To properly use the product, read this manual thoroughly and retain
for easy reference, inspection, and maintenance. Ensure the end user
receives this manual.
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or
transmitted, in any form or by any means, mechanical, electronic, photocopying, recording, or otherwise,
without the prior written permission of Yaskawa. No patent liability is assumed with respect to the use of the
information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality
products, the information contained in this manual is subject to change without notice. Every precaution has
been taken in the preparation of this manual. Yaskawa assumes no responsibility for errors or omissions.
Neither is any liability assumed for damages resulting from the use of the information contained in this
publication.
YAS KAWA ELE CTR IC TOBP C730600 36C 1000-Series Option PG-B3 Installation Manual3
Page 4
1 Preface and Safety
B3
1Preface and Safety
Yaskawa manufactures products used as components in a wide variety of industrial systems
and equipment. The selection and application of Yaskawa products remain the responsibility
of the equipment manufacturer or end user. Yaskawa accepts no responsibility for the way its
products are incorporated into the final system design. Under no circumstances should any
Yaskawa product be incorporated into any product or design as the exclusive or sole safety
control. Without exception, all controls should be designed to detect faults dynamically and
fail safely under all circumstances. All systems or equipment designed to incorporate a
product manufactured by Yaskawa must be supplied to the end user with appropriate
warnings and instructions as to the safe use and operation of that part. Any warnings
provided by Yaskawa must be promptly provided to the end user. Yaskawa offers an express
warranty only as to the quality of its products in conforming to standards and specifications
published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS
OFFERED. Yaskawa assumes no liability for any personal injury, property damage, losses,
or claims arising from misapplication of its products.
◆ Applicable Documentation
The following manuals are available for the option:
The installation manual is packaged with
the option and contains information
required to install the option and set up
related drive parameters.
Yaskawa Drive
Yaskawa AC Drive
1000-Series
Quick Start Guide
Yaskawa AC Drive
1000-Series
Technical Manual
4YASKAWA ELECTRIC TOBP C730600 36C 1000-Series Option PG-B3 Installation Manual
The drive manuals cover basic installation, wiring, operation
procedures, functions, troubleshooting, and maintenance
information.
The manuals also include important information about
parameter settings and drive tuning.
Access these sites to obtain Yaskawa instruction manuals:
U.S.: http://www.yaskawa.com
Europe: http://www.yaskawa.eu.com
Japan: http://www.e-mechatronics.com
For questions, contact your local Yaskawa sales office or the
nearest Yaskawa representative.
Page 5
1 Preface and Safety
DANGER
W ARNING
◆ Terms and Abbreviations
Note:Indicates supplemental information that is not related to safety messages
Drive: Yaskawa AC Drive 1000-Series
Option: Yaskawa AC Drive 1000-Series Option Motor PG Feedback Complementary: Type PG-B3
PG: Pulse Generator or Encoder mounted on the motor
V/f: V/f Control
V/f w/PG: V/f Control with PG
CLV: Closed Loop Vector Control
AOLV/PM: Advanced Open Loop Vector Control for PM
CLV/PM: Closed Loop Vector Control for PM
◆ Registered Trademarks
Trademarks are the property of their respective owners.
◆ Supplemental Safety Information
Read and understand this manual before installing, operating, or servicing this option. Install
the option according to this manual and local codes.
The following conventions indicate safety messages in this manual. Failure to heed these
messages could cause fatal injury or damage products and related equipment and systems.
Indicates a hazardous situation, which, if not avoided, will result in death or serious
injury.
Indicates a hazardous situation, which, if not avoided, could result in death or
serious injury.
Indicates a hazardous situation, which, if not avoided, could result in minor or
moderate injury.
Indicates an equipment damage message.
■General Safety
General Precautions
• The diagrams in this book may include options and drives without covers or safety shields to
illustrate details. Be sure to reinstall covers or shields before operating any devices. Use the option
according to the instructions described in this manual.
• Any illustrations, photographs, or examples used in this manual are provided as examples only and
may not apply to all products to which this manual is applicable.
• The products and specifications described in this manual or the content and presentation of the
manual may be changed without notice to improve the product and/or the manual.
