D9412GV4/D7412GV4/D7212GV4 Table of Contents | en3
Table of Contents
1GV4 Control Panel Connections (D9412GV4 Shown)5
2Upgrade GV4 Hardware and Programming7
2.1Receive Existing Control Panel Programming7
2.1.1Receive Existing Control Panel Programming with RPS7
2.2Upgrade Hardware to a GV4 Series Control Panel7
2.2.1Prepare to Remove Existing Hardware7
2.2.2Remove the Existing Control Panel7
2.2.3Install the GV4 Control Panel In the Enclosure8
2.2.4Replace the Terminal Strips8
2.3Upgrade Programming to a GV4 Control Panel Programming9
2.3.1Upgrade a GV3 Series, GV2 Series, G Series, or Non-G Series Control Panel to a GV4 or Later Using
Remote Programming Software (RPS) 5.14 or Later9
3Programming the Control Panel10
3.1RPS Programming over a Network Using the DX4020 Ethernet Network Interface Module10
3.2RPS Programming over a Network Using the ITS-DX4020-G GPRS/GSM Communicator10
3.3RPS Programming Using the DX4010V2 RS-232/USB Serial Interface Module10
3.4RPS Programming Using the B420 Ethernet Communication Module10
3.5Programming Using the Keypad Tools Menu10
4Programming to Set Up Central Station Reporting11
4.1Basic Telephone Set Up in RPS11
4.2Basic Internet Protocol (IP)11
4.3Account Number11
5Programming the Control Panel for Common Reporting Options12
5.1Set Up Daily Test Report Using RPS12
5.2Set Up Open and Close Reports Using RPS12
5.2.1Area Wide Parameters12
5.2.2Set Authority Level12
6Setting Up Points and Outputs13
6.1Using the Relay Option Within Point Assignments13
6.2Point Index (Default Values)14
7Add System Users Locally With a Keypad16
7.1Add Users (CMD 56) Using a Keypad16
7.2Add Card (CMD 56) for Access Control Only Using a Keypad16
8Turning the System ON or OFF and Keypad Commands17
8en | Upgrade GV4 Hardware and ProgrammingD9412GV4/D7412GV4/D7212GV4
2.2.3Install the GV4 Control Panel In the Enclosure
1.Place the GV4 Control Panel in the enclosure using the mounting skirt hook holes on the
back of the control panel and the mounting skirt hooks on the enclosure.
If the control panel was previously mounted using the screw hole configuration, the you must
re-mount the new control panel. The GV4 control panel mounting screw hole locations do not
align with the locations for older control panels.
2.2.4Replace the Terminal Strips
1.Replace the removable terminal strips by pushing them straight down until they snap into
position.
2.Connect the battery and AC power.
F01U215242 | 01 | 2011.10Quick Reference GuideBosch Security Systems, Inc.
Page 9
D9412GV4/D7412GV4/D7212GV4 Upgrade GV4 Hardware and Programming | en9
2.3Upgrade Programming to a GV4 Control Panel Programming
NOTICE!
You must upgrade G Series and Non-G Series control panels to GV2 programming prior to
upgrading to GV4 programming.
2.3.1Upgrade a GV3 Series, GV2 Series, G Series, or Non-G Series Control Panel
to a GV4 or Later Using Remote Programming Software (RPS) 5.14 or Later
RPS version 5.14 or newer is required to upgrade an existing G Series, GV2, or GV3 Series
Control Panel installation to a GV4 Series Control Panel. Refer to the RPS help files for the
specific control panel for additional information on control panel conversion.
1.In RPS, highlight the control panel name by selecting it.
2.Click the View button on the Remote Programmer Toolbar.
3.In the resulting Panel Data - View window, click the Edit button.
4.In the resulting Panel Data - Edit window, select the new control panel type from the
Panel Type drop-down. (If the control panel is a G or Non-G Series control panel, you
must upgrade to GV2 first, followed by GV3, and then repeat each of these steps to
choose the GV4 control panel).
5.Click OK to close window.
6.Click Save in the Panel View window to save the changes and close the Panel View
window.
7.Click Connect. Once connected, the Panel Sync window opens.
8.Select the Send ALL RPS Data to Panel option button and click OK.
9.Once the sync completes, click Disconnect to disconnect from the control panel.
10en | Programming the Control PanelD9412GV4/D7412GV4/D7212GV4
3Programming the Control Panel
You can program the control panel with RPS using a network connection or serial connection.
You can program some paramaters of the control panel with keypad programming.
3.1RPS Programming over a Network Using the DX4020 Ethernet
Network Interface Module
For additional information, refer to IP Address Programming in the Conettix DX4020 Network
Interface Module Installation Guide (P/N: F01U045288).
3.2RPS Programming over a Network Using the ITS-DX4020-G
GPRS/GSM Communicator
For additional information, refer to the Conettix ITS-DX4020-G Installation Guide (P/
N: F01U163066).
3.3RPS Programming Using the DX4010V2 RS-232/USB Serial
Interface Module
For additional information, refer to the DX4020 RS-232/USB Serial Interface Module Installation
Instructions (P/N: F01U083036).
3.4RPS Programming Using the B420 Ethernet Communication
Module
For additional information, refer to Programming Through a Control Panel in the B420 Ethernet
Communication Module Installation and Operation Guide (P/N: F01U215236).
