Point Type Configuration ........................ 21
2 Bosch Security Systems, Inc. | 12/15 | F01U034973-03
D8125MUX | Installation and Operation Guide | 1.0 Introduction
.
1.0 Introduction
1.1 Description
Use the D8125MUX Multiplex Bus Interface Module to
connect multiplex points to the ZONEX bus on the
following Bosch Security Systems control panels: new
G Series (B9512G, B9512G-E, B8512G, B8512G-E),
G Series (D9412GV4, D7412GV4, D7212GV4,
D9412GV3, D7412GV3, D7212GV3, D9412GV2,
D7412GV2, D7212GV2, D9412G, D7412G, D7212G),
D9412, D7412, D7212, D9112, and D9124 with version
5.22 or greater firmware. Install the D8125MUX on
ZONEX 1 and ZONEX 2 (G Series, D9412, and D9112
only). The multiplex bus interface supports two
independent multiplex buses; therefore, a fault on one
multiplex bus does not prevent the other from
operating normally.
The D8125MUX scans the multiplex points connected
to it and reports the point status to the control panel.
Also available on the D8125MUX are auxiliary power
terminals labeled Power A (+,-), Power B (+,-) that
support remote devices requiring an uninterrupted
source of power.
The B600 Retrofit (ZONEX) module is
required to use the D8125MUX on the
See the Control Panel Approved Applications Compliance Guide or the Installation and System Reference Guide to
determine the required equipment and enclosures for
the application.
B9512G, B9512G-E, B8512G, and
B8512G-E control panels.
1.2 Listings
The D8125MUX is UL Listed as a subassembly in the
following categories:
US
UL 864 Control Units, System
(UOJZ)
UL1023 Household Burglar Alarm
Systems (NBSX)
UL1610 Central Station Alarm
Units (AMCX)
UL609 Local Alarm Units (AOTX)
UL365 Police Station Connect
Alarm Units (APAW)
UL1076 Proprietary Alarm Units
(APOU)
UL 985 Household Fire Warning
System Units
CA
ULC S303 Local Burglar Alarm Units
and Systems
ULC/ORD-C1076 Proprietary Burglar Alarm
Units and Systems
ULC/ORD-C1023 Household Burglar Alarm
System Units
The D7212GV2 and D7212G are not UL
Listed for UL 864 commercial fire
applications.
1.3 Specifications
Table 1: Specifications
Bosch Security Systems, Inc. | 12/15 | F01U034973-03
Operating Voltage Nominal 12 VDC
Current Requirements D8125MUX only: 140 mA
Maximum Current
678 mA
Draw (using both MUX
bus outputs and both
power outputs)
Operating Temperature +32°F to +120°F (0°C to
+49°C)
Relative Humidity 0 to 93%
Dimensions (H x W x
D)
1.0 in. x 3.25 in. x 5.5 in.
(25 mm x 8.3 cm x 14.0
cm)
3
D8125MUX | Installation and Operation Guide | 2.0 Operation
d
n
M
2.0 Operation
The D8125MUX indicates its status using the green
Operation LED (Figure 1). Refer to Table 2 for a
description of the Operation LED.
Figure 1: D8125MUX Multiplex Bus Interface
Module
1
RESET
12V IN OUT GND
ZONEX BUS
1 - Operation LED
Table 2: Operation LED Descriptions
FIRE MANUAL
WALK TEST
PROG
+- +- + - +-
PORT
POWER A
MUX BUS A
POWER B
MUX BUS B
3.0 Installation
The D8125MUX is installed in the control panel
enclosure and is connected to either ZONEX 1 or
ZONEX 2 on the control panel or the B600 Retrofit
(ZONEX) module.
3.1 Installing the enclosure
Follow the procedure below to install the D8125MUX
in the enclosure with the control panel or B600.
1. Align the D8125MUX module with any of the four
mounting locations in the enclosure. See Figure 2.
2. Use the screws provided with the module to
secure it in the enclosure.
Figure 2: Installation diagram
Horizontal Mounting
Locations
LED Status Meaning
Flashing 1/2
Indicates normal operation.
second on, 1/2
second off
Off A module fault is indicated.
Refer to Section 6.0
Troubleshooting on page 25.
On The Multiplex Point
Programmer is connected to
the D8125MUX.
Double flash Reset the D8125MUX EEPROM
with the reset pin by plugging
in the D5060 Programmer and
placing the shorting bar over
the reset pin. The LED rapidly
flashes twice followed by a
pause.
Vertical
Mounting
Locations
(Reserve
Dual Pho
Switcher
4 Bosch Security Systems, Inc. | 12/15 | F01U034973-03
D8125MUX | Installation and Operation Guide | 3.0 Installation
.
3.2 Wiring to the control panel
Follow the procedure below to wire one or two
D8125MUX modules to the 9000 Series, and G Series
control panels. For the B9512G, B9512G-E, B8512G,
B8512G-E control panels, see the Control Panels
Installation and System Reference Guide.
The B600 Retrofit (ZONEX) module is
required to use the D8125MUX on the
3.2.1 Disconnecting the Battery and Transformer
1. Disconnect the battery by unhooking the positive
2. Unplug the transformer.
B9512G, B9512G-E, B8512G, and
B8512G-E control panels.
Remove all power (AC and Battery) before
making any connections. Failure to do so
may result in personal injury and/or
equipment damage.
(red) battery lead from the battery.
3.2.2 Wiring Procedure
For Points 9 up to Point 127:
1. Connect the GND terminal of the D8125MUX to the
control panel ZONEX COMMON terminal.
2. Connect the OUT terminal of the D8125MUX
module to ZONEX IN 1.
3. Connect the IN terminal of the D8125MUX module
to ZONEX OUT 1.
4. Connect the AUX terminal of the D8125MUX to
ZONEX POWER + terminal.
For Points 129 up to Point 247:
1. Connect the GND terminal of the D8125MUX to the
control panel ZONEX COMMON terminal.
2. Connect the OUT terminal of the D8125MUX
module to ZONEX IN 2.
3. Connect the IN terminal of the D8125MUX module
to ZONEX OUT 2.
4. Connect the AUX terminal of the D8125MUX to
ZONEX POWER + terminal.
Do not connect more than one D8125MUX to ZONEX 1
(IN and OUT terminals) or ZONEX 2 (IN and OUT
terminals).
Reversed polarity damages the D8125MUX.
Make sure you wire the D8125MUX AUX
and GND terminals to the control panel.
