reading and Clearing Alarms
KEYPAD ENTRY DISPLAY COMMENT
ENTER
Alarm: 02 Reset Alarms: 1 <ENTER>
Comp A1 F ail - 1.80 Curr Alarm: 15:12 04/15/96
Comp A1 Fail - 1. 80 Cur rent Phase Reversal Alarm: 15:12 04/15/96
Compressor A1 Low Oil Pr Alarm: 10:34 04/15/96
Compressor A1 Low Oil Pressure Alarm: 10:34 04/15/96
Alarm: 02 Reset Alarms: 1 <ENTER>
Alarm: 00 Reset Alarms: 1 <ENTER>
Entering Fluid Temp xx.x dF
Leaving Fluid Temp xx.x dF
Percent Total Capacity xxx.x%
Total Number of Alarms xx
MODES: MODE_TBL List of All Curren t Modes
Press CPM Reset button first
Alarms reset and cleared
Returns to rotating default display
25
Table 15 — Operational and Mode Display Codes
CODE DESCRIPTION
LOCAL OFF Unit is off. LOCAL/OFF/REMOTE switch is in OFF
CCN OFF Unit is off. LOCAL/OFF/REMOTE switch is in
CLOCK OFF Unit is off due to internal clock schedule. LOR
LOCAL ON Unit is on. LOR switch is in LOCAL position and
CCN ON Unit is on due to CCN command. LOR switch is in
CLOCK ON Unit is on due to internal clock schedule or occu-
DUAL SP ACTI VE (1st SP)
DUAL SP ACTI VE (2nd SP)
TEMPERATURE RESET ACTIVE
DEMAND LIMIT ACTIVE
FSM CONTROLLING
RAMP LOADING ACTIVE
TIMED OVERRIDE ACTIVE
WSM CONTROLLING
SLOW CHANGE OVERRIDE
position or LOCAL/OFF/REMOTE switch is in REMOTE position and remote contacts are open.
LOCAL position and CCN control is enabled (Stop state) or CCN is enabled (Stop state) with LOR switch in REMOTE position and remote contacts closed.
switch is in LOCAL position.
CCN is disabled or LOR switch is in REMOTE position with contacts closed and CCN is disabled.
LOCAL position and CCN is enabled (Run state) or LOR switch is in REMOTE position with con­tacts closed and CCN is enabled (Run state).
pied override function. LOR switch is in LOCAL position.
Dual set point is in effect. In this mode, unit contin­ues to run in an occupied condition, and leaving fluid set point is automatically controlled to the CSP1 set point in the SET POINT function.
Dual set point is in effect. In this mode, unit contin­ues to run in unoccupied condition, but leaving fluid set point is automatically increased to a higher level (CSP2 set point is in SET POINT function).
Temperature reset is in effect. In this mode, unit is using temperature reset to adjust leaving fluid set point upward, and unit is currently controlling to the modified set point. The set point can be modi­fied based on re turn flu id, outdoor -air temp erat ure, space temperature, or 4 to 20 mA signal.*
Demand limit is in effect. This indicates that capacity of unit is being limited by demand limit control option. Because of this limitation, the unit may not be able to produce the desired leaving fluid temperature. Demand limit can be controlled by a switch or 4 to 20 mA signal.*
Flotronic™ System Manager (FSM) is controlling the chiller.
Ramp load (pulldown) limiting is in effect. In this mode, the rate at which leaving fluid temperature is dropped is limited to a predetermined value to prevent compressor overloading. See CRAMP set point in the SET POINT function (page 27). The pulldown limit can be modified, if desired, to any rate from 0.2° F to 2° F (0.1° to 1° C)/minute.
Timed override is in effect. This is a 1 to 4 hour temporary override of the programmed sche dul e, forcing unit to occupied mode. Override can be implemented with unit und er LOCA L/ R EMOTE or CCN control. Override expires after each use.
Water System Manager is controlling the chiller.
Slow change override is in effect. The leaving fluid temperature is close to and moving towards the control point.
CODE DESCRIPTION
OFF TO ON DELA Y ACTIVE
LOAD LIMIT ACTIVE
2 CHILLR LEAD LAG ACTIVE
2 CHILLR LL COMM FAILURE
CIRCUIT A LOW DISCHARGE SUPERHT
CIRCUIT B LOW DISCHARGE SUPERHT
CIRCUIT A HIGH SCT
CIRCUIT B HIGH SCT
LOW COOLER SUCTION TEMPERATURE
Chiller is being held off by Minutes Off Time found by keying . Also, normal operation of the chiller
includes a minimum 1.5 minute delay after a capacity stage change has been made. This delay is adjustable from 1.5 to 6 minutes.
