Bosch D8129 Installation Manual

EN
Installation and Operation Guide
Octo-relay Module
D8129 | Installation and Operation Guide | 1.0 G Series Control Panels EN | 2
1.1 Specifications
1.0 G Series Control Panels
Use the D8129 Octo-relay Module to add programmable relay outputs to the system in groups of eight to the G Series Control Panels (D9412GV4, D7412GV4, D7212GV4, D9412GV3, D7412GV3, D7212GV3, D9412GV2, D7412GV2, D7212GV2, D9412G, D7412G, D7212G), the D9124 control panel, and the new G Series control panels (B9512G, B8512G).
The new G Series panels (B9512G, B8512G) require the B600 Retrofit (ZONEX) Module to use the B8129.
On the B9512G, D9412GV4, D9412GV3, D9412GV2, and D9412G, you can add up to 128 Octo-relay outputs (relay numbers 1 to 128) to the system using 16 D8129 Modules. The B8512G, D7412GV4, D7412GV3, D7412GV2, and D7412G allow up to 64 relay outputs. Review the control panel installation and compliance documents to determine the number of D8129 modules each panel can support and any power requirements and limitations.
The D7212GV4, D7212GV3, D7212GV2, and D7212G support up to 24 output relays (3 D8129 Modules).
The D8129 Modules for relay numbers 1 to 64 connect to ZONEX 1. The D8129 Modules for relay numbers 65 to 128 connect to ZONEX 2. Refer to
2
on page 3.
The D8129 outputs can be assigned functions individually. Functions include alarm, auxiliary relay, sensor reset, arming status, and point status. Review the control panel installation or programming documents, or RPS help for complete programming details.
The D8129 relay outputs are not supervised and cannot be used for the primary indication device in commercial fire applications.
It is possible for relay outputs to activate while setting the D8129 switches, or changing the control panel programming. You can disconnect the equipment connected to relay outputs when performing these functions.
Figure 1 and Figure
Table 1: Specifications
Voltage Nominal 12 VDC Current 130 mA maximum
Wiring UL864 Control Panel Wiring Connection
Maximum Wire Resistance: 0.1 Ω
Maximum Distance Wire Size
Non-UL864 Control Panel Wiring
Maximum Wire Resistance: 4 Ω
Maximum Distance Wire Size
Relay Output (Form “C” dry contact)
Resistive Load Maximums
During pulsed operation, the relay will maintain closure for minimum of 1 sec.
Requirements
5 ft 22 AWG 5 ft 18 AWG
1.5 m 0.6 mm
1.5 m 1.0 mm
Connection Requirements
200 ft 22 AWG 200 ft 18 AWG
60 m 0.6 mm 60 m 1.0 mm
Voltage 5-24 VDC
Current 1 mA - 1 Amp
1.2 Configuration
Five D8129 switches determine the relay numbers for the eight relay outputs. Table 2 shows the switch settings.
Table 2: DIP Switch Settings
Relay Number
1 to 8 OFF-ON-ON-ON-ON ZONEX 1 9 to 16 ON-OFF-ON-ON-ON ZONEX 1 17 to 24 OFF-OFF-ON-ON-ON ZONEX 1 25 to 32 ON-ON-OFF-ON-ON ZONEX 1 33 to 40 OFF-ON-OFF-ON-ON ZONEX 1 41 to 48 ON-OFF-OFF-ON-ON ZONEX 1 49 to 56 OFF-OFF-OFF-ON-ON ZONEX 1 57 to 64 ON-ON-ON-OFF-ON ZONEX 1 65 to 72 OFF-ON-ON-ON-ON ZONEX 2 73 to 80 ON-OFF-ON-ON-ON ZONEX 2 81 to 88 OFF-OFF-ON-ON-ON ZONEX 2 89 to 96 ON-ON-OFF-ON-ON ZONEX 2 97 to 104 OFF-ON-OFF-ON-ON ZONEX 2 105 to 112 ON-OFF-OFF-ON-ON ZONEX 2 113 to 120 OFF-OFF-OFF-ON-ON ZONEX 2 121 to 128 ON-ON-ON-OFF-ON ZONEX 2
DIP Switch Setting
Control Panel or B600 Connection
Bosch Security Systems, Inc. | 11/15 | F01U036302-09
D8129 | Installation and Operation Guide | 1.0 G Series Control Panels EN | 3
Figure 1: D8129 Connections to the D9412GV2, D9412G, D9124
1
21 22
Disable All Except Battery
Charging And Programming
PERIPHERAL DEVICE CONNECTIONS
RED POWER +
YELLOW DATA BUS A
GREEN DATA BUS B
BLACK COMMON
N.F.P.A.
ZONEX OUT 1 Style 3.5 Signaling Line Circuits
ZONEX IN 1
ZONEX OUT 2
ZONEX IN 2
ZONEX POWER +
ZONEX COMMON
Point 8
GND FAULT
Detect
D
E
I
N
S
A
A
Operation Monitor
B
B
L
Pulses When Normal
L
GRN
Flickers When Ringing
E
E
Reset Pin
32
31
30
29
28
27
26
25
24
23
PROG CONN
4
4
GND AU DATA
1 2 3 4 5 6 7 8
4
Note: Do not loop wires around the terminals.
4
GND AU DATA
1 2 3 4 5 6 7 8
1 - Control Panel 2 - ZONEX 1 Connection (Relays 1 to 64) - connect multiple
4 - Power limited
D8129 modules in parallel.
3 - ZONEX 2 Connection (Relays 65 to 128) - connect multiple
D8129 modules in parallel.
Figure 2: D8129 Connections to the D7412GV2, D7212GV2, D7412G, D7212G
Pin
1
Low Battery
RED
CLASS 2 TRANS
1
16.5 VAC 40 VAC Part No. D1640 Internally Fuse Requires Unsw
2
Do Not Share
+ AUX PO
3
BATTERY N
4
Maximum Charging
Current 1.4 Amps.
BATTERY POSITIVE ONLY
5
RELAY A
6
RELAY B
7
RELAY C
8
COMMON
9
EARTH GRO
10
GROUND FAUL
PR AL
Re
E CONNECTIONS
POWER +
DATA BUS A
DATA BUS B
COMMON
ZONEX OUT 1
ZONEX IN 1
Battery
amming
32
31
30
29
28
27
3
GND AU
PROG CONN
3
DATA
1
2 3 4 5
2
3
2
7 8
6
1 - Control Panel 2 - ZONEX 1 Connection for Relays 1 to 64 (1 to 24 for
D7212GV2/D7212G). Connect multiple D8129 modules in parallel.
Bosch Security Systems, Inc. | 11/15 | F01U036302-09
3
3 - Power limited