AEG PROTECT B. 1500, PROTECT B. 3000, PROTECT B. 2000, PROTECT B. 1000, PROTECT B. 750 User Manual

...
OPERATING INSTRUCTIONS UPS
PROTECT B.
750
PROTECT B.
PROTECT B. 1000 PROTECT B. 1500 PROTECT B. 2000
1
PROTECT B. 3000
The following security advices are an important component of the manual and will prevent any operation errors and protect you against possible dangers. Read the manual thoroughly before you first use the appliance.
2
1 Notes on these Operating
Instructions
Duty to Provide Information
These operating instructions will help you to install and operate the U PROTECT B. 750, PROTECT B. 1000, PROTECT B. 1500, PROTECT B. 2000 or PROTECT B. 3000 as well as the associated external battery units PROTECT B. 1500 BP, PROTECT B. 2000 BP or PROTECT B. 3000 BP – all referred to as PROTECT B. in this document – safely and properly, and for its intended purpose. These operating instructions contain important information necessary to avoid dangers during operation.
Please read these instructions carefully prior to commissioning!
These operating instructions are a composite part of PROTECT B.
The operator of this unit is obliged to communicate these operating instructions to all personnel transporting or starting up PROTECT B. or performing maintenance or any other work on the unit.
ninterruptible Power Supply (UPS),
Validity
These operating instructions comply with the current technical specifications of PROTECT B. at the time of publication. The contents do not constitute a subject matter of the contract, but serve for information purposes only.
Warranty and Liability
Our goods and services are subject to the general conditions of supply for products of the electrical industry, and our general sales conditions. We reserve the right to alter any specifications given in these operating instructions, especially with regard to technical data and operation.
3
Claims in connection with supplied goods must be submitted within eight days of receipt, along with the packing slip. Subsequent claims cannot be considered.
The warranty does not apply for damage caused by non­compliance with these instructions (such damage also includes damaging the warranty seal). AEG will accept no liability for consequential damage. AEG will rescind all obligations such as warranty agreements, service contracts, etc. entered into by AEG and its representatives without prior notification in the event of maintenance and repair work being carried out with anything other than original AEG spare parts or spare parts purchased by AEG.
Handling
PROTECT B. is designed and constructed so that all necessary steps for start-up and operation can be performed without any internal manipulation of the unit. Maintenance and repair work may only be performed by trained and qualified personnel.
Illustrations are provided to clarify and facilitate certain steps. If danger to personnel and the unit cannot be ruled out in the
case of certain work, it is highlighted accordingly by pictograms explained in Chapter 3.
Hotline
If you still have questions after having read these operating instructions, please contact your dealer or our "Hotline":
Tel.: +49 (0)180 5 234 787 Fax: +49 (0)180 5 234 789 Internet: www.AEGpartnernet.com
Copyright
No part of these operating instructions may be transmitted, reproduced and/or copied by any electronic or mechanical means without the express prior written permission of AEG.
© Copyright AEG 2009. All rights reserved.
4
Table of Contents
1 Notes on these Operating Instructions.............................3
2 System Description ..........................................................7
2.1 Overview ...................................................................7
2.2 Functionality..............................................................8
3 Safety .............................................................................10
3.1 General Safety Instructions.....................................10
3.2 Safety Instructions for PROTECT B........................10
3.3 Certification .............................................................14
3.4 Technical Data........................................................15
4 Set-Up and Operation ....................................................20
4.1 Unpacking and Inspection.......................................20
4.2 Point of installation..................................................21
4.3 Connections, Operation / Display Elements............22
4.3.1 Front view:........................................................22
4.3.2 Operating panel ...............................................23
4.3.3 Rear view (connections): .................................24
5 Commissioning...............................................................26
5.1 Deployment.............................................................26
5.1.1 Tower (Stand alone deployment).....................26
5.1.2 19” Rack Mount Setup.....................................28
5.2 Additional battery installation setup.........................32
5.3 Emergency Power Off (EPO) set up.......................33
5.4 Electric start-up.......................................................34
5.4.1 Connection.......................................................34
5.4.2 Configuration....................................................35
5.5 Operation.................................................................36
5.5.1 Normal Operation.............................................36
5.5.2 Battery Operation / Autonomous Operation.....36
5.5.3 Unit Overload...................................................37
5.5.4 System Diagnosis / Battery Test......................38
5
5.6 Interfaces and communication................................39
5.6.1 Data line protection RJ11 and RJ45
(modem / telephone / fax / network).................39
5.6.2 Computer interfaces RS232 and USB.............40
5.6.3 Communication slot
(PROTECT B.1500 / B.2000 / B.3000):............40
5.6.4 Shutdown and UPS management software.....40
6 Signalling and failure solution.........................................42
6.1 LED display.............................................................42
6.2 Audible Alarm Trouble Shooting: ............................44
6.3 General Fault Diagnosis and Fault Rectification.....44
7 Maintenance...................................................................46
7.1 Battery replacement................................................47
8 Storage, Dismantling and Disposal................................52
9 Glossary.........................................................................53
9.1 Technical terms.......................................................53
6
2 System Description
PROTECT B. is an Uninterruptible Power Supply (UPS) for essential loads such as PCs,
i
The PROTECT B. series is a compact, interactive, sinusoidaly operating USP, available with an output power rate of 750, 1000, 1500, 2000 and 3000 VA.
The design of the USP allows horizontal / lying operation (Rack/19" with 2U) and vertical / standing operation (Tower).
2.1 Overview
The front of the UPS provides several LEDs and four push buttons for easy configuration, control and management. The panel also informs about the state of the power in the alternating current (AC) branch, indications on net failures and the charging state of the Output of the UPS. You will find two LED bars for output load and battery capacity, two state indicators (net available, battery active) and four alarm indicators (power failure, failure, battery discharged, overload). With the push button the acoustic alarm can be deactivated and the self test of the UPS will be started.
workstations, servers, network components, telecommunication equipment and similar devices.