This function determines the maximum allowable capacity that can be running and is accomplished through the Flotronic System Manager. The unit may not be able to produce the desired leaving fluid temperature.
This mode indicates that Master and Slave chillers have been configured and are operating using the Dual Chiller control. This is a series water flow arrangement where chilled fluid is piped to the Slave Chiller first and then through the Master Chiller. Leaving Fluid Temperature control is performed based on Master Chiller Leaving Fluid Temperature.
This mode indicates that communication has been lost between the Master and Slave chillers. Both chillers will return to a stand-alone mode of operation until communication is restored.
If the discharge superheat is less than 5° F (2.8° C) and falling, a circuit loader will be deenergized every 30 seconds. The final stage will not be unloaded unless an alarm condition is present.
See description for Circuit A above.
If the circuit is running and the Saturated Condensing Temperature (SCT) is greater than the Maximum Condensing Temperature Set point (MCT_SP) minus 12° F (6.7° C), the control will not add any stages.
If the SCT is greater than the MCT_SP plus 5° F (2.8° C), the circuit will be unloaded and shut down if necessary. If the SCT is greater than the MCT_SP plus 2° F (1.1° C) for one minute, a loader will be deenergized.
If the SCT is greater than the MCT_SP minus 4° F (2.2° C), the control will compare the maximum operatin g pressure set point (MOP_SP) with the modi­fied MOP_SP (MOP_CTRL).
If the MOP_CTRL is greater than the MOP_SP, the mode will be cleared. Otherwise the control will display the high SCT override mode. The capacity control routine will not add any stages. If the circuit is at its lowest capacity, this mode will be ignored.
See description for Circuit A above.
Circuit A and/or B low saturated suction condition exists. Control will not increase capacity on affected circuits. The EXV of the affected circuit(s) will be opened until the condition does not exist.
CCN — Carrier Control Network CSP — Cooling Set Point CRAMP — Cooling Ramp Loading EXV — Electronic Expansion Valve LOR — Local/Off/Remote SP —Set Point WSM — Water System Manager
*A field-supplied 500 Ohm 1/
the input terminals when using a 4 to 20 mA signal.
LEGEND
W resistor must be installed across
2
Table 16 — Reading Current Operating Mode
KEYP AD ENTR Y DISPL AY
MODES :MODE_TBL CCN ON
DEMAND LIMIT ACTIVE
26
TEST FUNCTION — The test function operates the diagnos-
ENTER
tic program. To initiate the test function, the LOCAL/OFF/ REMOTE switch must be in the OFF position.
To reach a particular test, press its subfunction number fol­lowed by the key then scroll to the desired test by pressing the down arrow key. Refer to Ta ble 17 for a complete descrip­tion of the test function.
To start a test of discrete outputs, press . To end the test, simply press the key or press . Pressing
ENTER
ENTER
the key after a test has started advances the system to the next test, whether the current test is operating or has timed out. Circuit A discrete outputs can be tested in and in­clude loaders, minimum load valve, oil heater (if equipped), motor cooling solenoids, oil pump, and oil solenoi ds. Similarly, Circuit B discrete outputs can be tested in . Additional discrete outputs, including condenser fans, cooler heater, water pumps, and remote alarms can be tested in .
®
Press to access Valves and Motormaster
control analog outputs. Scroll down to display Circuit A EXV Valve with a target percent of 0%. Press to step the EXV to 25%. Pressing three additional times will move the
ENTER
ENTER
EXV to 50%, 75%, and 100% The EXV may be closed in 25% steps by pressing for each desired step. Wait 30 sec-
ENTER
onds between each step when opening and closing for the valve to stop moving. Pressing the down arrow will display Circuit B EXV Valve and it is tested in the same manner as Circuit A. Also available for test are Circuit A water valve (if equipped) and the Circuit A and B Fan speed % (direct control Motor­master device) outputs for 30GX chillers. These are tested in the same manner as the EXV valves. Note that condenser fan motors are NOT started during fan speed quick tests. Measure 4 to 20 mA dc output using meter in series with violet wire to controller. See pages 74 and 75 of Field W iring section.
While the unit is in test, you can leave the test function and access another display or function by pressing the appropriate keys. However, a component that is operating when another function is accessed remains operating. You must re-enter the test function and press to shut down the component.
ENTER
Components with a timed operating limit time out normally even if another function is accessed.
Since the Test function checks only certain outputs, it is a good practice to also check all inputs and outputs accessible through the Status function. These can be located by pressing
through . If keypad is not used for 10 minutes, the unit automa tically l eave s the tes t functi on and res umes t he normal rotating display . See Table 18.
