Point Type Configuration ........................ 21
2 Bosch Security Systems, Inc. | 12/15 | F01U034973-03
D8125MUX | Installation and Operation Guide | 1.0 Introduction
.
1.0 Introduction
1.1 Description
Use the D8125MUX Multiplex Bus Interface Module to
connect multiplex points to the ZONEX bus on the
following Bosch Security Systems control panels: new
G Series (B9512G, B9512G-E, B8512G, B8512G-E),
G Series (D9412GV4, D7412GV4, D7212GV4,
D9412GV3, D7412GV3, D7212GV3, D9412GV2,
D7412GV2, D7212GV2, D9412G, D7412G, D7212G),
D9412, D7412, D7212, D9112, and D9124 with version
5.22 or greater firmware. Install the D8125MUX on
ZONEX 1 and ZONEX 2 (G Series, D9412, and D9112
only). The multiplex bus interface supports two
independent multiplex buses; therefore, a fault on one
multiplex bus does not prevent the other from
operating normally.
The D8125MUX scans the multiplex points connected
to it and reports the point status to the control panel.
Also available on the D8125MUX are auxiliary power
terminals labeled Power A (+,-), Power B (+,-) that
support remote devices requiring an uninterrupted
source of power.
The B600 Retrofit (ZONEX) module is
required to use the D8125MUX on the
See the Control Panel Approved Applications Compliance Guide or the Installation and System Reference Guide to
determine the required equipment and enclosures for
the application.
B9512G, B9512G-E, B8512G, and
B8512G-E control panels.
1.2 Listings
The D8125MUX is UL Listed as a subassembly in the
following categories:
US
UL 864 Control Units, System
(UOJZ)
UL1023 Household Burglar Alarm
Systems (NBSX)
UL1610 Central Station Alarm
Units (AMCX)
UL609 Local Alarm Units (AOTX)
UL365 Police Station Connect
Alarm Units (APAW)
UL1076 Proprietary Alarm Units
(APOU)
UL 985 Household Fire Warning
System Units
CA
ULC S303 Local Burglar Alarm Units
and Systems
ULC/ORD-C1076 Proprietary Burglar Alarm
Units and Systems
ULC/ORD-C1023 Household Burglar Alarm
System Units
The D7212GV2 and D7212G are not UL
Listed for UL 864 commercial fire
applications.
1.3 Specifications
Table 1: Specifications
Bosch Security Systems, Inc. | 12/15 | F01U034973-03
Operating Voltage Nominal 12 VDC
Current Requirements D8125MUX only: 140 mA
Maximum Current
678 mA
Draw (using both MUX
bus outputs and both
power outputs)
Operating Temperature +32°F to +120°F (0°C to
+49°C)
Relative Humidity 0 to 93%
Dimensions (H x W x
D)
1.0 in. x 3.25 in. x 5.5 in.
(25 mm x 8.3 cm x 14.0
cm)
3
D8125MUX | Installation and Operation Guide | 2.0 Operation
d
n
M
2.0 Operation
The D8125MUX indicates its status using the green
Operation LED (Figure 1). Refer to Table 2 for a
description of the Operation LED.
Figure 1: D8125MUX Multiplex Bus Interface
Module
1
RESET
12V IN OUT GND
ZONEX BUS
1 - Operation LED
Table 2: Operation LED Descriptions
FIRE MANUAL
WALK TEST
PROG
+- +- + - +-
PORT
POWER A
MUX BUS A
POWER B
MUX BUS B
3.0 Installation
The D8125MUX is installed in the control panel
enclosure and is connected to either ZONEX 1 or
ZONEX 2 on the control panel or the B600 Retrofit
(ZONEX) module.
3.1 Installing the enclosure
Follow the procedure below to install the D8125MUX
in the enclosure with the control panel or B600.
1. Align the D8125MUX module with any of the four
mounting locations in the enclosure. See Figure 2.
2. Use the screws provided with the module to
secure it in the enclosure.
Figure 2: Installation diagram
Horizontal Mounting
Locations
LED Status Meaning
Flashing 1/2
Indicates normal operation.
second on, 1/2
second off
Off A module fault is indicated.
Refer to Section 6.0
Troubleshooting on page 25.
On The Multiplex Point
Programmer is connected to
the D8125MUX.
