Thank you for deciding to purchase the PROTECT 1.M
UPS from AEG Power Solutions. The following safety
instructions are an important part of the operating
instructions are will protect you against problems from
operating errors and possible dangers. Please read these
instructions carefully prior to commissioning!
2
1 Notes on these Operating
Instructions
Duty to provide information
These operating instructions help you to install and operate the
Uninterruptible Power Supply (UPS) PROTECT 1.M as well as
its USV modules PROTECT 1.040 and associated external
battery units PROTECT 1.M BP (referred to below jointly as
PROTECT 1.M) in accordance with its designated use, safely
and correctly. These operating instructions contain important
information for avoiding dangers.
Please read these instructions carefully prior to
commissioning!
These operating instructions are an integral part of
PROTECT 1.M.
The operator of this unit is obliged to communicate these
operating instructions to all personnel transporting or starting
up PROTECT 1.M or performing maintenance or any other
work on the unit.
Validity
These operating instructions comply with the current technical
specifications of PROTECT 1.M at the time of publication. The
contents do not constitute a subject matter of the contract, but
serve for information purposes only.
Warranty and liability
We reserve the right to alter any specifications given in these
operating instructions, especially with regard to technical data
and operation.
Claims in connection with supplied goods must be submitted
within one week of receipt, along with the packing slip.
Subsequent claims cannot be considered.
The warranty does not apply for damage caused by noncompliance with these instructions (such damage also includes
damage to the warranty seal). AEG will accept no liability for
consequential damage. AEG will rescind all obligations such as
3
warranty agreements, service contracts, etc. entered into by
AEG or its representatives without prior notice in the event of
maintenance and repair work being carried out with anything
other than original AEG parts or spare parts purchased
from AEG.
Handling
PROTECT 1.M is designed and constructed so that all
necessary steps for start-up and operation can be performed
without any internal manipulation of the unit. Maintenance and
repair work may only be performed by trained and qualified
personnel.
Illustrations are provided to clarify and facilitate certain steps.
If danger to personnel and the unit cannot be ruled out in the
case of certain work, it is highlighted accordingly by
pictographs explained in the safety regulations of chapter 3.
Hotline
If you still have questions after having read these operating
instructions, please contact your dealer or our "Hotline":
No part of these operating instructions may be transmitted or
reproduced by any electronic or mechanical means without the
express prior written permission of AEG.
The PROTECT 1.M connection to the mains can be either
three or one-phase. The load connection, i.e. the UPS output,
is always one-phase. The online-/double-converter technology
guarantees the highest levels of reliability and performance.
This standard product is designed as a highly intelligent
module construction with a rack-type design. One module of
the AEG USV PROTECT 1.040 corresponds to an UPS with
full functions. Depending on the requirements for output power
and serviceability, the user can increase or reduce the number
of modules in the AEG UPS PROTECT 1.M to achieve an
optimum price/ performance ratio.
important loads such as small data centres,
servers, network components,
telecommunication facilities and the like.
Module for UPS
communikation
& LCD display
Connection
terminals
Fig.: Diagram in principle of the PROTECT 1.M
L1
L2 L3
UPS INPUT
N
PROTECT
UPS module
PROTECT
UPS module
PROTECT
UPS module
+
Battery system
7
1.040
1.040
1.040
_
1
2
6
NL
UPS OUTPUT
The PROTECT 1.M has been designed for operating up to six
UPS modules. Depending on the output power required, the
unit is operated in normal mode with between one and six
modules installed. These modules can easily be installed,
removed or replaced under a very wide range of operating
conditions.
PROTECT 1.M uses a high-performance communication
module to collect information from the individual UPS modules
via the internal network within the unit and displays this
information on an LC display. This greatly facilitates operation
of the UPS.
PROTECT 1.M protects your systems against numerous power
supply problems such as mains failures, voltage and frequency
fluctuations, under and overvoltage, voltage distortions, voltage
harmonics, etc.
SBS
PFC
Input
Fig.: Component diagram of an individual PROTECT 1.040 UPS module
Filter
Battery
charger
Rectifier
Battery system
Inverter
DC/DC Booster
Control logic
(external)
Mains
filter
DSP
Output
The UPS is connected between the public utility mains and the
loads to be protected.
