Yaskawa P7 User Manual

P7 Metasys® N2
Technical Manual
Models: CIMR-P7U* Document Number: TM.P7.22
This Section provides warnings and cautions pertinent to this product that if not heeded, may result in personal injury, fatality or equipment damage. Yaskawa is not responsible for consequences of ignoring these instructions.
WARNING
YASKAWA manufactures component parts that can be used in a wide variety of industrial applications. The selection and application of YASKAWA products remain the responsibility of the equipment designer or end user. YASKAWA accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances should any YASKAWA product be incorporated into any product or design as the exclusive or sole safety control. Without exception, all controls should be designed to detect faults dynamically and to fail safely under all circumstances. All products designed to incorporate a component part manufactured by YASKAWA must be supplied to the end user with appropriate warnings and instructions as to that part’s safe use and operation. Any warnings provided by YASKAWA must be promptly provided to the end user. YASKAWA offers an express warranty only as to the quality of its products in conforming to standards and specifications published in the YASKAWA manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS OFFERED. YASKAWA assumes no liability for any personal injury, property damage, losses, or claims arising from misapplication of its products.
WARNING
Read and understand this manual before installing, operating, or servicing this drive. All warnings, cautions, and instructions must be
followed. Qualified personnel must perform all activity. The drive must be installed according to this manual and local codes.
Do not connect or disconnect wiring while the power is on. Do not remove covers or touch circuit boards while the power is on. Do
not remove or insert the digital operator while power is on.
Before servicing, disconnect all power to the equipment. The internal capacitor remains charged even after the power supply is turned
off. Status indicator LEDs and Digital Operator display will be extinguished when the DC bus voltage is below 50 VDC. To prevent electric shock, wait at least 5 minutes after all indicators are OFF and measure DC bus voltage and verify that it is at a safe level.
Do not perform a withstand voltage test on any part of the unit. This equipment uses sensitive devices and may be damaged by high
voltage.
The drive is not suitable for circuits capable of delivering more than the specified RMS symmetrical amperes. Install adequate branch
short circuit protection per applicable codes. Refer to the specification. Failure to do so may result in equipment damage and/or personal injury.
Do not connect unapproved LC or RC interference suppression filters, capacitors, or over voltage protection devices to the output of
the drive. Capacitors may generate peak currents that exceed drive specifications.
To avoid unnecessary fault displays, caused by contactors or output switches placed between drive and motor, auxiliary contacts must
be properly integrated into the control logic circuit.
YASKAWA is not responsible for any modification of the product made by the user, doing so will void the warranty. This product
must not be modified.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power. To meet CE directives, proper line filters and proper installation are required. Some drawings in this manual may be shown with protective covers or shields removed, to describe details. These must be replaced
before operation.
Observe Electrostatic Discharge Procedures when handling the drive and drive components to prevent ESD damage. The attached equipment may start unexpectedly upon application of power to the drive. Clear all personnel from the drive, motor and
machine area prior to applying power. Secure covers, couplings, shaft keys, machine beds and all safety equipment before energizing the drive.
i
Introduction
The Metasys N2 protocol is considered a CASE option for the P7U drive and is not included in the standard P7U drive. If the Metasys N2 protocol is necessary, make sure that the correct drive has been ordered and received.
This manual explains the specifications and handling of the Metasys N2 protocol for the Yaskawa model P7U drive. The P7U drive with the Metasys N2 protocol selected, connects the P7U drive to a Metasys N2 network and facilitates the exchange of data.
This document pertains to the Yaskawa P7U drive. Additionally, in this document, the word “inverter”, “ac drive” and “drive” may be used interchangeably.
To ensure proper operation of this product, read and understand this manual. For details on installation and operation of the P7U drive or details on specific P7U parameters, refer to the P7U User Manual, document reference TM.P7.01. For details on P7U MODBUS communications, refer to the P7U MODBUS are on the CD that was supplied with the drive and available for download at www.drives.com.
For more information on the Metasys N2 protocol, please visit www.jci.com. GPD is a trademark of Yaskawa, Inc.
MODBUS Metasys
®
is a registered trademark of Schneider Electric, Inc.
®
N2 is a trademark of Johnson Controls, Inc.