Power connectors, communication interfaces and connections for telephone and network are located on the rear of the PROTECT B. Important UPS parameters and data are constantly monitored and are transmitted via USB or serial RS232 to the “CompuWatch” Software on the management computer. The optional SNMP adapter allows remote monitoring via SNMP connector and multi server shutdown (starting with B.1500).
The main features of the PROTECT B. are:
VI (Line Interactive) protection technology
with sinusoidal output voltage
AVR control system
(automatic voltage regulation with mains operation)
7
Micro processor control for high availability,
suited for generator mode
Easy extension of battery capacity using external
batteries (starting with B.1500)
Advanced battery management with integrated
protection against extreme discharge and overcharge
Overload and short circuit proofMaintenance free, sealed lead batteries,
hot swappable (starting with B.1500)
User friendly display
for optimal readability / configuration
Intelligent monitoring system
with USB and RS232 interface
Surge protection (RJ11 / RJ45)
for phone, fax, modem and network (10/100MBit/s)
Expansion slot for extension cards, i.e. SNMP
(starting with B.1500)
“CompuWatch” software for shutdown, state report
and measurement for all popular operating systems (among others Windows, Mac, Linux)
Compact design / variable deployment
due to combination design as tower / rack (19” kit available optionally for all models)
2.2 Functionality
The UPS is connected to a shockproof socket between the public utility's mains and the loads to be protected.
Under normal operating conditions, i.e. if PROTECT B. is supplied with mains voltage, the battery charger will ensure that the battery is always completely charged.
During this operating status, the loads connected to PROTECT B. are supplied with voltage via mains filters which provide effective protection against mains voltage peaks and high-frequency faults.
In case of sustained mains undervoltage or overvoltage within defined ranges, the automatic voltage regulator (AVR) further
8
stabilizes the load voltage. As a result, voltage fluctuations in the public utility's mains are reduced to a level which is acceptable for the loads. This is performed without recourse to the internal energy storage, something which in turn has a positive effect on battery availability.
UPS block diagram PROTECT B.
The static bypass switch is activated in the event of a mains failure. The inverter then takes over the voltage supply of the connected loads, in order to prevent the risk of data loss or damage to the loads. PROTECT B. supplies voltage until the battery is discharged, allowing you to shut down your IT system properly and switch it off. The standby time mainly depends on the connected loads. If the mains power supply is back to normal values, the UPS will switch back the loads to mains supply. The battery charger will then recharge the battery.
For safety reasons (as required by German standards, VDE), the mains input in the unit will be disconnected by a two-pole switch in the event of a mains failure. Energy backfeed to the mains and voltage supply to the pins of the mains connector are thus reliably avoided.
Furthermore, additional protective measures ensure effective protection for the data/network interface.
9
3 Safety
The unit
may only be opened by trained and qualified
Repairs may only be carried out by
3.1 General Safety Instructions
Read these operating instructions carefully prior to commissioning of the PROTECT B. UPS and observe the safety instructions!
Only use the unit if it is in a technically perfect condition and always in accordance with its intended purpose, while being aware of safety and danger aspects, and in accordance with the operating instructions! Immediately eliminate any faults which could be detrimental to safety.
The following pictograms are used in these operating instructions to identify dangers and important information:
Danger!
Identifies risk of fatal injury to the operator.
Attention!
Identifies risk of injury and risk of damage to the unit and parts of the unit.
Information!
i
Useful and important information for operating the UPS.
3.2 Safety Instructions for PROTECT B.
This chapter contains important instructions for the PROTECT B. UPS. These must be followed during assembly, operation and maintenance of the uninterruptible power supply and the batteries.
The UPS carries high voltage. Danger! personnel.
qualified customer service staff!
10
The output may be live, even if the UPS is not
connected to the mains supply,
as the UPS has
For health and safety reasons, the unit must be
circuit currents.
Incorrect connection or isolation faults can lead
connections, sparking
The unit has a warning signal that sounds when
the battery voltage of PROTECT B. is exhausted
or when the UPS is not working in its normal
Observe the following safety instructions to
manent operational safety of and safe
its own internal power supply (battery)!
earthed correctly!
PROTECT B. may only be operated with or connected to a 230 Vac mains with protective grounding using a mains connection cable with PE conductor (included in the delivery) that has been tested in accordance with German standards (VDE).
Danger! Risk of burning!
The battery has powerful short­to melting of the plug
potential and severe burns!
mode.
ensure per work with the UPS:
Do not dismantle the UPS! (The UPS does not contain
any parts which require regular maintenance. Bear in mind that the warranty will be invalidated if the unit is opened!)
Do not install the unit in direct sunshine or in close
proximity of heaters!
The unit is designed to be installed inside in heated
rooms. Never install the UPS in the vicinity of water or in an excessively damp environment!
Condensation may occur if the UPS is brought from a cold
environment into the room where it is to be installed. The UPS must be absolutely dry prior to start-up. As a result, leave it to acclimatize for at least two hours.
11
Never connect the mains input to the UPS output.
Even after the mains voltage has been
disconnected, the components within the UPS
remain connected to the battery and can thus
hocks. It is therefore imperative
to disconnect the battery circuit before carrying
If it is necessary to replace the battery or carry
out maintenance work, this must be done by or
t familiar with
Only authorised persons are allowed in the
Ensure that no fluids or foreign bodies can penetrate the
UPS!
Do not block the air vents of the unit! Keep children away
from the unit and ensure that objects are never inserted through the air vents!
Do not connect household appliances such as hairdryers
to the UPS!
The mains connection should be near the unit and easily
accessible to facilitate disconnecting the AC input or pulling out the plug!
During operation, do not disconnect the mains connection
cable from the UPS or from the socket outlet in the building (shockproof socket), otherwise the protective grounding of the UPS and all the loads connected to it will be cancelled.
Danger! Electric shocks!
cause electric s out any maintenance or repair work!
under the supervision of a specialis batteries and the necessary safety precautions!
vicinity of the batteries!
