www.zenithappliances.com
Room Air Conditioner
SERVICE MANUAL
MODELS: ZW5000
CAUTION
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
• ONLY FOR AUTHORIZED SERVICE PERSONNEL.
Air Conditioner Service Manual |
|
TABLE OF CONTENTS |
|
Safety Precautions.......................................................................................................................................... |
3 |
Dimensions ..................................................................................................................................................... |
7 |
Outside Dimensions ................................................................................................................................... |
7 |
Product Specifications .................................................................................................................................. |
8 |
Installation ....................................................................................................................................................... |
9 |
Select the Best Location ........................................................................................................................... |
9 |
How to Install.............................................................................................................................................. |
9 |
Installation Kits Content(Some Models) ................................................................................................... |
10 |
How to Secure the Drain Pipe .................................................................................................................. |
11 |
Operation ...................................................................................................................................................... |
12 |
Features ................................................................................................................................................... |
12 |
Insulation Resistance Test........................................................................................................................ |
12 |
About the Controls on the Air conditioner ................................................................................................ |
12 |
Disassembly .................................................................................................................................................. |
13 |
Mechanical Parts...................................................................................................................................... |
13 |
Air Handling Parts .................................................................................................................................... |
14 |
Electrical Parts ......................................................................................................................................... |
15 |
Refrigerating Cycle................................................................................................................................... |
16 |
Schematic Diagram....................................................................................................................................... |
19 |
Wiring Diagram......................................................................................................................................... |
19 |
Troubleshooting Guide ................................................................................................................................. |
20 |
Piping System .......................................................................................................................................... |
20 |
Troubleshooting Guide ............................................................................................................................. |
21 |
Room Air Conditioner Voltage Limits........................................................................................................ |
23 |
Exploded View .............................................................................................................................................. |
26 |
Replacement Parts List ................................................................................................................................ |
27 |
2 Room Air Conditioner
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
■Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
WARNING This symbol indicates the possibility of death or serious injury.
CAUTION This symbol indicates the possibility of injury or damage to property only.
■ Meanings of symbols used in this manual are as shown below.
Be sure not to do.
Be sure to follow the instruction.
WARNING
Installation
Always install the expansion panel(s). |
Do not place the power cord near a heater. |
•Improper assembly or installation may cause incorrect operation, including injury, fire, and electric shock hazards.
Do not use the power cord near flammable gas or combustibles such as gasoline, benzene, thinner, etc.
• It may cause explosion or fire.
• It may cause fire and electric shock.
Do not disassemble or modify products.
• It may cause electric shock and failure.
Gasolin
Service Manual 3
Safety Precautions
Operation
Plug in the power plug properly.
•Otherwise, it will cause electric shock or fire.
Do not modify power cord length.
•It will cause electric shock or fire.
Unplug the unit if strange sounds, odors, or smoke come from it.
•Otherwise it will cause fire and electric shock accident.
Do not operate or stop the |
Do not damage or use an |
unit by inserting or pulling |
unspecified power cord. |
out the power plug. |
|
• It will cause electric shock or |
• It will cause electric shock or |
fire. |
fire. |
ON
Use the air conditioner on a |
Always plug into a |
single outlet circuit. (See page 7.) |
grounded outlet. |
Do not share the outlet with |
|
other appliances. |
|
• It will cause electric shock or |
• No grounding may cause |
fire. |
electric shock. |
Do not use the socket if it is |
Do not operate with wet |
loose or damaged. |
hands or in damp |
|
environment. |
• It may cause fire and electric |
• It may cause electric shock. |
shock. |
|
4 Room Air Conditioner
|
Safety Precautions |
|
|
Close all doors, windows and other |
Ventilate before operating air conditioner |
outside openings to the room. |
when gas goes out. |
• The air conditioner must be operated in |
• It may cause explosion, fire,and burn. |
a enclosed area to be most effective. |
|
If water enters the product, turn off the |
Do not clean the air conditioner with |
|
power switch of the main body of |
||
water. |
||
appliance. Contact service center after |
||
|
||
taking the power plug out from the socket. |
|
|
• It will cause electric shock or failure of |
• Water may enter the unit and degrage the |
|
machine. |
insulation.It may cause an electric shock. |
ENGLISH
CAUTION
Installation
Never touch the metal parts of the unit when removing the filter.
•They are sharp and may cause injury.
Do not block the inlet or |
Ensure that the outer case |
outlet. |
is not damaged by age or |
|
wear. |
•It may cause failure of appliance • If the outer case is damaged,
or performance deteriorate. it must be repaired or replaced immediately.
Leaving it damaged could result in the air conditioner falling out of the window, creating a safety hazard.
Owner ,s Manual 5
Safety Precautions
Be cautious not to touch the sharp edges when installing.
• It may cause injury.
Operation
Hold the plug by the head |
Unplug the air conditioner |
when taking it out. |
if it will not be used for a |
|
long period. |
• It may cause electric shock |
• It will waste power consumption |
and damage. |
in vain and it may cause accident. |
Sharp edges
Unplug the air conditioner |
Do not put a pet or house |
before cleaning it. |
plant where it will be |
|
exposed to direct air flow. |
• Since the fan rotates at high |
• This could injury the pet or |
speed during operation, it may |
plant. |
cause injury. |
|
Always insert the filter |
Use a soft cloth to clean. Do |
securely. |
not use wax, thinner, or a |
Clean it every two weeks. |
strong detergent. |
• Operation without filters will |
• The appearance of the air |
cause failure. |
conditioner may deteriorate, |
|
change color, or develop |
|
surface flaws. |
Do not use this appliance for special purposes such as pets, foods, precision machinery, or objects of art.