®
Technical Manual, document reference TM.P7.11. All technical manuals and support files
ii
Table of Contents
Chapter 1 Installation...........................................................................1-1
Installation Check Sheet.....................................................................................1-3
Metasys N2 Set-Up ............................................................................................1-5
Chapter 2 Network Connection .......................................................... 2-1
Physical Connection ...........................................................................................2-3
Chapter 3 P7U Drive Functions.......................................................... 3-1
P7U Drive Functions...........................................................................................3-3
Cable Loss Configuration and Behavior .............................................................3-4
P7U Drive Fault Numbers...................................................................................3-6
Chapter 4 Metasys N2 Point Database............................................... 4-1
Metasys N2 Analog Input (AI) Summary ............................................................4-3
Metasys N2 Analog Output (AO) Summary ........................................................4-4
Metasys N2 Binary Input (BI) Summary .............................................................4-5
Metasys N2 Binary Output (BO) Summary.........................................................4-5
Chapter 5 Mailbox Function................................................................ 5-1
Mailbox Function Points .....................................................................................5-3
Chapter 6 P7U Bypass Applications.................................................. 6-1
Bypass/Engineered Drive Parameter Settings ...................................................6-3
Appendix A T r oubleshooting................................................................. 1
Troubleshooting Check List ...................................................................................3
Installing and Configuring Metasys N2 ..................................................................6
Wiring And Cabling ................................................................................................8
Drive Faults ...........................................................................................................9
Appendix B Hex/Dec Conversion.......................................................... 1
Hex/Dec Conversion Table .................................................................................... 3
iii
This page intentionally left blank.
iv
Chapter 1 Installation
This chapter covers the initial set-up procedure for the P7U drive on a Metasys N2 network.
Installation Check Sheet................................................... 1 – 3
Metasys N2 Set-Up.............................................................1 – 5
Installation 1-1
This page intentionally left blank.
Installation 1-2
Installation Check Sheet
The following is a quick reference guide to the installation and configuration of the P7U drive with the Metasys N2 protocol. Make a copy of this page and check-off each item as it is completed. For detailed information please refer to the detailed sections that follow.
1: Unpack the drive and verify that all components are present and undamaged.
2: Connect power to the drive and verify that the drive functions. This includes running the drive in local mode from the
digital operator without the network selected or connected. Refer to the P7U User Manual for more information on connecting and operating the drive.
3: Remove power from the drive and wait for the charge lamp to be completely extinguished. Wait at least five additional
minutes after all indicators are off. Measure the DC bus voltage and verify that it is at a safe level.
4: Connect the drive to the Metasys N2 communication network. Refer to Chapter 2 – Network Connection for the Metasys
N2 connection procedure.
5: If this drive is either the first or the last device on the network, set the terminating resistor switch, S1-1, to ON. If this
device is not the first or last device on the network, set the terminating resistor switch, S1-1, to OFF. Refer to Chapter 2 –
Network Connection for details.
6: Configure the Metasys N2 network for the drive as a VND device. Refer to the documentation included with the Metasys
N2 configuration software.
7: Set parameters b1-01, b1-02, H5-01, H5-02 and H5-08 to their appropriate values. Refer to Table 1.1 - Drive
Communication Parameter Settings on page 1-5.
Installation 1-3
This page intentionally left blank.
Installation 1-4
Metasys N2 Set-Up
A Ya skawa Electric America, Inc. (YEA) representative is responsible for proper configuration of the drive for its primary application, while a Johnson Controls, Inc. representative is responsible for field panel programming to make use of the drive’s functionality in the building automation system as a VND device. As such, there must be coordination between the Yaskawa Electric America and Johnson Controls representatives to ensure that the programming of the drive is consistent with the particular application requirements. After verifying that the drive installation and wiring are correct, apply power to the drive. Table 1.1 below lists the parameters and their values required for proper Metasys N2 communication and control.
P7U Drive Parameter Settings for Metasys N2 Communications
Table 1.1 - Drive Communication Parameter Settings
Parameter Number Digital Operator Display Settings for Metasys N2 Communication
b1-01 Reference Source 2: Serial Com b1-02 Run Source 2: Serial Com H5-01 Serial Comm Adr Select the drive address (default = 1F hex (31 dec)) H5-02 Serial Baud Rate 3: 9600 Baud H5-08 Protocol Select
1: N2 (Metasys)
CAUTION
A YEA representative should set the drive parameters to their appropriate values. Changes made to the parameters other than what is listed in the table above can result in damaging the drive or building equipment.
Programming the P7U Drive for Metasys N2
The procedure for programming the P7U drive for communication on an Metasys N2 network is shown in the table below: Refer to the P7U User Manual, TM.P7.01, for detailed information on using the P7U Operator.
Table 1.2 - Drive Programming Procedure for Metasys N2
Description Key Operation Digital Operator Display
Apply Power to the drive
Select Programming Menu
Press the MENU key until the display matches
the display to the right.
Enter Programming Menu
Press the DATA ENTER key to select the Programming Menu (A1 blinking)
x3
-DRIVE- Rdy
U1-01 = 0.00Hz
- - - - - - - - - - - - - - - - - - - - - - - - - ­ U1-02 = 0.00Hz U1-03 = 0.00A
- - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - -
Frequency Ref
-ADV­** Main Menu **
Programming
-ADV-
Initialization
A1-00 = 0
Select Language
Press the UP ARROW key until Reference
Select Sequence Parameters
Source is displayed (b1 blinking).
