These operation instructions are part of the product.
●
Retain operation instructions during product life.
●
Pass on instructions to any subsequent user or owner of the product.
Purpose of the document:
This document contains information for installation, commissioning, operation and maintenance staff . It is intended
to support device installation and commissioning.
Reference documents:
Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA
(refer to <Addresses>).
SA 07.2 – SA 16.2 /SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Safety instructions
1.Safety instructions
1.1.Basic information on safety
Standards/directives
Safety instructions/warn-
ings
Qualification of staff
Commissioning
Operation
Our products are designed and manufactured in compliance with recognised
standards and directives.This is certified in a Declaration of Incorporation and an
EU Declaration of Conformity.
The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
All personnel working with this device must be familiar with the safety and warning
instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to av oid personal injury or property
damage.
Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out by suitably qualified personnel authorised by the end user or contractor
of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Prior to commissioning, it is important to check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation.The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Prerequisites for safe and smooth operation:
●
Correct transport, proper storage, mounting and installation, as well as careful
commissioning.
●
Only operate the device if it is in perf ect condition while observing these instructions.
●
Immediately report any faults and damage and allow for corrective measures.
●
Observe recognised rules for occupational health and safety.
●
Observe national regulations.
●
During operation, the housing warms up and surface temperatures > 60 °C may
occur.To prevent possible b urns, we recommend checking the surf ace temperature using an appropriate thermometer and wearing protective gloves, if required, prior to working on the device.
Protective measures
The end user or the contractor are responsible for implementing required protective
measures on site, such as enclosures, barriers, or personal protective equipment
for the staff.
Maintenance
T o ensure saf e device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior written consent of the manufacturer.
1.2.Range of application
AUMA multi-turn actuators are designed for the operation of industrial valves, e.g.
globe valves, gate valves, butterfly valves, and ball valves.
Other applications require explicit (written) confirmation by the manufacturer.
The following applications are not permitted, e.g.:
●
●
●
●
Industrial trucks according to EN ISO 3691
Lifting appliances according to EN 14502
Passenger lifts according to DIN 15306 and 15309
Service lifts according to EN 81-1/A1
Potentially explosive areas, with the exception of zone 22
●
Radiation exposed areas in nuclear power plants
No liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of the device's
designated use.
Information
These operation instructions are only valid for the "clockwise closing" standard
version, i.e. driven shaft turns clockwise to close the valve.
1.3.Applications in Ex zone 22 (option)
Actuators of the indicated series basically meet the requirements for applications in
dust hazardous locations of ZONE 22 in compliance with the ATEX directive
2014/34/EU.
To comply with all requirements of the ATEX directive, observe the following points:
●
Actuators are marked with the explosion protection designation II3D... for use
in ZONE 22.
●
Maximum surface temperature of actuators
-T150 °C for ambient temperatures up to +60 °C or
-T190 °C for ambient temperatures up to +80 °C.
Increased dust deposit on the equipment was not considered for the determin-
ation of the maximum surface temperature.
●
The following conditions must be fulfilled to respect the maximum permissible
surface temperatures at the actuator:
-Respecting types of duty and technical manufacturer data
-Correct connection of thermal motor protection (thermoswitches or PTC
thermistor)
●
●
●
●
●
1.4.Warnings and notes
The following warnings draw special attention to saf ety-rele v ant procedures in these
operation instructions, each marked by the appropriate signal word (DANGER,
WARNING, CAUTION, NOTICE).
Ambient temperature
Tripping temperature
Thermal motor protection
Maximum
surface temperature
T150 °C140 °Cup to +60 °C
T190 °C155 °Cup to +80 °C
The connector may only be connected or disconnected when not live.
The cable glands and cable entries used have to meet the requirements of
category II3D and must at least comply with enclosure protection IP67.
The actuators must be connected by means of an external earth connection
(accessory part) to the equipotential earth bonding or integrated into an earthed
piping system.
T o ensure comb ustible dust hazard protection, seal hollow shaft against ing ress
of dust:
-Using threaded plug (ref. no. 511.0) and appropriate seal
-Using metallic stem protection tube, protective cap and V-seal (ref. no.
