AEG PROTECT A User Manual

OPERATING INSTRUCTION UPS
PROTECT A.
PROTECT A.
PROTECT A.PROTECT A.
PROTECT A. 1400
1
1 Notes on these Operating
Instructions
Duty to Provide Information
These operating instructions will help you to install and operate the Uninterruptible Power Supply (UPS), PROTECT A. 1000 or PROTECT A. 1400, all referred to as PROTECT A. in this document, safely and properly, and for its intended purpose. These operating instructions contain important information necessary to avoid dangers during operation.
Please read these instructions carefully prior to commissioning!
These operating instructions are a composite part of PROTECT A.
The operator of this unit is obliged to communicate these instructions to all personnel transporting or starting PROTECT A. or performing maintenance or any other work on the unit.
Validity
These operating instructions comply with the current technical specifications of PROTECT A. at the time of publication. The contents do not constitute a subject matter of the contract, but serve for information purposes only.
Warranty and Liability
We reserve the right to alter any specifications given in these operating instructions, especially with regard to technical data and operation.
Claims in connection with supplied goods must be submitted within eight days of receipt, along with the packing slip. Subsequent claims cannot be considered.
The warranty does not apply for damage caused by non­compliance with these instructions (such damage also includes damaging the "Q.A." warranty seal). AEG will accept no liability for consequential damage. AEG will rescind all obligations such as warranty agreements, service contracts,
2
etc. entered into by AEG and its representatives without prior notification in the event of maintenance and repair work being carried out with anything other than original AEG spare parts or spare parts purchased by AEG.
Handling
PROTECT A. is designed and constructed so that all necessary steps for start-up and operation can be performed without any internal manipulation of the unit. Maintenance and repair work may only be performed by trained and qualified personnel.
Hotline
If you still have questions after having read these operating instructions, please contact your dealer or our "Hotline":
Phone: +49 (0)180 5 234 787 Fax: +49 (0)180 5 234 789 Internet: www.aegpss.de
Copyright
No part of these operating instructions may be transmitted or reproduced by any electronic or mechanical means without the express prior written permission of AEG.
© Copyright AEG 2006. All rights reserved.
3
1.1 Declaration of Conformity
4
2 Safety
2.1 Important Safety Instructions
Read these operating instructions carefully prior to commissioning of the PROTECT A. UPS and observe the safety instructions!
Only use the unit if it is in a technically perfect condition and always in accordance with its intended purpose, while being aware of safety and danger aspects, and in accordance with the operating instructions! Immediately eliminate any faults which could be detrimental to safety.
The following pictograms are used in these operating instructions to identify dangers and important information:
Danger!
Identifies risk of fatal injury to the operator.
Warning!
Identifies risk of injury and risk of damage to the unit and parts of the unit.
Information!
Useful and important hints for the operation of the
i
UPS.
2.2 Safety Instructions for PROTECT A.
This chapter contains important instructions for the PROTECT A. UPS. These must be followed during assembly, operation and maintenance of the uninterruptible power supply and the batteries.
The UPS carries high voltage. Danger! The unit
may only be opened by trained and qualified personnel. Repairs may only be carried out by
qualified customer service staff!
5
The output may be live, even if the UPS is not connected to the mains supply, as the UPS has its own internal power supply (battery)!
For health and safety reasons, the unit must be earthed correctly!
PROTECT A. may only be operated with or connected to a 230 VAC mains with protective grounding using a mains connection cable with PE conductor (included in the delivery) that has been tested in accordance with German standards (VDE).
Danger! Risk of burning!
The battery has powerful short-circuit currents. Incorrect connection or isolation faults can lead to melting of the plug connections, sparking potential and severe burns!
The unit has a warning signal that sounds when the battery voltage of PROTECT A. is exhausted or when the UPS is not working in its normal mode.
Observe the following safety instructions to ensure permanent operational safety of and safe work with the UPS:
Do not dismantle the UPS!
(The UPS does not contain any parts which require regular maintenance. Bear in mind that the warranty will be invalidated if the unit is opened!)
Do not install the unit in direct sunshine or in close
proximity of heaters!
The unit is designed to be installed inside in heated
rooms. Never install the UPS in the vicinity of water or in an excessively damp environment!
Condensation may occur if the UPS is brought from a
cold environment into the room where it is to be installed. The UPS must be absolutely dry prior to start­up. As a result, leave it to acclimatise for at least two hours.
6
Never connect the mains input to the UPS output!
Ensure that no fluids or foreign bodies can penetrate
the UPS!
Do not block the side air vents of the unit! Keep
children away from the unit and ensure that objects are never inserted through the vents!
Do not connect household appliances such as
hairdryers to the UPS!
The mains connection should be near the unit and
easily accessible to facilitate disconnecting the AC input or pulling out the plug!
During operation, do not disconnect the mains
connection cable from the UPS or from the socket outlet in the building (shockproof socket), otherwise the protective grounding of the UPS and all the loads connected to it will be cancelled.