Figure 3: D8125MUX Wiring Diagram
PERIPHERAL DEVICE CONNECTIONS
POWER +
RED
A BUS A
T
A
D
YELLOW
GREEN DATA BUS B
BLACKCOMMON
P.A.
F.
N.
ZONEX OUT 1
Style 3.5
Signaling
Line
Circuits
ZONEX IN 1
ZONEX OUT 2
ZONEX IN 2
ZONEX POWER +
ZONEX COMMON
Point 8
GND F
Detect
E
N
A
B
L
E
PROG
CONN
LT
AU
D
I
S
A
Operation Monitor
B
Pulses When Normal
L
GRN
Flickers When Ringing
E
4
12
RESET
12V IN OUT GND
ZONEX BUS
FIRE MANUAL
PROG
+- +- + - +-
PORT
POWER A
WALK TEST
MUX BUS A
POWER B
MUX BUS B
RESET
12V IN OUT GND
ZONEX BUS
FIRE MANUAL
PROG
+- +- + - +-
PORT
POWER A
WALK TEST
3
MUX BUS A
POWER B
MUX BUS B
1 - D8125MUX on ZONEX 1
2 - D8125MUX on ZONEX 2
Bosch Security Systems, Inc. | 12/15 | F01U034973-03
3 - ZONEX Common Terminal
4 - Supervised, Power Limited.
5
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
4.0 Program Multiplex Bus
Points
Use the D5060 Programmer (Figure 4 and Table 3) to
program multiplex bus points for the B9512G,
B9512G-E, B8512G, B8512G-E, D9412GV4, D7412GV4,
D7212GV4, D9412GV3, D7412GV3, D7212GV3,
D9412GV2, D7412GV2, D7212GV2, D9412G, D7412G,
D7212G, D9412, D7412, D7212, and D9112 control
panels. In addition to programming points, the D5060
can also be used to program and read information
from a D8125MUX.
The B600 Retrofit (ZONEX) module is
required to use the D8125MUX on the
B9512G, B9512G-E, B8512G, and
B8512G-E control panels.
Table 3: D5060 LED Definitions
Display Definition
Adr Enter address.
A.dr Enter address for Interrogation Mode.
bAd Battery voltage is below 15 V.
Err Point was not programmed correctly.
Lob Battery voltage is below 16 V.
noP No response from point.
PnL Communications with the D8125 failed.
rSP Point responds to address.
tYP Enter point type.
t.YP Enter point type for Interrogation Mode
4.1 Connecting the D5060
Figure 4: D5060 Multiplex Point Programmer
EXT.
POWER
INTERROGATION MODE
YESNO
DOWN
MULTIPLEX POINT PROGRAMMER
SERIAL PORTMUX
ON
(HOLD)
3
2
1
456
0
OFF
(HOLD)
(HOLD)
9
#
ENTER
78
*
CLEAR
INTERROGATE
POINTS
UP
1. When using external power, attach the flying leads
2. Use the serial cable provided to connect the
3. For multiplex devices without DIP switches, use
Programmer
of the included power cable to the output
terminals of a 16.5 VAC transformer. Insert the
plug end into the jack labeled EXT. POWER on the
programmer. Refer to Figure 5, Figure 6, and
Figure 7.
D8125MUX to the jack labeled SERIAL PORT on
the programmer.
the multiplex programmer cable provided to
connect the point to be programmed to the port
labeled MUX POINTS as shown in Figure 5. Use the
appropriate connector, either the alligator clips or
the probes, to connect the programmer to a point.
For multiplex points with programmable DIP
switches, program the point using the DIP
switches. Connect the programmer to the
D8125MUX as shown in Figure 6.
6 Bosch Security Systems, Inc. | 12/15 | F01U034973-03
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
.
Figure 5: Installing Multiplex Points without
DIP Switches Wiring Diagram
3
1
12V IN OUT GND
ZONEX BUS
EXT.
POWER
INTERROGATION MODE
RESET
FIRE MAN UAL
PROG
PORT
WALK TEST
SERIAL PORTMUX
2
+-+-+ -+-
POWER A MUX BUS A
POWER B
MUX BUS B
POINTS
4
1 - External power
2 - D8125MUX
3 - Multiplex point without DIP switches
(non-i models)
4 - D5060 Multiplex Point Programmer
Figure 7: Programmer Cables (included)
1
2
3
1 - C310 Serial Cable
2 - C319 External Power Supply Cable
3 - C320 Multiplex Programmer Cable
Figure 6: Installing Multiplex Points with DIP
Switches Wiring Diagram
1
12V IN OUT GND
EXT.
POWER
INTERROGATION MODE
RESET
FIRE MANUAL
ZONEX BUS
WALK TEST
SERIAL PORTMUX
2
PROG
+-+- +- +-
PORT
POWER A MUX BUS A
POWER B
POINTS
MUX BUS B
3
1 - External power
2 - D8125MUX
3 - D5060 Multiplex Point Programmer
Bosch Security Systems, Inc. | 12/15 | F01U034973-03
7
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
4.2 Programming
Table 4: Point Type Entry Code
4.2.1 Powering the D5060
Turn on the D5060 by pressing and holding the [1] key
until the unit beeps. To turn the unit off, press and
hold the [#] and [*] keys simultaneously until the unit
beeps.
After 5 minutes of inactivity, the
programmer powers down automatically
to conserve power.
4.2.2 Programming Points
1. The D5060 shows the prompt Adr after it is
powered. This indicates that it is ready to begin
programming.
2. If the multiplex device has no DIP switches,
connect the D5060 to the point to be programmed
as shown in Figure 5 on page 7. If the multiplex
device has DIP switches, program the device using
its DIP switches.
If the multiplex device has no DIP
switches, connect the D8125MUX and the
multiplex device to be programmed to the
D5060 for simultaneous programming
(Figure 5). If the multiplex device has DIP
switches, program the device using its DIP
switches, and program the D8125MUX
using the D5060 (Figure 6 on page 7).
3. Enter the point’s three-digit address. The address
must be between 1 and 255. Press [#].
The programmer shows tyP.
4. Enter the number corresponding to the point type
you are programming as shown in Table 4 and
press [#]. The programmer alternately shows the
address and the point type.
When you program for a multiplex smoke
device by entering decimal value 4 or 5
Table 4, an 18-second timer starts
counting. Do not disconnect the multiplex
smoke device until after the timer counts
down to zero.
