6en | GV3 Control Panel Connections (D9412GV3 Shown)GV3 Series v8.03 to v8.05
F01U266681 | 01 | 2012.03Quick Reference GuideBosch Security Systems, Inc.
GV3 Series v8.03 to v8.05 Upgrade GV3 Hardware and Programming | en7
2Upgrade GV3 Hardware and Programming
2.1Receive Existing Control Panel Programming
2.1.1Update the D5200 Programmer
If you use the D5200 programmer to program the control panel, you must have the current
GV2 handlers for all upgrades to GV3. If you have not previously updated your D5200
programmer handlers, download all current GV2 handlers to the D5200 from the handler
server.
The versions for the handlers on your programmer must be:
- GV2MAIN v1.04 or later- RADXUSR1 v1.06 or later- RADXUSR2 v1.05 or later
- RADXPNTS v1.08 or later- RADXSKED v1.04 or later- RADXAXS v1.06 or later
- GV2AUX v1.04 or later
To download the handlers:
1.Connect an RJ-11 telephone cord between the TELCO port on the D5200 programmer
and an outside telephone jack that accepts pulse dialing.
2.Turn on the D5200 programmer and enter the password.
3.Use the down arrow key to scroll to UPDATE and then press the [ENTER GROUP] key.
4.Type the name of the handler you wish to update (for example, GV2MAIN), in the
HandName field.
5.Press [ENTER] to scroll to Phone.
6.Enter the telephone number for downloading handlers, 18006574584.
NOTICE!
If the phone line requires you to first dial 9 to reach an outside line, include the 9 in the phone
number you typed in Step 6 (i.e., type 918006574584).
7.Press [ENTER] to scroll to Mode.
8.Press the space bar until you see TELCO->A (or TELCO->B if the B card is present in the
D5200 programmer).
9.Press [ENTER] to begin the handler download.
2.1.2Receive Existing Control Panel Programming with a D5200 Programmer
NOTICE!
GV3 control panels require updated GV2MAIN and GV2AUX handlers. Refer to
Section 2.1.1 Update the D5200 Programmer, page 7 for instructions to download the latest
handlers to your programmer.
1.Check the programmer memory for available space (> 40 kb free space is recommended).
2.Receive a copy of the a handler from the old control panel and save it to your D5200
Programmer.
3.If the control panel is a G or Non-G Series control panel, you must manually record the
9000MAIN and the RADXAUX1 programming. You must then add the information using
the new GV2MAIN and GV2AUX handlers into the D5200 Programmer before you can
send the program to the GV3 panel.
2.1.3Receive Existing Control Panel Programming with RPS
1.In RPS, double-click on the control panel name.
2.Click Connect. Once connected, the Panel Sync window opens.
3.Select the Recieve Panel Data option button and click OK.
8en | Upgrade GV3 Hardware and ProgrammingGV3 Series v8.03 to v8.05
2.2Upgrade Hardware to a GV3 Series Control Panel
2.2.1Prepare to Remove Existing Hardware
1.Power down the existing control panel by disconnecting the battery and the AC power.
2.Remove the four removable terminal strips by tilting the strip up and outward.
Do not remove the wiring from the terminal strip.
1 - Removable terminal strips
2.2.2Remove the Existing Control Panel
1.Remove the lock down tab screw.
2.Lift up on the control panel to free it from the enclosure mounting hooks, and remove the
control panel from the enclosure it.
1 - Lock down tab
2.2.3Install the GV3 Control Panel In the Enclosure
1.Place the GV3 Control Panel in the enclosure using the mounting skirt hook holes on the
back of the control panel and the mounting skirt hooks on the enclosure.
F01U266681 | 01 | 2012.03Quick Reference GuideBosch Security Systems, Inc.
GV3 Series v8.03 to v8.05 Upgrade GV3 Hardware and Programming | en9
NOTICE!
If the control panel was previously mounted using the screw hole configuration, the you must
re-mount the new control panel. The GV3 control panel mounting screw hole locations do not
align with the locations for older control panels.
2.2.4Replace the Terminal Strips
1.Replace the four removable terminal strips by pushing them straight down until they snap
into position.
2.Connect the battery and AC power.
2.3Upgrade Programming to a GV3 Control Panel Programming
NOTICE!