When replacing the battery/batteries, the following must be observed: Only ever use identical maintenance-free sealed lead batteries with the same data as the original battery/ batteries.
12
Danger! Explosive!
Never open
or damage batteries. (Electrolyte may leak out
lectric shocks and high
Never throw batteries into open fire. and damage skin and eyes. It may be toxic!)
Batteries can cause e short-circuit currents.
Therefore, take the following safety precautions when working with batteries:
Take off watches, rings and other metallic
objects!
Only use tools with insulated handles! For personal safety reasons, never switch on the
main switch when the mains connector of PROTECT B. is disconnected!
13
3.3 Certification
14
3.4 Technical Data
Model power
PROTECT B. 750 750 VA / 500 W PROTECT B. 1000 1000 VA / 700 W PROTECT B. 1500 1500 VA / 1050 W PROTECT B. 2000 2000 VA / 1340 W PROTECT B. 3000 3000 VA / 2100 W
UPS Input
Rated output voltage 220 / 230 / 240 Vac Input voltage range 154 / 161 / 168 Vac ± 4%
Frequency (autom. detection) 50 / 60 Hz ± 5 Hz
Curr. consumption (full-load) PROTECT B. 750 5 A
PROTECT B. 1000 8 A PROTECT B. 1500 10 A PROTECT B. 2000 10 A PROTECT B. 3000 16 A Connection IEC power connector
(wide) 176 / 184 / 192 Vac ± 4%
(standard) until 264 / 276 / 288 Vac ± 4%
> 40 Hz (generator mode)
(IEC 320)
USP output
Rated output voltage / 220 / 230 / 240 Vac AVR-technology
Rated output voltage in ± 5 % battery mode
Frequency in battery mode 50 Hz / 60 Hz ± 0.1 Hz
15
Output current power (at 230 Vac) PROTECT B. 750 3.2 A PROTECT B. 1000 4.3 A PROTECT B. 1500 6.5 A PROTECT B. 2000 8.7 A PROTECT B. 3000 13 A Transfer time at mains outage 2-4 ms (typical),
6 ms max. 13 ms max.
in generator operation Voltage waveform sinusoidal Outlets Non-heating appliance
connectors acc. to IEC 320 Overload response 110% for 3 min. /
at mains operation 150% for 200 ms Overload response 110% for 30 s /
at battery operation 120% for 100ms Overheat and short circuit protection Yes
Battery
Autonomy time at rated load 5 min.
Extendable from B.1500 Rated time with external battery packs
Number of connected battery packs
1 15 min. - - - 15 min. - - - 24 min. 2 30 min. 30 min. 27 min. 27 min. 45 min. 3 50 min. - - - 40 min. - - - 55 min. 4 65 min. 65 min. 50 min. 50 min. 75 min.
Autonomy time at rated load
1500 VA Tower
1500 VA Rack
2000 VA Tower
2000 VA Rack
3000 VA Tower/Rack
Deep discharge protection / yes Overload protection
16
Recharge time 3 h (UPS in (to 90 % of rated capacity) standard configuration)
7 h (UPS with 1 add. battery pack)
12 h (UPS with 2 add. battery packs)
18 h (UPS with 3 add. battery packs)
24 h (UPS with 4 add. battery packs)
Type Sealed, maintenance free,
hot swappable (from B.1500) PROTECT B. 750 12 V / 7 Ah x 2 PROTECT B. 1000 12 V / 9 Ah x 2 PROTECT B. 1500 / B. 1500BP 12 V / 7 Ah x 4 PROTECT B. 2000 / B. 2000BP 12 V / 9 Ah x 4 PROTECT B. 3000 12 V / 5 Ah x 8 PROTECT B. 3000 BP 12 V / 5 Ah x 8 x 2
Communication
Interfaces USB and RS232
Additionally from
PROTECT B.1500:
Communication slot
for i.e. SNMP as well as
input contact for
emergency shutdown Shutdown-Software on CD For all typical operating
systems, e.g. Windows,
Linux, Mac, Unix, FreeBSD,
Novell, Sun
Physical data
Noise (1 m distance) < 45 dB(A) Operation temperature range 0°C - 40°C Humidity 0 - 90% (without condens.) Installation height up to 1000 m at rated power
17
Number of outlets PROTECT B. 750 4 x IEC 320 PROTECT B. 1000 6 x IEC 320 PROTECT B. 1500 6 x IEC 320 (sep. module) PROTECT B. 2000 6 x IEC 320 (sep. module) PROTECT B. 3000 8 x IEC 320-10 A
1 x IEC 320-16 A
Equipment colour Black line Size W x H x D (mm) Standard model
(Size in horizontal / lying view) PROTECT B. 750 235 x 88 x 383 PROTECT B. 1000 235 x 88 x 383 PROTECT B. 1500 + B.1500BP (2 x 217) x 88 x 414 PROTECT B. 2000 + B.2000BP (2 x 217) x 88 x 414 PROTECT B. 3000 438 x 88 x 582 PROTECT B. 1500BP 217 x 88 x 414 PROTECT B. 2000BP 217 x 88 x 414 PROTECT B. 3000BP 438 x 88 x 582
Weight (kg) PROTECT B. 750 8.6 kg PROTECT B. 1000 9.6 kg PROTECT B. 1500 + B.1500BP 18.5 kg PROTECT B. 2000 + B.2000BP 18.5 kg PROTECT B. 3000 31.5 kg PROTECT B. 1500BP 12.0 kg PROTECT B. 2000BP 12.0 kg PROTECT B. 3000BP 40.5 kg Cooling boosted self cooling Store temperature range -15°C - +50°C
(UPS electronic) Battery / UPS with integr. battery 0°C - +35°C Certification CE
18
Guidelines
The PROTECT B. complies with the product norm EN 50091. The CE symbol on the unit certifies the compliance to the EG
guidelines for 73/23 EEC low voltage and for 89/336 EEC electromagnetic compatibility (EMC), when following the installation instructions in the manual.