568.1, 568.2, 568.3) for rising valve stem
As a general rule, the requirements of IEC 60079 Parts 14 and 17 must be respected in dust hazardous locations. During commissioning, service, and
maintenance, special care as well as qualified and trained personnel are required
for safe actuator operation.
6
SA 07.2 – SA 16.2 /SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Safety instructions
Indicates an imminently hazardous situation with a high level of risk. Failure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a medium level of risk. F ailure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a low level of risk. Failure to
observe this warning may result in minor or moderate injury . Ma y also be used
with property damage.
Potentially hazardous situation. Failure to observe this warning may result in
property damage. Is not used for personal injury.
Arrangement and typographic structure of the warnings
Type of hazard and respective source!
Potential consequence(s) in case of non-observance (option)
→
Measures to avoid the danger
→
Further measure(s)
Safety alert symbol warns of a potential personal injury hazard.
The signal word (here: DANGER) indicates the level of hazard.
1.5.References and symbols
The following references and symbols are used in these instructions:
Information
The term Information preceding the text indicates important notes and information.
Symbol for CLOSED (valve closed)
Symbol for OPEN (valve open)
Important information before the next step.This symbol indicates what is required
for the next step or what has to be prepared or observed.
< >Reference to other sections
T erms in brack ets shown abov e refer to other sections of the document which provide
further information on this topic.These terms are either listed in the index, a heading
or in the table of contents and may easily be located.
7
SA 07.2 – SA 16.2 /SAR 07.2 – SAR 16.2
Identification AM 01.1/AM 02.1
2.Identification
2.1.Name plate
Figure 1: Arrangement of name plates
[1]Actuator name plate
[2]Actuator controls name plate
[3]Motor name plate
[4]Additional plate, e.g. KKS plate (Power Plant Classification System)
Actuator name plate
Figure 2: Actuator name plate (example)
(= manufacturer logo); (= CE mark)
[1]Name of manufacturer
[2]Address of manufacturer
[3]Type designation
[4]Order number
[5]Serial number
[6]Speed
[7]Torque range in direction CLOSE
[8]Torque range in direction OPEN
[9]Type of lubricant
[10]Permissible ambient temperature
[11]Can be assigned as an option upon customer request
[12]Enclosure protection
[13]Data Matrix code
8
SA 07.2 – SA 16.2 /SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Identification
Actuator controls name plate
Figure 3: Actuator controls name plate
(= manufacturer logo)
[1]Type designation
[2]Order number
[3]Serial number
[4]Actuator terminal plan
[5]Wiring diagram for controls
[6]Mains voltage
[7]AUMA power class switchgear
[8]Permissible ambient temperature
[9]Enclosure protection
[10]Control
[11]Data Matrix code
Motor name plate
Figure 4: Motor name plate (example)
(= manufacturer logo); (= CE mark)
[1]Motor type
[2]Motor article number
[3]Serial number
[4]Current type, mains voltage
[5]Rated power
[6]Rated current
[7]Type of duty
[8]Enclosure protection
[9]Motor protection (temperature protection)
[10]Insulation class
[11]Speed
[12]Power factor cos phi
[13]Mains frequency
[14]Data Matrix code
9
SA 07.2 – SA 16.2 /SAR 07.2 – SAR 16.2
Identification AM 01.1/AM 02.1
Descriptions referring to name plate indications
Type designationFigure 5:Type designation (example)
1.Type and size of actuator
2.Flange size
Type and size
These instructions apply to the following devices types and sizes:
●
Type SA = Multi-turn actuators for open-close duty
Sizes: SA 07.2, 07.6, 10.2, 14.2, 14.6, 16.2
●
Type SAR = Multi-turn actuators for modulating duty
Sizes: 07.2, 07.6, 10.2, 14.2, 14.6, 16.2
●
Type AM = AUMA MATIC actuator controls
Sizes: 01.1, 02.1
Order number
Actuator serial number
AUMA power class for
switchgear
The product can be identified using this number and the technical data as well as
order-related data pertaining to the device can be requested.
Please always state this number for any product inquiries.