• When ordering new copies of the manual, contact a Yaskawa representative or the nearest Yaskawa
sales office and provide the manual number shown on the front cover.
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operating company is responsible for any injuries or equipment damage resulting
from failure to heed the warnings in this manual.
The PG-B3 Option allows the user to connect an incremental encoder with complementary
output (PG) for motor speed feedback to the drive and take advantage of the V/f with PG,
Closed Loop Vector, and Closed Loop Vector for PM motors control modes. The option
helps increase the control accuracy and higher performance.
This PG encoder signal allows the drive to compensate for subtle variations in the load,
while providing the drive with the necessary data to control the output frequency and
maintain an accurate constant speed.
The PG-B3 Option reads a maximum input frequency from the PG encoder of 50 kHz. Be
sure to select an PG encoder with an output of maximum 50 kHz when operating at
maximum speed.
◆ Applicable Models
The option can be used with the drive models in Tab le 1 .
Table 1 Applicable Models
Drive SeriesDrive Model Number
A1000All models
L1000AAll models
8YASKAWA ELECTRIC TOBP C730600 36C 1000-Series Option PG-B3 Installation Manual
Page 9
3 Receiving
B3
B3
3Receiving
Please perform the following tasks upon receiving the option:
• Inspect the option for damage. Contact the shipper immediately if the option appears
damaged upon receipt.
• Verify receipt of the correct model by checking the model number printed on the option
nameplate (Refer to Figure 1 on page 10 for more information).
• Contact your supplier if you have received the wrong model or the option does not
• A Phillips screwdriver (M3 metric / #1, #2 U.S. standard size) is required to install the
option.
• A straight-edge screwdriver (blade depth: 0.4 mm, width: 2.5 mm) is required to wire the
option terminal block.
• A pair of diagonal cutting pliers.
• A small file or medium-grit sandpaper.
Note: Tools required to prepare option cables for wiring are not listed in this manual.
YASKAWA ELECTRIC TOBP C730600 36C 1000-Series Option PG-B3 Installation Manual9
Page 10
4 Option Components
PG-B3
Underside
F
E
A
B
D
C
B3
B3
4Option Components
◆ PG-B3 Option
Figure 1
A – Terminal block TB1D – Installation hole
B – Model numberE – Terminal block TB2
C – Connector (CN5)F – Ground terminal and installation
<1> The ground wires provided in the option shipping package must be connected during installation.
Figure 1 PG-B3 Option Components
◆ Terminal Blocks TB1 and TB2
hole
<1>
IGIG
TB1
Refer to Table 6 on page 25 for details on TB1 and TB2 terminal functions and signal levels.
10YASKAWA ELECTRIC TOBP C730600 36C 1000-Series Option PG-B3 Installation Manual
A-A+FESDZ-Z+B-B+
AO
IGIP
TB2
ZO
IG
BO
Page 11
5 Installation Procedure
W ARNING
5Installation Procedure
◆ Section Safety
DANGER
Electric Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
Disconnect all power to the drive, wait at least the amount of time specified on the drive
front cover safety label. After all indicators are off, measure the DC bus voltage to
confirm safe level, and check for unsafe voltages before servicing. The internal capacitor
remains charged after the power supply is turned off.
Electrical Shock Hazard
Do not remove the front covers of the drive while the power is on.
Failure to comply could result in death or serious injury.
The diagrams in this section may include options and drives without covers or safety
shields to show details. Be sure to reinstall covers or shields before operating any devices.
Use the option according to the instructions described in this manual.
Do not allow unqualified personnel to use equipment.
Failure to comply could result in death or serious injury.
Maintenance, inspection, and replacement of parts must be performed only by authorized
personnel familiar with installation, adjustment, and maintenance of this product.
Do not touch circuit boards while the power to the drive is on.
Failure to comply could result in death or serious injury.
YASKAWA ELECTRIC TOBP C730600 36C 1000-Series Option PG-B3 Installation Manual11
Page 12
5 Installation Procedure
NOTICE
W ARNING
Do not use damaged wires, stress the wiring, or damage the wire insulation.