Double flash Reset the D8125MUX EEPROM
with the reset pin by plugging
in the D5060 Programmer and
placing the shorting bar over
the reset pin. The LED rapidly
flashes twice followed by a
pause.
Vertical
Mounting
Locations
(Reserve
Dual Pho
Switcher
4 Bosch Security Systems, Inc. | 12/15 | F01U034973-03
D8125MUX | Installation and Operation Guide | 3.0 Installation
.
3.2 Wiring to the control panel
Follow the procedure below to wire one or two
D8125MUX modules to the 9000 Series, and G Series
control panels. For the B9512G, B9512G-E, B8512G,
B8512G-E control panels, see the Control Panels
Installation and System Reference Guide.
The B600 Retrofit (ZONEX) module is
required to use the D8125MUX on the
3.2.1 Disconnecting the Battery and Transformer
1. Disconnect the battery by unhooking the positive
2. Unplug the transformer.
B9512G, B9512G-E, B8512G, and
B8512G-E control panels.
Remove all power (AC and Battery) before
making any connections. Failure to do so
may result in personal injury and/or
equipment damage.
(red) battery lead from the battery.
3.2.2 Wiring Procedure
For Points 9 up to Point 127:
1. Connect the GND terminal of the D8125MUX to the
control panel ZONEX COMMON terminal.
2. Connect the OUT terminal of the D8125MUX
module to ZONEX IN 1.
3. Connect the IN terminal of the D8125MUX module
to ZONEX OUT 1.
4. Connect the AUX terminal of the D8125MUX to
ZONEX POWER + terminal.
For Points 129 up to Point 247:
1. Connect the GND terminal of the D8125MUX to the
control panel ZONEX COMMON terminal.
2. Connect the OUT terminal of the D8125MUX
module to ZONEX IN 2.
3. Connect the IN terminal of the D8125MUX module
to ZONEX OUT 2.
4. Connect the AUX terminal of the D8125MUX to
ZONEX POWER + terminal.
Do not connect more than one D8125MUX to ZONEX 1
(IN and OUT terminals) or ZONEX 2 (IN and OUT
terminals).
Reversed polarity damages the D8125MUX.
Make sure you wire the D8125MUX AUX
and GND terminals to the control panel.
Figure 3: D8125MUX Wiring Diagram
PERIPHERAL DEVICE CONNECTIONS
POWER +
RED
A BUS A
T
A
D
YELLOW
GREEN DATA BUS B
BLACKCOMMON
P.A.
F.
N.
ZONEX OUT 1
Style 3.5
Signaling
Line
Circuits
ZONEX IN 1
ZONEX OUT 2
ZONEX IN 2
ZONEX POWER +
ZONEX COMMON
Point 8
GND F
Detect
E
N
A
B
L
E
PROG
CONN
LT
AU
D
I
S
A
Operation Monitor
B
Pulses When Normal
L
GRN
Flickers When Ringing
E
4
12
RESET
12V IN OUT GND
ZONEX BUS
FIRE MANUAL
PROG
+- +- + - +-
PORT
POWER A
WALK TEST
MUX BUS A
POWER B
MUX BUS B
RESET
12V IN OUT GND
ZONEX BUS
FIRE MANUAL
PROG
+- +- + - +-
PORT
POWER A
WALK TEST
3
MUX BUS A
POWER B
MUX BUS B
1 - D8125MUX on ZONEX 1
2 - D8125MUX on ZONEX 2
Bosch Security Systems, Inc. | 12/15 | F01U034973-03
3 - ZONEX Common Terminal
4 - Supervised, Power Limited.
5
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
4.0 Program Multiplex Bus
Points
Use the D5060 Programmer (Figure 4 and Table 3) to
program multiplex bus points for the B9512G,
B9512G-E, B8512G, B8512G-E, D9412GV4, D7412GV4,
D7212GV4, D9412GV3, D7412GV3, D7212GV3,
D9412GV2, D7412GV2, D7212GV2, D9412G, D7412G,
D7212G, D9412, D7412, D7212, and D9112 control
panels. In addition to programming points, the D5060
can also be used to program and read information
from a D8125MUX.
The B600 Retrofit (ZONEX) module is
required to use the D8125MUX on the
B9512G, B9512G-E, B8512G, and
B8512G-E control panels.
Table 3: D5060 LED Definitions
Display Definition
Adr Enter address.
A.dr Enter address for Interrogation Mode.
bAd Battery voltage is below 15 V.