HISTORY FUNCTION — Pressing displays total machine operating hours. Scroll down to display machine run time and starts, and total run time and starts for each compres­sor. Refer to Table 19 for a complete description of the func­tion. When the PSIO-1 module is replaced or downloaded with Version 4.0 or later software, the number of starts and run hours may be changed one time. Record the current values from the PSIO before removing the module or downloading new software. The number of starts and hours may be changed
by entering the desired value at the HSIO and pressing the
key.
Pressing displays the last 10 alarms along with a description and time and date of occurrence of each alarm.
SET POINT FUNCTION — Set points are entered through the keypad. Set points can be changed within the upper and lower limits, which are fixed. The ranges are listed below. Refer to Tabl e 20 for a complete description of the function.
Cooling Set Point 1 and 2
Water:
38 to 70 F
(3.3 to 21.1 C)
Medium
T emp erature Brine:
14 to 70 F
(–10 to 21.1 C)
Temperature Brine:
Low
–13 to 70 F
(–25 to 21.1 C)
Reset Set Points
Maximum
Reset Range:
–30 to 30 F
(–17 to 17 C)
External Signal Reset: 4 to 20 mA (2 to 10 vdc with
External
T emp erature Reset:
–40 to 240 F
(–40 to 118 C)
500 Ohm
1
/2 watt resistor)
Chiller Fluid :
0° to 15 F
(0° to 8 C)
Demand Limit Set Points Switch Input: Step 1 — 0 to 100% Capacity Reduction
Step 2 — 0 to 100% Capacity Reduction
External Signal: Maximum Demand Limit 4 to 20 mA
(2 to 10 vdc with 500 Ohm Minimum Demand Limit 4 to 20 mA (2 to 10 vdc with 500 Ohm
1
/2 watt resistor)
1
/2 watt resistor) Loadshed Demand Delta: 0 to 60% Maximum Loadshed Time: 0 to 120 min.
Head Pressure Set Points Air cooled chillers (30GX): 80 to 135 F (26.7 to 57.2 C) W ater cooled chill ers (30HX): 80 to 128 F (26.7 to 53.3 C) Set Point Table
— The unit operating set points can be found under . Use the down arrow key to scroll through the set points. The first set point is Cool Set Point 1. This is the oc­cupied chilled fluid set point. Scroll down to Cool Set Point 2 and then to the Cooling Ramp load multiplier which is config­urable from 0.2 to 2.0° F/min. (0.11 to 1.1° C/min.). This value is the maximum rate at which the leaving fluid temperature is allowed to drop without adding a stage. Cooling Set Point 2 is used in conjunction with the dual set point switch function. This is used as the low temperature set point for ice duty or as the unoccupied set point. Press the down arrow key to display the Circuit A and B head pressure set points. The remaining set points in this subfunction include demand limit, LCW (leaving chilled water) delta alarm limit, minutes off time, and motor temperature set point.
Display Units
— Press to display the units of mea-
sure being used. Type 0 is for Engli sh and type 1 is for Metric. Address
— For CCN configurations, press and scroll
down to display the address and bus number of the chiller.
— Press and scroll down to read and change the
Time unit day of week, time, day of month, m onth of year a nd year of century . See the examples in Table 20 for making changes to these value s.
27
Table 17 — Test Function and Subfunction Directory
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 Circuit A Discrete Outputs
2 Circuit B Discrete Outputs
Circuit A Discrete Output Loader A1 Relay is OFF
Loader A1
ENTER
Relay is ON Loader A2
Minimum Load Valve A Circuit A Oil Heater A1 Mtr. Cooling Solenoid A2 Mtr. Cooling Solenoid Circuit A Oil Pump Oil Solenoid A1 Oil Solenoid A2
Circuit B Discrete Output Loader B1 Relay is OFF
Loader B1
ENTER
Relay is ON Loader B2
Minimum Load Valve B
Similarly, use to test remaining outputs. Press the down arrow key or to turn an output off.
NOTE: Output will display Rela y is ABSENT when not configured
Similarly, use to test remaining outputs. Press the down arrow key or to turn an
output off.
ENTER
ENTER
ENTER
ENTER
3 Unit Discrete Outputs
Circuit B Oil Heater B1 Mtr. Cooling Solenoid B2 Mtr. Cooling Solenoid Circuit B Oil Pump Oil Solenoid B1 Oil Solenoid B2
NOTE: Output will display Rela y is ABSENT when not configured
Unit Discrete Output Fan 1 Relay is OFF
Fan 1
ENTER
Relay is ON Fan 2
Similarly, use to test remaining outputs.