Decimal
Point Type
Value
0 Remove point from D8125MUX
1 Contact
2 Sensor (or single point module)
3 I/O module
4 Multiplex smoke without low
temperature
5 Multiplex smoke with low temperature
(0°C)
6 Dual point
5. Press [#] to program a point connected to the
D5060 and the D8125MUX (if connected), or press
[1] to program the D8125MUX only. If the
multiplex device has DIP switches, program the
device using its DIP switches.
Press [*] at any time to return to a
previous step in the procedure.
6. If the point is programmed correctly, the unit
beeps once and shows Adr, indicating it is ready to
program the next point. If the point was not
programmed correctly, the unit sounds a threebeep error tone and one of the following messages
appears:
Err: The point was not programmed correctly.
PnL: Communications with the D8125MUX failed.
7. Press [*] to clear the entry, or press [#] to
reprogram.
If programming the D8125MUX and multiplex
device simultaneously and only one receives the
program, the D5060 shows Adr. If having troubles
with the point after installation, try programming
the D8125MUX and multiplex devices separately.
4.2.3 Removing a Point from the D8125MUX
1. Apply power to the D5060 and connect the
programmer to the D8125MUX only.
2. Enter the address of the point you want to remove.
3. When prompted for a point type, press [0]. Refer
to Table 4. Then press [#].
4. Press [1] to remove the point.
5. If the point is programmed correctly, the D5060
beeps once and Adr appears.
8 Bosch Security Systems, Inc. | 12/15 | F01U034973-03
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
.
4.2.4 Interrogation Mode
You can also use the programmer to read information
from the D8125MUX and multiplex points. Refer to
Section 4.1 Connecting the D5060 Programmer on page
6 to install the D5060.
4.2.4.1 Reading Information from the D8125MUX
1. To enter Interrogation Mode, press and hold [7]
and [9] simultaneously until the unit beeps.
2. The LED marked INTERROGATION MODE lights.
A.dr appears prompting you to enter a starting
address.
3. Enter an address followed by [#]. The
Interrogation LED flashes.
4. Press [#] to read point information from the
D8125MUX at that address.
5. Press [4] to read the previous address information
from the D8125MUX.
6. Press [6] to read the next address information
from the D8125MUX.
If communication between the unit and
the D8125MUX fails, the unit sounds a
three-beep error tone and shows PnL.
7. Exit Interrogation Mode by pressing and holding
[*] until the unit beeps.
4.2.4.2 Reading Information from MUX Points
Disconnect all multiplex points from the
D8125MUX and the multiplex bus before
reading multiplex point information.
1. To enter Interrogation Mode, press and hold [7]
and [9] simultaneously until the unit beeps. The
LED marked INTERROGATION MODE lights.
2. The display reads A.dr prompting you to enter a
starting address. Enter an address and press [#].
3. Press [1].
4. When t.YP appears at the keypad, enter the point
type of the multiplex point as shown in Table 4 on
page 8 and press [#].
5. If a point responds to the address, the
programmer beeps once and rSP appears. If the
point does not respond, the unit beeps three times
and the display reads noP.
6. Exit Interrogation Mode by pressing and holding
[*] until the unit beeps.
4.3 Wiring the D8125MUX to
Multiplex Points
Do not use shielded or twisted pair cable.
1. Connect Power A+ and Power A- on the D8125MUX
to multiplex devices that require uninterrupted
auxiliary power. Refer to Figure 8 on page 9. Up to
200 mA is available at these terminals.
2. Connect MUX BUS A+ and A- on the D8125MUX to
the positive and negative bus wires of the
multiplex points. The maximum allowable current
on MUX BUS A is 75 mA.
3.
Remove power from the D8125MUX before
connecting or disconnecting multiplex
Figure 8: Wiring the D8125MUX to Detection
1 - To Loop B BUS –
2 - To Loop B BUS +
3 - To Loop B Power –
4 - To Loop B Power +
devices. Connecting or disconnecting a
multiplex device while the D8125MUX is
powered could cause the multiplex device
address setting to reprogram or scramble.
Systems Multiplex Points
D8125MUX
MUX BUS A
POWER A
+-+-+-+-
56
MUX BUS B
POWER B
1
3
8
7
5 - To Loop A BUS –
6 - To Loop A BUS +
7 - To Loop A Power –
8 - To Loop A Power +
2
4
Bosch Security Systems, Inc. | 12/15 | F01U034973-03
9
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
4.4 Using Power B and MUX BUS B
Table 6: Control Panel to D8125MUX Distance
(Optional)
It might be necessary to use the Power B (+, -) and
MUX BUS B (+, -) terminals for isolation purposes. For
example, an Authority Having Jurisdiction (AHJ) might
require that fire points and burglar points be on
independent buses.
1. Connect Power B+ and Power B- on the
D8125MUX to multiplex devices that require
uninterrupted auxiliary power. Up to 200 mA is
available at these terminals.
2. Connect MUX BUS B + and B - on the D8125MUX
to the positive and negative bus wires of the
multiplex points. The maximum allowable current
on MUX BUS B is 75 mA.
Maximum Impedance: 4.0 Ω at +68°F (+20°C)
nominal
Maximum Distance Size
250 ft 22 AWG
600 ft 18 AWG
76 m 0.65 mm
193 m 1.02 mm
Fire applications require 18 AWG.
Figure 9: Wiring Multiplex Devices to MUX Bus
D8125MUX
4.5 Wiring Multiplex Devices to the
Multiplex Bus
Use one two-wire data expansion loop using MUX BUS
A, or distribute the devices on both MUX BUS A and B.
Table 5 shows the maximum distance per MUX bus
output - each D8125MUX has two multiplex bus
outputs. Table 6 shows the maximum distance
between the control panel and the D8125MUX.
Determine the required wire gauge for each multiplex
bus expansion loop (Table 5). Programming the
individual multiplex points with the D5060 assigns
them to point numbers. Daisy chain and T-tapping
configurations are acceptable. Refer to Figure 9.
Table 5: D8125MUX Line Length
MUX BUS A
Maximum Wire Impedance: 33 Ω
AWG (mm) Length in Ft (m)
22 (0.8 mm) 2000 (610)*
18 (1.2 mm) 5000 (1524)*
MUX BUS B
Maximum Wire Impedance: 33 Ω
AWG (mm) Length in Ft (m)
22 (0.8 mm) 2000 (610)*
18 (1.2 mm) 5000 (1524)*
* Current requirements for multiplex points vary. The
maximum allowable distance you can locate remote
points might be reduced. Do not exceed 75 mA
maximum on each MUX bus output.
D8125MUX
1 - Multiplex device
1
1
10 Bosch Security Systems, Inc. | 12/15 | F01U034973-03
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
.