Failure to comply could result in death or serious injury.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to
overheating of electrical connections.
Damage to Equipment
Observe proper electrostatic discharge (ESD) procedures when handling the option,
drive, and circuit boards.
Failure to comply may result in ESD damage to circuitry.
Never shut the power off while the drive is running or outputting voltage.
Failure to comply may cause the application to operate incorrectly or damage the drive.
Do not operate damaged equipment.
Failure to comply may cause further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance.
Use shielded twisted-pair wires and ground the shield to the ground terminal of the drive.
Properly connect all pins and connectors.
Failure to comply may prevent proper operation and possibly damage equipment.
Check wiring to ensure that all connections are correct after installing the option
and connecting any other devices.
Failure to comply may result in damage to the option.
Prior to installing the option, wire the drive, make the necessary connections to the drive
terminals, and verify that the drive functions normally. Refer to the Quick Start Guide
packaged with the drive for information on wiring and connecting the drive.
Figure 2 shows an exploded view of the drive with the option and related components for
reference.
Figure 2
A
B
L
K
C
D
J
E
I
F
H
G
A – Insertion point for CN5G – Removable tabs for wire routing
B – Option cardH – Ground wire
C – Included screwsI – Drive grounding terminal (FE)
D – Front coverJ – Connector CN5-A
E – Digital operatorK – Connector CN5-B
F – Terminal coverL – Connector CN5-C
Refer to the instructions below to install the option.
1. Shut off power to the drive, wait the appropriate amount of time for voltage to
dissipate, then remove the digital operator (E) and front covers (D, F). Refer to the
Quick Start Guide packaged with the drive.
DANGER! Electrical Shock Hazard. Disconnect all power to the drive and wait at least the amount of time
specified on the drive front cover safety label. After all indicators are off, measure the DC bus voltage to
confirm safe level, and check for unsafe voltages before servicing to prevent electric shock. The internal
capacitor remains charged even after the power supply is turned off.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling
the option, drive, and circuit boards. Failure to comply may result in ESD damage to circuitry.
Figure 3
Figure 3 Remove the Front Covers and Digital Operator
3. Connect one end of the ground wire (H) to the ground terminal (I) using one of the
remaining screws (C). Connect the other end of the ground wire (H) to the
remaining ground terminal and installation hole on the option (B) using the last
remaining provided screw (C).
Figure 5
B
C
I
H
Figure 5 Connect the Ground Wire
Note: 1. The option package includes two ground wires. Use the longer wire when plugging the option into
connector CN5-C on the drive side. Use the shorter wire when plugging the option into connector
CN5-B. Refer to Option Package Contents on page 9 for more information.
2. There are two screw holes on the drive for use as ground terminals (I). When connecting three options,
two ground wires will need to share the same drive ground terminal.
about 5.5 mm (7/32”)
When not using
crimped insulated
sleeves
Pull back the shielding and lightly
twist the end with fingers, keeping
the ends from fraying.
To PG at motor
(do not solder ends)
Loosen the screws and
insert the wire into the
opening on the terminal block.
Blade depth of
0.4 mm or less
Blade width of
2.5 mm or less
B3
4. Prepare and connect the wire ends as shown in Figure 6 and Figure 7. Refer to
Wire Gauges and Tightening Torques on page 24 to confirm that the proper
tightening torque is applied to each terminal. Take particular precaution to ensure
that each wire is properly connected and wire insulation is not accidentally pinched
into electrical terminals.
WARNING! Fire Hazard. Tighten all terminal screws according to the specified tightening torque. Loose
electrical connections could result in death or serious injury by fire due to overheating electrical connections.
Tightening screws beyond the specified tightening torque may result in erroneous operation, damage the
terminal block, or cause a fire.
NOTICE: Heat shrink tubing or electrical tape may be required to ensure that cable shielding does not
contact other wiring. Insufficient insulation may cause a short circuit and damage the option or drive.
Figure 6
Figure 7
5. Wire the motor PG encoder to the terminal block on the option. Refer to Figure 8
and Figure 9 for wiring instructions.