3.5Programming Using the Keypad Tools Menu
For additional information, refer to the GV4 Series Program Entry Guide (P/N: F01U218312).
F01U215242 | 01 | 2011.10Quick Reference GuideBosch Security Systems, Inc.
Page 11
D9412GV4/D7412GV4/D7212GV4 Programming to Set Up Central Station Reporting | en11
4Programming to Set Up Central Station Reporting
NOTICE!
You can program these items using RPS and the steps listed below. You can also use keypad
programming (refer to the D9412GV4/D7412GV4/D7212GV4 Program Entry Guide (P/
N: F01U218312).
4.1Basic Telephone Set Up in RPS
1.Go to PANEL WIDE PARAMETERS→Phone and Phone Parameters.
2.Enter the primary telephone number in the Phone 1 field.
3.If a secondary telephone number is required, enter it in the Phone 2 field.
4.Go to Panel Wide Parameters→Communicator→Route Group 1.
5.Enter Phone 1 in the Primary Device field.
6.If a secondary telephone is required, enter Phone 2 in the Backup Device field.
4.2Basic Internet Protocol (IP)
1.Go to PANEL WIDE PARAMETERS→Communicator→Route Group 1 Primary Device.
2.Select SDI Address 88 Path 1.
3.Go to PANEL WIDE PARAMETERS→SDI RPS/Enhanced Comm→Enable Enhanced Communications to Yes.
4.Go to PANEL WIDE PARAMETER→Enhanced Communications.
5.Select or enter the following values:
NOTICE!
Enhanced Communications settings usually follow the recommendations of the Central
Stations’ staff.
If using an ITS-DX4020-G for communication, refer to the ITS-DX4020-G Installation and Operation Guide (P/N: F01U163066).
If using an B420 Ethernet Communication Module, refer to the B420 Ethernet Communication Module Installation and Operation Guide (P/N: F01U215236).
ParameterValue
Enable Enhanced CommunicationYES
Path 1 Network AddressIP or Network address of Central Station
receiver
Path 1 Port NumberPort Number of Central Station receiver
12en | Programming the Control Panel for Common Reporting OptionsD9412GV4/D7412GV4/D7212GV4
5Programming the Control Panel for Common
Reporting Options
5.1Set Up Daily Test Report Using RPS
1.Go to SCHEDULES→Skeds.
2.Enter Function Code 9 (Test Report) in an unused Sked.
3.Select NO for the Deferred parameter to send test reports regardless of other test
reports sending between scheduled test reports.
4.Select NO for the Hourly parameter to send test reports only when the sked executes and
not every hour.
5.Enter the time at which you wish the schedule to send the report.
6.Leave the Date parameter disabled so that the sked executes by days of the week instead
of only on a selected date.
7.Select YES for each day of the week.
8.Select NO for:
–Except On Holiday
–Holidays 1 - 4
5.2Set Up Open and Close Reports Using RPS
5.2.1Area Wide Parameters
To report each area independently:
–Go to AREA WIDE PARAMETERS→Area/Bell,Open/Close Options→Acct Open/Close in
RPS. Select NO (default).
–Go to Area Open/Close in RPS). Select YES (default).
To report by account (Close signal is sent when the last area in an account is armed; Open
signal is sent when the first area is disarmed):
– Go to AREA WIDE PARAMETERS→Area/Bell,Open/Close Options→Acct Open/Close
in RPS. Select YES.
– Go to Area Open/Close in RPS. Select NO.
NOTICE!
If you want Perimeter Open and Close, select Perimeter O/C = YES.
5.2.2Set Authority Level
1.Go to USER INTERFACE→Authority Levels.
2.Go to the Authority Level to be used by users sending Open and Close reports.
3.Select E (enabled) for Area Open/Close.
4.Select E for Restricted Open/Close.
5.Select E for Perimeter Open/Close.
F01U215242 | 01 | 2011.10Quick Reference GuideBosch Security Systems, Inc.
Page 13
D9412GV4/D7412GV4/D7212GV4 Setting Up Points and Outputs | en13
6Setting Up Points and Outputs
6.1Using the Relay Option Within Point Assignments
Relay Programming allows any one point or several points to latch a single relay through
software when the selected point generates an alarm. Relays are number 1 through 8 and are
programmed by entering the number of the relay (1 - 8) in the Relay column in Point
Assignments. This relay latches on a generated alarm and resets after acknowledging and then
clearing the alarm from memory.
D8129 Actual Relay Number
Relay
D7412GV4/D7212GV4
1
D9412GV4
1973
21074
31175
41276
51377
61478
71579
81680
1
For the D7412GV4 and D7212GV4, connect to Terminal 28 for data (Zonex 1 Out).
2
For the D9412GV4, connect to Terminal 26 for data (Zonex 2 Out).
Tab le 6. 1 Actual Relays Latched by Control Panel Type
2
Switch NumberSetting
1ON
2OFF
3ON
4ON
Tab le 6. 2 D8129 Switch Settings for All Control Panel Types
NOTICE!
Programmers must be aware of the following considerations:
–Do not use relays designated within Point Assignments for multiple functions. For
example, Relays 73 through 80 on the D9412GV4 should not be used for relay-followpoint or area-wide or panel-wide relays.