ENTER
Press the down arrow key or to turn an
Fan 3
output off.
Fan 4 Fan 5 Energizes Circuit A fans for 30HXA units. Fan 6 Energizes Circuit B fans for 30HXA units. Cooler Pump
ENTER
Condenser Pump Cooler Heater Alarm Remote Alarm 1 Currently not supported.
28
Table 17 — Test Function and Subfunction Directory (cont)
SUBFUNCTION KEYPAD ENTRY DISPLA Y COMMENT
3 Unit Discrete Outputs (cont)
4 Valves and Motormaster
ENTER
ENTER
ENTER
ENTER
Remote Alarm 2 Currently not supported. Remote Alarm 3 Currently not supported.
Remote Alarm 4 Currently not supported. Remote Alarm 5 Currently not supported. Remote Alarm 6 Currently not supported. Remote Alarm 7 Currently not supported. Remote Alarm 8 Currently not supported. Remote Alarm 9 Currently not supported. Remote Alarm 10 Currently not supported. Remote Alarm 11 Currently not supported. Remote Alarm 12 Currently not supported. Remote Alarm 13 Currently not supported. Remote Alarm 14 Currently not supported. Remote Alarm 15 Currently not supported. Remote Alarm 16 Currently not supported.
Valves and Motor Master Circuit A EXV Valve Target Percent = 0% Circuit A EXV Valve
Step in 25% increments.
Target Percent = 25% Circuit A EXV Valve
Target Percent = 50% Circuit A EXV Valve
Target Percent = 75%
Wait 30 seconds between each step for valv e to stop moving.
Valve may be closed in 25% increments by key­ing in . Wait 30 seconds between
ENTER
each step for valve to stop moving. Circuit A EXV Valve Target Percent = 100%
Circuit B EXV Valve Target Percent = 0%
Circuit A Water Valv e Target Percent = 0%
Test same method as for Circuit A.
Test same method as for EXV valves. Circuit A% Fan Speed Test same method as for EXV valves.
EXV — Electronic Expansion Valve
LEGEND
KEYPAD ENTRY DISPLAY RESPONSE COMMENTS
ENTER
ENTER
EXV — Electronic Expansion Valve
ENTER
ENTER
LEGEND
Circuit A Discrete Output Loader A1 Relay is OFF Loader A1 Relay is ON
Loader A1 Relay is OFF
Valves and Motor Master Circuit A EXV Valve Target Percent = 0% Circuit A EXV Valve Target Percent = 25%
Circuit A EXV Valve Target Percent = 0
Circuit B% Fan Speed Test same method as for EXV valves.
Table 18 — Using Test Function
Appears on screen momentarily, then will switch to Loader A1.
Compressor Loader A1 solenoid energized Compressor Loader A1 solenoid deenergized
Continue pressing to step to 50%, 75%, and 100%. Wait 30 seconds between each step for valve to stop moving. Continue pressing to step closed.
29
ENTER
ENTER
Table 19 — History Function and Subfunction Directory
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 Operating Hours
Machine Operating Hours xxx.x hours
Machine St arts xxx
Circuit A
Number of hours unit has at least 1 compres­sor running
Number of unit starts from zero capacity
2 Alarm History
Operating Hours xxx.x hours
Compressor A1 Hours xxx.x hours
Compressor A2 Hours xxx.x hours
Starts Compressor A1 Starts
xxx Compressor A2 Starts
xxx Circuit B
Compressor B1 Hours xxx.x hours
Compressor B2 Hours xxx.x hours
Starts Compressor B1 Starts
xxx Compressor B2 Starts
xxx Previous Alarm 1 - description
Alarm description, time/day of occurrence
Previous Alarm 2 - description Alarm description, time/day of occurrence
Previous Alarm 3 - description Alarm description, time/day of occurrence
Previous Alarm 4 - description Alarm description, time/day of occurrence
Previous Alarm 5 - description Alarm description, time/day of occurrence
Previous Alarm 6 - description Alarm description, time/day of occurrence
Previous Alarm 7 - description Alarm description, time/day of occurrence
Previous Alarm 8 - description Alarm description, time/day of occurrence
Previous Alarm 9 - description Alarm description, time/day of occurrence
Previous Alarm 10 - description Alarm description, time/day of occurrence
These values may be changed once, when new software is downloaded or when the PSIO-1 module is replaced (Version 4.0 and later)
List 10 most recent alarms. Use when necessary.
30
Loading...
+ 78 hidden pages