Refer to Option Terminal Functions on page 25 for a detailed description of the
■Parameter Settings and Connections for Different Encoder Types
Connecting a Single-Pulse Encoder
When using a single-pulse encoder in V/f with PG control mode, connect the pulse output
from the PG to the option and set drive parameter F1-21 to 0.
Connecting a Two-Pulse Encoder
When using a two-pulse encoder, connect the A and B pulse outputs on the PG to the option
and set F1-21 to 1.
When using a two-pulse encoder in Closed Loop Vector control mode, connect pulse outputs
A and B from the encoder to the corresponding terminals on the option.
Connecting a Two-Pulse Encoder with Z Marker Pulse
When using a two-pulse encoder with Z marker pulse, connect the A, B, and Z pulse outputs
to the corresponding terminals on the option.
Control MethodV/f with PGClosed Loop Vector
No. of Encoders1 (CN5-C)2 (CN5-B)1 (CN5-C)2 (CN5-B)
Single Pulse (A)F1-21 = 0F1-37 = 0N/AN/A
Two Pulse (AB Quadrature)F1-21 = 1F1-37 = 1No setting required No setting required
Two Pulse with Marker (ABZ)F1-21 = 1F1-37 = 1No setting required No setting required
Depending on the drive model, some drives may require routing the wiring through
the side of the front cover to the outside. In these cases, cut out the perforated
openings on the left side of the drive front cover as shown in Figure 10-A and leave
no sharp edges to damage wiring.
Route the wiring inside the enclosure as shown in Figure 10-B for drives that do not
require routing through the front cover.
Refer to the Peripheral Devices & Options section of the drive Technical Manual for
Figure 10
more information.
5 Installation Procedure
A – Route wires through the openings
provided on the left side of the
front cover.
<1> The drive will not meet NEMA Type 1 requirements if wiring is exposed outside the enclosure.
8. Set drive parameters in Table 7 for proper motor rotation.
A pulse
B pulse
The A pulse leads, followed
by the B pulse displaced at 90 degrees
Time
→
B3
A+ A- B+ B- Z+ Z-
3456
A+ A- B+ B- Z+ Z-
5634
B3
With a two-pulse or three-pulse PG encoder, the leading pulse determines the
motor rotation direction. A PG encoder signal with leading A pulse is considered to
Figure 12
Figure 13
be rotating forward (counter-clockwise when viewing rotation from motor load side).
Figure 12 Displacement of A and B Pulses
After connecting the PG encoder outputs to the option, apply power to the drive and
manually rotate the motor and check the rotation direction by viewing monitor U1-05
on the digital operator.
Reverse motor rotation is indicated by a negative value for U1-05; forward motor
rotation is indicated by a positive value.
If monitor U1-05 indicates that the forward direction is opposite of what is intended,
reverse the two A pulse wires with the two B pulse wires on option terminal TB1 as
shown in Figure 13.
Figure 13 A Channel and B Channel Wire Switching
If switching the wires is inconvenient, set drive parameter F1-05/F1-32 to 1 to switch
the direction of how the option reads pulses from the PG encoder output.
Please note that when the drive is initialized using A1-03 =1110, 2220, 3330, the
value for F1-05/F1-32 will reset to factory default and the parameter will need to be
adjusted again to switch the direction.
◆ Wire Gauges, Tightening Torque, and Crimp Terminals
■Wire Gauges and Tightening Torques
Wire gauge and torque specifications are listed in Tab l e 4 .
Table 4 Wire Gauges and Tightening Torques
Ter min al
Signal
A+, A–, B+,
B–, Z+, Z–,
FE, IP, IG
AO, IG, BO,
IG, ZO, IG
■
Crimp Terminals
Screw
Size
M2
Tightening
Torque
Nxm
(inxlb)
0.22 to 0.25
(1.95 to 2.21)
Yaskawa recommends using CRIMPFOX 6 by Phoenix Contact or equivalent crimp
terminals with the specifications listed in Table 5 for wiring to ensure proper connections.
Note: Properly trim wire ends so loose wire ends do not extend from the crimp terminals.
The following parameters set the drive for operation with the option. Set parameters as
needed. Parameter setting methods can be found in the drive Quick Start Guide or Technical
Manual.
