AEG MBS 6000 User Manual

0 (0)
AEG MBS 6000 User Manual

Externe Handumgehungseinheit für USV PROTECT C.6000R

External Bypass Unit

for UPS PROTECT C.6000R

Typ / Type

MBS 6000

AEG Power Solutions GmbH

Änderung / Revision

01 / Schenuit/ Schneider

Datum / Date

09.07.2009

Operating instructions 8000019069 BAL, en

1 General

The external, manually operated bypass unit is an option for the PROTECT C.6000R UPS series in a rack version with 2U. It is used for disconnecting the UPS, for example for maintenance purposes, whilst the connected loads continue to be supplied without interruption. As well as solely bypass operation, an additional switch setting permits UPS test operation. Separately fused non-heating appliance connectors make it possible for the loads to be supplied directly from the MBS 6000. LEDs with various colours clearly signal which operating status has been selected.

Scope of delivery:

External bypass unit MBS 6000

2 connection cables to the UPS

Operating instructions

Prerequisite:

♦ AEG UPS in the PROTECT C.6000R series

Technical data:

Nominal connection voltage /

230 VAC 50/60 Hz

- frequency

 

 

 

Nominal current

32 A

 

 

Number of output sockets

8x IEC320 C13 (10 A),

(load connection)

fused in pairs

 

by miniature fuse

 

5 x 20 mm, T10A

 

additional non-fused

 

output on terminal

 

 

Housing colour

blackline

 

 

Dimensions (HxWxD)

88 mm x 483 mm x 350 mm

19-inch / rack operation

2U x 19"

 

 