•It is an air conditioner, not a precision refrigeration system.
Do not drink water drained from air conditioner. Do not direct airflow at room occupants only.
•It is not sanitary and could cause illness or personal injury hazard.
x a W
Thinner
6 Room Air Conditioner
Dimensions
Dimensions
SymbolsUsedin this Manual
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
NOTICE This symbol indicates special notes.
OutsideDimensions
|
|
|
W |
|
|
|
|
|
|
D |
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
H
Model
Dimension |
|
All Model |
|
|
|
W |
mm(inch) |
439(17 5/16") |
H |
mm(inch) |
283(11 1/8") |
D |
mm(inch) |
326(12 13/16") |
Service Manual 7
Product Specifications
Product Specifications
MODELS |
GWHD5000 |
|
|
||
ITEMS |
|
|
|
|
|
COOLING CAPACITY (BTU/h) |
5,000 |
|
|
|
|
POWER SUPPLY (Phase, V, Hz) |
1ø , 115V, 60HZ |
|
|
|
|
INPUT (W) |
515 |
|
|
|
|
OPERATING CURRENT (AMP.) |
4.8 |
|
|
|
|
REFRIGERANT CONTROL |
CAPILLARY TUBE |
|
|
|
|
REFRIGERANT CHARGE (R-22) |
200g (7.0 Oz) |
|
|
|
|
INSIDE FAN |
TURBO |
|
|
|
|
OUTSIDE FAN |
ROPELLER FAN WITH SLINGER RING |
|
|
|
|
AIR DISCHARGE |
2-WAY (RIGHT AND LEFT) |
|
|
|
|
CHASSIS |
TOP-DOWN |
|
|
|
|
PROTECTOR |
• OVERLOAD PROTECTOR FOR COMPRESSOR |
|
• INTERNAL PROTECTOR FOR FAN MOTOR |
||
|
||
|
|
|
TEMPERATURE CONTROL |
THERMOSTAT |
|
|
|
|
ROCKER SWITCH-1 |
2 POSITIONS(POWER ON, POWER OFF) |
|
|
|
|
ROCKER SWITCH-2 |
2 POSITIONS(HI FAN, LOW FAN) |
|
|
|
|
FAN MOTOR |
6 POLES |
|
|
|
NOTICE SPECIFICATIONS ARE SUBJECT TO MINOR CHANGE WITHOUT NOTICE FOR FURTHER IMPROVEMENT.
8 Room Air Conditioner
Installation
Installation
This air conditioner is designed with a button-down chassis so it can be easily installed in a window.
SelecttheBest Location
1.To prevent vibration and noise, make sure the unit is installed securely and firmly.
2.Install the unit where the sun does not shine directly on the unit.
3.The outside of the cabinet must extend outward for at least 10" and there should be no obstacles, such as a fence or wall, within 20" from the back of the cabinet because it will prevent heat radiation of the condenser. Restriction of outside air will greatly reduce the cooling efficiency of the air conditioner.
INSIDE
COOLED AIR
CAUTION: All side louvers of the cabinet |
60" |
|
must remain exposed on the outdside of |
- |
|
30" |
||
the structure. |
||
|
||
4. Install the unit slanted slightly so the back is slightly |
Figure 1 |
|
lower than the front (about 1/4"). This will force con- |
||
|
||
densed water to the outside. |
|
5.Install the unit with the bottom about 30"~60" above the floor level.
OUTSIDE
FENCE
AWNING
HEAT
RADIATION
ABOUT 1/2 "
Over 20"
HowtoInstall
Window Requirements
NOTICE All supporting parts should be secured to firm wood, masonry, or metal.
1.This unit is designed for installation in standard double hung windows with actual opening widths of 21" to 35". The upper and lower sash must open sufficiently to allow a clear vertical opening of 12" from the bottom of the sash to the window stool.
2.If storm window presents interference, fasten a 2" wide wood strip to the inner window sill across the full width of the sill. The wood strip should be thick enough to raise the height of the window sill so that the unit can be installed without interference by the storm window frame. See Figure. 3. Top of wood strip should be approximately 3/4" higher than the storm window frame (STORM WINDOW FRAME) or wood strip (OUTDOORS) to help condensation to drain properly to the outside.
3.Install a second wood strip (approximately 6" long by 11/2" wide and same thickness as first strip) in the center of the outer sill flush against the back off the inner sill. This will raise the L bracket as shown Figure. 3.
4.If the distance between STORM WINDOW FRAME and WOOD STRIP MOUNTED ON TOP OF INNER SILL is more than 1", two of wood strip are not necessary.
INNER SILL
|
OUTER |
|
SILL |
INDOORS |
OUTDOORS |
Figure 2 |
|
WOOD STRIP MOUNTED |
1" MAX. |
ON TOP OF INNER SILL |
3/4" |
|
CLEARANCE |
|
STORM |
INNER |
WINDOW |
FRAME |
|
SILL |
|
WOOD STRIP |
|
FOR L BRACKET |
|
|
OUTER |
|
SILL |
INDOORS |
OUTDOORS |
Figure 3 |
|
Service Manual 9