For the 73/23 EEC low voltage guidelines Reference number EN 62040-1-1 : 2003
For the 89/336 EMC guidelines Reference number EN 50091-2 : 1995
EN 61000-3-2 : 1995 EN 61000-3-3 : 1995
Warning:
i
This is a class A – UPS product. In a domestic environment, this product may cause radio interference, in which case, the user may be required to take additional measures.
19
4 Set-Up and Operation
Claims for damage during transport must always
4.1 Unpacking and Inspection
The unit has been fully tested and inspected. Although the unit has been packed and shipped with the usual degree of care, damage during transport cannot be ruled out completely.
be made with the transport company!
i
Check the shipping container for damage on arrival. If necessary, ask the transport company to check the goods and make a record of the damage in the presence of the member of staff from the transport company and register the damage with the AEG representative or dealer within eight days of delivery.
Check the delivery is complete:
PROTECT B. with 700, 1000, 1500, 2000 or 3000 VA Two plastic feet plus two fixing bras (for B.3000) Mains connection cable with shockproof plug Two load connection cables USB / RS232 communication cable CD with "CompuWatch" shutdown software Operating instructions
Check for complete delivery of ordered options like additional battery modules, 19” mounting kits or communication options like a SNMP card etc.
Please contact our hotline (see page 4) in case of any discrepancy.
The original packaging provides effective protection against mechanical shocks and should be retained so the unit can be transported safely later on.
20
Please keep the plastic packaging bags away from babies and children in order to safeguard against suffocation accidents.
Handle the components with care. Please take into account their weights. It may be necessary to engage the help of a second person, particularly in the case of the PROTECT B. 3000 model.
4.2 Point of installation
PROTECT B. is designed to be installed in a protected environment. When installing the unit, pay attention to such factors as sufficient ventilation and suitable ambient conditions.
PROTECT B. is air-cooled. Do not obstruct the air vents!
The UPS should preferably be operated at room temperature (between 15°C and 25°C).
Install the UPS in a room that is dry, relatively dust-free and free of chemical vapours.
Make sure that no magnetic storage media are stored and/or operated close to PROTECT B.
Check the nameplate to make sure the voltage and frequency data correspond to the values applicable to your loads.
21
4.3 Connections, Operation / Display Elements
wit
with type rating detail
with type rating details
4.3.1 Front view:
Model designation
h type rating details
PROTECT B.750 and B.1000
Model designation
PROTECT B.1500 and B. 2000 (Battery module and UPS)
Model designation
PROTECT B. 3000
s
22
4.3.2 Operating panel
Explanations (see also chapter 6)
1. Main switch of the UPS (mains switch)
2. Pushbutton for system test (manually triggering) or switching off the buzzer
3. Pushbutton to view the configuration
4. Enter button
5. LED for operating mode (details on page 42)
6. LED for current output rate voltage
7. LED for line mode
8. LED for battery mode
9. Bar graph LEDs for load level
10. Bar graph LEDs for battery capacity (remaining autonomy time)
11. LED for rectifier failure
12. LED error display (e.g. UPS overtemperature, short circuit)
13. LED for battery problem (e.g. discharged)
14. LED for fails/overload is timed out /or short output
23
4.3.3 Rear view (connections):
PROTECT B. 750 und 1000
Comments:
1. Mains connection (UPS input) with electric fuse and integrated spare fuse
2. Load connections (UPS outputs)
3. Surge protection (RJ11/RJ45) for data interface for phone, fax, modem or network (10/100MBit/s)
4. Communication interface RS232 (9pin SUB-D socket)
5. USB communication interface
24
Comments:
SNMP
COM.PORT
EPO
OUT
IN
INPUT
10A MAX
INPUT :48VDC 50A(NOM)
TO/FROM EXTERNAL BATTERY
BREAKER 250VAC/13A
PUSH
TO RESET
10A MAX
OUTPUT
TO/FROM EXTERNAL BATTERY
INPUT
:48VDC 50A(NOM)
+
RS232
_
_
+
EPO
USB
SNMP
TO/FROM EXTERNAL BATTERY
INPUT : 96VDC 24A£¨NOM£©
OUT
IN
Us/Out/Ausg 16A
Max
Us/Out/Ausg 10A
Max
Ue/In/Eing 16A Max
INPUT PROTECTION
120A
/ 250VA
344-00128-00
( 10 A max / Outlet )
OUTPUT PROTECTION
1. Mains connection (UPS input)
2. Load connections (UPS outputs) PROTECT B. 3000 with additional load connection (IEC 320-16A)
3. Surge protection (RJ11/RJ45) for data interface for phone, fax, modem or network (10/100MBit/s)
4. Communication interface RS232 (9pin SUB-D socket)
5. USB communication interface
6. Communication slot for optional expansion cards
7. Connection for external battery module (battery extension)
8. Mains input circuit breaker
9. Circuit breaker for load connections (only for PROTECT B. 3000)
10. Input contact for emergency shutdown (EPO)
25
5 Commissioning
5.1 Deployment
The UPS was constructed for both horizontal / flat (rack/19") operation and vertical / standing (tower) operation.
Operation the unit for longer time above an ambient temperature of 25° C reduces the lifetime of the batteries.
Position the UPS unit at least 20 cm away of any other electronic equipment to prevent interference.
After deployment and assembly of the UPS follow the steps for activation as explained in chapter 5.4
5.1.1 Tower (Stand alone deployment)
All models are qualified for stand alone use. PROTECT B. 750 and 1000 consist each of only one component and can be set up either standing or lying position
PROTECT B. 750 / 1000 standing and lying
PROTECT B. 1500 and B. 2000 are operated always in combination with at least one additional battery module. Because of the air intake in the front and the rear there is a variety of deployment positions.