Tab l e 7 Related Parameters
No.
(Addr. Hex)
A1-02
(102)
F1-01
(380)
<2> <3>
F1-02
(381)
F1-03
(382)
F1-04
(383)
F1-05
(384)
<3>
NameDescription
0: V/f Control
Control
Method
Selection
PG 1 Pulses
per Revolution
PG Feedback
Loss Operation
Selection
PG Overspeed
Operation
Selection
PG Deviation
Operation
Selection
PG 1 Rotation
1: V/f Control with PG
2: Open Loop Vector Control
3: Closed Loop Vector Control
5: Open Loop Vector Control for PM
6: Advanced Open Loop Vector Control for PM
7: Closed Loop Vector Control for PM
Sets the pulses to be read from the pulse generator.
Sets the stopping method after PG disconnect (PGo).
0: Ramp to stop (decelerates at time set to C1-02)
1: Coast to stop
2: Fast Stop (decelerates at the time set to C1-09)
3: Continue running
4: No alarm display
NOTICE: Due to potential damage to the motor and
machinery, only use settings 3 and 4 under special
circumstances.
Sets the stopping method after detecting overspeed.
0: Ramp to stop (decelerates at time set to C1-02)
1: Coast to stop
2: Fast Stop (decelerates at the time set to C1-09)
3: Continue running
NOTICE: Due to potential damage to the motor and
machinery, do not use the "Continue running" setting
except under special circumstances.
0: Ramp to stop (decelerates at time set to C1-02)
1: Coast to stop
2: Fast Stop (decelerates at the time set to C1-09)
3: Continue running
NOTICE: Due to potential damage to the motor and
machinery, do not use the "Continue running" setting
except under special circumstances.
0: Forward = A pulse leads
1: Forward = B pulse leads
Control
Mode
All Modes
V/f w/ PG
CLV
CLV/PM
V/f w/ PG
CLV
CLV/PM
V/f w/ PG
CLV
CLV/PM
V/f w/ PG
CLV
CLV/PM
AOLV/PM
V/f w/ PG
CLV
CLV/PM
Values
<1>
Default:
Range: <1>
Default:
<1>
Min: <1>
Max: <1>
Default: 1
<1>
Range:
Default: 1
Range: 0 to 3
<1>
Default:
Range: 0 to 3
<1>
Default:
Range: 0, 1
26YASKAWA ELECTRIC TOBP C730600 36C 1000-Series Option PG-B3 Installation Manual
Page 27
6 Related Parameters
Pulses × 60
F1-01
×
F1-13 (load side)
F1-12 (motor side)
No.
(Addr. Hex)
F1-06
(385)
<3>
F1-08
(387)
F1-09
(388)
F1-10
(389)
F1-11
(38A)
F1-12
(38B)
<3> <5>
F1-13
(38C)
<3> <5>
F1-14
(38D)
F1-18
<3>
(3AD)
F1-19
<3>
(3AE)
F1-21
(3BC)
<3>
F1-30
(3AA)
<6>
NameDescription
Sets the division ratio for PG encoder pulse output.
Set as a three-digit number: x is the first digit, y is the
PG 1 Ratio for
PG Pulse
Monitor
second digit, and z is the third digit:
(1 + x)
Ratio =
yz
When only the A pulse is read, this ratio is disabled
and pulses are set as 1/32 : 1.
PG Overspeed
Level
Overspeed Det.
Time
Excessive
Speed
Deviation Det.
Level
Excessive
Speed
Deviation Det.
Time
PG 1 Gear
Teeth 1
PG 1 Gear
Teeth 2
PG Disconnect
Det. Time
Reverse
Rotation Det.
for PG 1
Reverse
Rotation Det.
for PG 1
PG 1 Option
Function
Motor 2 PG
Connector
Sets the level for detecting overspeed as a percentage
of the maximum output frequency.
Sets the time required for the motor to exceed the
level set in F1-08 to trigger a fault.
Sets the degree of speed deviation to trigger a dEv
fault. Set as a percentage of the maximum output
frequency.