Err Point was not programmed correctly.
Lob Battery voltage is below 16 V.
noP No response from point.
PnL Communications with the D8125 failed.
rSP Point responds to address.
tYP Enter point type.
t.YP Enter point type for Interrogation Mode
4.1 Connecting the D5060
Figure 4: D5060 Multiplex Point Programmer
EXT.
POWER
INTERROGATION MODE
YESNO
DOWN
MULTIPLEX POINT PROGRAMMER
SERIAL PORTMUX
ON
(HOLD)
3
2
1
456
0
OFF
(HOLD)
(HOLD)
9
#
ENTER
78
*
CLEAR
INTERROGATE
POINTS
UP
1. When using external power, attach the flying leads
2. Use the serial cable provided to connect the
3. For multiplex devices without DIP switches, use
Programmer
of the included power cable to the output
terminals of a 16.5 VAC transformer. Insert the
plug end into the jack labeled EXT. POWER on the
programmer. Refer to Figure 5, Figure 6, and
Figure 7.
D8125MUX to the jack labeled SERIAL PORT on
the programmer.
the multiplex programmer cable provided to
connect the point to be programmed to the port
labeled MUX POINTS as shown in Figure 5. Use the
appropriate connector, either the alligator clips or
the probes, to connect the programmer to a point.
For multiplex points with programmable DIP
switches, program the point using the DIP
switches. Connect the programmer to the
D8125MUX as shown in Figure 6.
6 Bosch Security Systems, Inc. | 12/15 | F01U034973-03
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
.
Figure 5: Installing Multiplex Points without
DIP Switches Wiring Diagram
3
1
12V IN OUT GND
ZONEX BUS
EXT.
POWER
INTERROGATION MODE
RESET
FIRE MAN UAL
PROG
PORT
WALK TEST
SERIAL PORTMUX
2
+-+-+ -+-
POWER A MUX BUS A
POWER B
MUX BUS B
POINTS
4
1 - External power
2 - D8125MUX
3 - Multiplex point without DIP switches
(non-i models)
4 - D5060 Multiplex Point Programmer
Figure 7: Programmer Cables (included)
1
2
3
1 - C310 Serial Cable
2 - C319 External Power Supply Cable
3 - C320 Multiplex Programmer Cable
Figure 6: Installing Multiplex Points with DIP
Switches Wiring Diagram
1
12V IN OUT GND
EXT.
POWER
INTERROGATION MODE
RESET
FIRE MANUAL
ZONEX BUS
WALK TEST
SERIAL PORTMUX
2
PROG
+-+- +- +-
PORT
POWER A MUX BUS A
POWER B
POINTS
MUX BUS B
3
1 - External power
2 - D8125MUX
3 - D5060 Multiplex Point Programmer
Bosch Security Systems, Inc. | 12/15 | F01U034973-03
7
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
4.2 Programming
Table 4: Point Type Entry Code
4.2.1 Powering the D5060
Turn on the D5060 by pressing and holding the [1] key
until the unit beeps. To turn the unit off, press and
hold the [#] and [*] keys simultaneously until the unit
beeps.
After 5 minutes of inactivity, the
programmer powers down automatically
to conserve power.
4.2.2 Programming Points
1. The D5060 shows the prompt Adr after it is
powered. This indicates that it is ready to begin
programming.
2. If the multiplex device has no DIP switches,
connect the D5060 to the point to be programmed
as shown in Figure 5 on page 7. If the multiplex
device has DIP switches, program the device using
its DIP switches.
If the multiplex device has no DIP
switches, connect the D8125MUX and the
multiplex device to be programmed to the
D5060 for simultaneous programming
(Figure 5). If the multiplex device has DIP
switches, program the device using its DIP
switches, and program the D8125MUX
using the D5060 (Figure 6 on page 7).
3. Enter the point’s three-digit address. The address
must be between 1 and 255. Press [#].
The programmer shows tyP.
4. Enter the number corresponding to the point type
you are programming as shown in Table 4 and
press [#]. The programmer alternately shows the
address and the point type.
When you program for a multiplex smoke
device by entering decimal value 4 or 5
Table 4, an 18-second timer starts
counting. Do not disconnect the multiplex
smoke device until after the timer counts
down to zero.
