Bosch POPEX B299 Installation Manual

1 | Overview
3.4 | Wire to the POPIT devices
To show the fi rmware version using an LED fl ash pattern:
- If the optional tamper switch is installed: With the enclosure door open, activate the tamper switch (push and release the switch).
- If the optional tamper switch is NOT installed: Momentarily short the tamper pins. Refer to Figure 5.1 for an example of fl ash pattern
s.
5 | Show the fi rmware version
Figure 5.1: Firmware LED fl ash patterns When the tamper switch is activated (closed to open), the heartbeat LED stays OFF for 3 sec before indicating the fi rmware version. The LED pulses the major, minor, and micro digits of the fi rmware version, with a 1 sec pause after each digit. Flashing patterns do not start until the tamper is open (short is removed). In the following example, the version 1.4.3 shows as LED fl ashes: [3 sec pause] *___****___*** [3 sec pause, then normal operation].
4 | LED descriptions
The module includes one blue heartbeat LED to indicate that the module has power and to indicate the module’s current state. Refer to Table 4.1.
Flash Pattern Function
Flashes once every 1 sec
Normal state. Indicates normal operation state.
3 quick fl ashes every 1 sec
x3
Communication error state. Indicates (the module is in a “no communication state”) resulting in an SDI2 communication error.
ON Steady LED trouble state. Module is not
powered (for OFF Steady only), or some other trouble condition prohibits the module from controlling the heartbeat LED.
OFF Steady
Table 4.1: LED descriptions
3.3 | Wire to the control panel
You can connect modules to the SDI2 data bus by parallel wire run from the control panel to each module, wire from module to module, or a combination of the two techniques. Refer to Figure 3.4.
Refer to Figure 3.4 to wire a zone expansion loop. Wire resistance on each sensor loop must be less than 100 Ω with the detection devices connected. The terminal strip supports 12 to 22 AWG (2.0 to 0.65 mm) wires.
+ + - -
TMPR
POPEX
- - + + - +
- - + + - +
1 2
3
3
4
5
4
6
Figure 3.4: Wiring a zone expansion loop
Callout ― Description
1 ― B299
2 ― POPIT module (D9127U/T shown)
3 ― D9127 sensor loop
4 ― 33 kΩ EOL resistor (P/N: 15-03130-022)
5 ― POPEX loop 2 (electrically identical to loop 1)
6 ― POPEX loop 1 (electrically identical to loop 2)
2.1 | Valid addresses and point numbers per control panel
Valid B299 addresses are dependant on the number of points allowed by a particular control panel.
Control panel Valid B299
addresses
Corresponding point numbers
B9512G B9512G-E
0 - 5 9 - 99, 100 - 199, 200 -
299, 300 - 399, 400 - 499, 500 - 599
B8512G B8512G-E
0 9 - 99
3 | Installation
Set the address switch for the proper address and then install the module into the enclosure. Wire the module to the control panel.
CAUTION!
Remove all power (AC and battery) before making any connections. Failure to do so might result in personal injury and/or equipment damage.
3.1 | Mount the module in the enclosure
Mount the module into the enclosure’s 3-hole mounting pat­tern using the mounting screws and mounting bracket. Refer to Figure 3.1.
Figure 3.1: Mounting the module in the enclosure
Callout ― Description
1 ― Module with mounting bracket installed
2 ― Enclosure
3 ― Mounting screws (3)
NOTICE!
Use either the terminal strip wiring or interconnect wiring connector to the control panel. Do not use both. When connecting multiple modules, you can combine terminal strip and interconnect wiring connectors in series.
SDI2
RESET
RESET
ZONEX
ZONEX
TAMPER
TAMPER
SDI2
SDI2
PWR+/R
PWR+/R
A/Y
A/Y
B/G
B/G
COM/B
COM/B
PWR+/R
PWR+/R
A/Y
A/Y
B/G
B/G
COM/B
COM/B
24
25
26
27
28
29
23
26
W
ARNI
ARNING!G!
Multi-B
Multi-Battery y
in
inst
all
alla
tion
tion requiuiress
Model D122
Model D122
or
or
D122L
D122L
Dual B
Dual Battery HaHarnes
s.
s.
Impr
oper in
oper inst
all
alla
tion
tion
can
can
be a
be a fir
e haza
e hazard
.
Battery
: Replace
: Replace
ever
y 3
y 3 to o 5 5 year
s wi
s with h
one or t
one or tw
o Model
o Model
D126 or D1218 12 V
D126 or D1218 12 V
Lea
d Acid B
d Acid Batteries.s.
Battery
: Replace
: Replace
ever
y 3
y 3 to o 5 5 year
s wi
s with h
one or t
one or tw
o Model
o Model
D126 or D1218 12 V
D126 or D1218 12 V
Lea
d Acid B
d Acid Batteries.s.
