AEG MBS 6000 User Manual

Externe Handumgehungseinheit für USV PROTECT C.6000R
External Bypass Unit for UPS PROTECT C.6000R
Typ / Type MBS 6000
AEG Power Solutions GmbH Änderung / Revision 01 / Schenuit/ Schneider Datum / Date 09.07.2009
Operating instructions 8000019069 BAL, en
1 General
The external, manually operated bypass unit is an option for the PROTECT C.6000R UPS series in a rack version with 2U. It is used for disconnecting the UPS, for example for maintenance purposes, whilst the connected loads continue to be supplied without interruption. As well as solely bypass operation, an additional switch setting permits UPS test operation. Separately fused non-heating appliance connectors make it possible for the loads to be supplied directly from the MBS 6000. LEDs with various colours clearly signal which operating status has been selected.
Scope of delivery:
External bypass unit MBS 6000 2 connection cables to the UPS Operating instructions
Prerequisite:
AEG UPS in the PROTECT C.6000R series
Technical data:
Nominal connection voltage /
- frequency
230 VAC 50/60 Hz
Nominal current 32 A Number of output sockets
(load connection)
8 x IEC 320 C13 (10 A),
fused in pairs
by miniature fuse
5 x 20 mm, T
additional non-fused
output on terminal Housing colour blackline Dimensions (HxWxD)
19-inch / rack operation
88 mm x 483 mm x 350 mm
2
U x 19"
2
10 A