4.6 Installing a Multiplex Device
4.6.1 Adding Multiplex Devices to the Control
Panel
As shown in Table 7, several types of multiplex devices
are available. Each multiplex accessory device is
packaged with instructions connecting to the multiplex
bus output.
Table 7: Multiplex Devices
Product Point Type
DS7432 Eight Input Remote Module 6
DS7450 Flush Mount Single Multiplex
1
Contact Point
DS7452 Surface Mount Single
1
Multiplex Contact Point
DS7457 Single Multiplex Input Module 2
DS7460 Dual Zone Input Module 6
DS7465 Input/Output Module 3
MX775 (DS7470) Multiplex PIR
2
Intrusion Detector – 50 ft (15 m)
Mirror
MX934 (DS7471) Multiplex PIR
2
Intrusion Detector – 35 ft (11 m)
Mirror
MX938 (DS7472) Ceiling Mount
2
Multiplex PIR Intrusion Detector
MX540 (DS7473) Multiplex PIR
2
Intrusion Detector – 40 ft (12 m)
Fresnel Lens
MX794 (DS7474) Multiplex Long
2
Range PIR Intrusion Detector
MX950 (DS7476) Multiplex
2
PIR/Microwave TriTech Intrusion
Detector
MX835 (DS7477) Multiplex
2
PIR/Microwave TriTech Intrusion
Detector with Pet Immunity
MX250 Photoelectric Smoke or Photo
4
Off board points for G Series, D9124, D9412, and
D9112 are numbered 9 through 127 and 129 through
247 (G Series, D7412, and D7212 use off board Points
9 through 75 only; G Series use off board Points 9
through 40 only). G Series, D9412, and D9112 reserves
Points 128 and 248 for internal use. The D8125MUX
connected to ZONEX 1 monitors Points 9 through 127,
whereas the D8125MUX connected to ZONEX 2
monitors Points 129 through 247.
The D8125MUX and multiplex points
connected to ZONEX 2 must be
programmed in the D8125MUX with DIP
switches as Points 9 through 127. Refer to
Table 8 on page 12.
4.6.2 Removing Multiplex Devices from the
Control Panel
To remove a multiplex device from the system:
1. Connect the device to the D5060.
2. Enter the address.
3. Enter 0 for the point type.
Ensure that the D8125MUX is not powered
before connecting or disconnecting
multiplex devices. Connecting or
disconnecting a multiplex device while the
D8125MUX is powered causes the
multiplex device address setting to
reprogram or scramble.
After any programming or hardware
change, do a functional test of the system
as required by local codes.
with Heat Detector and MXB2W Base
D7050/D7050TH Photoelectric or
4
Photo with Heat Detector and D7050B6 Base Lot #249 and greater
Bosch Security Systems, Inc. | 12/15 | F01U034973-03
11
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
Table 8: Point Conversion Table
If ZONEX
2 Pt. # is
Program
as
If ZONEX
2 Pt. # is
Program
as
If ZONEX
2 Pt. # is
Program
as
If ZONEX
2 Pt. # is
Program
as
If ZONEX
2 Pt. # is
Program
as
129 9 153 33 177 57 201 81 225 105
130 10 154 34 178 58 202 82 226 106
131 11 155 35 179 59 203 83 227 107
132 12 156 36 180 60 204 84 228 108
133 13 157 37 181 61 205 85 229 109
134 14 158 38 182 62 206 86 230 110
135 15 159 39 183 63 207 87 231 111
136 16 160 40 184 64 208 88 232 112
137 17 161 41 185 65 209 89 233 113
138 18 162 42 186 66 210 90 234 114
139 19 163 43 187 67 211 91 235 115
140 20 164 44 188 68 212 92 236 116
141 21 165 45 189 69 213 93 237 117
142 22 166 46 190 70 214 94 238 118
143 23 167 47 191 71 215 95 239 119
144 24 168 48 192 72 216 96 240 120
145 25 169 49 193 73 217 97 241 121
146 26 170 50 194 74 218 98 242 122
147 27 171 51 195 75 219 99 243 123
148 28 172 52 196 76 220 100 244 124
149 29 173 53 197 77 221 101 245 125
150 30 174 54 198 78 222 102 246 126
151 31 175 55 199 79 223 103 247 127
152 32 176 56 200 80 224 104
12 Bosch Security Systems, Inc. | 12/15 | F01U034973-03
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
.
4.7 Point Matrix Tables
Only use one D8125MUX per ZONEX output. Refer to Table 9 beginning on page 14 for ZONEX 1. Refer to Table
10 beginning on page 17 for ZONEX 2
If configuring the system with DS7457i, DS7461i, or DS7465i MUX devices. Refer to Table 11 on page 19 if
configuring the system with the DS7460iMUX device.
The type of multiplex device used determines the quantity of devices you can connect to the D8125MUX. Do not
program two multiplex points to the same point number. After programming all the points, perform a Service
Walk Test. Refer to the control panel’s operation and installation guide for information on the Service Walk Test.
If a multiplex point is not functioning, check for duplicate addresses.
Two sheets of peel-off labels are supplied with the D8125MUX. Each label has two parts. Place the smaller part
(with the point number) on the multiplex point. Throw away the larger part. Use the sheet marked Bank 1 for
Points 9 through 127 and the sheet marked Bank 2 for Points 129 through 247. G Series, and D7212 Control
Panels use the sheet marked Bank 1.
Bosch Security Systems, Inc. | 12/15 | F01U034973-03
13
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
Table 9: DS7457i, DS7461i, and DS7465i
Switch Settings When Using
D8125MUX on ZONEX 1
Point
(Relay)
Address
1 2 3 4 5 6 7 8
009 ••
010 ••
011 •••
012 ••
013 • ••
014 •••
015 • • • •
016 •
017 • •
018 ••
019 • • •
020 ••
021 • • •
022 •••
023 • • • •
024 ••
025 • • •
026 •••
027 • • • •
028 •••
029 • • • •
030 ••••
031 • • • • •
032 •
033 • •
034 ••
035 •••
036 ••
Note: When using the DS7465i Input/Output Module, only
Addresses 009 through 064 support the relay option
(009 through 024 on the D7212GV2 and D7212G).