26
When operating the system with more than one battery module, the UPS can be positioned between the modules. The following graphic displays the possibilities:
PROTECT B. 1500 / 2000 standing and lying (standard version)
PROTECT B. 3000 can be operated in the standing and lying position as well. Putting up the UPS upright requires the use of the two provided supports. The supports have to be positioned in the front third and rear third of the unit.
PROTECT B.3000 standing
Please consider for the location of setup also the guidelines on page 21 of the manual.
27
5.1.2 19" Rack Mount Setup
ROTECT B. 750, 1000, 1500, 2000 and 3000 can be installed in 19” racks. The UPS and external battery enclosure need 2U of valuable rack space. Mount the UPS preferable in the lower third of the rack with respect to the mass centre and sufficient ventilation.
Use the optional 19” mounting kit for the installation in the rack.
PROTECT B. 750 und B.1000
1. Fix the mounting ears on the side of the UPS according to the following figure.
2. Mount these subsequently to the slide assemblies.
3. Insert UPS into the slide assemblies and lock it in the rack enclosure.
28
4. Add up the front panels for both sides. The mechanical installation of the UPS is completed now.
PROTECT B. 1500 und B. 2000
This model is designed such that the UPS and the battery module can be mounted beside each other into the rack.
29
1. Place the UPS on a flat and in a clean place that the front side of the UPS is facing to you.
2. Loosen the screws in the middle of the cover and remove the covers from both units.
3. Fix the (wide) mounting bracket to the open front. Rack mounting holes stand out on each side of the units.
4. Secure the bracket with the supplied screws to the UPS and the battery module.
5. Reinstall the covers.
30
6. Align the second (smaller) mounting bracket at the rear of both units and mount them with the enclosed screws.
7. Install Plug of the battery module with the socket at the rear panel of the USP. Fix the output module to the notch of the battery module.
The setup of the rack-mount is completed.
PROTECT B. 1500 BP / B. 2000 BP
If you want to install optional external battery modules in a 19” rack use two of the units together and follow the steps 1 to 7 as described above.
31
PROTECT B. 3000 / B. 3000 BP
For mounting the 3000 VA UPS in a 19” rack fix the mounting ears to the UPS and install the unit to the rails. Do the same for the optional battery module.
100%
25%
50%75%
LINE MODE
ON / OFF
BAT. MODE
100%
25%
75%50%
TEST
TAGE RANGE:
VOL
INPUT
TYPE:
PSDR F
AIL
220V AC
NORMAL
F
AULT
CNFG
230V
AC
TOR
GENERA
BAD BA
T.
ENTER
240V AC
WIDE RANGE
OVER LOAD
5.2 Additional battery installation setup
PROTECT B. 1500, 2000 und 3000 include external battery ports that allow connecting additional battery modules. This provides additional battery runtime.
Caution:
Connect the battery connectors quickly and check for a tight fit of the connections.
PROTECT B. 1500 und B. 2000
There is one external battery port on the UPS and on the battery pack.
1. Connect the battery cable to the external battery port of the rear of UPS.
2. Then connect the supplied battery cable from extended battery module to the external battery port on the rear of the UPS.
If continuing to add up extended battery packs, repeat above step.
32
PROTECT B. 3000
After pressing the EPO all outputs of the UPS are
ting the system you have
to quit / reset the EPO and manually restart the
Connect the supplied battery module cable from extended battery module to the external battery port of the rear of UPS. If continuing to add up extended battery module, repeat above steps.
5.3 Emergency Power Off (EPO) set up
PROTECT B. 1500, 2000 and 3000 include EPO port that allows power to be shut down the protected equipment immediately and does not follow the shutdown procedure from any power management software.
Note:
i
Follow the procedure to install the EPO switch as below.
1. Check the UPS is turned off.
2. Remove the power supply from the EPO cradle
3. Connect isolated, normally-open, dry contacts
4. Use non-shield wiring, size 0,3 mm² - 0.75
5. Verify that the externally-connected EPO switch
6. Plug in the UPS, then pressing power switch
without power. For restar UPS by pressing the on / off button.
on the rear of the UPS by loosening the two outer screws.
(rated to handle 60Vdc maximum, 30Vac RMS maximum, and 20mA maximum) across the EPO device to Pin 1 and Pin 2.
mm². Plug the connector into the socket and fix it by screwing the two outer screws tight.
is not activated to enable power to the UPS output receptacles.
button to turn on the UPS.
33
7. Activate the external EPO switch to test the EPO function
8. De-activate the external EPO switch and restart the UPS.
5.4 Electric start-up
First compare the setting with the rated voltage valid in your country. The factory default setting is 230 V
Make any changes in accordance with the description in chapter 5.4.2 “Configuration”.
5.4.1 Connection
Now connect the input of the UPS (pos. 1 fig. p. 24/25) to the mains connection cable provided and plug the mains connector into a suitable shockproof socket.
1. Avoid using extension cables and/or adapters. In particular in the case of high­capacity types, ensure that the fusing in your sub-distribution is adequately dimensioned: The PROTECT B. 3000 for example requires its own connection with a 16 A fuse. No other loads should be connected to this circuit!
2. Then connect the outputs of your UPS (pos. 2 fig. p. 24/25) to your loads. Use the load connection cables provided for this. Don’t switch on the loads yet. Please contact your dealer if you require additional load connection cables.
3. Now switch on the UPS. To do this, press and hold the UPS main switch for about 3 seconds until the display goes on.
4. The UPS acknowledges your command by starting a self test. During this automatically running procedure a periodically audible signal can be heard The green "Mains" LED is permanently illuminated when the normal
34
operating stag has been reached (pos. 7 p. 3).
Please shut down the entire system if you cannot
solve any problems which occur. Please contact
In case anything different occurs, please follow the instructions in Chapters 6.2 / 6.3.
i
In particular, bear in mind the considerable power consumption of loads such as laser printers, large CRT monitors and the like which can quickly lead to a UPS overload.