–Relays should not be selected to follow points programmed as Invisible Points.
NOTICE!
The default indexes are not always the best selection.
If you experience unwanted trouble conditions, refer to Table 6.5, Page 15 and make any
necessary adjustments.
Inovonics EchoStream Wireless points produce a Short when faulted and an Open for a
tamper.
To make a custom Point Index, refer to (Table 6.4 and Table 6.5).
Pt Type DescriptionPt Type Description
024-Hour6O/C/ Port
1Perimeter7D279 (O/C Non-Priority)
2Interior8D279 (Priority)
3Interior Follower9Easikey
4Keyswitch
11AUX AC Supervision
Maintained
5Keyswitch
Momentary
Tab le 6. 4 Point Type Selections
NOTICE!
The selections in Table 6.5 indicate:
–D = Delayed Response
–I = Instant Alarm
–S = Supervisory
–T = Trouble
–Blank = No Response
To make a custom point index, use Table 6.4 on Page 14 and Table 6.5 on Page 15. For
example, to create an Interior Follower point with a delay on Open and Trouble on Short, use
Point Type 3 and Point Response 5.
F01U215242 | 01 | 2011.10Quick Reference GuideBosch Security Systems, Inc.
Page 15
D9412GV4/D7412GV4/D7212GV4 Setting Up Points and Outputs | en15
Point Response
0123456789ABCDEF
Selections*
Armed OpenIIIIDDIIDIIIIIT
ShortIIIIIIDDDI IIIII
Disarmed OpenTTTIITIT
ShortTTTITII
24-HourOpenITITITSTSSN/A
ShortI I TTI TTSSS
*Selections: D = Delayed Response, I = Instant Alarm, S = Supervisory, T = Trouble, B = No
Response
16en | Add System Users Locally With a KeypadD9412GV4/D7412GV4/D7212GV4
7Add System Users Locally With a Keypad
7.1Add Users (CMD 56) Using a Keypad
StepOperator EntryKeypad Response
1Enter Command 56Enter Passcode
2Enter passcode and press [ENT].Enter User #
3Enter the user number and press [ENT].USER # (default name text)
4EnterAdd Passcode?
5EnterEnter New Code
6Enter the new user’s passcode.Enter New Again
7Re-enter the new passcode.Code Changed
Tab le 7. 1 Adding Users with Command 56
7.2Add Card (CMD 56) for Access Control Only Using a Keypad
StepOperator EntryKeypad Response
1Command 56Enter Passcode
2Enter passcode and press [ENT]Enter User #
3Enter the user number and press [ENT]USER# (default name text)
4EnterChange Passcode?
5NextAdd Card?
6EnterPresent Card
7Present the credential to the reader.Card Added
Tab le 7. 2 Adding Cards with Command 56
NOTICE!
To use Add Card (CMD 56), you must program the Assign Door prompt within Command
Center Assignments with the D9210C door controller number. If you do not program the
Assign Door prompt, the keypad reads 9210 NOT READY.
F01U215242 | 01 | 2011.10Quick Reference GuideBosch Security Systems, Inc.
Page 17
D9412GV4/D7412GV4/D7212GV4 Turning the System ON or OFF and Keypad Commands | en17
8Turning the System ON or OFF and Keypad Commands
8.1Arming and Disarming the System
8.1.1Master Arming
Enter the passcode and [ENTER] to arm all areas where the user has authority and are areas
within the scope of the keypad.
8.1.2Disarming
Enter the passcode and [ENTER] to disarm all areas where the user has authority and are
areas within the scope of the keypad.
8.1.3Set Duress +1 Using RPS
1.Go to PANEL WIDE PARAMETERS→Miscellaneous→Duress Type. Select 1.
2.Go to AREA WIDE PARAMETERS→Area Parameters→Duress Enable. Select YES.
3.Go to User Interface→Authority Levels. In the authority levels to be used, select E for
the Send Duress parameter.
8.2Basic and Advanced Commands
Basic CommandsAdvanced Commands
CMD 1 (Master Arm) [Master Arms only the
area assigned to the Keypad]
For each of the following commands, press [9] [9] [ENTER]. Press [NEXT] to view each
command.
–1 - View Log
–2 - Print Log
–3 - Display Revision
–4 - Service Walk
–5 - Default Text
Some programming parameters are preset for compliance with SIA standard CP-01 (false
alarm prevention). These settings are in AREA WIDE PARAMETERS→Area Parameters. They
affect control panel operation as described below.
–Master Arm-No Exit=YES: This setting provides for a Perimeter Delay point to be faulted
when master arming each area, or the arming state defaults to Perimeter Delayed.
–Exit Delay Warning=YES: When this parameter is set to YES, the alarm bell pulses on and
off every two seconds for the remaining 10 sec of Exit Delay.
–Entry Delay Warning=YES: When this parameter is set to YES, the alarm bell pulses on
and off every two seconds for the remaining 10 sec of Entry Delay.
F01U215242 | 01 | 2011.10Quick Reference GuideBosch Security Systems, Inc.
To calculate the switch settings for POPITS, you must determine the value to use in the
calculation. For addresses 9 through 127, subtract 9. For addresses 129 through 247,
subtract 129. Use the following procedure with address 48 as the example, substituting the
actual values in your calculation.
1.Subtract 9 from 48. The result is 39.