You must upgrade G Series and Non-G Series control panels to GV2 programming prior to
upgrading to GV3 programming.
2.3.1Upgrade a GV2 Series, G Series, or Non-G Series Control Panel to a GV3
Using a D5200 Series Programmer
1.Send a copy of each saved handler from the D5200 to the new control panel.
2.Test the control panel for operation.
3.Delete the saved control panel information from the D5200.
2.3.2Upgrade a Control Panel to a GV3 Using Remote Programming Software
(RPS) 5.12 or Higher
1.In RPS, highlight the control panel name by selecting it.
2.Click the View button on the Remote Programmer Toolbar.
3.In the resulting Panel Data - View window, click the Edit button.
4.In the resulting Panel Data - Edit window, select the new control panel type from the
Panel Type drop-down. (If the control panel is a G or Non-G Series control panel, you
must upgrade to GV2 first, and then repeat each of these steps to choose the GV3
control panel.) Click OK to close the window.
5.Click Save in the Panel View window to save the changes and close the Panel View
window.
6.Click Connect. Once connected, the Panel Sync window opens.
7.Select the Send ALL RPS Data to Panel option button and click OK.
8.Once the sync completes, click Disconnect to disconnect from the control panel.
12en | Programming to Set Up Central Station ReportingGV3 Series v8.03 to v8.05
4Programming to Set Up Central Station Reporting
4.1Basic Telephone
1.Go to PANEL WIDE PARAMETERS (GV2MAIN)→Phone (Phone and Phone Parameters
in RPS).
2.Enter the primary telephone number in the Phone 1 field.
3.If a secondary telephone number is required, enter it in the Phone 2 field.
4.Go to Panel Wide Parameters→Routing→Route Group 1.
5.Enter 1 in the Primary field.
6.If a secondary telephone is required, enter 2 in the Secondary (Backup in RPS) field.
4.2Basic Internet Protocol (IP)
1.Go to PANEL WIDE PARAMETERS (GV2MAIN)→Routing→Route Group 1 Primary.
2.Enter 1.
3.Go to Enhanced Routing→Route Group 1 Primary SDI (88 or 92).
4.Select YES.
5.Go to GV2AUX→Enhanced Communications.
6.Select or enter the following values:
NOTICE!
Enhanced Communications settings usually follow the recommendations of Central Stations
staff.
If using an ITS-DX4020-G for communication, refer to the ITS-DX4020-G Installation and Operation Guide (P/N: F01U163066).
ParameterValue
Enable Enhanced CommunicationYES
Path 1 IP AddressIP address of Central Station receiver
Path 1 Port NumberPort Number of Central Station receiver
If the control panel is programmed to send a heartbeat poll to the central station, a rate of 75 sec
maintains the virtual link in most network configurations.
4.3Account Number
In RPS, go to AREA WIDE PARAMETERS (GV2MAIN) and enter the account number (up to 10
digits) in the Account Number parameter.
For a D5200 Programmer, receive a copy of GV2MAIN and then go to AREA WIDE PARAMETERS→Area Parameters. Enter the 4 digit account number in Acct#Digit 7&8 and
Acct# Digit 9&10, press Send-Load to send changes to panel.
NOTICE!
Area 1 is the only area turned on by default.
1
Poll rate recommended by Central Station
F01U266681 | 01 | 2012.03Quick Reference GuideBosch Security Systems, Inc.
GV3 Series v8.03 to v8.05 Programming the Control Panel for Common Reporting Options | en13
5Programming the Control Panel for Common
Reporting Options
5.1Set Up Daily Test Report Using a D5200 or RPS
1.Go to RADXSKED→Schedules→Skeds.
2.Enter Function Code 9 (Test Report) in an unused Sked.
3.Select NO for the Deferred parameter to send test reports regardless of other test
reports sending between scheduled test reports.
4.Select NO for the Hourly parameter to send test reports only when the sked executes and
not every hour.
5.Enter the time at which you wish the schedule to send the report.
6.Leave the Date parameter disabled so that the sked executes by days of the week instead
of only on a selected date.
7.Select YES for each day of the week.
8.Select NO for:
–Except On Holiday
–Holidays 1 - 4
5.2Set Up Open and Close Reports Using a D5200 or RPS
5.2.1Area Wide Parameters
To report each area independently:
–Go to AREA WIDE PARAMETERS (GV2MAIN)→Open/Close Options→Acct O/C on the
D5200. Go to AREA WIDE PARAMETERS (GV2MAIN)→Area/Bell,Open/Close Options→Acct Open/Close in RPS. Select NO (default).