On the Internet at http://www.auma.com > Service & Support >myAUMA, we offer
a service allowing authorised users to download order-related documents such as
wiring diagrams and technical data (both in German and English), inspection certificate
and the operation instructions when entering the order number.
Table 1:
Description of serial number (with example 0516MD12345)
MD123451605
Positions 1+2: Assembly in week = week 0505
Positions 3+4:Year of manufacture = 201616
Internal number for unambiguous product identificationMD12345
The switchgear used in the actuator controls (reversing contactors/thyristors) are
classified according to AUMA power classes (e.g. A1, B1, ....).The power class
defines the max. permissible rated power (of the motor) the switchgear has been
designed for. The rated power (nominal power) of the actuator motor is indicated in
kW on the motor name plate. For the assignment of the AUMA power classes to the
nominal power of the motor types, refer to the separate electrical data sheets.
For switchgear without assignment to an y power classes, the actuator controls name
plate does not indicate the power class but the max. rated power in kW.
Control
10
Table 2:
Control examples (indications on actuator controls name plate)
DescriptionInput signal
24 V DC
48 V DC
60 V DC
115 V AC
Control voltage 24 V DC for OPEN - CLOSE control via digital inputs (OPEN,
STOP, CLOSE)
Control voltage 48 V DC OPEN - CLOSE control via digital inputs (OPEN,
STOP, CLOSE)
Control voltage 60 V DC OPEN - CLOSE control via digital inputs (OPEN,
STOP, CLOSE)
Control voltage 115 V A C f or OPEN - CLOSE control via digital inputs (OPEN,
STOP, CLOSE)
Input current for setpoint control via analogue input0/4 – 20 mA
SA 07.2 – SA 16.2 /SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Identification
Data Matrix code
2.2.Short description
Multi-turn actuator
Actuator controls
Local controls
When registered as authorised user, you ma y use our A UMA Assistant App to scan
the Data Matrix code and directly access the order-related product documents without
having to enter order number or serial number.
Figure 6: Link to AUMA Assistant App:
For further Service & Support, software/apps/... refer to www.auma.com.
Definition in compliance with EN 15714-2/EN ISO 5210:
A multi-turn actuator is an actuator which transmits torque to a valve f or at least one
full revolution. It is capable of withstanding thrust.
AUMA multi-turn actuators SA 07.2 – SA 16.2/SAR 07.2 – SAR16.2 are driven by
an electric motor and are capable of withstanding thrust in combination with output
drive type A. For manual operation, a handwheel is provided. Switching off in end
positions may be either by limit or torque seating. Actuator controls are required to
operate or process the actuator signals.
AM 01.1/AM02.1 actuator controls are used to operate AUMA actuators and are
supplied ready for use.The actuator controls may be mounted directly to the actuator
or separately on a wall bracket.The functions of AM 01.1/AM02.1 actuator controls
include standard valve control in OPEN-CLOSE duty, position indications and different
signals right through to position control (option).
Operation (via push-buttons), setting and indication can be performed directly at the
actuator controls (contents of these instructions).
11
SA 07.2 – SA 16.2 /SAR 07.2 – SAR 16.2
Transport, storage and packaging AM 01.1/AM 02.1
3.Transport, storage and packaging
3.1.Transport
For transport to place of installation, use sturdy packaging.
Hovering load!
Risk of death or serious injury.
→
Do NOT stand below hovering load.
→
Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.
→
Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.
→
Actuators mounted to gearboxes: Attach ropes or hooks f or the purpose of lifting
by hoist only to the gearbox using eyebolts and NOT to the actuator.
→
Actuators mounted to controls: Attach ropes or hooks for the purpose of lifting
by hoist only to the actuator and NOT to the controls.
→
Respect total weight of combination (actuator, actuator controls , gearbox, v alve)
→
Secure load against falling down, sliding or tilting.
→
Perform lift trial at low height to eliminate any potential danger e.g. by tilting.