The power sections of the UPS module rectifier convert the
mains voltage to DC voltage for supplying the inverters. The
circuit technology used (PFC) enables sinusoidal current
consumption and therefore operation with little system
8
disturbance. Separate battery chargers configured with switch
mode power supply technology are responsible for charging or
trickle-charging the battery connected in the intermediate
circuit. The configuration of these charging rectifiers means the
harmonic content of the charging current for the battery is
almost zero, which increases the service life of the battery
even more. The inverters are responsible for converting the DC
voltage into a sinusoidal output voltage. A microprocessordriven control based on a pulse-width modulation (PWM)
integrated in each UPS module guarantees, in conjunction with
digital signal processor technology and extremely fast
pulsating IGBT power semiconductors of the inverters, a
voltage system of the highest quality and availability on the
secured busbar.
In the event of mains faults (e.g. current failures), the voltage
continues to be supplied from the inverters to the load without
any interruption. From this point onwards, the inverters draws
their power from the battery instead of the rectifiers. Since no
switching operations are necessary, there is no interruption in
the supply to the load.
The greatest possible supply reliability of connected loads is
attained by the parallel connection of up to max. six PROTECT
1.040 UPS modules. The n+x technology thus guarantees
maximum reliability through up multiple active redundancy on
the one hand as well as on the other hand the possibility of
increased power with simple redundancy or even only higher
UPS power without any redundancy.
The automatic electronic bypass serves to increase the
reliability of the supply further. It switches the public mains
directly through to the load without any interruption, e.g. when
there is a system overload. As a result, the automatic bypass
represents an extra passive redundancy for the load.
9
A
A
A
A
A
A
An integrated, manually operated bypass unit ensures an
uninterrupted supply to the connected loads in the case of
maintenance and/or service work. The internal electronic part
(with the exception of the metal-clad manual bypass) can be
disconnected via the mains input miniature circuit breakers.
Load
Number of
UPS modules
4kV
kV
8
12 kV
16 kV
20 kV
24 kV
1
module
no
redundancy
---
2
modules
n+1
(4 kVA)
no
redundancy
- --
3
modules
n+2
(8 kVA)
n+1
(4 kVA)
no
redundancy
- - -
4
modules
n+3
(12 kVA)
n+2
(8 kVA)
n+1
(4 kVA)
no
redundancy
- - -
5
modules
n+4
(16 kVA)
n+3
(12 kVA)
n+2
(8 kVA)
n+1
(4 kVA)
no
redundancy
---
Fig.: Table showing the level of redundancy depending on the installed
Inherent noise (1m distance)
PROTECT 1.M (system) < 62 dB(A)
PROTECT 1.040 (module) < 55 dB(A)
Cooling type Forced air cooling through
variable-speed fans
Operating temperature range 0 °C to +40 °C
Battery systems
(recommended):
+15°C to +25°C
Storage temperature range 0°C to +40°C
Relative humidity 20% – 90%
12
Site altitude Up to 1000 m at nominal output
Use more than 1000 m above sea
level results in the following
reduction in output power:
Housing colour Blackline
Weight:
PROTECT 1.M (chassis) 75 kg
PROTECT 1.040 (module) 15 kg per module
Dimensions W x H x D:
PROTECT 1.M (chassis) 442 mm x 965 mm x 700 mm
PROTECT 1.040 (module) 405 mm x 87 mm x 530 mm
Directives
The PROTECT 1.M meets the product standard EN 50091.
The CE mark on the unit confirms compliance with the EC
outline directives for 73/23 EEC – Low voltage and for 89/336
EEC – Electromagnetic compatibility if the installation
instructions described in the operating instructions are
observed.
For 73/23 EEC low-voltage directive
reference number EN 62040-1-1 : 2003
For 89/336 EMC directive
reference number EN 50091-2 : 1995
EN 61000-3-2 : 1995
EN 61000-3-3 : 1995
Height (m) 1000 1500 2000 2500 3000
Power 100% 95% 90% 85% 80%
i
Warning:
This is a class A
generate radio interference in the domestic
environment. In this case, the user can be
required to employ additional interference
suppression measures.
-device. This product can
13
3 Safety Regulations
3.1 Important Instructions and Explanations
The instructions for operation and maintenance as well as the
following safety regulations must be complied with to ensure
the safety of personnel as well as to ensure the continued
availability of the unit. All personnel installing/dismantling,
starting up, operating or servicing the units must be familiar
with and observe these safety regulations. Only trained and
qualified personnel may perform the work described, using
tools, equipment, test equipment and materials intended for the
purpose and in perfect working condition.