–Go to Area O/C on the D5200. Go to Area Open/Close in RPS). Select YES (default).
To report by account (Close signal is sent when the last area in an account is armed; Open
signal is sent when the first area is disarmed):
–Go to AREA WIDE PARAMETERS (GV2MAIN)→Open/Close Options→Acct O/C on the
D5200. Go to AREA WIDE PARAMETERS (GV2MAIN)→Area/Bell,Open/Close Options→Acct Open/Close in RPS. Select YES.
–Go to Area O/C on the D5200. Go to Area Open/Close in RPS. Select NO.
NOTICE!
If you want Perimeter Open and Close, select Perimeter O/C = YES.
5.2.2Set Authority Level
1.Go to USER INTERFACE (GV2MAIN)→Authority Levels.
2.Go to the Authority Level to be used by users sending Open and Close reports.
3.Select E (enabled) for Area O/C (Area Open/Close in RPS).
4.Select E for Restricted O/C (Restricted Open/Close in RPS).
5.Select E for Perimeter O/C (Perimeter Open/Close in RPS).
14en | Setting Up Points and OutputsGV3 Series v8.03 to v8.05
6Setting Up Points and Outputs
6.1Using the Relay Option Within Point Assignments
Relay Programming allows any one point or several points to latch a single relay through
software when the selected point generates an alarm. Relays are number 1 through 8 and are
programmed by entering the number of the relay (1 - 8) in the Relay column in Point
Assignments. This relay latches on a generated alarm and resets after acknowledging and then
clearing the alarm from memory.
D8129 Actual Relay Number
Relay
1973
21074
31175
41276
51377
61478
71579
81680
1
For the D7412GV3 and D7212GV3, connect to Terminal 28 for data (Zonex 1 Out).
2
For the D9412GV3, connect to Terminal 26 for data (Zonex 2 Out).
Tab le 6. 1 Actual Relays Latched by Control Panel Type
D7412GV3/D7212GV3
1
D9412GV3
2
Switch NumberSetting
1ON
2OFF
3ON
4ON
Tab le 6. 2 D8129 Switch Settings for All Control Panel Types
NOTICE!
Programmers must be aware of the following considerations:
–Do not use relays designated within Point Assignments for multiple functions. For
example, Relays 73 through 80 on the D9412GV3 should not be used for relay-followpoint or area-wide or panel-wide relays.
–Relays should not be selected to follow points programmed as Invisible Points.
6.2Point Index (Default Values)
Pt Index
Number
124-Hour Instant Audible Alarm on Open or
2Invisible/Silent Hold Up on Short18D279 (Priority)
3Fire Pull Station Alarm on Short19Easikey Input
4Smoke Detector with Reset Alarm on Short20POPIT Motion Sensor Interior
5Smoke Detector with Verification Reset and
6Bell Supervision Trouble on Open/Short22Fire Supervisory on Open, Trouble on Short
7Perimeter Instant Alarm on Open or Short,
8Perimeter Delay on Short, Instant Alarm on
DescriptionPt Index
Number
17D279 (Non-Priority)
Short
21POPIT Motion Sensor Perimeter
Alarm on Short
23Non-Fire Supervisory on Open, Trouble on
Watch Point when Disarmed
24Local, No Visual or Audible Display on Any Fault
Short, Watch Point when Disarmed
Description
Short
Armed or Disarmed with Relay Output
F01U266681 | 01 | 2012.03Quick Reference GuideBosch Security Systems, Inc.
GV3 Series v8.03 to v8.05 Setting Up Points and Outputs | en15
Pt Index
Number
9Perimeter Instant Alarm on Open or Short,
DescriptionPt Index
Number
25Perimeter Delay on Open, Alarm on Short
Description
Local while Disarmed
10Interior Instant Alarm on Open or Short2624-Hour Instant Audible Alarm on Open or
Short
11Interior Delay on Short, Alarm on Open2724-Hour Instant Audible Alarm on Open or
Short
12Interior Instant Alarm on Open or Short, Local
while Disarmed
13Interior Follower Delay on Short, Alarm on
Open
2824-Hour Instant Audible Alarm on Open or
Short
2924-Hour Instant Audible Alarm on Open or
Short
14Maintained Keyswitch3024-Hour Instant Audible Alarm on Open or
Short
15Momentary Keyswitch3124-Hour Instant Audible Alarm on Open or
Short
16Open/Close on Fault
Tab le 6. 3 Point Index Numbers and Descriptions
NOTICE!