Sets the time required a speed deviation situation to
trigger a fault.
Number of gear teeth between the PG and motor.
A gear ratio of 1 will be used if any of these
parameters is set to 0.
Sets the time in seconds for PG encoder disconnect to
be detected.
0: Disabled
n: Number of times a dv3 situation must be detected
to trigger a fault.
0: Disabled
n: Number of times a dv4 situation must be detected
to trigger a fault.
0: A pulse detection
1: AB pulse detection
Selects the PG option connector for motor 2.
0: CN5-C
1: CN5-B
Sets the pulses to be read from the pulse generator.
0: Forward = A pulse leads
1: Forward = B pulse leads
Number of gear teeth between the PG and motor.
A gear ratio of 1 will be used if any of these
parameters is set to 0.
Sets the division ratio for PG encoder pulse output.
Set as a three-digit number where x is the first digit, y
is the second digit, and z is the third digit:
(1 + x)
Ratio =
yz
Control
Mode
V/f w/ PG
CLV
V/f w/ PG
CLV
V/f w/ PG
V/f w/ PG
CLV
Values
Default: 1024
Min: 0
Max: 60000
Default: 0
Range: 0, 1
Default: 0
Min: 0
Max: 1000
Default: 1
Min: 1
Max: 132
When only the A pulse is read, this ratio is disabled
and pulses are set as 1/32 : 1.
F1-37
(3BD)
<7>
<1> Varies by drive models.
<2> The number of output pulses for the PG encoder can be calculated with the following formula:
<3> The parameter is available only for the drive connector CN5-C.
<4> Value changes according to the control mode selection in A1-02.
<5> Enabled only when using the V/f with PG control mode.
<6> Depending on the drive series, a second PG encoder (PG 2) may not be possible. Refer to the drive Technical
Manual for the drive in your application.
<7> The parameter is available only for the drive connector CN5-B.
Ta bl e 8 lists the various fault codes related to the option and pulse generator. Refer to the
drive Technical Manual for further details on fault codes.
Check the following items first when an error code occurs on the drive:
• Are the cables connected properly and securely?
• Is the option properly installed to the drive?
• Did a momentary power loss occur?
Table 8 Fault Displays, Causes, and Possible Solutions
Digital Operator DisplayFault Name
dEv
CausePossible Solution
The load is too heavy.Reduce the load.
The acceleration and
deceleration times are set too
short.
The load is locked up.Check the machine.
Parameters are set
inappropriately.
Motor brake is engaged.Ensure the motor brake releases properly.
Digital Operator DisplayFault Name
dv1
CausePossible Solution
The PG encoder is disconnected
or is not wired properly, or the
PG option or PG encoder are
damaged.
Digital Operator DisplayFault Name
dv2
CausePossible Solution
PG encoder cable noise
interference.
Speed Deviation (for Control Mode with PG)
The deviation between the speed reference and speed feedback is greater than the
setting in F1-10 for longer than the time set to F1-11.
Increase the acceleration and deceleration times (C1-01 through C1-08).
Check the settings of parameters F1-10 and F1-11.
Z Channel Pulse Fault Detection
The motor turned one full rotation while failing to detect the Z channel pulse.
• Rewire the PG encoder and make sure all wiring including shielded wiring is
properly connected.
• If the problem continues after cycling power, replace the PG option or the PG
encoder.
Z Channel Pulse Noise Fault Detection
The Z channel pulse is out of phase by more than 5 degrees for the number of
times specified in parameter F1-17.
Separate the PG encoder cable wiring from the source of the noise (e.g., drive
output wiring).
YASKAWA ELECTRIC TOBP C730600 36C 1000-Series Option PG-B3 Installation Manual29
Page 30
7 Troubleshooting
The PG encoder is disconnected
or is not wired properly, or the
PG option or PG encoder are
damaged.
Digital Operator DisplayFault Name
dv3
CausePossible Solution
The Z channel pulse offset is not
set properly to E5-11.
An external force on the load
side caused the motor to move.
Noise interference along the PG
encoder cable is affecting the A
channel or B channel.
The PG encoder is disconnected
or is not wired properly, or the
PG option or PG encoder are
damaged.