Decimal
Point Type
Value
0 Remove point from D8125MUX
1 Contact
2 Sensor (or single point module)
3 I/O module
4 Multiplex smoke without low
temperature
5 Multiplex smoke with low temperature
(0°C)
6 Dual point
5. Press [#] to program a point connected to the
D5060 and the D8125MUX (if connected), or press
[1] to program the D8125MUX only. If the
multiplex device has DIP switches, program the
device using its DIP switches.
Press [*] at any time to return to a
previous step in the procedure.
6. If the point is programmed correctly, the unit
beeps once and shows Adr, indicating it is ready to
program the next point. If the point was not
programmed correctly, the unit sounds a threebeep error tone and one of the following messages
appears:
Err: The point was not programmed correctly.
PnL: Communications with the D8125MUX failed.
7. Press [*] to clear the entry, or press [#] to
reprogram.
If programming the D8125MUX and multiplex
device simultaneously and only one receives the
program, the D5060 shows Adr. If having troubles
with the point after installation, try programming
the D8125MUX and multiplex devices separately.
4.2.3 Removing a Point from the D8125MUX
1. Apply power to the D5060 and connect the
programmer to the D8125MUX only.
2. Enter the address of the point you want to remove.
3. When prompted for a point type, press [0]. Refer
to Table 4. Then press [#].
4. Press [1] to remove the point.
5. If the point is programmed correctly, the D5060
beeps once and Adr appears.
8 Bosch Security Systems, Inc. | 12/15 | F01U034973-03
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
.
4.2.4 Interrogation Mode
You can also use the programmer to read information
from the D8125MUX and multiplex points. Refer to
Section 4.1 Connecting the D5060 Programmer on page
6 to install the D5060.
4.2.4.1 Reading Information from the D8125MUX
1. To enter Interrogation Mode, press and hold [7]
and [9] simultaneously until the unit beeps.
2. The LED marked INTERROGATION MODE lights.
A.dr appears prompting you to enter a starting
address.
3. Enter an address followed by [#]. The
Interrogation LED flashes.
4. Press [#] to read point information from the
D8125MUX at that address.
5. Press [4] to read the previous address information
from the D8125MUX.
6. Press [6] to read the next address information
from the D8125MUX.
If communication between the unit and
the D8125MUX fails, the unit sounds a
three-beep error tone and shows PnL.
7. Exit Interrogation Mode by pressing and holding
[*] until the unit beeps.
4.2.4.2 Reading Information from MUX Points
Disconnect all multiplex points from the
D8125MUX and the multiplex bus before
reading multiplex point information.
1. To enter Interrogation Mode, press and hold [7]
and [9] simultaneously until the unit beeps. The
LED marked INTERROGATION MODE lights.
2. The display reads A.dr prompting you to enter a
starting address. Enter an address and press [#].
3. Press [1].
4. When t.YP appears at the keypad, enter the point
type of the multiplex point as shown in Table 4 on
page 8 and press [#].
5. If a point responds to the address, the
programmer beeps once and rSP appears. If the
point does not respond, the unit beeps three times
and the display reads noP.
6. Exit Interrogation Mode by pressing and holding
[*] until the unit beeps.
4.3 Wiring the D8125MUX to
Multiplex Points
Do not use shielded or twisted pair cable.
1. Connect Power A+ and Power A- on the D8125MUX
to multiplex devices that require uninterrupted
auxiliary power. Refer to Figure 8 on page 9. Up to
200 mA is available at these terminals.
2. Connect MUX BUS A+ and A- on the D8125MUX to
the positive and negative bus wires of the
multiplex points. The maximum allowable current
on MUX BUS A is 75 mA.
3.
Remove power from the D8125MUX before
connecting or disconnecting multiplex
Figure 8: Wiring the D8125MUX to Detection
1 - To Loop B BUS –
2 - To Loop B BUS +
3 - To Loop B Power –
4 - To Loop B Power +
devices. Connecting or disconnecting a
multiplex device while the D8125MUX is
powered could cause the multiplex device
address setting to reprogram or scramble.
Systems Multiplex Points
D8125MUX
MUX BUS A
POWER A
+-+-+-+-
56
MUX BUS B
POWER B
1
3
8
7
5 - To Loop A BUS –
6 - To Loop A BUS +
7 - To Loop A Power –
8 - To Loop A Power +
2
4
Bosch Security Systems, Inc. | 12/15 | F01U034973-03
9
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.