The default indexes are not always the best selection.
If you experience unwanted trouble conditions, refer to Table 6.5 on Page 16 and make any
necessary adjustments.
Bosch Commercial Wireless points produce a Short when faulted and an Open for a tamper.
To make a custom Point Index, refer to (Table 6.4 and Table 6.5).
Pt Type DescriptionPt Type Description
024-Hour6O/C/ Port
1Perimeter7D279 (O/C Non-Priority)
2Interior8D279 (Priority)
3Interior Follower9Easikey
4Keyswitch11AUX AC Supervision
5Keyswitch Memory
Tab le 6. 4 Point Type Selections
NOTICE!
The selections in Table 6.5 indicate:
–D = Delayed Response
–I = Instant Alarm
–S = Supervisory
–T = Trouble
–Blank = No Response
To make a custom point index, use Table 6.4 on Page 15 and Table 6.5 on Page 16. For
example, to create an Interior Follower point with a delay on Open and Trouble on Short, use
Point Type 3 and Point Response 5.
16en | Setting Up Points and OutputsGV3 Series v8.03 to v8.05
Point Response
0123456789ABCDEF
Selections*
Armed OpenIIIIDDIIDIIIIIT
ShortIIIIIIDDDIIIIII
Disarmed OpenTTTIITIT
ShortTTTITII
24-HourOpenITITITSTSSN/A
ShortIITTITTSSS
Tab le 6. 5 Point Response Selections
F01U266681 | 01 | 2012.03Quick Reference GuideBosch Security Systems, Inc.
GV3 Series v8.03 to v8.05 Add System Users Locally With a Keypad | en17
7Add System Users Locally With a Keypad
7.1Add Users (CMD 56) Using a Keypad
StepOperator EntryKeypad Response
1Enter Command 56Enter Passcode
2Enter passcode and press [ENT].Enter User #
3Enter the user number and press [ENT].USER # (default name text)
4EnterChange Passcode?
5EnterEnter New Code
6Enter the new user’s passcode.Enter New Again
7Re-enter the new passcode.Code Changed
Tab le 7. 1 Adding Users with Command 56
7.2Add Card (CMD 56) for Access Control Only Using a Keypad
StepOperator EntryKeypad Response
1Command 56Enter Passcode
2Enter passcode and press [ENT]Enter User #
3Enter the user number and press [ENT]USER# (default name text)
4EnterChange Passcode?
5NextAdd Card?
6EnterPresent Card
7Present the credential to the reader.Card Added
Tab le 7. 2 Adding Cards with Command 56
NOTICE!
To use Add Card (CMD 56), you must program the Assign Door prompt within Command
Center Assignments with the D9210B door controller number. If you do not program the
Assign Door prompt, the keypad reads 9210 NOT READY.
For each of the following commands, press [9] [9] [ENTER]. Press [NEXT] to view each
command.
–1 - View Log
–2 - Print Log
–3 - Display Revision
–4 - Service Walk
–5 - Default Text
F01U266681 | 01 | 2012.03Quick Reference GuideBosch Security Systems, Inc.
GV3 Series v8.03 to v8.05 Turning the System ON or OFF and Keypad Commands | en19
8.3SIA CP-01 False Alarm Prevention Options
NOTICE!
Some programming parameters are preset for compliance with SIA standard CP-01 (false
alarm prevention). These settings are in AREA WIDE PARAMETERS (GV2MAIN)→Area Parameters. They affect control panel operation as described below.
–Master Arm-No Exit=YES: This setting provides for a Perimeter Delay point to be faulted
when master arming each area, or the arming state defaults to Perimeter Delayed.
–Exit Delay Warning=YES: When this parameter is set to YES, the alarm bell pulses on and
off every two seconds for the remaining 10 sec of Exit Delay.
–Entry Delay Warning=YES: When this parameter is set to YES, the alarm bell pulses on
and off every two seconds for the remaining 10 sec of Entry Delay.