5.4.2 Configuration
To reconfigure the internal UPS setup options, follow the procedure as below:
1. Press the Configure
2. Press the Configure
3. After selecting the mode, press the Enter
our hotline (see page 4).
5. When the LINE MODE display is lit, switch
seconds. Then UPS will transfer from configure mode to “output voltage mode” showing the value by a flashing LED at 220 Vac, 230 Vac or 240 Vac.
second, the UPS allows you to select the “output voltage mode” one by one.
more than three seconds, the “output voltage mode” is configured.
on your loads one after the other. Note the maximum permitted UPS load when doing this (pos. 9 fig. p. 42).
button more than three
button more than one
button
4. UPS will automatically transfer from configure mode to “operating mode” displayed by a flashing LED beside NORMAL, GENERATOR or WIDE RANGE.
5. Press the Configure second; the UPS will allow you to select the “operating mode” one by one.
button more than one
35
6. After selecting the mode, press the confirmation button
configuation.
5.5 Operation
Once you have connected the UPS to a suitable mains connection, you can start operation using the UPS main switch.
On and Off switch
To switch on the USP press the button for about 3
sec. (until the display goes on).
To switch off the UPS press the button until the UPS
signal stops.
Normally, the UPS operates continuously. The UPS now supplies the output with voltage, this being signaled by the green LED LINE MODE which lights up permanently (pos. 7 p. 42).
5.5.1 Normal Operation
During normal operation, i.e. when mains voltage is available, the built-in battery charger keeps the battery fully charged and the mains voltage monitoring system switches the inverter to standby mode.
The connected loads are powered using the monitored and filtered mains voltage, which is additionally stabilised by the integrated AVR control unit.
more than three seconds to complete the
The UPS capacity utilisation can be read off the bar chart of the operating panel (pos. 9, fig. p. 42).
5.5.2 Battery Operation / Autonomous Operation
When there is a mains failure or if the input voltage moves outside the tolerance range, the inverter automatically switches over to autonomous mode and supplies the loads with voltage from the battery. This drains the capacity of the battery and it is discharged. This status is signalled by the yellow LED BAT.MODE flashing as well as an intermittent acoustic signal (s. p. 42)
36
If the UPS does not automatically return to normal operation
If the LED BAT.MODE flashes every second, it is
ystem and all connected
loads! Shut down the UPS as well using the main
after a few minutes, close all jobs as usual and switch off your loads (e.g. PC) before the battery is fully discharged. This lengthens the service life of the battery! Switch OFF the UPS by pressing the main switch .
During the discharge process as the battery capacity consistently drops, the LED BAT.MODE flashes, accompanied by an intermittent double acoustic signal (once every four seconds). When the battery undervoltage limit is reached (acoustic signal every second), the electronic of the UPS switches off the power supply for the loads.
Never store the unit in this condition! The discharged battery system should be recharged within a week.
time shut down the s switch.
When the mains voltage comes back, the UPS must be switched on again using the main switch (only applies if it was previously switched off manually), in order to recharge the battery and thus store sufficient battery capacity for any possible future mains failures.
The batteries will be charged automatically when connected to the mains, independently of the mode set. The charging time after longer discharge of the batteries depends especially of the number of connected external battery units.
The charging time up to 90% of the rate capacity for a standard UPS is about 3 hours.
5.5.3 Unit Overload
If the unit is overloaded (load > 110 %), an intermittent signal is heard. The power supply to the connected loads is maintained, however the connected total load must be reduced immediately.
Non-observance of the "Unit overload" condition may cause the total loss of all UPS functions!
37
Also avoid short-term unit overloads, which may, for example,
Never connect any additional loads to the UPS
if there is a mains failure, i.e. if the UPS is
occur when connecting a laser printer or laser fax machine. Do not connect any household appliances to the UPS.
working in emergency power operation.
The UPS output is de-energised if there is an overload of 150 % for longer than 200 ms during normal operation. During emergency power operation, an instant shutdown additionally takes place if there is a unit overload of > 120 % (see Chapter
3.4). As a rule, if there has never been an overload during normal operation, there will not be one during battery operation either.
5.5.4 System Diagnosis / Battery Test
It is possible to press the "TEST" button
perform a manual check on the major hardware components of the UPS. This test can only be initiated if the unit is operating normally, and it involves switching the loads over to UPS inverter supply for a few seconds. As well as checking the procedures and the functional capability of the static bypass switch, this check also involves drawing current from the battery for a short time. The inverter has to provide the entire load supply, which means the entire process chain is tested with this function. Normal operation is restored after the check.
(pos. 2 p. 42) to
38
Executing the Test:
ection supports networks with
To execute the manual check press the button
about five seconds until the UPS acoustic signal fades out.
Additionally the button has the function to deactivate
the acoustic alarm signal. Press the button the acoustic alarm it audible for about 1 second. The tone stops. Any new error that is reported by a signal activates the alarm signal again.
Note:
The acoustic signal can not be switched off in the following situations:
Battery weak, overload, fan failure, fan error, time cutout, overheat.
If the monitoring electronics detect an irregularity during the procedure described above, the load is immediately switched back onto the mains and is thus supplied with voltage. At the same time, an acoustic fault signal and the corresponding signals from LEDs in acc. with Chapter 6 "Signalling" are output.
Faults detected and signalled during diagnosis must be rectified; otherwise there is a risk of load voltage loss if a mains failure occurs!
for
when
5.6 Interfaces and communication
5.6.1 Data line protection RJ11 and RJ45 (modem / telephone / fax / network)
The incoming data lines are connected to the “IN” line at the rear of the UPS. The “OUT” line is connected via data line with your terminal.
The data line prot transfer rates between 10 and 100 MBit/s.
i
39
5.6.2 Computer interfaces RS232 and USB
The UPS offers various interfaces to manage the system and to comfortable readout state information and important parameters. The protocol is optimized for operation with the shutdown and UPS management software “CompuWatch” from AEG. To connect to the UPS use the provided RS232 or USB cable by attaching them to a free port of your pc.