The PG encoder rotational
direction set to F1-05 is in the
opposite direction of the motor
wiring.
Digital Operator DisplayFault Name
dv4
CausePossible Solution
The Z channel pulse offset is not
set properly to E5-11.
Noise interference along the PG
encoder cable is affecting the A
or B pulse.
• Rewire the PG encoder and make sure all wiring including shielded wiring is
properly connected.
• If the problem continues after cycling power, replace the PG option or the PG
encoder.
Inversion Detection
• Torque reference and acceleration are in opposite directions.
• The speed reference and actual motor speed differ by over 30% for the number
of pulses set to parameter F1-18.
Set the value for Δθ to E5-11 as specified on the motor nameplate. Replacing the
PG encoder or changing the application so the motor rotates in reverse requires
readjustment of the Z channel pulse offset.
• Make sure the motor is rotating in the proper direction.
• Investigate problems on the load side causing motor rotation in the opposite
direction.
• Rewire the PG encoder and make sure all wiring including shielded wiring is
properly connected.
• If the problem continues after cycling power, replace the PG option or the PG
encoder.
Make sure motor wiring for each phase (U, V, W) is connected properly.
Inversion Prevention Detection
Pulses indicate that the motor is rotating in the opposite direction of the speed
reference. Set the number of pulses to trigger inverse detection to F1-19.
Note: To avoid nuisance faults, be sure to disable inverse detection in applications
where the motor may rotate in the opposite direction of the speed reference. Set
F1-19 to 0 to disable this feature.
• Set the value for Δθ to E5-11 as specified on the motor nameplate.
• If the problem continues after cycling power, replace the PG option or the PG
encoder.
Replacing the PG encoder or changing the application so the motor rotates in
reverse requires readjustment of the Z channel pulse offset.
• Make sure the motor is rotating in the proper direction.
• Investigate problems on the load-side that may be causing the motor to rotate in
the opposite direction.
Brake is holding the PG encoder. Ensure the brake releases properly.
PG Encoder Disconnected
Detected when no PG encoder pulses received for a time longer than setting in
F1-14.
Reconnect the cable.
Correct the wiring.
Make sure the correct power supply is properly connected to the PG encoder.
Table 9 Operation Error Displays, Causes, and Possible Solutions
Digital Operator DisplayFault Name
oPE06
CausePossible Solution
Control mode requires installing
a PG option, but no PG option is
installed (A1-02 = 1, 3, or 7).
Control Method Selection Error
Correct the setting for the control method.
• Connect a PG option.
• Correct the value set to A1-02.
◆ Preventing Noise Interference
Take the following steps to prevent erroneous operation caused by noise interference:
• Use shielded wire for the PG encoder signal lines.
• Limit the length of all motor output power cables to less than 100 m. Limit the length of
open-collector output lines to less than 50 m.
• Separate the control wiring to the option, main circuit input power wiring, and motor
output power cables.
• Ground the shield on the PG encoder side and the drive side. If noise problems arise in the
PG encoder signal, verify that the shield is properly grounded and ground one end of the
signal line or remove the ground connection on both ends.
Room 1011, Tower W3 Oriental Plaza, No. 1 East Chang An Ave.,
Dong Cheng District, Beijing, 100738, China
Phone: 86-10-8518-4086
YASKAWA ELECTRIC TAIWAN CORPORATION
9F, 16, Nanking E. Rd., Sec. 3, Taipei, 104, Taiwan
Phone: 886-2-2502-5003
YASKAWA ELECTRIC INDIA PRIVATE LIMITED
#17/A Electronics City, Hosur Road Bangalore 560 100 (Karnataka), India
Phone: 91-80-4244-1900
http://www.yaskawaindia.in
Fax: 55-11-5581-8795
Fax: 44-1236-458182
Fax: 82-2-784-8495
Fax: 65-6289-3003
Fax: 86-21-5385-3299
Fax: 86-10-8518-4082
Fax: 886-2-2505-1280
Fax: 91-80-4244-1901
YASKAWA ELECTRIC CORPORATION
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture
thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure
to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.