Switch Number (• = ON)
Table 9: DS7457i, DS7461i, and DS7465i
Switch Settings When Using
D8125MUX on ZONEX 1 (continued)
Point
(Relay)
Address
1 2 3 4 5 6 7 8
037 • • •
038 •••
039 • • • •
040 ••
Maximum Number of Points (D7212G)
041 • • •
042 •••
043 • • • •
044 •••
045 • • • •
046 ••••
047 • • • • •
048 ••
049 • • •
050 •••
051 • • • •
052 •••
053 • • • •
054 ••••
055 • • • • •
056 •••
057 • • • •
058 ••••
059 • • • • •
060 ••••
61 • • • • •
062 •••••
063 • • • • • •
064 •
Note: When using the DS7465i Input/Output Module, only
Addresses 009 through 064 support the relay option
(009 through 024 on the D7212GV2 and D7212G).
Switch Number (• = ON)
14 Bosch Security Systems, Inc. | 12/15 | F01U034973-03
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
.
Table 9: DS7457i, DS7461i, and DS7465i
Switch Settings When Using
D8125MUX on ZONEX 1 (continued)
Point
(Relay)
Address
1 2 3 4 5 6 7 8
065 • •
066 ••
067 • ••
068 ••
069 • • •
070 •••
071 • • • •
072 ••
073 • • •
074 •••
075 • • • •
Maximum for D7412G, D7412, and D7212
076 •••
077 • • • •
078 ••••
079 • • • • •
080 ••
081 • • •
082 •••
083 • • • •
084 •••
085 • • • •
086 ••••
087 • • • • •
088 •••
089 • • • •
090 ••••
091 • • • • •
092 ••••
Note: When using the DS7465i Input/Output Module,
only Addresses 009 through 064 support the relay
option (009 through 024 on the D7212GV2 and
D7212G).
Switch Number (• = ON)
Maximum for DS7465i
Table 9: DS7457i, DS7461i, and DS7465i
Switch Settings When Using
D8125MUX on ZONEX 1 (continued)
Point
(Relay)
Address
1 2 3 4 5 6 7 8
083 • • • •
084 •••
085 • • • •
086 ••••
087 • • • • •
088 •••
089 • • • •
090 ••••
091 • • • • •
092 ••••
093 • • • • •
094 •••••
095 • • • • • •
096 ••
097 • • •
098 •••
099 • • • •
100 •••
101 • • • •
102 ••••
103 • • • • •
104 •••
105 • • • •
106 ••••
107 • • • • •
108 ••••
109 • • • • •
110 •••••
Note: When using the DS7465i Input/Output Module,
only Addresses 009 through 064 support the relay
option (009 through 024 on the D7212GV2 and
D7212G).
Switch Number (• = ON)
Bosch Security Systems, Inc. | 12/15 | F01U034973-03
15
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
Table 9: DS7457i, DS7461i, and DS7465i
Switch Settings When Using
D8125MUX on ZONEX 1 (continued)
Point
(Relay)
Address
1 2 3 4 5 6 7 8
111 • • • • • •
112 •••
113 • • • •
114 ••••
115 • • • • •
116 ••••
117 • • • • •
118 •••••
119 • • • • • •
120 ••••
121 • • • • •
122 •••••
123 • • • • • •
124 •••••
125 • • • • • •
126 ••••••
127 • • • • • • •
128 NOT USED
Note: When using the DS7465i Input/Output Module,
only Addresses 009 through 064 support the relay
option (009 through 024 on the D7212GV2 and
D7212G).
Switch Number (• = ON)
16 Bosch Security Systems, Inc. | 12/15 | F01U034973-03
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
.
Table 10: DS7457i, DS7461i, and DS7465i
Switch Settings When Using
D8125MUX on ZONEX 2
Zone
(Point)
Address
1 2 3 4 5 6 7 8
129 ••
130 ••
131 •••
132 ••
133 • ••
134 •••
135 • • • •
136 •
137 • •
138 ••
139 • • •
140 ••
141 • • •
142 •••
143 • • • •
144 ••
145 • • •
146 •••
147 • • • •
148 •••
149 • • • •
150 ••••
151 • • • • •
152 •
153 • •
154 ••
155 • • •
156 ••
157 • • •
158 •••
Switch Number (• = ON)
Table 10: DS7457i, DS7461i, and DS7465i
Switch Settings When Using
D8125MUX on ZONEX 2 (continued)
Zone
(Point)
Address
1 2 3 4 5 6 7 8
159 • • • •
160 ••
161 • • •
162 •••
163 • • • •
164 •••
165 • • • •
166 ••••
167 • • • • •
168 ••
169 • • •
170 •••
171 • • • •
172 •••
173 • • • •
174 ••••
175 • • • • •
176 •••
177 • • • •
178 ••••
179 • • • • •
180 ••••
181 • • • • •
182 •••••
183 • • • • • •
184 •
185 • •
186 ••
187 • ••
188 ••
Switch Number (• = ON)
Bosch Security Systems, Inc. | 12/15 | F01U034973-03
17
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
Table 10: DS7457i, DS7461i, and DS7465i
Switch Settings When Using
D8125MUX on ZONEX 2 (continued)
Zone
(Point)
Address
1 2 3 4 5 6 7 8
189 • ••
190 •••
191 • •••
192 ••
197 • • • •
198 ••••
199 • • • • •
200 ••
201 • • •
202 •••
203 • • • •
204 •••
205 • • • •
206 ••••
207 • • • • •
208 •••
209 • • • •
210 ••••
211 • • • • •
212 ••••
213 • • • • •
214 •••••
215 • • • • • •
216 ••
217 • • •
218 •••
219 • • • •
220 •••
221 • • • •
222 ••••
Switch Number (• = ON)
Table 10: DS7457i, DS7461i, and DS7465i
Switch Settings When Using
D8125MUX on ZONEX 2 (continued)
Zone
(Point)
Address
1 2 3 4 5 6 7 8
223 • • • • •
224 •••
225 • • • •
226 ••••
227 • • • • •
228 ••••
229 • • • • •
230 •••••
231 • • • • • •
232 •••
233 • • • •
234 ••••
235 • • • • •
236 ••••
237 • • • • •
238 •••••
239 • • • • • •
240 ••••
241 • • • • •
242 •••••
243 • • • • • •
244 •••••
245 • • • • • •
246 ••••••
247 • • • • • • •
248 NOT USED
Switch Number (• = ON)
18 Bosch Security Systems, Inc. | 12/15 | F01U034973-03
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
.