20en | Setting DIP SwitchesGV3 Series v8.03 to v8.05
9Setting DIP Switches
9.1D9127 U/T POPIT Dip Switch Key
POPIT addresses are binary. Refer to Table 9.1:
Switch Number 0123456
Binary Value6432168421
Tab le 9. 1 POPIT Dip Switch Keys
To calculate the switch settings for POPITS, you must determine the value to use in the
calculation. For addresses 9 through 127, subtract 9. For addresses 129 through 247,
subtract 129. Use the following procedure with address 48 as the example, substituting the
actual values in your calculation.
1.Subtract 9 from 48. The result is 39.
2.Set the switches that add up to 39 to the OFF positions (32 + 4 + 2 + 1 = 39).
SW 1 OFF = 32
SW 4 OFF = 4
SW 5 OFF = 2
SW 6 OFF = 1
9.2D9210B Switch Settings
For additional information, refer to the Access Control Interface Module D9210B Operation and
Installation Guide (P/N: 32206).
9.3D720, D1255, D1260 Dip Switch Settings
For additional information, refer to:
– D720 Series Keypads Installation Instructions (P/N: 7406918000)
– D1255/D1255B Keypads Installation Instructions (P/N: 7406819000)
or
– D1260/D1260B Keypads Installation Guide (P/N: 48101)
9.4D9131A Dip Switch Settings
For additional information, refer to the Parallel Printer Interface D9131A Installation Guide (P/
N: F01U135506).
9.5D8129 OctoRelay Dip Switch Settings
For additional information, refer to the D8129 OctoRelay Module Operating and Installation
Guide (P/N: F01U036302).
9.6D8128C OctoPOPIT Dip Switch Settings
For additional information, refer to the D8128C OctoPOPOIT Module Operating Instructions (P/
N: 7407710000).
9.7D8128D OctoPOPIT Dip Switch Settings
For additional information, refer to the D8128D OctoPOPOIT Module Installation Guide (P/
N: F01U070537).
F01U266681 | 01 | 2012.03Quick Reference GuideBosch Security Systems, Inc.
GV3 Series v8.03 to v8.05 Reporting Format Definitions | en21
10Reporting Format Definitions
Modem IIIa2 EventModem IIIa2 Code
D6500 Mode
A point supervisory
condition occurred
A valid local access
occurred
A valid remote access
callback occurred
A valid remote access
occurred
AC Fail – mains power
supply
AC Restore – mains
power supply
Access Denied – Door
Secured
Access Denied –
Interlocked
Access Denied – No rights
in area by card
Access Denied – Unknown IDADspppNriaDDpppAccess Denied1 421 aa uuu
ssxDGppp
AlarmAspppNriaBApppBurglary1 130 aa ppp
Alarm Cross PointAspppNriaBMpppBurglary1 130 aa ppp
Alarm Exit ErrorAspppNria/idiiiEApppEntry/Exit1 134 aa ppp
Alarm with Recent Closing AspppNria/CRpppEntry/Exit1 459 aa uuu
All SDI devices are
missing, power is shorted
All SDI devices are
restored, power is normal
An individual SDI device is
missing.
An individual SDI device is
restored.