RS232 interface: The interface is connected via a 9 pole Sub-D connector on the back of the unit (pos. 4 p. 24 / 25). PIN configuration: 2 = RxD; 3 = TxD; 5 = GND.
USB interface: The connection via USB is recognized automatically (pos 5 p. 24 / 25).
USB- and RS232 interfaces can not be used at the same time.
i
5.6.3 Communication slot (PROTECT B. 1500 / 2000 / 3000):
If the cover on the rear of the UPS is removed, additional optionally available communication components can be installed there.
SNMP board: Slot card for direct connection of the UPS to the Ethernet network with RJ 45 (TCP/IP)
Details can be found in the description enclosed with the particular optional component. Other boards are in preparation.
Using the communication slot deactivates the RS232 interface of chapter. 5.6.2.
i
5.6.4 Shutdown and UPS management software
Especially for monitoring the state of the UPS and the supply of power AEG developed the software “CompuWatch”.
40
In combination with the intelligent UPS the software ensures high availability of all IT components and full data integrity.
The shutdown software “CompuWatch” supports most popular operating systems like Windows 98/ME, WindowsNT/2000/ XP, Linux, Novell Netware, IBM AIX, HP-UX, SUN Solaris, Mac OS X, ...
Details concerning installation on diverse operating systems can be found in the manual on the CD.
Download of updates via www.AEGpartnernet.com >> PRODUCTS >> Software >> CompuWatch
41
6 Signalling and failure solution
6.1 LED display
1. Main switch of the UPS (mains switch)
2. Push button for manually triggering the system test or switching off the buzzer
3. Push button to view the configuration
4. Acknowledgement button
5. INPUT TYPE: LED for preselected operation state and output voltage
NORMAL: (Normal mode) The LED indicator will illuminate during normal mode, the UPS accepts AC input voltage range from +/-20%.
GENERATOR: (Generator mode) No change to voltage window. However, the low frequency transfer point is changed to 40Hz and there is no limitation for high frequency transfer point.
WIDE RANGE: (Extended UPS) AC input voltage ranges from -30% / +20%.
6. VOLTAGE RANGE: LED for current output rate voltage 220Vac / 230Vac (ex factory) / 240Vac.
7. LINE MODE: Green LED for power mode. The line LED indicator illuminates when the AC source is present.
8. BAT. MODE: Yellow LED for battery mode. The LED indicator will flash every four seconds when the UPS
42
is providing battery power to your equipment. On the other hand, the LED indicator gives you a warning which will flash every two seconds when the battery is low.
9.
LED: Bar chart LEDs showing UPS utilization. The LED indicator and the load level indicator will illuminate to show the load level; linearly subdivided in 25% steps.
10.
11. PSDR FAIL: LED error display for corrupt inverter.
12. FAULT: Central error LED display, e.g. when UPS is
13. BAD BAT.: LED for battery problem (e.g.
14. OVERLOAD: LED for violation of overload time limit.
LED: Bar chart LEDs showing battery capacity (remaining standby time). The battery level indicator will illuminate to show battery level. Each LED indicator displays a 25% capacity level.
overloaded or encounters a short circuit on the output.
discharged). The LED indicator will flash every two seconds when the battery failes or if the battery is disconnected. Please check your battery connection; replace the battery or contact your local dealer for a battery replacement kit.
The LED indicator will light on when the UPS overload timeout. (Information concerning the time limit is available in chapter 3.4).
LED indicator and
43
6.2 Audible Alarm Trouble Shooting:
Problem Cause Solution
Sounding every 4 seconds
Sounding every second
Continuously sounding
The UPS is on battery Check the input voltage,
The battery is running low Save your work and turn
Output overload Check load level indicator
The UPS fails Please contact your local
Battery may need to charge or service
the input fuse resp. the circuit breaker
off your equipment
and remove some load
dealer
Charge or replace the battery
6.3 General Fault Diagnosis and Fault Rectification
Problem Cause Solution
The UPS is not on when power switch is pressed
The power cord is not connected correctly
The wall outlet may be faulty
Check the power cord connection, especially the fit of the plug in the socket of the UPS
Please contact your local qualified electrician
The UPS output may short-circuit or overload
Internal fuse may be blown
44
1. Disconnect all loads and restart UPS. Connect loads again one by one.
2. Ensure loads are not detective or shorted internally
Please contact your local dealer
UPS could not provide power to the load
Output fuse it released
UPS output recognizes overload or short circuit
Check the output fuse (B. 3000)
Check the connected cable Ensure the load does not
exceed the maximum rating of UPS
Battery has reduced backup time
.
Connected equipment lose power while connected to the UPS
The UPS fault LED lights on
Battery is not charged
Battery may not able to hold a full charge due to age.
The UPS may be over- loaded
The UPS may be failed
The UPS fails Save your work and turn off
Re-charge the battery at least 24 hours
Replace Battery
Check the load status on the bar graph, reduce the load if necessary
Please contact your local dealer
equipment. Please contact your local dealer
If you cannot solve the problem which has occurred, stop the entire procedure, switch off the UPS and disconnect the connector from the socket. Please contact our hotline in this case (see page 4).
Please have the serial number of the unit as well as the purchase date to hand in this case. The hotline will provide you with technical support and can inform you about further procedures once you have described the problem.
45
7 Maintenance
The PROTECT B. consists of advanced and resistant components. To guarantee a continuous and high availability it is recommended to check the unit (especially the batteries and the fans) in regular intervals (at least every 6 months).
CAUTION:
Follow safety and security regulations unconditionally!
Visual control
When going through the visual control check whether:
mechanical defects or foreign matter is visible in the
system
conducting dirt or dust sediments are in the unit and dust sediments prevent optimal ventilation in and out
the unit.
CAUTION:
Before going through the next step disconnect the PROTECT B. from the mains.
If the unit is very dusty it is recommended to clean the UPS with compressed air to enable optimal ventilation.