Table 11: DS7460i Switch Settings When Using
D8125MUX
Address
Zone/Relay
1 2 3 4 5 6 7 8
009/010 ••
011/012 •••
013/014 • ••
015/016 ••••
017/018 ••
019/020 •••
021/022 •••
023/024 ••••
025/026 • ••
027/028 ••••
029/030 • • ••
031/032 •••••
033/034 ••
035/036 •••
037/038 •••
039/040 ••••
041/042 •••
043/044 ••••
045/046 ••••
047/048 •••••
049/050 • ••
051/052 ••••
053/054 • •••
055/056 •••••
057/058 • • ••
059/060 •••••
Switch Number (• = ON)
Table 11: DS7460i Switch Settings When Using
D8125MUX (continued)
Address
Zone/Relay
1 2 3 4 5 6 7 8
061/062 • • • ••
063/064 ••••••
065/066 ••
067/068 •••
069/070 •••
071/072 ••••
073/074 •••
075/076 ••••
077/078 ••••
079/080 •••••
081/082 •••
083/084 ••••
085/086 ••••
087/088 •••••
089/090 ••••
091/092 •••••
093/094 •••••
095/096 ••••••
097/098 • ••
099/100 ••••
101/102 • •••
103/104 •••••
105/106 • •••
107/108 •••••
109/110 • ••••
111/112 ••••••
113/114 • • ••
115/116 •••••
117/118 • • •••
119/120 ••••••
121/122 • • • ••
123/124 ••••••
Switch Number (• = ON)
Bosch Security Systems, Inc. | 12/15 | F01U034973-03
19
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
Table 11: DS7460i Switch Settings When Using
D8125MUX (continued)
Address
Zone/Relay
1 2 3 4 5 6 7 8
125/126 • • • • ••
127/128 NOT USED
129/130 ••
131/132 •••
133/134 • ••
135/136 ••••
137/138 ••
139/140 •••
141/142 •••
143/144 ••••
145/146 • ••
147/148 ••••
149/150 • • ••
151/152 •••••
153/154 ••
155/156 •••
157/158 •••
159/160 ••••
161/162 •••
163/164 ••••
165/166 ••••
167/168 •••••
169/170 • ••
171/172 ••••
173/174 • •••
175/176 •••••
177/178 • • ••
179/180 •••••
181/182 • • • ••
183/184 ••••••
185/186 ••
187/188 •••
Switch Number (• = ON)
Table 11: DS7460i Switch Settings When Using
D8125MUX (continued)
Address
Zone/Relay
1 2 3 4 5 6 7 8
189/190 •••
191/192 ••••
193/194 •••
195/196 ••••
197/198 ••••
199/200 •••••
201/202 •••
203/204 ••••
205/206 ••••
207/208 •••••
209/210 ••••
211/212 •••••
213/214 •••••
215/216 ••••••
217/218 • ••
219/220 ••••
221/222 • •••
223/224 •••••
225/226 • •••
227/228 •••••
229/230 • ••••
231/232 ••••••
233/234 • • ••
235/236 •••••
237/238 • • •••
239/240 ••••••
241/242 • • • ••
243/244 ••••••
245/246 • • • • ••
247/248 NOT USED
Switch Number (• = ON)
20 Bosch Security Systems, Inc. | 12/15 | F01U034973-03
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
.
4.8 Single Input Multiplex Devices
The devices listed in Table 12 reserve a single point on
the MUX bus. Single Input Multiplex points can be
programmed as Points 9 through 127 (ZONEX 1) and
129 through 247 (ZONEX 2) (238 devices) on G Series,
D9412, and D9112; Points 9 through 75 (67 devices)
on G Series, D7412, and D7212; Points 9 through 40
on G Series (32 devices). When programming the point
type for Single Input Multiplex points using a D5060
Programmer, refer to Table 12 for information on how
to configure the point type. Tamper conditions on
multiplex points are treated as Missing conditions by
the control panel.
Table 12: Single Input Multiplex Device Point
Response Configuration
Device Type Point
Type
DS7450 Flush Mount Single
1 NO
Multiplex Contact Point
DS7452 Surface Mount
1 NO
Single Multiplex Contact
Point
DS7457 Single Multiplex
2 Configurable
Input Module
MX775 (DS7470) Multiplex
2 NO
PIR Intrusion Detector - 50
ft (15 m) Mirror
MX934 (DS7471) Multiplex
2 NO
PIR Intrusion Detector - 35
ft (11 m) Mirror
MX938 (DS7472) Ceiling
2 NO
Mount Multiplex PIR
Intrusion Detector
MX540 (DS7473) Multiplex
2 NO
PIR Intrusion Detector - 40
ft. (12 m) Fresnel Lens
MX794 (DS7474) Multiplex
2 NO
Long Range PIR Intrusion
Detector
MX950 (DS7476) Multiplex
2 NO
PIR/Microwave TriTech
Intrusion Detector
MX835 (DS7477) Multiplex
2 NO
PIR/Microwave TriTech
Intrusion Detector with Pet
Immunity
Point
Response
(NO or NC)
4.9 MX250 Photoelectric Smoke
Detectors and MXB2W Base or
D7050 Photoelectric Smoke
Detector and D7050-B6 Base
The MX250 and MX250TH Photoelectric Smoke
Detectors with MXB2W Base or D7050 and D7050TH
Photoelectric Smoke Detectors and D7050-B6 Base
reserve a single point on the multiplex bus. Single
input Multiplex points can be programmed as points 9
through 127 (ZONEX 1) and 129 through 247 (ZONEX
2) (238 smoke detectors) on G Series, D9124, D9412,
or D9112; points 9 through 75 (67 smoke detectors)
on G Series, D7412, and D7212; and (32 smoke
detectors) points 9 through 40 on G Series. Other
wiring restrictions can reduce the maximum number of
photoelectric smoke detectors on the multiplex bus.
Refer to the MX250 Installation Guide (P/N: 45253) and
the D7050 Installation Instructions (P/N: 47458) for
additional information.
When programming an MX250 Series or D7050 Series
Photoelectric Smoke Detector and base with a D5060
Programmer, refer to Table 13 for information on
configuring the point type.
Table 13: MX250, MX250TH, D7050, and
D7050TH Point Type Configuration
Device Type Point
Type
Photoelectric Smoke
Detector and Base
4 NO
The rotary address switches must be set
to the “B” range address to work with the
D8125MUX.
Point
Response
Bosch Security Systems, Inc. | 12/15 | F01U034973-03
21
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
4.10 DS7460(i) Dual Input Multiplex
Module
The DS7460(i) reserves two points on the MUX bus.