2.Set the switches that add up to 39 to the OFF positions (32 + 4 + 2 + 1 = 39).
SW 1 OFF = 32
SW 4 OFF = 4
SW 5 OFF = 2
SW 6 OFF = 1
9.2D9210C Access Control Interface Module Rotary Address
Switch Settings
For additional information, refer to the D9210C Access Control Interface Module Installation and
Operation Guide (P/N: F01U201526).
9.3D720, D1255, D1260, D1265 Dip Switch Settings
For additional information, refer to:
–D720 Series Keypads Installation Instructions (P/N: 7406918000)
–D1255/D1255B Keypads Installation Instructions (P/N: 7406819000)
–D1260/D1260B Keypads Installation Guide (P/N: 48101)
–D1265 Keypads Installation Guide (P/N: F01U169129)
9.4D9131A Dip Switch Settings
For additional information, refer to the Parallel Printer Interface D9131A Installation Guide (P/
N: F01U135506).
9.5D8129 OctoRelay Dip Switch Settings
For additional information, refer to the D8129 OctoRelay Module Operating and Installation
Guide (P/N: F01U036302).
9.6D8128C OctoPOPIT Dip Switch Settings
For additional information, refer to the D8128C OctoPOPOIT Module Operating Instructions (P/
N: 7407710000).
9.7D8128D OctoPOPIT Dip Switch Settings
For additional information, refer to the D8128D OctoPOPOIT Module Installation Guide (P/
N: F01U070537).
For additional information, refer to the B820 SDI2 Inovonics Interface Module Installation Guide
(P/N: F01U215241).
F01U215242 | 01 | 2011.10Quick Reference GuideBosch Security Systems, Inc.
Page 21
D9412GV4/D7412GV4/D7212GV4 Reporting Format Definitions | en21
10Reporting Format Definitions
Modem IIIa2 EventModem IIIa2 Code
D6500 Mode
A point supervisory condition
occurred
A valid local access occurredRsF01NLSSuccessful Download/
A valid remote access callback
occurred
A valid remote access occurred RsssFNRSSuccessful Download/
AC Fail – mains power supplyPssssNATAC Loss1 301 00 000
AC Restore – mains power
supply
Access Denied – Door Secured ADspppNria/idiiiDZppp or
Access Denied – InterlockedADspppNria/idiiiDWppp or
Access Denied – No rights in
area by card
(NEW) Access Denied - No
rights in area by passcode
Access Denied – Unknown IDADspppNriaDDpppAccess Denied1 421 aa uuu
Access GrantedAGspppNria/idiiiDGppp or
Add Card to a UserNsD30NidiiiDAuuuLocal OnlyLocal Only
(NEW) Add Key Fob to User
(Assign Card Event)
AlarmAspppNriaBApppBurglary1 130 aa ppp
Alarm Cross PointAspppNriaBMpppBurglary1 130 aa ppp
Alarm Exit ErrorAspppNria/idiiiEApppEntry/Exit1 134 aa ppp
Alarm with Recent ClosingAspppNria/CRpppEntry/Exit1 459 aa uuu
All Points Tested by UserRsssFNRilTCLocal OnlyLocal Only
All SDI devices are missing,
power is shorted
All SDI devices are restored,
power is normal
An individual SDI device is
missing.
An individual SDI device is
restored.
An invalid remote access
callback occurred
An invalid remote access
occurred
Area Watch EndNsD52Nria/idiiiiTZLocal OnlyLocal Only
1
zzz indicates an SDI, or SDI2 device address value, or network trouble condition. Reference Table 10.2 for more
22en | Reporting Format DefinitionsD9412GV4/D7412GV4/D7212GV4
Modem IIIa
2
EventModem IIIa2 Code
D6500 Mode
Modem IIIa2 Code
Bosch SIA Mode
Contact ID EventContact ID
Code
Area Watch StartNsD51Nria/idiiiiTWLocal OnlyLocal Only
Armed perimeter delayCsiiiNria/idiiiNLArmed STAY3 441 aa uuu
Armed perimeter instantCsiiiNria/idiiiNLArmed STAY3 441 aa uuu
Bypass by SDI deviceNspppNria/pidddUBpppZone/Sensor Bypass1 570 aa ppp
Bypass by SkedNspppNria/aikkkUBpppZone/Sensor Bypass1 570 aa ppp
Bypass by UserNspppNria/idiiiUBpppZone/Sensor Bypass1 570 aa ppp
Bypass PointNspppNriaUBpppZone/Sensor Bypass1 570 aa ppp
Change own passwordNsDO4NidiiiiJViiiiLocal OnlyLocal Only
Change another’s password or
NsDO4NidiiiiJViiiiLocal OnlyLocal Only
card
Checksum failure on
TsD15NYFRAM Checksum Bad1 303 00 000
configuration memory
(NEW) Closing by AccountCsiiiNidiiiCLO/C by account3 401 00 uuu