The time intervals for the visual control depend mainly on the local situation at the deployment site.
Battery control
The aging process can be detected by regular capacity probes. Make comparison measurements every 12 month e.g. by simulating a power failure and check how long the standby time lasts. The load should always be the same for each simulation. Dramatic changes compared to the last measurements require a change of batteries. Contact your local dealer or call our hotline (see page 4).
46
Fan control
A battery can present a risk of electrical shock
.
The following precautions should be observed
f you are not qualified service personnel to
replace the battery, do not attempt to open the
battery door. Please call local dealer or
The fan has to be checked on a regular basis for dust intrusion and strange untypical sounds. Clogged ventilation has to be cleaned. If the fan makes a strange noise or runs irregular contact the hotline (see page 4).
7.1 Battery replacement
CAUTION:
and can be very dangerous if handled improperly before replacing the batteries.
Turn off the UPS and disconnect the utility power cord
from the wall outlet.
Remove rings, watches, and other metal objects. If the battery replacement kit is damaged in anyway or
shows signs of leakage, contact your dealer immediately.
Properly recycle or dispose of used battery. Do not
dispose of batteries in a fire. The batteries may explode.
Note:
i
I
distributor immediately.
47
PROTECT B. 750 and B.1000
1. Unscrew the two screws on the side and remove the front panel carefully on both ends. Make sure that the panel does not tilt too much.
2. Disconnect the battery cable from the UPS and remove the battery retaining battery bracket to the right so that the battery can be pulled out to the front.
3. Withdraw the new batteries from the transport container an put into the right position. Fix both blocks together and connect the electric connections of the extracted battery system.
4. Slide the new battery carefully into shaft of the UPS until the end. Mount the bracket for fixing the battery pack and connect the system electrically. Push the contact together quickly and firmly. Take care of the right polarity ( red - red / black - black)
48
5. Close and reinstall the front panel. Take care to push it in firmly and fix the front panel with the two screws from the beginning.
PROTECT B. 1500 und B. 2000
1. Unscrew the two screws from the battery case and remove front panel by pulling on both ends.
2. Disconnect the battery cable from the battery module and remove the bracket by sliding it to the side. (Remember the position of the bracket for the reassembly. The notches are good for orientation).
49
3. Withdraw the new batteries from the transport container and put into the right position. Fix both blocks together and connect the electric connections of the extracted battery system.
4. Slide the new battery carefully into shaft of the UPS until the end.
5. Mount the bracket for fixing the battery pack and connect the cable joint between the battery packs (red-red / black-black). Close and reinstall the front panel. Take care to push it in firmly and fix the front panel with the two screws from the beginning.
The battery exchange is completed.
Alternatively a complete battery module can be provided ex factory as a spare part. Ask your
i
PROTECT B. 3000
1. Remove the left front panel carefully by pulling on
local dealer or call the hotline (see page 4).
both ends.
2. Disconnect the battery cable and remove the battery bracket.
50
3. Pull first the right battery out and then the left one.
4. Withdraw the new batteries from the transport container and put into the right position. Fix both blocks together and connect the electric connections with the junction line of the extracted battery system.
5. Slide the new batteries into battery module carefully into the shaft.
6. Mount the bracket for fixing the battery pack and connect the system electrically ( red - red / black ­black).
7. Close and reinstall the previously removed front panel.
The battery exchange is completed.
51
8 Storage, Dismantling and Disposal
Long storage times without charging or
discharging the battery at regular intervals may
Connect PROTECT B. to the mains without load
ing it into storage, in order to make
The charging time should be at least as long as
Storage
lead to permanent damage of the battery.
If the battery is stored at room temperature (20 will automatically discharge at a rate of 3-6 % per month due to internal reactions. Storing the battery at temperatures above room temperature should be avoided. A high storage temperature also means greater battery self-discharge.
Batteries that are stored at room temperature should be recharged every six months to maintain their full capacity and service life.
before putt
i
sure that the battery is fully charged.
recommended in chapter 3.4 “Technical Data”.
Dismantling
0
C to 300C) it
The system is dismantled in reverse order of the installation instructions.
Disposal
In the interest of environmental protection and recycling, please dispose condemned components in accordance with the regulations and legal guidelines when permanently taking the system out of operation.
52
9 Glossary
9.1 Technical terms
AVR Automatic Voltage Regulation
DC/DC Booster Circuit technology to boost the direct voltage
EPO E
PFC P
Appliance protection Surge technology term
Class D see appliance protection LED L
SNMP S
VFD Output V
VI Output V
VFI Output V
against mains voltage variations
on a higher voltage level
mergency Power Off
device for emergency shut down
ower Factor Correction Circuit technology to minimize circuit backfeed (important for non linear loads)
The conventional mains surge protection consists of an mains earthwire (class B), an overvoltage protection (class C) and an appliance protection (class D) – see also e.g. under http://www.phoenixcontact.de (topic „TRABTECH“)
ight Emitting Diode Electronic semiconductor component, commonly called light diode. Used for optical signaling.
imple Network Management Protocol common protocol in networks to manage / control appliances
oltage and Frequency Dependent from mains supply The UPS output depends of mains voltage and frequency variations. Former notation: OFFLINE
oltage Independent from mains supply The UPS output is independent of mains voltage and frequency variations. The mains voltage however is rectified by electronic / passive voltage regulators. Former notation: LINE-INTERACTIVE
oltage and Frequency Independent from mains supply The UPS output is independent of mains voltage and frequency variations. Former notation: ONLINE
53
Guarantee certificate
Type: …….…………………......................................................
Serial-no.: ……………………..……………...............................
Date of purchase: …………….............……………………........
Trading stamp / Signature
Specifications are subject to change without notice.
AEG Power Solutions GmbH
Emil-Siepmann-Straße 32
59581 Warstein-Belecke
Germany
Operating Instructions UPS
BAL 8000015758_01 EN
54
Loading...