Dual input multiplex points can be programmed as
Points 9 through 127 (ZONEX 1) and 129 through 247
(ZONEX 2) (59 per ZONEX, 118 modules) on G Series,
D9412, and D9112: Points 9 through 75 (33 modules)
on G Series, D7412, and D7212; Points 9 through 40
on G Series (16 modules). When programming dual
points, they occupy first an odd point number, then an
even point number. For example, DS7460(i) Modules
must be programmed to occupy Points 9 and 10, not
10 and 11.
When using the D5060 programmer, only
program the odd or first point on the
In addition, both points on the DS7460i must have a
Point Index assigned to it when programming the
control panel. If one of the two points is not required
on the device, simply place the 47 kΩ end-of-line (EOL)
resistor on the point input terminals and program the
unused point with the same Point Index. When
programming the point type for the DS7460(i), using
the D5060 Programmer refer to Table 14 for
information on configuring the point type. Tamper
conditions on multiplex points are treated as Missing
conditions by the control panel.
Table 14: DS7460(i) Point Type Configuration
Device Type Point Type Point Response
DS7460i Dual
Input Multiplex
Module
module. The even or second point is
automatically added.
The DS7460i cannot be used for Point 75
on G Series, D7412, and D7212 or for
Points 127 or 247 on G Series, D9412, and
D9112. Failure to observe these
programming requirements will result in
intermittent missing conditions.
6 Configurable
(N/O or N/C)
4.11 DS7432 Eight Input Remote
Module
This device type reserves eight points on the multiplex
bus. Each D8125MUX supports fifteen DS7432s on
G Series, D9412, and D9112 Control Panels, up to
eight on G Series, D7412, and D7212 Control Panels,
and up to four on G Series Control Panels. The
DS7432s occupy groups of eight points; however,
when programming the DS7432 with the multiplex
point programmer, program them as four sets of dual
points. For example, if using a DS7432 on the system
for Points 9 through 16, program Points 9, 11, 13, and
15 as dual points with the even points being added
automatically. Program starting point locations for the
DS7432 on G Series, D9412, and D9112 Control Panels
as follows: 9, 17, 25, 33, 41, 49, 57, 65, 73, 81, 89, 97,
105, 113, 121. Refer to Table 15.
Table 15: DIP Switch Settings
DIP Switch
ZONEX 1/
ZONEX 2
9/129 Open Open Open Open Closed
17/137 Open Open Open Closed Open
25/145 Open Open Open Closed Closed
33/153 Open Open Closed Open Open
41/161 Open Open Closed Open Closed
49/169 Open Open Closed Closed Open
57/177 Open Open Closed Closed Closed
65/185 Open Closed Open Open Open
73/193 Open Closed Open Open Closed
81/201 Open Closed Open Closed Open
89/209 Open Closed Open Closed Closed
97/217 Open Closed Closed Open Open
105/225 Open Closed Closed Open Closed
113/233 Open Closed Closed Closed Open
121/241 Open Closed Closed Closed Closed
1 2 3 4 5
Points 127/128 and 247/248 cannot be
programmed when using DS7432s
(G Series, D9412, or D9112).
22 Bosch Security Systems, Inc. | 12/15 | F01U034973-03
D8125MUX | Installation and Operation Guide | 4.0 Program Multiplex Bus Points
.
Program starting point locations for the DS7432 on
G Series, D7412, D7212 as follows: 9, 17, 25, 33, 41,
49, 57, and 65. Program starting point locations for the
DS7432 on G Series as follows: 9, 17, 25, and 33.
Failure to observe this programming requirement will
result in intermittent missing conditions. All eight
points on the DS7432 must also have a Point Index
assigned to them. If any of the eight point inputs are
not required on the device, place the 47 kΩ EOL
resistor on the point input terminals. Refer to Table 16
for information on configuring the point type. Tamper
conditions on multiplex points are treated as Missing
conditions by the control panel. Removing the cover
and activating the tamper results in a missing
condition for all eight points.
Table 16: DS7432 Point Type Configuration
Device Type Point
Type
DS7432 Eight Input
6 Configurable
Remote Module
Point
Response
(NO or NC)
4.12 DS7465(i) Input/Output Module
This device type reserves a single point on the MUX
bus and provides a Form C (NO, C, NC) relay output.
The relay output number assigned to this module is the
same as the point number assigned to it. For example,
if this device was programmed as Point 27, the relay
number is also 27.
The relay output on this module is a fully
programmable relay and follows the relay
The maximum number of DS7465i Modules that can be
placed on the control panels is 56 as points 9 through
64 for G Series, D9412, D7412, D7212, and D9112;
and 16 as points 9 through 24 for G Series. Place the
DS7465(i) on the D8125MUX connected to ZONEX 1.
If only the relay is required for the installation, assign a
Point Index for the programmed point location, and
place a 47 kΩ EOL resistor on the point input
terminals. Refer to Table 17 for point type
configuration.
programming of the control panel.
Table 17: DS7465(i) Point Type Configuration
Device Type Point
Type
DS7465(i)
Input/Output Module
3 Configurable
Point
Response
(NO or NC)
Tamper conditions on multiplex points are treated as
Missing conditions by the control panel. Using DS7465i
Input and Output Modules on the system does not
interfere with the use of D8129 OctoRelay Modules.
Control the relay output on each DS7465 using any of
the following control panel options:
•Relay follows Point for Points 9 through 64 (Points
9 through 34 for G Series) (refer to the Relay
Response Type section in the control panel’s
program entry guide).
When the DS7465i is programmed to
follow a point, the relay can have a
delayed response of 2 to 5 sec.
• Area or Panel Wide Relay functions
• Schedules (skeds)
• [Command] [5] [4]
• Remote Programming Software control
• Enter Key Relay Number (refer to Command
Center Assignments in the control panel’s program
entry guide)
•BFSK Relay (G Series, D7412, and D7212 only)
Bosch Security Systems, Inc. | 12/15 | F01U034973-03
23
D8125MUX | Installation and Operation Guide | 5.0 Testing the System
5.0 Testing the System
5.1 Local Walk Test (Command 44)
While disarmed, check the security system’s status by
entering [COMMAND] [4] [4] at the D1255 or D1260
Keypad. This command initiates a System Walk Test.
Each point of protection is scanned by the control
panel, and points are displayed on the D1255 as they
are activated. An accompanying tone is heard from the
keypad to alert the user of an activated point. When all
the burg points are tested, 0 POINTS TO TEST
appears and the system returns to normal operation.
Points failing to report during the Walk Test can be
viewed by pressing [NEXT] until the display reads
VIEW UNTESTED ? Press [NEXT] to view the faulty
points.
Refer to the Security System Owner’s Manual
(P/N: 71-06633-000) for more details on the Local
Walk Test features.