Figure 7: Example: Lifting the actuator
Table 3:
Weight of AM 01.1/AM 02.1 actuator controls
Table 4:
Weights for multi-turn actuators SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2
with 3-phase AC motors
Type designation
Actuator
SAR 07.2
SAR 07.6
Motor type
1)
Weight approx. [kg]Electrical connection
Weight
approx. [kg]
7AUMA plug/socket connector with screw-type connection
2)
19VD...SA 07.2/
20AD...
20VD...SA 07.6/
21AD...
12
SA 07.2 – SA 16.2 /SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Transport, storage and packaging
Weights for multi-turn actuators SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2
with 3-phase AC motors
Type designation
Motor type
1)
Actuator
SAR 10.2
SAR 14.2
SAR 14.6
SAR 16.2
Refer to motor name plate1)
Indicated weight includes AUMA NORM multi-turn actuator with 3-phase AC motor, electrical con-
2)
nection in standard version, output drive type B1 and handwheel. For other output driv e types, heed
additional weights.
Table 5:
Weights for multi-turn actuators SA 07.2 – SA 16.2 / SAR 07.2 – SAR 16.2
With 1-phase AC motors
Protect against floor dampness by storage on a shelf or on a wooden pallet.
→
Cover to protect against dust and dirt.
→
Apply suitable corrosion protection agent to uncoated surfaces.
Damage due to excessively low storage temperatures!
→
AUMA MATIC actuator controls may NOT be stored below –40 °C
For long-term storage (more than 6 months), observe the following points:
1.Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
14
SA 07.2 – SA 16.2 /SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Transport, storage and packaging
2.At an interval of approx. 6 months:
Check for corrosion. If first signs of corrosion show , apply ne w corrosion protection.
3.3.Packaging
Our products are protected by special packaging for transport when leaving the
factory .The packaging consists of environmentally friendly materials which can easily
be separated and recycled.We use the following packaging materials: wood,
cardboard, paper, and PE foil. For the disposal of the packaging material, we
recommend recycling and collection centres.
15
SA 07.2 – SA 16.2 /SAR 07.2 – SAR 16.2
Assembly AM 01.1/AM 02.1
4.Assembly
4.1.Mounting position
The product described in this document can be operated in any mounting position.
Restriction:When using oil instead of grease within the actuator gear housing, the
hollow shaft mounting position must be perpendicular, with the flange pointing
downward.The type of lubricant used is indicated on the actuator name plate (short
designation F...= grease; O...= oil).
4.2.Handwheel fitting
InformationFor transport reason, handwheels with a diameter of 400 mm and larger are supplied
separately within the scope of delivery.
Figure 8: Handwheel
[1]Spacer
[2]Input shaft
[3]Handwheel
[4]Retaining ring
1.If required, fit spacer [1] on input shaft [2].
2.Slip handwheel [3] onto input shaft.
3.Secure handwheel [3] using the retaining ring [4] supplied.
Information
The retaining ring [4] (together with these operation instructions) is stored in a
weatherproof bag, which is attached to the device prior to delivery.
4.3.Multi-turn actuator: mount to valve/gearbox
Danger of corrosion due to damage to paint finish and condensation!
→
Touch up damage to paint finish after work on the device.
→
After mounting, connect the device immediately to electrical mains to ensure
that heater minimises condensation.
4.3.1.Output drive type A
●
Application
Output drive for rising, non-rotating valve stem
●
Capable of withstanding thrust
16
SA 07.2 – SA 16.2 /SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Assembly
Design
Information
Output mounting flange [1] with axial bearing stem nut [2] form one unit.Torque is
transmitted to valve stem [3] via stem nut [2].
Figure 9: Design of output drive type A
[1]Output mounting flange
[2]Stem nut with dog coupling
[3]Valve stem
To adapt the actuators to available output drive types A with flanges F10 and F14
(year of manufacture: 2009 and earlier), an adapter is required.The adapter can be
ordered from AUMA.
4.3.1.1. Stem nut: finish machining
This working step is only required if stem nut is supplied unbored or with pilot
✔
bore.
Figure 10: Output drive type A
[1]Stem nut
[2]Axial needle roller bearing
[2.1] Axial bearing washer
[2.2] Axial needle roller and cage assembly
[3]Spigot ring
1.Remove spigot ring [3] from output drive.