Note: The item selected will blink.
x2
Installation 1-5
-ADV-
Sequence
- - - - - - - - - - - - - - - - - - - - - - - - - -
b1-01 = 2
Reference Source
Table 1.2 - Drive Programming Procedure for Metasys N2
Description Key Operation Digital Operator Display
Select Reference Command Source
Press DATA ENTER key to edit b1-01 (value blinking). Press the UP ARROW key to change the parameter value until the display matches the display shown on the right. Press the DATA ENTER key to accept the entry. “Entry Accepted” will be displayed if successful.
Note: Since communications has not been established, a “CALL” alarm may be generated. Press the STOP key to clear the alarm. If communications has not been established within the timeout interval, the alarm will reoccur. Press the STOP key to clear the “CALL” alarm whenever it occurs.
-ADV-
- - - - - - - - - - - - - - - - - - - - - - - - - -
Reference Source
b1-01 = 2 *2*
Serial Com
“1”
Press the UP ARROW key until Run Source is
Select Run Command Source
displayed (02 blinking). Press DATA ENTER key to edit b1-02 (value blinking). Press the UP ARROW key to change the parameter value until the display matches the display shown on the right. Press the DATA ENTER key to accept the entry. “Entry Accepted” will be displayed if successful. If 02 is blinking, press the RESET key to go back to the b1 menu (b1 blinking).
Select Serial Communications Parameters
Press the UP ARROW key until Serial Com Setup is displayed (H5 blinking).
Select N2 (Metasys))
Press the RESET key to select an H5 parameter (01 blinking). Press the UP ARROW key until H5-08 is displayed (08 blinking). Press the DATA ENTER key to edit the H5-08 parameter (value blinking). Press the UP ARROW key to change the parameter value until the display matches the display shown on the right. Press the DATA ENTER key to accept the entry. “Entry Accepted” will be displayed if successful.
Note: N2 (Metasys) must be selected prior to setting the node address.
x21
x7
-ADV-
Run Source
- - - - - - - - - - - - - - - - - - - - - - - - - -
b1-02 = 2 *1*
Serial Com
“1”
-ADV-
Serial Com Setup
- - - - - - - - - - - - - - - - - - - - - - - - - -
H5-01 = 1F
Serial Comm Adr
-ADV-
Protocol Select
- - - - - - - - - - - - - - - - - - - - - - - - - -
H5-08 = 1 *1*
N2 (Metasys)
“0”
Installation 1-6
Table 1.2 - Drive Programming Procedure for Metasys N2
Description Key Operation Digital Operator Display
Press the DOWN ARROW key until parameter H5-01 is displayed (01 blinking). Press the DATA ENTER key to edit parameter H5-01 (value blinking). Press the RESET or RIGHT ARROW key to select the digit to edit. The selected digit will blink. Press the UP ARROW or DOWN ARROW keys to change the value of the selected digit until the correct value is displayed. Press the DATA ENTER key to accept the entry. Edit all digits prior to pressing the DATA ENTER key. “Entry Accepted” will be displayed if successful.
Press the UP ARROW key until parameter H5-02 is displayed (02 blinking). Press the DATA ENTER key to edit parameter H5-02 (value blinking). Press the UP ARROW key to change the parameter value until the display matches the display shown on the right. Press the DATA ENTER key to accept the entry. “Entry Accepted” will be displayed if successful.
Select Node Address
Select Baud Rate of 4800 Baud
x7
-ADV-
- - - - - - - - - - - - - - - - - - - - - - - - - -
*This is always entered as a hexadecimal value. Refer to the conversion chart in Appendix B for information on converting decimal values to their hexadecimal equivalents
- - - - - - - - - - - - - - - - - - - - - - - - - -
Serial Comm Adr
H5-01 = 1F*
(0~255)
“1F”
-ADV-
Serial Baud Rate
H5-02 = 3 *3*
9600 Baud
“3”
-DRIVE-
Select The Drive Mode
Enter The Drive Mode
- - - - - - - - - - - - - - - - - - - - - - - - - -
-DRIVE- Rdy
U1-01 = 0.00Hz
- - - - - - - - - - - - - - - - - - - - - - - - - ­ U1-02 = 0.00Hz U1-03 = 0.00A
** Main Menu **
Operation
Frequency Ref
Installation 1-7
This page intentionally left blank.
Installation 1-8
Chapter 2 Network Connection
This chapter discusses how to connect the P7U drive to a Metasys N2 network.
Physical Connection.......................................................... 2 – 3
Network Connection 2-1
This page intentionally left blank.
Network Connection 2-2
Loading...
+ 37 hidden pages