Danger! Electric shocks!
Even after the mains voltage has been disconnected, the components within the UPS remain connected to the battery and can thus cause electric shocks. It is therefore imperative to disconnect the battery circuit before carrying out any maintenance or repair work!
If it is necessary to replace the battery or carry out maintenance work, this must be done by or under the supervision of a person familiar with batteries and the necessary safety precautions!
Only authorised persons are allowed in the vicinity of the batteries!
When replacing the battery/batteries, the following must be observed: Only ever use identical maintenance-free sealed lead batteries with the same data as the original battery/batteries.
Danger! Explosive!
Never throw batteries into open fire. Never open or damage batteries. Electrolyte may leak out and damage skin and eyes. It may be toxic!
7
Therefore, take the following safety precautions when working with batteries:
Take off watches, rings and other metallic objects!
Always use tools with insulated handles!
Batteries can cause electric shocks and high short-circuit currents.
For personal safety reasons, never switch on the main switch when the mains connector of PROTECT A. is disconnected!
8
3 System Description
PROTECT A. is an uninterruptible power supply (UPS) for essential loads such as personal
i
Mains filter in the mains input incl. mains energy
A.V.R. control system
(automatic voltage regulation with mains operation)
Battery charger for charging the battery
Battery as energy storage medium for bridging mains
Inverter for the supply of connected loads with AC
Static bypass switch for switching over the loads to the
computers (PCs) or ISDN telecommunication equipment and similar devices. It consists of:
backfeed protection
failures (for supplying the inverter)
voltage during mains failures
inverter in the case of a mains failure
UPS Block diagram PROTECT A.
The UPS is connected to a shockproof socket between the public utility's mains and the loads to be protected.
Under normal operating conditions, i.e. if PROTECT A. is supplied with mains voltage, the battery charger will ensure that the battery is always completely charged. During this operating status, the loads connected to PROTECT A. are supplied with voltage via double mains filters which provide
9
effective protection against mains voltage peaks and high­frequency faults.
In case of sustained mains undervoltage or overvoltage within defined ranges, the automatic voltage regulator (A.V.R.) further stabilises the load voltage. As a result, voltage fluctuations in the public utility's mains are reduced to a level which is acceptable for the loads. This is performed without recourse to the internal energy storage, something which in turn has a positive effect on battery availability.
The static bypass switch is activated in the event of a mains failure. The inverter then takes over the voltage supply of the connected loads, in order to prevent the risk of data loss or damage to the loads. PROTECT A. supplies voltage until the battery is discharged, allowing you to shut down your IT system properly and switch it off. The standby time mainly depends on the connected loads. If the mains power supply is back to normal values, the UPS will switch back the loads to mains supply. The battery charger will then recharge the battery.
For safety reasons (as required by German standards, VDE), the mains input in the unit will be disconnected by a two-pole switch in the event of a mains failure. Energy backfeed to the mains and voltage supply to the pins of the mains connector are thus reliably avoided.
10
4 Set-Up and Operation
Installing the UPS is as easy as following the steps shown.
4.1 Inspection
Remove the UPS from its packaging and inspect it for damage that may have occurred during shipping. If any damage is discovered, repack the unit and return it to the place of purchase.
4.2 Placement
Install the UPS unit in any protected environment that provides adequate airflow around the unit which is free from excessive dust, corrosive fumes and conductive contaminants.
Do not operate your UPS in an environment where the ambient temperature or humidity is high. Also, place the UPS at least 20 cm away from the monitor to avoid interference.
11
In
coming phone, fax,
4.3 Charging
This unit is shipped from the factory with its internal battery fully charged, however, some power may be lost during shipping and the battery should be recharged prior to use. Plug the unit into an appropriate power supply and allow the UPS to charge fully by leaving it plugged in for at least 8 hours with no load (no electrical devices such as computers, monitors, etc.).
4.4 Computer connection
Connect one computer-related device to each of the power sockets found on the back of the UPS.
8 hours
4.5 Data lines protection
Plug the incoming internet line into the “In” socket at the back of the PROTECT A. UPS.
modem line
12
RS232
-
connection
USB port
Use one more internet line cable and plug one end of the internet line cable to the “Out” socket at the back of the PROTECT A. UPS. Plug the other end of the modem input socket as shown.
4.6 USB and serial cable connection
To allow for unattended system shutdown for your operating system, connect the USB or the RS232 serial cable as shown below. For the USB serial cable just simply plug into the UPS and PC and it will be auto detected.
4.7 Turn On/Off
To turn on the PROTECT A., press the power switch lightly. To turn off the PROTECT A., press the power switch again.
4.8 Deep discharge protection
The PROTECT A. is equipped with Green Power Function. For saving power and protecting the battery, this method of deep discharge protection is adopted in inverter mode.