2.Remove stem nut [1] together with axial needle roller bearings [2].
17
SA 07.2 – SA 16.2 /SAR 07.2 – SAR 16.2
Assembly AM 01.1/AM 02.1
3.Remove axial bearing washers [2.1] and axial needle roller and cage assemblies
[2.2] from stem nut [1].
4.Drill and bore stem nut [1] and cut thread.
Information: When fixing in the chuck, make sure stem nut runs true!
5.Clean the machined stem nut [1].
6.Apply sufficient Lithium soap EP multi-purpose grease to axial needle roller and
cage assemblies [2.2] and axial bearing washers [2.1], ensuring that all hollow
spaces are filled with grease.
7.Place greased axial needle roller and cage assemblies [2.2] and axial bearing
washers [2.1] onto stem nut [1].
8.Re-insert stem nut [1] with bearings [2] into output drive.
Information:Ensure that dogs or splines are placed correctly in the keyway of
the hollow shaft.
9.Screw in spigot ring [3] until it is firm against the shoulder.
4.3.1.2. Multi-turn actuator (with output drive type A): mount to valve
Figure 11: Assembly of output drive type A
[1]Valve stem
[2]Output drive type A
[3]Screws to actuator
[4]Valve flange
[5]Screws to output drive
1.If the output drive type A is already mounted to the multi-turn actuator: Loosen
screws [3] and remove output drive type A [2].
2.Check if the flange of output drive type A matches the valve flange [4].
3.Apply a small quantity of grease to the valve stem [1].
4.Place output drive type A on valve stem and turn until it is flush on the valve
flange.
5.Turn output drive type A until alignment of the fixing holes.
6.Screw in fastening screws [5], however do not completely tighten.
7.Fit multi-turn actuator on the valve stem so that the stem nut dogs engage into
the output drive sleeve.
The flanges are flush with each other if properly engaged.
➥
8.Adjust multi-turn actuator until alignment of the fixing holes.
9.Fasten multi-turn actuator with screws [3].
18
SA 07.2 – SA 16.2 /SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Assembly
10. Fasten screws [3] crosswise with a torque according to table.
Table 9:
Tightening torques for screws
Tightening torque [Nm]Threads
Strength class A2-80/A4–80
10M6
24M8
48M10
82M12
200M16
392M20
11. Turn multi-turn actuator with handwheel in direction OPEN until valve flange
and output drive A are firmly placed together.
12. Tighten fastening screws [5] between valve and output drive type A crosswise
applying a torque according to table.
4.4.Output drive types B and E
●
Application
For rotating, non-rising valve stem
●
Not capable of withstanding thrust
Design
Connection between hollow shaft and valv e or gearbox via output drive sleeve fixed
to the hollow shaft of the multi-turn actuator via retaining ring.
When exchanging the output drive slee v e , later retrofitting to a different output drive
type is possible
●
Output drive types B and E: Output drive sleeve with bore according to DIN
3210
●
Output drive types B1 – B4: Output driv e slee ve with bore according to EN ISO
5210
2.Check if output drive of multi-turn actuator [1] matches the output drive of
valve/gearbox or valve/gearbox valve shaft [2/3].
3.Apply a small quantity of grease to the valve or gearbox shaft [3].
4.Fit multi-turn actuator [1].
Information: Ensure that the spigot fits uniformly in the recess and that the
mounting faces are in complete contact.
20
SA 07.2 – SA 16.2 /SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Assembly
5.Fasten multi-turn actuator with screws according to table.
Information: We recommend applying liquid thread sealing material to the
screws to avoid contact corrosion.
6.Fasten screws crosswise to a torque according to table.
Table 10:
Tightening torques for screws
Tightening torque [Nm]Threads
Strength class A2-80/A4–80
10M6
24M8
48M10
82M12
200M16
392M20
4.5.Accessories for assembly
4.5.1.Stem protection tube for rising valve stem
Figure 14: Assembly of the stem protection tube
[1]Protective cap for stem protection tube (fitted)
[1]*Option: Protective cap made of steel (screwed)
[2]Stem protection tube
[3]V-seal
1.Seal all threads with hemp, Teflon tape, or thread sealing material.
