These operating instructions will help you to install and operate the
Uninterruptible Power Supply (UPS), PROTECT A. 1000 or
PROTECT A. 1400, all referred to as PROTECT A. in this
document, safely and properly, and for its intended purpose. These
operating instructions contain important information necessary to
avoid dangers during operation.
Please read these instructions carefully prior to
commissioning!
These operating instructions are a composite part of
PROTECT A.
The operator of this unit is obliged to communicate these
instructions to all personnel transporting or starting PROTECT A.
or performing maintenance or any other work on the unit.
Validity
These operating instructions comply with the current technical
specifications of PROTECT A. at the time of publication. The
contents do not constitute a subject matter of the contract, but
serve for information purposes only.
Warranty and Liability
We reserve the right to alter any specifications given in these
operating instructions, especially with regard to technical data
and operation.
Claims in connection with supplied goods must be submitted
within eight days of receipt, along with the packing slip.
Subsequent claims cannot be considered.
The warranty does not apply for damage caused by noncompliance with these instructions (such damage also
includes damaging the "Q.A." warranty seal). AEG will accept
no liability for consequential damage. AEG will rescind all
obligations such as warranty agreements, service contracts,
2
etc. entered into by AEG and its representatives without prior
notification in the event of maintenance and repair work being
carried out with anything other than original AEG spare parts
or spare parts purchased by AEG.
Handling
PROTECT A. is designed and constructed so that all
necessary steps for start-up and operation can be performed
without any internal manipulation of the unit. Maintenance and
repair work may only be performed by trained and qualified
personnel.
Hotline
If you still have questions after having read these operating
instructions, please contact your dealer or our "Hotline":
No part of these operating instructions may be transmitted or
reproduced by any electronic or mechanical means without
the express prior written permission of AEG.
Read these operating instructions carefully prior to
commissioning of the PROTECT A. UPS and observe the
safety instructions!
Only use the unit if it is in a technically perfect condition and
always in accordance with its intended purpose, while being
aware of safety and danger aspects, and in accordance with
the operating instructions! Immediately eliminate any faults
which could be detrimental to safety.
The following pictograms are used in these operating
instructions to identify dangers and important information:
Danger!
Identifies risk of fatal injury to the operator.
Warning!
Identifies risk of injury and risk of damage to the
unit and parts of the unit.
Information!
Useful and important hints for the operation of the
i
UPS.
2.2 Safety Instructions for PROTECT A.
This chapter contains important instructions for the PROTECT
A. UPS. These must be followed during assembly, operation
and maintenance of the uninterruptible power supply and the
batteries.
The UPS carries high voltage. Danger! The unit
may only be opened by trained and qualified
personnel. Repairs may only be carried out by
qualified customer service staff!
5
The output may be live, even if the UPS is not
connected to the mains supply, as the UPS has
its own internal power supply (battery)!
For health and safety reasons, the unit must be
earthed correctly!
PROTECT A. may only be operated with or connected to a
230 VAC mains with protective grounding using a mains
connection cable with PE conductor (included in the delivery)
that has been tested in accordance with German standards
(VDE).
Danger! Risk of burning!
The battery has powerful short-circuit currents.
Incorrect connection or isolation faults can lead to
melting of the plug connections, sparking potential
and severe burns!
The unit has a warning signal that sounds when
the battery voltage of PROTECT A. is exhausted
or when the UPS is not working in its normal
mode.
Observe the following safety instructions to
ensure permanent operational safety of and
safe work with the UPS:
♦ Do not dismantle the UPS!
(The UPS does not contain any parts which require
regular maintenance. Bear in mind that the warranty
will be invalidated if the unit is opened!)
♦ Do not install the unit in direct sunshine or in close
proximity of heaters!
♦ The unit is designed to be installed inside in heated
rooms. Never install the UPS in the vicinity of water or
in an excessively damp environment!
♦ Condensation may occur if the UPS is brought from a
cold environment into the room where it is to be
installed. The UPS must be absolutely dry prior to startup. As a result, leave it to acclimatise for at least two
hours.
6