An invalid remote access
callback occurred
An invalid remote access
occurred
Armed perimeter delayCsiiiNria/idiiiNLArmed STAY3 441 aa uuu
Armed perimeter instantCsiiiNria/idiiiNLArmed STAY3 441 aa uuu
Bypass by RemoteNspppNriaUBpppZone/Sensor Bypass1 570 aa ppp
Bypass by SDI deviceNspppNria/pidddUBppp Zone/Sensor Bypass1 570 aa ppp
Bypass by SkedNspppNria/aikkkUBpppZone/Sensor Bypass1 570 aa ppp
Bypass by UserNspppNria/idiiiUBpppZone/Sensor Bypass1 570 aa ppp
Bypass PointNspppNriaUBpppZone/Sensor Bypass1 570 aa ppp
22en | Reporting Format DefinitionsGV3 Series v8.03 to v8.05
Modem IIIa
2
EventModem IIIa2 Code
Checksum failure on
Modem IIIa2 Code
D6500 Mode
Bosch SIA Mode
TsD15NYFRAM Checksum Bad1 303 00 000
Contact ID EventContact ID
Code
configuration memory
Closing by AreaCsiiiNria/idiiiCLO/C by User3 401 aa uuu
Closing Early by AreaCsiiiNria/idiiiCKEarly O/C3 451 aa uuu
Closing Late by AreaCsiiiNria/idiiiCJLate O/C3 452 aa uuu
Communication failure by
TsB01NrggYCFailure to communicate event 1 354 00 000
route group
Communication failure by
NsB01NrggYKFailure to communicate event 3 354 00 000
by phone restored
Control panel battery low Tsss9NYTLow System Battery1 302 00 000
Control panel battery
Tsss9NYMBattery Missing/Dead1 311 00 000
missing
Control panel battery
Rsss9NYRLow System Battery3 302 00 000
restored to normal
Create Status ReportSssssNYYStatus Report to Follow1 605 00 000
Date changed – no user
NsD07NJDTime/Date Reset1 625 00 000
identified
Dated changed by userNsD07NidiiiJDTime/Date Reset1 625 00 uuu
Door Closed, RestoralRspppNriaDHpppAccess Door propped open1 426 aa ppp
Door Left Open AlarmAspppNriaDLpppAccess Door propped open1 426 aa ppp
Door Left Open TroubleTspppNriaDMpppAccess Door propped open1 426 aa ppp
DuressDsiiiNria/idiiiHADuress1 121 aa uuu
Event Log OverflowAsD01NJOEvent Log Overflow1 624 00 000
Event Log Threshold has
TsD01NJLEvent Log 90% Full1 623 00 000
been reached
Extend Close TimeTsD26Nria/idiii/
Auto-arm Time Extended1 464 aa uuu
tihhmmCE
Extra PointTspppNriaXEpppMaintenance Alert1 393 aa ppp
Fail To Close by AreaTsssENriaCIFailed to Close1 454 aa 000
Fail To Open by AreaTsssENriaOIFailed to Open1 453 aa 000
Fire AlarmFspppNriaFApppFire1 110 aa ppp
Fire Cancel\siiiNria/idiiiFCCancel1 406 aa ppp
Fire MissingMspppNriaFYpppFire Trouble1 373 aa ppp
Fire Restoral from AlarmHsspppNriaFHpppFire3 110 aa ppp
Fire Restoral from Trouble HspppNriaFJpppFire Trouble3 373 aa ppp
Fire SupervisionEspppNriaFSpppFire Supervisory1 200 aa ppp
Fire Supervision from
EspppNriaFVpppFire Supervisory3 200 aa ppp
Restore
Fire TroubleGsspppNriaFTpppFire Trouble1 373 aa ppp
Fire Walk Test EndRsssFNria/idiiiFKFire Test3 604 aa uuu
Fire Walk Test StartTsssFNria/idiiiFIFire Test1 604 aa uuu
Force Armed Perimeter
CsiiiNria/idiiiNFPartial Arm3 456 aa uuu
Delay
F01U266681 | 01 | 2012.03Quick Reference GuideBosch Security Systems, Inc.
GV3 Series v8.03 to v8.05 Reporting Format Definitions | en23
Modem IIIa
2
EventModem IIIa2 Code
Force Armed Perimeter
Modem IIIa2 Code
D6500 Mode
Bosch SIA Mode
CsiiiNria/idiiiNFPartial Arm3 456 aa uuu
Contact ID EventContact ID
Code
Instant
Forced Close Early by
CsiiiNria/idiiiCFEarly O/C3 451 aa uuu
Area
Forced Close Late by Area CsiiiNria/idiiiCFLate O/C3 452 aa uuu
Forced Closing by AreaCsiiiNria/idiiiCFO/C by user3 401 aa uuu
Forced PointTspppNriaXWpppZone/Sensor Bypass1 570 aa ppp
Invalid local access
TsF01NLUUnsuccessful access1 413 00 000
detected
Low battery on a wireless