Battery
: Replace
: Replace
ever
y 3
y 3 to o 5 5 year
s wi
s with h
one or t
one or tw
o Model
o Model
D126 or D1218 12 V
D126 or D1218 12 V
Lea
d Acid B
d Acid Batteries.s.
POPEX
PWR A B COM
SDI2
TMPR
B
G
Y
R
1
2
Callout ― Description
1 ― Bosch control panel
2 ― B299 POPEX module
Figure 3.2: SDI2 terminal wiring from control panel to B299
3.2 | Mount and wire the tamper switch
You can connect an optional tamper switch for one module in an enclosure. Installing the optional tamper switch:
1. Mount the ICP-EZTS Tamper Switch (P/N: F01U009269) into the enclosure’s tamper switch mounting location. For complete instructions, refer to EZTS Cover and Wall Tamper Switch Installation Guide (P/N: F01U003734).
2. Plug the tamper switch wire onto the module’s tamper switch connector. Refer to Figure 1.1.
SDI2
RESET
RESET
ZONEX
ZONEX
TAMPER
TAMPER
SDI2
SDI2
PWR+/R
PWR+/R
A/Y
A/Y
B/G
B/G
COM/B
COM/B
PWR+/R
PWR+/R
A/Y
A/Y
B/G
B/G
COM/B
COM/B
24
25
26
27
28
29
23
26
W
ARNI
ARNING!G!
Multi-B
Multi-Battery y
in
inst
all
alla
tion
tion requiuiress
Model D122
Model D122
or
or
D122L
D122L
Dual B
Dual Battery HaHarnes
s.
s.
Impr
oper in
oper inst
all
alla
tion
tion
can
can
be a
be a fir
e haza
e hazard
.
Battery
: Replace
: Replace
ever
y 3
y 3 to o 5 5 year
s wi
s with h
one or t
one or tw
o Model
o Model
D126 or D1218 12 V
D126 or D1218 12 V
Lea
d Acid B
d Acid Batteries.s.
Battery
: Replace
: Replace
ever
y 3
y 3 to o 5 5 year
s wi
s with h
one or t
one or tw
o Model
o Model
D126 or D1218 12 V
D126 or D1218 12 V
Lea
d Acid B
d Acid Batteries.s.
Battery
: Replace
: Replace
ever
y 3
y 3 to o 5 5 year
s wi
s with h
one or t
one or tw
o Model
o Model
D126 or D1218 12 V
D126 or D1218 12 V
Lea
d Acid B
d Acid Batteries.s.
1
2
3
Callout ― Description
1 ― Bosch control panel
2 ― Innerconnect cable (P/N: F01U79745, included)
3 ― B299 POPEX module
Figure 3.3: SDI2 innerconnect cable wiring from control panel
to B299
Use the control panel terminals labeled R, Y, G, B (PWR, A, B, COM) when wiring to the module. Connect them to the module terminals labeled R, Y, G, B (PWR, A, B, COM). You can also use the SDI2 innerconnect cable. Refer to Figures 3.2 and 3.3.
2 | SDI2 address settings
The address switch determines the address for the module. The control panel uses the address to establish communication between itself and the module. The address also determines the associated point numbers. Refer to Section 6 Confi guration for information related to the address switch. Use a slotted screwdriver to set the address switch.
NOTICE!
The module reads the address switch setting during power up. If you change the switches after you apply power to the module, cycle the power to the module in order for the new setting to be enabled.
Set the address switch per the control panel confi guration. If multiple B299 modules reside on the same system, each B299 module must have a unique address. Figure 2.1 shows the address switch settings for address 0.
Figure 2.1: Address switch
The B299 POPEX Module is an SDI2 compatible, POPIT expansion module that communicates to the control panel over the SDI2 bus. The B299 supports up to 100 POPIT devices by wiring to the POPEX terminal strip and providing one or two addressable POPIT busses.
1
2
3
4
5
6
7
Figure 1.1: POPEX module
Callout ― Description
1 ― 3-hole mounting pattern
2 ― Address switch
3 ― SDI2 interconnect wiring connectors (to control panel or additional modules)
4 ― SDI2 terminal strip (to control panel or additional modules)
5 ― Heartbeat LED (blue)
6 ― Tamper switch (optional) connector
7 ― POPEX terminal strip (POPIT Bus))
Bosch Security Systems, Inc.
130 Perinton Parkway Fairport, NY 14450 USA
www.boschsecurity.com
© 2016 Bosch Security Systems, Inc. F.01U.300.043 | 06 | 2016.01
Trademarks
All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly.
Bosch Security Systems, Inc. product manufacturing dates
Use the serial number located on the product label and refer to the Bosch Security Systems, Inc. website at http:// www.boschsecurity.com/datecodes/.