Closing by AreaCsiiiNria/idiiiCLO/C by User3 401 aa uuu
Closing Early by AreaCsiiiNria/idiiiCKEarly O/C3 451 aa uuu
Closing Late by AreaCsiiiNria/idiiiCJLate O/C3 452 aa uuu
Communication failure by
route group
Communication failure by
route group restored
Communication trouble by
TsB01NrggYCFailure to communicate
event
NsB01NrggYKFailure to communicate
event
TsB01Nrgg/pidddYSCommunication Trouble
1 354 00 000
3 354 00 000
1 350 00
1
zzz
network
Communication trouble by
NsB01Nrgg/pidddYKCommunicationTrouble
3 350 00
1
zzz
network restored
Communication trouble by
TsB01NphhhYSCommunication Trouble1 350 00 000
phone
Communication trouble by
NsB01NphhhYKCommunication Trouble3 350 00 000
phone restored
Control panel battery lowTsss9NYTLow System Battery1 302 00 000
Control panel battery missingTsss9NYMBattery Missing/Dead1 311 00 000
Control panel battery restored
Rsss9NYRLow System Battery3 302 00 000
to normal
(NEW) Control Panel Off-lineTsssFNid5002TSSystem Shutdown1 308 00 F02
(NEW) Control Panel On-lineRsssFNid5002TESystem Shutdown3 308 00 F02
Create Status ReportSssssNYYStatus Report to Follow1 605 00 000
Date changed – no user
NsD07NJDTime/Date Reset1 625 00 000
identified
Dated changed by userNsD07NidiiiJDTime/Date Reset1 625 00 uuu
Delete User by UserNsDO5NidiiiJXiiiLocal OnlyLocal Only
(NEW) DNS FailureTsB01Nrg8/pidddYSCommunication Trouble
(NEW) DNS Failure RestoreNsB01Nrg8/pidddYKCommunication Trouble
1 350 00
3 350 00 1zzz
1
zzz
Door Closed, RestoralRspppNriaDHpppAccess Door propped open 1 426 aa ppp
Door cycled by userAGspppNria/idiiiDGpppLocal OnlyLocal Only
Door Left Open AlarmAspppNriaDLpppAccess Door propped open 1 426 aa ppp
Door Left Open TroubleTspppNriaDMpppAccess Door propped open 1 426 aa ppp
Door locked by userALspppNria/idiiiDYpppLocal OnlyLocal Only
Door secured by userASspppNria/idiiiDCpppLocal OnlyLocal Only
Door unlocked by userAUspppNria/idiiiDOpppLocal OnlyLocal Only
DuressDsiiiNria/idiiiHADuress1 121 aa uuu
(NEW) DNS Failure RPSTsB01Nrg8/pi099YSCommunication Trouble
1
zzz indicates an SDI, or SDI2 device address value, or network trouble condition. Reference Table 10.2 for more
1 350 00
1
zzz
details.
F01U215242 | 01 | 2011.10Quick Reference GuideBosch Security Systems, Inc.
Page 23
D9412GV4/D7412GV4/D7212GV4 Reporting Format Definitions | en23
2
Modem IIIa
EventModem IIIa2 Code
(NEW) DNS Failure Restore
Modem IIIa2 Code
D6500 Mode
Bosch SIA Mode
NsB01Nrg8/pi099YKCommunication Trouble
Contact ID EventContact ID
Code
3 350 00
1
zzz
RPS
(NEW) Equipment Fail
TsD29NIA001System Peripheral Trouble
1 330 00
1
zzz
(SDI2 only)
(NEW) Equipment Restore
(SDI2 only)
RsD29NIR001System Peripheral Trouble
Restore
3 330 00
1
zzz
Event Log OverflowAsD01NJOEvent Log Overflow1 624 00 000
Event Log Threshold has been
TsD01NJLEvent Log 90% Full1 623 00 000
reached
Extend Close Time by AreaTsD26Nria/idiii/
Auto-arm Time Extended1 464 aa uuu
tihhmmCE
Extra PointTspppNriaXEpppMaintenance Alert1 393 aa ppp
Fail To Close by AreaTsssENriaCIFailed to Close1 454 aa 000
Fail To Open by AreaTsssENriaOIFailed to Open1 453 aa 000
Fire AlarmFspppNriaFApppFire1 110 aa ppp
Fire Cancel\siiiNria/idiiiFCCancel1 406 aa uuu
Fire MissingMspppNriaFYpppFire Trouble1 373 aa ppp
Fire Restoral from AlarmHsspppNriaFHpppFire3 110 aa ppp
Fire Restoral from TroubleHspppNriaFJpppFire Trouble3 373 aa ppp
Fire SupervisionEspppNriaFSpppFire Supervisory1 200 aa ppp
Fire Supervision from Restore EspppNriaFVpppFire Supervisory3 200 aa ppp
Fire TroubleGsspppNriaFTpppFire Trouble1 373 aa ppp
Fire Walk Test EndRsssFNria/idiiiFKFire Test3 604 aa uuu
Fire Walk Test StartTsssFNria/idiiiFIFire Test1 604 aa uuu
Force Armed Perimeter DelayCsiiiNria/idiiiNFPartial Arm3 456 aa uuu
Force Armed Perimeter Instant CsiiiNria/idiiiNFPartial Arm3 456 aa uuu