TspppNriaXTpppRF Low Battery1 384 aa ppp
point
Low battery restore on a
RspppNriaXRpppRF Low Battery3 384 aa ppp
wireless point
Missing AlarmMspppNriaUZpppGeneral Alarm1 140 aa ppp
Missing Fire SupervisionGMspppNriaFZpppFire Trouble1 200 aa ppp
Missing SupervisionMTspppNriaBZpppLoss of Supervision - RPM1 382 aa ppp
Missing TroubleVspppNriaUYpppLoss of Supervision - RPM1 382 aa ppp
Non- Fire Cancel Alarm\siiiNria/idiiiBCCancel1 406 aa ppp
Normal start-up of the
NsD14NRRSystem Reset1 305 00 000
control panel
Opening by AreaOsiiiNria/idiiiOPO/C by user1 401 aa uuu
Opening Early by AreaOsiiiNria/idiiiOKEarly O/C1 451 aa uuu
Opening Late by AreaOsiiiNria/idiiiOJLate O/C1 452 aa uuu
Parameters changed by
NsD02NYGPanel Programming Changed 1 306 00 000
RPS
Phone Line Missing (1 or 2)TsssBNLT1 or NLT2Telco 1 Fault1 351 00 000
Phone Line Restored (1 or 2)RsssBNLR1 or NLR2Telco 1 Fault3 3515 00 000
Point Bus FailTsssDNETProtection Loop1 370 00 000
Point Bus Restoral, power
RsssDNERProtection Loop3 370 00 000
normal or bus not missing
RAM Fail with RPSTsF02NRAUnsuccessful access1 413 00 000
Relay Reset by
NsD22NpidddROrrrSounder/Relay3 320 00 000
Programmer
Relay Reset by RemoteNsD24NROrrrSounder/Relay3 320 00 000
Relay Reset by SkedNsD20NaikkkROrrrSounder/Relay3 320 00 000
Relay Reset by UserNsD18NidiiiROrrrSounder/Relay3 320 00 000
Relay Set by Programmer NsD21NpidddRCrrrSounder/Relay1 320 00 000
Relay Set by RemoteNsD23NRCrrrSounder/Relay1 320 00 000
Relay Set by SkedNsD19NaikkkRCrrrSounder/Relay1 320 00 000
Relay Set by UserNsD28NidiiiRCrrrSounder/Relay1 320 00 000
Remote Reset – System
NsD11NRNSystem Reset1 305 00 000
was reset by RPS
RestoralRspppNriaBRpppSensor Trouble3 380 aa ppp
Restoral from AlarmRspppNriaBHpppBurglary3 130 aa ppp
Restoral from Ground
RspppNriaBRpppGround Fault3 310 aa ppp
Fault
ROM Checksum Fail (Not
AsD12NYXROM Checksum bad1 304 00 000
Used)
Sensor ResetNsD27Nria/idiiiXIrrrSounder/Relay3 320 00 000
Service Walk Test EndRsssFNidiiiTEService On/Off Premises3 466 aa uuu
Time Changed by UserNsD07NidiiiJTTime/Date Reset1 625 00 uuu
TroubleTspppNriaBTpppSensor Trouble1 380 aa ppp
Trouble with Ground Fault TspppNriaBTpppGround Fault1 310 aa ppp
Unverified EventKspppNriaUGpppCross-zone Trouble1 378 aa ppp
User Alarm 7Usss7Nria/idiiiUAPersonal Emergency1 101 aa uuu
User Alarm 9UUsss9Nria/idiiiPADuress1 121 aa uuu
User Passcode Tamper –
NsD03NriaJAWrong Code Entry1 461 aa 000
Too Many Attempts
Walk Test EndRsssFNria/idiiiTEWalk test mode3 607 aa uuu
Walk Test StartTsssFNria/idiiiTSWalk test mode1 607 aa uuu
Watchdog Reset – SDI
NsD09NpidddYWSystem Reset1 305 00 000
Device Reported
identifies the Source
Table 10.1 Reporting Format Definitions
F01U266681 | 01 | 2012.03Quick Reference GuideBosch Security Systems, Inc.
GV3 Series v8.03 to v8.05 Frequently Asked Questions | en25
11Frequently Asked Questions
What does it mean when my keypad reads "CALL FOR SERVICE"?
That keypad is not receiving data from the control panel.
What does it mean when my keypad reads "SERVICE KEYPAD"?
A supervised keypad has lost communications with the control panel.
How do I arm an area that is not assigned to my keypad?
Add to the FUNCTION LIST a menu item with a function code of 1 and with CC ADDRESS 1-8
set to YES, and a menu item with a function code of 2 and with CC ADDRESS 1-8 set to Yes.
Assign the function codes to the necessary command center. The new menu items allow your
users to select the area they wish to arm or disarm.