4.9 Battery removal
Disconnect all power sources before battery replacement. Follow Fig. 1 below to remove the screw located on the bottom of the front panel and then open the front cover.
13
Fig. 1
Fig. 2
Fig. 3
After removing the front cover, follow Fig. 2 above to remove partition by unscrewing it. Then follow Fig. 3 to remove the battery.
4.10 Shutdown- and UPS management software
The "CompuWatch" software specially developed for these purposes by AEG continuously checks the mains supply and the UPS status.
14
In conjunction with the "intelligent" UPS, this ensures that the availability of IT components and data security are guaranteed.
The "CompuWatch" shutdown software supports different operating systems: Windows 98SE/ME, Windows NT/2000/ XP, Linux SUSE, Linux RedHat, Novell NetWare, IBM AIX, HP-UX, SUN Solaris, Mac OS, and others.
Refer to the manual on the CD for details about installing the software on the various operating systems.
5 UPS overview
Connections, Operation / Display Elements:
Front view
Rear view
1 Red LED to signal "Warning/fault"
2 LED bar graph for UPS load and battery
capacity. The bar graph show the load of the UPS system if the mains power is available (normal operation). In the battery operation, the LEDs indicate the capacity of the batteries: 0 ~ 25%: 1. LED 26% ~ 50%: 1. and 2. LED 51% ~ 75%: 1., 2. and 3. LED 76% ~ 100%: All 4 LEDs are lighting
3 Green LED lighting to signal "Mains”
Green LED flashing: Battery mode
4 Main switch of the UPS (mains switch)
1 Load connections (UPS outputs)
2 Mains connection (UPS input)
3 Data line interface for phone, fax, modem
4 RS232 communication interface
(SUB-D 9-pin socket)
5 USB port
6 Input breaker
15
Transfer time at mains
Operating temperature
5.1 Specifications
MODELL
Type
UPS-input
UPS-output
Battery
Indicator
Acoustic alarm
Protection
General data
Communication
Input voltage
Input voltage range without battery mode Frequency (auto selection) Rated output voltage /AVR-technology Rated output voltage in battery mode Frequency in battery mode
outage
Output Waveform
Type
Autonomy time (full Load) Recharge time (to 90% of rated capacity)
AC mode
Backup mode
Fault
Backup mode
Low battery
Overload
Battery replacement
Fault USP
Size W x H x D (mm)
Weight (kg)
range
Audible noise (1 m distance)
Interfaces
Shutdown-Software (on CD)
PROTECT A. 1000 PROTECT A. 1400
1000 VA / 600 W 1400 VA / 840 W
220 Vac / 230 Vac / 240 Vac
170 – 280 Vac
50 / 60 Hz ± 5 Hz
220 Vac / 230 Vac / 240 Vac
±10%
50 / 60 Hz ± 1 Hz
2 – 6 ms (typical)
Modified sinewave
12 V / 7 Ah x 2 12 V / 9 Ah x 2
3 min
8 h
Green LED lighting
LED bar graph (LED 2 to 5) indicates the load capacity
Green LED flashing
LED bar graph (LED 2 to 5) indicates the battery capacity
Red LED lighting
Sounding every 10 seconds
Sounding every second
Sounding every 0.5 second
Sounding every 2 seconds
Continuously sounding
Discharge, overcharge, and overload protection
140 x 180 x 370
14 kg 14,5 kg
0° - 40°C
Relative humidity: 0 – 90 % (non-condensing)
< 45 dB (A)
USB and RS232 for status and measurement levels
Included for all typical operating systems
(e.g. Windows, Linux, Mac)
16
Verify that the load matches the
6 Trouble shooting
SYMPTOM CAUSE REMEDY
No LED display on the front panel
Alarm buzzer beeps continuously when AC supply is normal
When power failure, back-up time is short
Mains normal but LED is flashing
Communication lost between UPS and computer.
Missing battery Charge battery up to 4 hours
Battery fault Replace with the same type of
Power switch not pressed Turn on the switch again
UPS overload
UPS overload Remove some non-critical load
Battery voltage is too low Charge battery 4 hours or more
Battery fault due to high temperature operational environment, or improper treatment of battery
Fuse is blown Replace with the same type of
Power cable is loose Reconnect the power cable
Software not properly installed
Cable not properly connected Check if the RS232-cable is
battery
UPS capability as specified in the specs
Replace with the same type of battery
fuse
properly
Check the settings of the software
properly connected to COM1 / COM2 of the computer and reconfirm the settings once again
If any abnormal situations occur that are not listed above, please call the service centre immediately.
17
Guarantee certificate
Type: …….…………………......................................................
Serial-no.: ……………………..……………...............................
Date of purchase: …………….............……………………........
Trading stamp / Signature
Specifications are subject to change without notice.
AEG Power Supply Systems GmbH
Emil-Siepmann-Str. 32
59581 Warstein-Belecke
Germany
Operating Instructions UPS
BAL 8000015757 EN
AEG0206EN
18