Forced Close Early by AreaCsiiiNria/idiiiCFEarly O/C3 451 aa uuu
Forced Close Late by AreaCsiiiNria/idiiiCFLate O/C3 452 aa uuu
Forced Closing by AreaCsiiiNria/idiiiCFO/C by user3 401 aa uuu
Forced PointTspppNriaXWpppZone/Sensor Bypass1 570 aa ppp
Invalid local access detectedTsF01NLUUnsuccessful access1 413 00 000
(NEW) IP Address ErrorTsssDNETSystem Peripheral Trouble
(NEW) IP Address Error
Restore
Low battery on a wireless
RsssDNERSystem Peripheral Trouble
Restore
TspppNriaXTpppRF Low Battery1 384 aa ppp
1 330 00
3 330 00
1
1
zzz
zzz
point
Low battery restore on a
RspppNriaXRpppRF Low Battery3 384 aa ppp
wireless point
Missing AlarmMspppNriaUZpppGeneral Alarm1 140 aa ppp
Missing Fire SupervisionGMspppNriaFZpppFire Trouble1 200 aa ppp
Missing SupervisionMTspppNriaBZpppLoss of Supervision - RPM 1 382 aa ppp
Missing TroubleVspppNriaUYpppLoss of Supervision - RPM 1 382 aa ppp
(NEW) Network Cable
TsssDNETSystem Peripheral Trouble
1 330 00
1
zzz
Disconnected
(NEW) Network Cable
Connected
RsssDNERSystem Peripheral Trouble
Restore
3 330 00
1
zzz
Non- Fire Cancel Alarm\siiiNria/idiiiBCCancel1 406 aa uuu
Normal start-up of the control
NsD14NRRSystem Reset1 305 00 000
panel
(NEW) Opening by AccountOSiiiNidiiiOPO/C by account1 401 00 uuu
1
zzz indicates an SDI, or SDI2 device address value, or network trouble condition. Reference Table 10.2 for more
24en | Reporting Format DefinitionsD9412GV4/D7412GV4/D7212GV4
Modem IIIa
2
EventModem IIIa2 Code
D6500 Mode
Modem IIIa2 Code
Bosch SIA Mode
Contact ID EventContact ID
Code
Opening by AreaOsiiiNria/idiiiOPO/C by user1 401 aa uuu
Opening Early by AreaOsiiiNria/idiiiOKEarly O/C1 451 aa uuu
Opening Late by AreaOsiiiNria/idiiiOJLate O/C1 452 aa uuu
Parameters changed by RPSNsD02NYGPanel Programming
1 306 00 000
Changed
Phone Line Missing 1TsssBNLT1Telco 1 Fault1 351 00 000
Phone Line Missing 2TsssBNLT2Telco 2 Fault1 352 00 000
Phone Line Restored 1RsssBNLR1Telco 1 Fault3 351 00 000
Phone Line Restored 2RsssBNLR2Telco 2 Fault3 352 00 000
Point Bus FailTsssDNETProtection Loop1 370 00 000
Point Bus Restoral, power
RsssDNERProtection Loop3 370 00 000
normal or bus not missing
RAM Fail with RPSTsF02NRAUnsuccessful access1 413 00 000
Relay Reset by ProgrammerNsD22NpidddROrrrSounder/Relay3 320 00 000
Relay Reset by SkedNsD20NaikkkROrrrSounder/Relay3 320 00 000
Relay Reset by UserNsD18NidiiiROrrrSounder/Relay3 320 00 000
Relay Set by ProgrammerNsD21NpidddRCrrrSounder/Relay1 320 00 000
Relay Set by SkedNsD19NaikkkRCrrrSounder/Relay1 320 00 000
Relay Set by UserNsD28NidiiiRCrrrSounder/Relay1 320 00 000
Remote Reset – System was
NsD11NRNSystem Reset1 305 00 000
reset by RPS
(NEW) Replace User’s Key Fob
NsD30NidiiiDAuuuLocal OnlyLocal Only
(Assign Card Event)
(NEW) Remove User’s Key Fob
NsD30NidiiiDAuuuLocal OnlyLocal Only
(Assign Card Event)
RestoralRspppNriaBRpppSensor Trouble3 380 aa ppp
Restoral from AlarmRspppNriaBHpppBurglary3 130 aa ppp
Restoral from Ground FaultRspppNriaBRpppGround Fault3 310 01 000
(NEW) RF Interference
TsD08NXQRF RCVR Jam
1 344 00
1
zzz
(SDI2 only)
(NEW) RF Interference Restore
RsD08NXHRF RCVR Jam Restore
3 344 00
1
zzz
(SDI2 only)
(NEW) RF Transmitter Low
TsD10NidiiiiXTBattery Test Failure1 309 00 uuu
Battery
(Key Fob)
(NEW) RF Transmitter Low
RsD10NidiiiiXRBattery Test Restore3 309 00 uuu
Battery Restore
(Key Fob)
(NEW) RF Transmitter
Gss001NriaFTpppMaintenance Alert1 393 aa ppp
Maintenance
(NEW) RF Transmitter
Hss001NriaFRpppMaintenance Alert3 393 aa ppp
Maintenance Restoral
ROM Checksum Fail (Not
AsD12NYXROM Checksum bad1 304 00 000
Used)
(NEW) SDI Device AC Fail
TsssDNEPExp. Module AC Loss
1 342 00
1
zzz
(SDI2 only)
(NEW) SDI Device AC Fail
RsssDNEQExp. Module AC Restore
3 342 00
1
zzz
Restore (SDI2 only)
1
zzz indicates an SDI, or SDI2 device address value, or network trouble condition. Reference Table 10.2 for more
details.