How do I perform area-specific functions from a keypad?
Use the MOVE TO AREA command (CMD 50) to move to an area within the keypad’s scope.
Can I default a lockcode without knowing the lockcode?
No. You must send the unit to the Bosch Repair Center.
How do I upgrade the control panel version?
Use the supplied firmware upgrade key to upgrade the firmware. Lift the control panel
faceplate cover to access the port to insert the upgrade key and read the instructions located
on the back of the faceplate.
How do I add an access card using the command center?
Use the ADD USER command (CMD 56) to add an access card. Present the access card to the
assigned door to add the card.
What does it mean when my keypad reads "9210 NOT READY"?
No door is assigned to the command center. Check the ASSIGN DOOR parameter within
COMMAND CENTER ASSIGNMENTS menu item, and then enter the D9210B address (1 - 8).
What are SDI addresses 33 to 40?
They are D9210B addresses.
What are SKEDS 41 to 56?
They are Open and Close windows.
How do I test a relay from the keypad?
Use the RELAY CONTROL command (CMD 54) to toggle relays.
How do I toggle the on-board relays A, B, and C?
Use the RELAY CONTROL command (CMD 54), and then the relay number: 253 for A; 254 for
B; and 255 for C.
How many Amp Hours can the panel sustain?
You can connect two (2) 18 Ah batteries for a total of 36 Ah. You can gain up to an additional
27 Ah with by connecting a D8132 module.
Is the control panel compatible with digital or VOIP phone lines?
The control panel has been tested with only analogue lines. Use a DX4020 to transmit over
Ethernet or a ITS-DX4020-G to transmit over cellular. You can use a C900V2 to convert
analogue signals to Ethernet for transmission to a D6600 receiver.
How do I silence a trouble condition?
Use the SILENCE TROUBLE SOUNDER command (CMD 4) to silence a trouble condition.
26en | Frequently Asked QuestionsGV3 Series v8.03 to v8.05
How do I clear alarm memory?
Ensure all points are normal, and the enter your passcode and press [ESC], or press the
[Clear] soft key.
How do I determine if I have a ground fault?
On the control panel, measure voltage on terminal 9 (common) and terminal 10 (earth
ground). Approximately 6.5 to 6.8 VDC is normal voltage and equals no ground fault.
Disconnect wires until you see normal voltage to find your ground.
Can I add wireless capability to this control panel?
Yes. Use the Bosch Commercial Wireless Kit (ISW-CWKIT-01) and the proper Bosch
Commercial Wireless transmitters to fully integrate wireless on the control panel.
What type of cable do I use to connect my computer’s COM port to a serial-enhanced direct
connection using the DX4010i?
A null modem cable is required.
How can I determine which points are not ready when my keypad reads "NOT READY TO
ARM"?
Press the NEXT key to scroll through faulted points. If the VIEW POINT STATUS menu item is
enabled, you can access it through the menu to determine the state of the faulted point.
What does it mean when my keypad reads "CHECK DEVICE"?
A point is faulted. The point is one that is configured to display as a device in the POINT INDEX
by marking YES for the DISPLAY AS DEVICE parameter.
I hear a trouble tone from my keypad but no point is shown as in trouble on the keypad.
How do I resolve this?
A point generates a trouble tone (buzz) when faulted if is configured to do so. To determine
which points are configured to buzz, look in the POINT INDEX for points with a non-zero value
for the BUZZ ON FAULT parameter.
How can I determine the meaning of an undefined signal received from central station?
Press 99 [ENTER] on the keypad to reveal the VIEW LOG menu item. Locate the signal in the
log by date and time.
Which reporting formats can the panel send?
Modem IIIa
2
or Contact ID. BFSK was replaced with Contact ID for the GV3 control panel.
What is the default Installer Code?
The code is 123.
What is the default User Code?
The code is 123456.
What is the default RPS Passcode?
The code is 999999.
Is the GV3 control panel keypad programmable?
No. You must program the control panel using the D5200 Series Programmer or RPS version
5.12 or higher.
What is the phone number to update the D5200 Series Programmer?
The number is 1-800-657-4584.
Where can I find free documentation and on-line support for this product?
Go to www.boschsecurity.us.
F01U266681 | 01 | 2012.03Quick Reference GuideBosch Security Systems, Inc.