21
SA 07.2 – SA 16.2 /SAR 07.2 – SAR 16.2
Assembly AM 01.1/AM 02.1
2.Screw stem protection tube [2] into thread and tighten it firmly.
Information: For stem protection tubes made of two or more segments, all
parts have to be thoroughly screwed together.
Figure 15: Protection tube made of segments with threaded sleeves (>900 mm)
[2]Segment of stem protection tube
[3]V-seal
[4]Threaded sleeve
3.Push down the sealing ring [3] onto the housing.
Information: For mounting segments, push down seals of segments down to
the sleeve (connecting piece).
4.Check whether protective cap [1] for stem protection tube is a vailable , in perfect
condition and tightly placed on or screwed to the tube.
Risk of bending or oscillation of protection tubes exceeding a length of 2 m!
Risk of damage at stem and/or protection tube.
→
Secure protection tubes exceeding 2 m by an appropriate support.
4.6.Mounting positions of local controls
The mounting position of the local controls is designed according to the order. If,
after mounting the actuator to the valve or the gearbo x on site , the local controls are
in an unfavourable position, the mounting position can be changed at a later date.
Four mounting positions shifted by respectively 90° are possible.
Figure 16: Mounting positions
22
SA 07.2 – SA 16.2 /SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Assembly
4.6.1.Mounting positions: modify
Hazardous voltage!
Risk of electric shock.
→
Disconnect device from the mains before opening.
1.Loosen screws and remove local controls.
2.Loosen 3 screws of the board, turn board to the new position and fasten the
screws.
3.Check whether O-ring is in good condition, correctly insert O-ring.
4.Turn local controls into new position and re-place.
Cable damage due to twisting or pinching!
Risk of functional failures.
→
Turn local controls by a maximum of 180°.
→
Carefully assemble local controls to avoid pinching the cables.
5.Fasten screws evenly crosswise.
23
SA 07.2 – SA 16.2 /SAR 07.2 – SAR 16.2
Electrical connection AM 01.1/AM 02.1
5.Electrical connection
5.1.Basic information
Danger due to incorrect electrical connection
Failure to observe this warning can result in death, serious injury , or property damage.
→
The electrical connection must be carried out exclusively by suitably qualified
personnel.
→
Prior to connection, observe basic information contained in this chapter.
→
After connection but prior to applying the voltage, observe the <Commissioning>
and <Test run> chapters.
Wiring diagram/terminal
plan
Permissible networks
(supply networks)
Current type, mains
voltage, mains fre-
quency
The pertaining wiring diagram/terminal plan (in German or English) is attached to
the device in a weather-proof bag, together with these operation instructions. It can
also be requested from AUMA (state order number, refer to name plate) or
downloaded directly from the Internet (http://www.auma.com).
Actuator controls (actuators) are suitable for use in TN and TT networks with directly
earthed star point for mains voltage up to maximum V AC. Use in IT networks for
nominal voltages up to maximum V AC are permissible. For IT network, a suitable,
approved insulation monitor measuring the pulse code is required.
Type of current, mains voltage and mains frequency must match the data on the
actuator controls and motor name plates. Also refer to chapter <Identification>/<Name
plate>.
Figure 17: Motor name plate (example)
[1]Type of current
[2]Mains voltage
[3]Mains frequency (for 3-phase and 1-phase AC motors)
External supply of the
electronics
Protection and sizing on
site
24
If electronics is supplied externally with 24 V DC, the power supply is smoothed via
an internal 1,000 µF capacitor).When selecting the power supply, care must be
taken to consider the capacitor inrush current upon powering up the unit.
For short-circuit protection and for disconnecting the actuator from the mains, fuses
and disconnect switches have to be provided by the customer.
The current values for sizing the protection can be derived from the current
consumption of the motor (refer to motor name plate) plus the current consumption
of actuator controls.
We recommend adapting the switchgear sizing to the max. current (I
) and selecting
max
and setting the overcurrent protection device in compliance with the indications in
the electrical data sheet.
