Bosch D8129 Specsheet

Intrusion Alarm Systems | D8129 Octo‑relay Module
D8129 Octo‑relay Module
www.boschsecurity.com
u Programmable relay functions
u Provides eight Form C relays
u 1 A at 30 VDC relay contact rating
The D8129 Octo-relay Module is suitable for applications requiring Form C relays to operate auxiliary systems or to display fire system status at remote annunciators. Building components such as HVAC, door lock releases, and stairwell pressurization can interface with the D8129 for complete system control and monitoring. Industrial, commercial, and institutional facilities are typical installations for the D8129 module. The eight on-board relays can be programmed to activate on system alarm, system trouble, individual zone or point faults, and through remote control by authorized users.
System overview
The D8129 Octo-relay Module provides eight programmable Form C relays. Each relay provides dry contact switching rated for 1.0 A at 30 VDC. The relays are accessed through on-board screw terminal connections. The D8129 uses information from the control panel serial data output to activate the relays. On-board switches are used to configure the D8129 for different operating modes, or to specify relay output numbers. These switches, along with control panel programming options, determine the D8129’s response to the serial
u Allows remote control of relays
data. Programming within the control panel can activate specific relays or sets of relays in response to system conditions. For the G Series control panels, slide switches are configured for specific relay output numbers, which are activated according to their programming. The D8129 uses five slide switches with multiple setting options to configure its mode of operation. The D8129 receives serial data from the control panel and activates relays in response to control panel conditions and slide switch settings. Relays can be programmed for remote control from a panel keypad.
Functions
Output Relays
Each relay output provides a normally-open and a normally-closed output.
Modes of Operation
A slide switch with multiple switch settings can be used to configure the module for a specific mode of operation for D8112 Series systems, or programming can be used to determine relay operation for G Series systems.
Certifications and approvals
Australia C-Tick
2 | D8129 Octo‑relay Module
Region Certification
USA UL AMCX: Central Station Alarm Units
(UL1610, UL1635), AMCX7: Central Station Alarm Units Certified for Canada (cULus), AOTX: Local Alarm Units (UL464, UL609), AOTX7: Local Alarm Units Certified for Canada (cULus), APAW: Police Station Alarm Units (UL365, UL464), APAW7: Police Sta­tion Alarm Units Certified for Canada (cULus), APOU7: Proprietary Alarm Units Certified for Canada (cULus), NBSX: Household Burglar Alarm System Units (UL1023), NBSX7: Household Burglar Alarm System Units Certified for Canada (cULus), UOJZ: Control Units, System (UL864, 9th edition),UTOU: Control Units and Accessories - House­hold System Type (UL985), UTOU7: Control Units and Accessories - House­hold System Type Certified for Canada (cULus)
CSFM see our website
FDNY-
6059 [D9412GV3 & D7412GV3]
CoA
FDNY-
6174
CoA
Canada ULC AMCX7.S1871 - Central Station Alarm
Units Certified for Canada
ULC NBSX7.S1871 Household Burglar Alarm
System Units Certified for Canada
ULC AOTX7.S1871 Local Alarm Units Certi-
fied for Canada
ULC APAW7.S1871 Police-station-connec-
ted Alarm Units Certified for Canada
Installation/configuration notes
Compatible Control Panels
• B9512G/B9512G-E
• B8512G/B8512G-E
• D9412GV4/D7412GV4/D7212GV4
• D9412GV3/D7412GV3/D7212GV3
• D9412GV2/D7412GV2/D7212GV2
1
The D7212GV4, D7212GV3, and D7212GV2 are not
1
1
1
listed for commercial fire applications.
Mounting Considerations
Up to four D8129 Octo-relay Modules can be mounted in a control panel enclosure. For additional modules, use the D137 Mounting Bracket.
Wiring Considerations
The D8129 connects to a control panel using the 12 VDC Auxiliary output, Serial Data Output, and common terminals. Use 1.5 mm to 0.6 mm (16 AWG to 22 AWG) wires from the module to the control panel.
1 Hardware pack
1 Literature pack
Technical specifications
Properties
Board Dimensions:
12 cm x 7.6 cm x 1.9 cm (5.0 in. x 3.0 in. x 0.75 in.)
Power Requirements
Current: 130 mA maximum
Voltage: 12 VDC nominal
Relays
Contact Rating: 1.0 A at 30 VDC for resistive load
Timing: During pulsed output, relay maintains closure for
1 sec
Type: Form C dry contact
Ordering information
D8129 Octo‑relay Module
Provides 8 programmable relays.
Order number D8129
Accessories
D137 Mounting Bracket
Used to mount accessory modules in D8103, D8108A, and D8109 enclosures.
Order number D137
D138 Mounting Bracket, Right Angle
Used to mount accessory modules in D8103, D8108A, and D8109 enclosures.
Order number D138
Parts included
Quantity Component
1 Octo-relay module
Loading...
+ 1 hidden pages