F01U215242 | 01 | 2011.10Quick Reference GuideBosch Security Systems, Inc.
Page 25
D9412GV4/D7412GV4/D7212GV4 Reporting Format Definitions | en25
(NEW) SDI2 Open TroubleTsssDNpiidddETExpansion Module Failure
(NEW) SDI2 Open Trouble
RsssDNpidddERExpansion Module Failure
3 330 00
1 333 00
3 333 00 1zzz
1
1
zzz
zzz
Restoral
Sensor ResetNsD27Nria/idiiiXIrrrSounder/Relay3 320 00 000
Service BypassQspppNriaXKpppService Request1 616 aa ppp
Service Bypass CancelQspppNriaXNpppService Request3 616 aa ppp
Service Walk Test EndRsssFNidiiiTEService On/Off Premises3 466 aa uuu
Service Walk Test StartTsssFNria/idiiiTSService On/Off Premises1 466 aa uuu
Sked Changed – No User
NsD06NaikkkJSSchedule Change1 630 00 000
Identified
Sked Changed by UserNsD06Nidiii/aikkkJSSchedule Change1 630 00 000
Swinger BypassNspppNriaUBpppSwinger Bypass1 575 aa ppp
Test Report – System Normal,
Expanded Status
RsssENRP & see D6600
CIM for Status
Periodic Test Report1 602 00 000
Items
Test Report – System Normal,
RsssENRPPeriodic Test Report1 602 00 000
Non-expanded Status
1
zzz indicates an SDI, or SDI2 device address value, or network trouble condition. Reference Table 10.2 for more
26en | Reporting Format DefinitionsD9412GV4/D7412GV4/D7212GV4
Modem IIIa
2
EventModem IIIa2 Code
Test Report – System Offnormal, Expanded Status
Modem IIIa2 Code
D6500 Mode
Bosch SIA Mode
RsssENRY & see D6600
CIM for Status
Contact ID EventContact ID
Code
Periodic Test – System
1 608 00 000
Trouble Present
Items
Test Report – System Offnormal, Non-expanded Status
Time Changed – No User
RsssENRYPeriodic Test – System
1 608 00 000
Trouble Present
NsD07NJTTime/Date Reset1 625 00 000
Identified
Time Changed by Receiver
NsD07Nid254JTTime/Date Reset1 625 00 F01
Sync
Time Changed by UserNsD07NidiiiJTTime/Date Reset1 625 00 uuu
TroubleTspppNriaBTpppSensor Trouble1 380 aa ppp
Trouble with Ground FaultTspppNriaBTpppGround Fault1 310 01 000
Unverified EventKspppNriaUGpppCross-zone Trouble1 378 aa ppp
User Alarm 7Usss7Nria/idiiiUAPersonal Emergency1 101 aa uuu
User Alarm 9UUsss9Nria/idiiiPADuress1 121 aa uuu
User Authority level has
NsD40NidiiiJZiiiLocal OnlyLocal Only
changed
User Passcode Tamper – Too
NsD03NriaJAWrong Code Entry1 461 aa 000
Many Attempts
Walk Test EndRsssFNria/idiiiTEWalk test mode3 607 aa uuu
Walk Test StartTsssFNria/idiiiTSWalk test mode1 607 aa uuu
Watchdog Reset – SDI Device
NsD09NpidddYWSystem Reset1 305 00 000
Reported identifies the Source
1
zzz indicates an SDI, or SDI2 device address value, or network trouble condition. Reference Table 10.2 for more
details.
Table 10.1 Reporting Format Definitions
F01U215242 | 01 | 2011.10Quick Reference GuideBosch Security Systems, Inc.
Page 27
D9412GV4/D7412GV4/D7212GV4 Reporting Format Definitions | en27
Contact ID data value (zzz) translations
SDI/SDI2 Bus Addresszzz Data ValuesDescription
1-16001-016SDI Keypad 1 through 16
17-19017-019SDI Printer 1 through 3
33-40033-040Access Module 1 through 8
80080SDI Automation Module1
88088SDI Network Module 1
92092SDI Network Module 2
2-25201-224SDI2 Octo-input Modules 1
through 24
66-77301-312SDI2 Octo-output Modules 1
through 12
151801SDI2 Premise RF Module
161-168851-858SDI2 RF Repeater 1 through 8
173401SDI2 Network Module 1
174402SDI2 Network Module 2
176-183501-508SDI2 Power Supply Module 1
through 8
88-91088-091Routes 1 through 4 on SDI
Network Module 1
92-95092-095Routes 1 through 4 on SDI
Network Module 2
11, 21, 31, 41411, 421, 431, 441Routes 1 through 4 on SDI2
Network Module 1
12, 22, 32, 42412, 422, 432, 442Routes 1 through 4 on SDI2
Network Module 2
99499DNS lookup error of RPS
hostname
Tab le 10 .2 Contact ID data value (zzz) translations table
What does it mean when my keypad reads "CALL FOR SERVICE"?
That keypad is not receiving data from the control panel.
What does it mean when my keypad reads "SERVICE KEYPAD"?
A supervised keypad has lost communications with the control panel.
How do I arm an area that is not assigned to my keypad?