5.2 Missing Multiplex Points
Multiplex points appearing as missing on the display
are usually not connected properly to the multiplex
bus, not programmed correctly, nor have incorrect DIP
switch settings.
Check the multiplex bus wiring to the missing point
and its programming.
5.4 Ground Fault Notification on
Multiplex Devices
When the Loop Input (+) is in a normal condition, a
ground fault on the Loop Input (+) terminal is initially
signaled as a point trouble. A ground fault condition is
signaled by the system after the normal 30 second
ground fault detect time. To witness the ground fault
indication on the keypad, the point trouble must be
cleared from the display by pressing [Command] [4]
on a D1255 and D1260 or [Trouble Silence] on a
D1256. The control panel History Log, shown on a
keypad or sent to the central station, also indicates the
ground fault detection. An Alarm condition is still
indicated even during the occurrence of a ground fault
condition.
When the loop is in an open position, a ground fault on
the Loop Input (+) terminal disrupts supervision. An
open on the loop does not indicate a new fault,
because the ground fault is interpreted as an open. A
short might indicate an Alarm condition depending on
the control panel’s programming.
5.3 Extra Multiplex Points
Extra Points occur when the D8125MUX sends point
transitions back to the control panel and the control
panel does not have a Point Index programmed for it.
Extra multiplex points are reported to the control
panel as a trouble event at the keypad or central
station. The keypad shows the default custom text for
the point number as programmed in the RADXPNTS
(handler).
When an extra point is activated during the Service
Walk Test, it appears as an extra point in the control
panel’s event log and at the local printer (if installed).
Use VIEW LOG to view the control panel’s event log.
Once an extra point is identified, check the
programming to see if it has a Point Index
programmed. Determine if the point belongs in the
system.
Refer to Section 6.0 Troubleshooting on page 25 for
more information.
24 Bosch Security Systems, Inc. | 12/15 | F01U034973-03
D8125MUX | Installation and Operation Guide |
.
6.0 Troubleshooting
Table 18: Troubleshooting
Symptom Diagnosis Remedy
Multiplex point appears as
missing at the keypads.
Points intermittently
appear as missing.
One or more multiplex
points remain in trouble
or alarm when all devices
appear normal.
Faulted multiplex points
do not generate alarms or
troubles as programmed.
Multiplex point is not connected
to MUX bus. Check wiring.
Multiplex point not
programmed.
MUX bus wires not connected to
D8125MUX.
Noise problem on MUX bus loop. Make sure MUX bus wires do not run over
Intermittent shorts or opens on
the MUX bus wires.
The MUX bus is open, shorted or
grounded.
Opens, shorts, or grounds at
various points in the MUX bus
can cause alarms and troubles
depending on multiplex point
programming.
Control panel’s reset hook
switch is down when event was
generated.
Two multiplex points are
programmed for the same
address.
Verify that a multiplex point programmed for the
missing multiplex point is connected to the MUX
bus wiring. Make sure its polarity is correct.
Check the Green Operation LED on the
D8125MUX. It should be flashing. An LED OFF
indicates no power, a D8125MUX PCB failure, or
an EEPROM failure on the D8125MUX.
Verify the missing point’s programming with the
Multiplex Point Programmer.
Verify the MUX bus wires are connected to the
correct terminals on the D8125MUX. Verify
correct polarity.
fluorescent lighting or near large AC power
transformers or conduits.
Verify the wiring to the multiplex points and the
D8125MUX does not have nicks or cuts in the
insulation that can short to nearby conduit.
Make sure wires are tight under terminals of
multiplex points and on the D8125MUX.
Remove the sensor wiring from the multiplex
point and meter it for continuity.
There should be no more than 100 of
resistance, plus the EOL resistance. If you read
less than the EOL resistance look for shorts in
the wiring.
With the wires for the sensor removed, use a
meter to check them for continuity to ground.
A ground before the EOL resistor on a multiplex
points’ sensor loop is interpreted as a short. If
the multiplex point is programmed for trouble
on short, a ground before the EOL causes the
multiplex point to send a trouble report.
The control panel ignores events generated
while the programming or reset switch is down.
Multiplex points programmed for the same
address do not function correctly. Check the
programming of each multiplex point with the
multiplex point programmer.
Bosch Security Systems, Inc. | 12/15 | F01U034973-03
25
D8125MUX | Installation and Operation Guide |
Table 18: Troubleshooting (continued)
Symptom
Control panel transmits
PT BUS TROUBLE reports.
Erroneous alarm or
trouble reports might
Short on D8125MUX, MUX bus
terminals, or short on control
panel ZONEX data terminals (25
& 26, 27 & 28).
follow. Erroneous alarm or
trouble reports appear at
keypads.
A multiplex point is programmed
for address 128 or 248 or a
D8128D OctoPOPIT on the same
system has address switches set
for Points 121 through 128 or
Points 241 through 248.
All off-board points report
as MISSING.
Short on Aux power, Terminal 3
or ZONEX power, Terminal 24.
If only one D8125MUX is
connected to the control panel,
the D8125MUX might be
incorrectly connected to the
control panel, or MUX bus wiring
might be disconnected from the
D8125MUX.
Points on the DS7432 all
appear missing.
Multiplex power terminals or
MUX bus terminals on DS7432
might be incorrectly wired.
Address switches on DS7432 set
for Points 121 through 128.
A short on either MUX BUS A or MUX BUS B
terminals generates a PT BUS TROUBLE report.
A short on BUS A or BUS B does not prevent the
other from normal operation. Determine what
series of points is wired to BUS A and BUS B.
Check wiring for shorts.
Confirm that a multiplex point is not
programmed as Point 128 or 248. Multiplex
points cannot be used as Points 128 or 248
(these are reserved for control panel functions).
OctoPOPITs cannot be used for Points 121 to
128 or 241 to 248.
Terminals 3 and 24 share a common circuit
breaker.
Check wiring and devices connected to these
terminals for shorts or grounds. Check
connections to D8125MUX and control panel for
errors. Check the green Operation LED on the
D8125MUX to see if it is flashing.
Verify the wiring on DS7432 is correct.
Ensure address switches on DS7432 are not set
for Points 121 through 128. These points are
reserved for control panel functions.
26 Bosch Security Systems, Inc. | 12/15 | F01U034973-03
D8125MUX | Installation and Operation Guide |
.
Bosch Security Systems, Inc. | 12/15 | F01U034973-03
27
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, NY 14450-9199
www.boschsecurity.com