Important instructions are emphasised by the words
"Caution", "Attention", "Note" and indented text.
Caution
This symbol identifies all working and operational
procedures requiring absolute compliance to
avoid any danger to persons.
Attention
This symbol identifies all working and operational
procedures requiring absolute compliance to
prevent any damage, irreparable or otherwise, to
the unit and its components.
Note
i
This symbol identifies technical requirements and
additional information requiring the operator's
attention.
3.2 Accident Prevention Regulations
Compliance with the accident prevention regulations valid in
the respective country of use and the general safety regulations
in accordance with IEC 364 is mandatory. The following safety
rules must be observed prior to performing any work on the
PROTECT 1.M:
14
♦ Disconnect the unit from the power supply
♦ Secure the unit against being switched back on
♦ Verify that the unit is disconnected from the power
supply
♦ Earth and short-circuit the unit
♦ Provide protection by covers or barriers for any
neighbouring live parts
3.3 Qualified Personnel
The PROTECT 1.M may only be transported, installed,
connected and serviced by qualified personnel who are familiar
with the pertinent safety and installation regulations. All work
performed must be inspected by responsible qualified
personnel.
The qualified personnel must be authorised by the responsible
safety officer of the installation to perform the work required.
Qualified personnel is defined as personnel
♦ having completed training and gained experience in the
respective field,
♦ familiar with the pertinent standards, rules and
regulations and accident prevention regulations,
♦ having received instruction on the mode of operation
and operating conditions of the PROTECT 1.M,
♦ capable of recognising and preventing dangers.
Regulations and definitions for qualified personnel can be
found in DIN 57105/VDE 0105, Part 1.
3.4 Safety Instructions for PROTECT 1.M
The UPS is live, and the voltage can be
dangerous. The unit may only be installed and
if necessary opened by trained and qualified
personnel. Repairs may only be carried out by
qualified customer service staff!
15
The output can be live, even when the UPS is not
connected to the mains supply!
For health and safety reasons, the unit must be
earthed correctly!
The PROTECT 1.M may only be operated with or connected to
three-phase or AC voltage power systems with protective
grounding using a mains connection cable with PE conductor
that has been tested according to German standards (VDE).
Risk of burning!
The battery has powerful short-circuit currents.
Incorrect connection or isolation faults can lead to
melting of the plug connections, sparking potential
and severe burns!
The unit has a warning signal that sounds when
the battery voltage of PROTECT 1.M is
exhausted or when the UPS is not working in its
normal mode (see also chapter 6.1 "Signalling",
page47ff and the following).
Observe the following safety instructions to
ensure permanent operational safety of and safe
work with the UPS and the battery modules
(special accessories):
♦ Do not dismantle the UPS!
(The UPS does not contain any parts that require regular
maintenance. Bear in mind that the warranty will be
invalidated if the unit is opened!)
♦ Do not install the unit in direct sunshine or in close
proximity of heaters!
♦ The unit is designed to be installed inside in heated
rooms. Never install the housing in the vicinity of water
or in an excessively damp environment!
♦ Condensation may occur if the UPS is brought from a cold
environment into the room where it is to be installed. The
16
UPS must be absolutely dry prior to start-up. As a result,
leave it to acclimatise for at least two hours.
♦ Never connect the mains input and the UPS output!
♦ Ensure that no fluids or foreign bodies can penetrate the
housing!
♦ Do not block the air vents of the unit! Make sure, for
example, that children do not insert any objects in the
ventilation openings!
♦ Do not connect household appliances such as hairdryers
to the UPS! Also take care when working with motor
loads. It is essential to avoid back-feeding the inverter,
e.g. if the load is intermittently operated in regenerative
mode.
Danger! Electric shocks!
Even after the mains voltage has been
disconnected, the components within the UPS
remain connected to the battery and can thus
cause electric shocks. It is therefore imperative
to disconnect the battery circuit before carrying
out any maintenance or repair work!
If it is necessary to replace the battery or carry
out maintenance work, this must be done by or
under the supervision of a specialist familiar with
batteries and the necessary safety precautions!
Only authorised persons are allowed in the
vicinity of the batteries!
When replacing the batteries, the following must be observed:
Only ever use identical, maintenance-free sealed lead batteries
with the same data as the original batteries.
Danger! Explosive!
Never throw batteries into open fire.
Never open or damage batteries. (Electrolyte
may leak out and damage skin and eyes. It may
be toxic!)
17