Add to the FUNCTION LIST a menu item with a function code of 1 and with CC ADDRESS 1-16
set to YES, and a menu item with a function code of 2 and with CC ADDRESS 1-16 set to Yes.
Assign the function codes to the necessary command center. The new menu items allow your
users to select the area they wish to arm or disarm.
How do I perform area-specific functions from a keypad?
Use the MOVE TO AREA command (CMD 50) to move to an area within the keypad’s scope.
Can I default a lockcode without knowing the lockcode?
No. You must send the unit to the Bosch Repair Center.
How do I upgrade the control panel’s firmware version?
When an update is available, you may either:
–use the optional firmware upgrade key to upgrade the firmware. Lift the control panel
faceplate cover to access the port to insert the upgrade key and read the instructions
located on the back of the faceplate.
OR
–obtain the firmware update file from Bosch and, using the RPS Firmware Update Wizard,
connect to the panel and send the new version to the control panel (local user
authorization may be required). Always re-test your system when the firmware version
has been changed.
How do I add an access card using the command center?
Use the ADD USER command (CMD 56) to add an access card. Present the access card to the
assigned door to add the card.
What does it mean when my keypad reads "9210 NOT READY"?
No door is assigned to the command center. Check the ASSIGN DOOR parameter within
COMMAND CENTER ASSIGNMENTS menu item, and then enter the D9210C address (1 - 8).
What are SDI addresses 33 to 40?
They are D9210C addresses.
What are SKEDS 41 to 56?
They are Open and Close windows.
How do I test a relay from the keypad?
Use the RELAY CONTROL command (CMD 54) to toggle relays.
How do I toggle the on-board relays A, B, and C?
Use the RELAY CONTROL command (CMD 54), and then the relay number: 253 for A; 254 for
B; and 255 for C.
How many Amp Hours can the panel sustain?
You can connect two (2) 18 Ah batteries for a total of 36 Ah. You can gain up to an additional
27 Ah with by connecting a D8132 module.
F01U215242 | 01 | 2011.10Quick Reference GuideBosch Security Systems, Inc.
Is the control panel compatible with digital or VOIP phone lines?
The control panel has been tested with only analog lines. Use a B420 Ethernet Communication
Module or a DX4020 to transmit over Ethernet or a ITS-DX4020-G to transmit over cellular.
You can use a C900V2 to convert analog signals to Ethernet for transmission to a D6600/
D6100i receiver.
How do I silence a trouble condition?
Use the SILENCE TROUBLE SOUNDER command (CMD 4) to silence a trouble condition.
How do I clear alarm memory?
Ensure all points are normal, and the enter your passcode and press [ESC], or press the
[Clear] soft key.
How do I determine if I have a ground fault?
On the control panel, measure voltage on terminal 9 (common) and terminal 10 (earth
ground). Approximately 6.5 to 6.8 VDC is normal voltage and equals no ground fault.
Disconnect wires until you see normal voltage to find your ground.
Can I add wireless capability to this control panel?
Yes. By adding the B820 SDI2 Interface Module, you are able to connect to an Inovonics
EN4200 EchoStream Serial Receiver via the SDI2 bus. By doing so, this allows you to connect
to any Inovonics EchoStream wireless peripheral.
What type of cable do I use to connect my computer’s COM port to a serial-enhanced direct
connection using the DX4010V2?
A D89 null modem cable or USB-A to USB-B cable is required.
How can I determine which points are not ready when my keypad reads "NOT READY TO
ARM"?
Press the NEXT key to scroll through faulted points. If the VIEW POINT STATUS menu item is
enabled, you can access it through the menu to determine the state of the faulted point.
What does it mean when my keypad reads "CHECK DEVICE"?
A point is faulted. The point is one that is configured to display as a device in the POINT INDEX
by marking YES for the DISPLAY AS DEVICE parameter.
I hear a trouble tone from my keypad but no point is shown as in trouble on the keypad.
How do I resolve this?
A point generates a trouble tone (buzz) when faulted if is configured to do so. To determine
which points are configured to buzz, look in the POINT INDEX for points with a non-zero value
for the BUZZ ON FAULT parameter.
How can I determine the meaning of an undefined signal received from central station?
Press 99 [ENTER] on the keypad to reveal the VIEW LOG menu item. Locate the signal in the
log by date and time.
Yes. RPS version 5.14 or later allows you to program all parameters of your GV4 control panel.
Keypad Programming, a function of the Tools Menu accessed with 99 [ENTER], allows you to
program many parameters of your GV4 control panel, for example, the RPS passcode. Refer to
Section 3.5 Programming Using the Keypad Tools Menu, page 10.
How do I set the address for the D1265 keypad?
Hold the Zero key for approximately 10 seconds.
Where can I find free documentation and on-line support for this product?
Go to www.boschsecurity.us.
What is the default passcode to enter into the web browser for the B420 Ethernet
Communication Module?
The correct default passcode is: B42V2.
How do I add an EN1224-ON keyfob per user?
Use the CMD 56 menu to add a keyfob to the desired user.
How do I add or remove an RF Point from the B820 SDI2 Inovonics Interface Module?
At the keypad, enter in [99] [Enter], followed by [Tools Menu], and then [RF Points].
F01U215242 | 01 | 2011.10Quick Reference GuideBosch Security Systems, Inc.