Copyright
This document is the intellectual property of Bosch Security Systems, Inc. and is protected by copyright. All rights reserved.
8 | Specifi cations
Dimensions 2.9 in x 5.0 in x 0.6 in (73.5 mm x 127 mm x 15.25
mm)
Voltage (input) 12 VDC
Current Standby: 35 mA + total device current
Alarm: 35 mA + total device current
Operating temperature 0°C to +50°C (+32°F to +122°F)
Relative humidity 5% to 93% at +32°C (+90°F) non-condensing
Terminal wire size 12 AWG to 22 AWG (2.0 mm to 0.65 mm)
SDI2 wiring Maximum distance - wire size (unshielded wire
only): 200 ft (60 m) - 22 AWG (0.65 mm), 500 ft (152 m) - 18 AWG (1.02 mm)
POPIT loop wiring Maximum wire length: 1800 ft (548 m) 22 AWG
(0.65 mm), 4497 ft (1370 m) 18 AWG (1.02 mm)
Compatibility Control panel: B9512G/B9512G-E (6 modules),
B8512G/B8512G-E (1 module). (Refer to the con­trol panel installation document for the number of supported devices.)
POPIT devices: D9127U/T, ZX776Z/ZX794Z PIR, ZX835 TriTech, ZX935Z/ZX938Z PIR, ZX970 TriTech, D278S 12V smoke base, D298S 24V smoke base, F220-B6PM popit smoke (master), F220-B6PS popit smoke base
7 | Certifi cations
Region Certifi cation
US UL 365 - Police Station Connected Burglar Alarm Units and
Systems
UL 609 - Local Burglar Alarm Units and Systems
UL 636 - Holdup Alarm Units and Systems
UL 864 - Control Units and Accessories for Fire Alarm Systems
UL 985 - Household Fire Warning System Units
UL 1023 - Household Burglar-Alarm System Units
UL 1076 - Proprietary Burglar Alarm Units and Systems
UL 1610 - Central Station Burglar Alarm Units
ANSI/SIA CP-01:2010
CSFM - California Offi ce of The State Fire Marshal
FCC Part 15 Class B
CA Canada CAN/ULC S303 - Local Burglar Alarm Units and Systems
CAN/ULC S304 - Signal Receiving Centre and Premise Alarm Control Units
ULC-S545 - Residential Fire Warning Alarm Systems Control units
ULC-ORD C1023 - Household Burglar Alarm System Units
ULC-ORD C1076 - Proprietary Burglar Alarm Units and Systems
ICES-003 - Digital Apparatus
6 Confi guration
Use the following POPIT programming table to confi gure the POPIT switch block. Switches are designated as being “ON” or “OFF.” These are depicted in the table below by the following; ON = o, OFF = blank. For example the swich settings for x09 looks like this: o,o,o,blank,o,o,blank (On,On,On,Off ,On,On,Off ).
Point number Switch B299
0123456
x00* o o o o o o o x01* o o o o o o x02* o o o o o o x03* o o o o o x04* o o o o o o x05* o o o o o x06* o o o o o x07* o o o o x08* o o o o o o x09 o o o o o x10 o o o o o x11 o o o o x12 o o o o o x13 o o o o x14 o o o o x15 o o o x16 o o o o o o x17 o o o o o x18 o o o o o x19 o o o o x20 o o o o o x21 o o o o
x22 o o o o x23 o o o x24 o o o o o x25 o o o o x26 o o o o x27 o o o x28 o o o o x29 o o o x30 o o o x31 o o x32 o o o o o o x33 o o o o o x34 o o o o o x35 o o o o x36 o o o o o x37 o o o o x38 o o o o x39 o o o x40 o o o o o x41 o o o o x42 o o o o x43 o o o x44 o o o o x45 o o o x46 o o o x47 o o x48 o o o o o x49 o o o o * Not available for use on B299 at address 0.
Point number Switch B299
0123456
x50 o o o o x51 o o o x52 o o o o x53 o o o x54 o o o x55 o o x56 o o o o x57 o o o x58 o o o x59 o o x60 o o o x61 o o x62 o o x63 o x64 oooooo x65 ooooo x66 oooo o x67 oooo x68 o o o o o x69 o o o o x70 o o o o x71 o o o
x72 o o o o o x73 o o o o x74 o o o o x75 o o o x76 o o o o x77 o o o x78 o o o x79 o o x80 o o o o o x81 o o o o x82 o o o o x83 o o o x84 o o o o x85 o o o x86 o o o x87 o o x88 o o o o x89 o o o x90 o o o x91 o o x92 o o o x93 o o x94 o o x95 o x96 o o o o o x97 o o o o x98 o o o o x99 o o o * Not available for use on B299 at address 0.
en Installation Guide
POPEX module
B299
Loading...