SA 07.2 – SA 16.2 /SAR 07.2 – SAR 16.2
AM 01.1/AM 02.1 Electrical connection
Table 11:
Current consumption controls
Max. current consumptionMains voltage
575 mA100 to 120 V AC (±10 %)
275 mA208 to 240 V AC (±10 %)
160 mA380 to 500 V AC (±10 %)
500 mA24 V DC (+20 %/-15 %) and AC motor
Table 12:
Maximum permissible protection
max. protectionRated powerSwitchgear
16 A (gL/gG)up to 1.5 kWReversing contactor A1
32 A (gL/gG)up to 7.5 kWReversing contactor A2
63 A (gL/gG)up to 15 kWReversing contactor A3
16 A (g/R) I²t<1,500A²sup to 1.5 kWThyristor B1
32 A (g/R) I²t<1,500A²sup to 3 kWThyristor B2
63 A (g/R) I²t<5,000A²sup to 5.5 kWThyristor B3
(switchgear with power class)
1)
Potential of customer
connections
Safety standards
Connecting cables
The AUMA power class (A1, B1, ...) is indicated on the actuator controls name plate1)
Consider the motor starting current (IA) (refer to electrical data sheet) when selecting
the circuit breaker .We recommend tripping characteristics D or K for circuit breakers
in accordance with IEC 60947-2. For controls with thyristors, we recommend safety
fuses instead of circuit breakers.
We recommend refraining from using residual current devices (RCD). However, if
an RCD is used within the mains, the residual current device must be of type B.
If actuator controls are mounted separately from actuator (actuator controls on wall
bracket): Consider length and cross section of connecting cable when defining the
protection required.
All input signals (control inputs) must be supplied with the same potential.
All output signals (status signals) must be supplied with the same potential.
Safety measures and safety equipment must comply with the respectively valid
national on site specifications. All externally connected devices shall comply with
the relevant safety standards for the place of installation.
●
We recommend using connecting cables and connecting terminals according
to rated current (IN) (refer to motor name plate or electrical data sheet).
●
For device insulation, appropriate (v oltage-proof) cables must be used. Specify
cables for the highest occurring rated voltage.
●
Use connecting cable with appropriate minimum rated temperature.
●
For connecting cables exposed to UV radiation (outdoor installation), use UV
resistant cables.
●
For the connection of position transmitters, screened cables must be used.
Cable installation in ac-
cordance with EMC
Signal and fieldbus cables are susceptible to interference. Motor cables are
interference sources.
●
Lay cables being susceptible to interference or sources of interference at the
highest possible distance from each other.
●
The interference immunity of signal and fieldbus cab les increases if the cables
are laid close to the earth potential.
●
If possible, avoid laying long cables and make sure that they are installed in
areas being subject to low interference.
25
SA 07.2 – SA 16.2 /SAR 07.2 – SAR 16.2
Electrical connection AM 01.1/AM 02.1
●
Avoid par allel paths with little cable distance of cables being either susceptible
to interference or interference sources.
[1]Cover
[2]Socket carrier with screw-type terminals
Plug-in electrical connection with screw-type terminals for power and control contacts.
Control contacts also available as crimp-type connection as an option.
S version (standard) with three cable entries. SH version (enlarged) with additional
cable entries. For cable connection, remove the AUMA plug/socket connector and
the socket carrier from cover.
Table 13:
Electrical connection via AUMA plug/socket connector
Control contactsPower contacts
No. of contacts max.
Connection diameter max.
earth conductor (PE)
6 mm2 (flexible)
10 mm2 (solid)
50 pins/sockets6 (3 equipped) + protective
1 to 50U1, V1, W1, U2, V2, W2, PEDesignation
250 V750 VConnection voltage max.
16 A25 ARated current max.
Screw connection, crimp-type (option)Screw connectionType of customer connection
2
2.5 mm
(flexible or solid)
For some special motors, the connection of the power terminals (U1, V1, W1, U2,
V2, W2) is not performed via the AUMA plug/socket connector but via a terminal
board directly at the motor.
26
Loading...
+ 58 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.