To properly use the product, read this manual
thoroughly and retain for easy reference, inspection,
and maintenance. Ensure the end user receives this manual.
PMC-U-MP33020CPU, MP3300, 20 axis, 40 0 MHz, 4MB SRAM
PMC-U-MP33320CPU, MP3300, 20 axis, 80 0 MHz, 8MB SRAM
PMC-U-MP33332CPU, MP3300, 32 axis, 80 0 MHz, 8MB SRAM
JEPMC-BU3304-EBase Unit with DC Power Supply, 1 Slot, MP3300iec
JEPMC-BU3303-EBase Unit with DC Power Supply, 3 Slots, MP3300iec
JEPMC-BU3302-EBase Unit with DC Power Supply, 8 Slots, MP3300iec
JEPMC-BU3301-EBase Unit with AC Power Supply, 8 Slots, MP3300iec
JAPMC-AN2300Analog Inputs (AI-01)
JAPMC-AN2310-EAnalog Outputs (AO-01)
JAPMC-DO2300Digital Output Modul e (DO-01)
JAPMC-IO2300-E Digital I/O Module (LIO-01)
JAPMC-IO2301-EDigital I/O Module (LIO-02)
JAPMC-IO2303Digital I/O Module (LIO-04)
JAPMC-IO2304Digital I/O Module (LIO-05)
JAPMC-IO2305-EDigital Multi-Function I/O Module (LIO-06)
JAPMC-CM2301-EEthernet & RS232C Communication (218IF-Y1)
JEPMC-MT2000-EHUB, MECHATROLINK-III NETWORK, 8 SLAVE PORTS
JEPMC-MT2020-EADAPTER, ETHERNET TO MECHATROLINK
JEPMC-MTD2310-EI/O MODULE, MECHATROLINK NETWORK, 64 IN, 64 OUT
JEPMC-MTA2900-EANALOG MODULE, MECHATROLINK NETWORK, 8 INPUT
JEPMC-MTA2910-EANALOG MODULE, MECHATROLINK NETWORK, 4 OUTPUT
JEPMC-W6012-A2-EMECHATROLINK-III CABLE, 0.2 M
JEPMC-W6012-A5-EMECHATROLINK-III CABLE, 0.5 M
JEPMC-W6012-01-EMECHATROLINK-III CABLE, 1.0 M
JEPMC-W6012-02-EMECHATROLINK-III CABLE, 2.0 M
JEPMC-W6012-03-EMECHATROLINK-III CABLE, 3.0 M
JEPMC-W6012-04-EMECHATROLINK-III CABLE, 4.0 M
JEPMC-W6012-05-EMECHATROLINK-III CABLE, 5.0 M
JEPMC-W6012-10-EMECHATROLINK-III CABLE, 10 M
JEPMC-W6012-20-EMECHATROLINK-III CABLE, 20 M
JEPMC-W6012-30-EMECHATROLINK-III CABLE, 30 M
JEPMC-W6012-40-EMECHATROLINK-III CABLE, 40 M
JEPMC-W6012-50-EMECHATROLINK-III CABLE, 50 M
JEPMC-BA3001Replacement Battery
JEPMC-OP2300Option Slot Cover
JEPMC-OP3001Replacement Power Supply Side Cover
JEPMC-OP3002Replacement Option Base Side Cover
3 Component Part Numbers
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 7
4 Base Units
4Base Units
The Base Unit provides the backplane to which Modules are mounted and supplies the required power to the Modules.
There are three models of Base Units, a one-slot model, a three-slot model, and an eight-slot model. This section shows
the appearance and part names of the Base Unit and describes the connector.
Appearance and Part Names
Figure 1 illustrates the appearance of the Base Unit and a part name.
Figure 1
RLYOUT connector
Power connector
Figure 1 Base Unit
8YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
Connector
The Base Unit has two connectors: an RLYOUT connector and a power connector.
RLYOUT Connector
The RLYOUT connector outputs the status of the CPU Module.
Figure 2
Figure 2 RLYOUT Connector Model: 734-302
Pin Assignme n ts
No.Signal LabelDescription
1OUT
2OUT
Power Connector
Connect the power supply to this connector.
Figure 3
4 Base Units
Normal operation: Circuit closed.
Error: Circuit open.
DC power supply4-2013522-3White
Pin Assignme n ts
Figure 3 RLYOUT Connector Model: 734-302
Type ModelColor
No.Signal LabelDescription
324 VDCPower input wire for 24 VDC
20 VDCPower input wire for 0 VDC
1FG
Connects to the frame ground. (Ground to
100 W max.)
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 9
5 CPU Specifications
5CPU Specifications
The hardware specifications of the CPU Unit are given in the following table.
Flash MemoryCapacit y: 40 MB (32 MB of user me mo ry )
SDRAMCapacity: 128 MB
SRAMCapacity: 8 MB (battery backup)
CalendarSeconds, minutes, hour, day, week, month, year, day of week, and timing (battery backup)
Ethernet10Base-T or 100Base -TX
MECHATROLINKMECHATROLINK-III: 1 circuit with 2 ports
USB 2.0 Type A host, 1 port
Compatible devices: USB storage
Seven-segment disp lay
Status indicators
USB status indicator
MECHATROLINK-III status indicators
Ethernet status indicators
DIP switch: Mode switch
STOP/SAVE switch. Refer to Switches on page 16 for detailed switch information.
CPU Communications Specifications
The specifications of the Communications Protocols built into the CPU Module are given in the following table.
ProtocolModeDetail
Modbus TCP
Ethernet/IP
OPCread/write
Custom Protocoln/ a
Network Variablesread/writ e
MP3300iec as Master (Client)Maximum Number of Data Bl ocks = 20
MP3300iec as Slave (Server)1000 registers in, 1000 registers out, 256 coils in, 256 coils out
MP3300iec as Master (Scanner)Maximum Number of Data Blocks = 10 0
MP3300iec as Slave (Adapter)
Total of 16 instances in, 16 instances out, arranged as 3 instances of
256 bytes, 3 instances of 128 bytes, and 10 instances of 496 bytes.
Any Global variable can be configured, requires OPC Server running
on PC
Use the YDeviceComm firmware library to create a cu stom
communication protocol.
Variables configured with MotionWorks IEC software that allow
automatic data transfer from controller to controller.
10YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
Display
MECHATROLINK-III status indicators
MECHATROLINK-III connectors
Status indicators
Mode switches
Ethernet status indicators
Ethernet connector
USB status indicator
CPU Module Appearance and Component Names
Figure 4 shows the appearance of the CPU Module and the compnent names.
Figure 4
5 CPU Specifications
Figure 4 CPU Module Component Names
CPU Module Connectors
The CPU Module has three types of connectors: MECHATROLINK-III, Ethernet, and USB.
MECHATROLINK-III Connectors
Figure 5 illustrates connectors used to connect MECHATROLINK-III communications devices.
Figure 5
Figure 5 MECHATROLINK-III Connectors
Ethernet Connectors
Figure 6 illustrates the connector used to connect Ethernet communications devices.
Figure 6
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 11
Figure 6 Ethernet Connector
5 CPU Specifications
r
USB Connector
Figure 5 illustrates the connector used to connect a USB memory device.
Figure 7
USB connecto
Open the cover.
Figure 7 USB Connector
NOTICE: Equipment Hazard. Before removing the USB memory device, press the STOP/SAVE switch and wait until the USB status
indicator goes out. If the USB memory device is removed while the USB status indicator is lit or flashing, the data may become
corrupted.
12 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
6 Installation and Usage Conditions
6Installation and Usage Conditions
This section describes installation and usage conditions for the MP3300iec Series Machine Controllers.
Install the MP3300iec Series Controllers in an environment with the following conditions.
Installation and Usage Conditions
Ta ble 1 MP3300iec Installation and Usage Conditions
ItemSpecification
Environmental
Conditions
Mechanical
Operating
Conditions
Electrical
Operating
Conditions
Installation
Conditions
Ambient Operating
Temperature
Ambient Storage Temperature-25 to 85°C
Ambient Operating Humidity10% to 95% RH (with no condensation)
Ambient Storage Humidity10% to 95% RH (with no condensation)
Pollution LevelConforms to JIS B 3502 Pollution Degree 2.
Corrosive GasThere must be no combustible or corrosive gas.
Operating Altitude2,000 m max.
Vibration Resistance
Shock Resistance
Noise Resistance
GroundGround to 100 Ω max.
Cooling MethodNatural cooling or forced-air cooling. Refer to Control Panel Cooling Method on page 14
0 to 60°C (Forced cooling is required if 55°C is exceeded.)
Conforms to JIS B 3502.
Continuous vibration: 5 to 9 Hz with single-amplitude of 1.75 mm
9 to 150 Hz with fixed acceleration of 4.9 m/s
Intermittent vibration: 5 to 9 Hz with single-amplitude of 3.5 mm
9 to 150 Hz with fixed acceleration of 9.8 m/s
10 sweeps each in X, Y, and Z directions for both intermittent and continuous vibration
Size of shock: Peak accel eration of 147 m/s
Duration: 11 ms
3 times each in X, Y, and Z directions
Conforms to EN 61000-6-2, EN 61000-6-4, and EN 55011 (Group 1 Class A).
Power supply noise (FT noise): ±2 kV min. for one minute
Radiation nois e (F T noise): ±1 kV min. for one minute
Ground noise (impulse noise): ±1 kV min. for 10 minutes
Electrostatic noise (contact disch a rge method): ±6 kV or more, 10 times
2
2
2
(15 G)
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 13
6 Installation and Usage Conditions
Fan
Fan
40 mm min.
10 mm
min.*
* For a control panel with natural cooling with the MBU-303 Base Unit: 30 mm min.
10 mm
min.*
40 mm min.
Approx.
40 mm
Direction
of air ow
Direction
of air ow
Approx.
40 mm
Control Panel Cooling Method
The components that are used in the Machine Controller require the ambient operating temperature to be between 0 and
60 °C. Use one of the methods described below to ensure adequate cooling in the control panel.
NOTICE: Equipment Damage. Use forced-air cooling if the ambient temperature exceeds 55°C.
Control Panels with Natural Cooling
• Do not mount t h e Mac hi ne Controller at the top of the control panel, where the hot a ir t hat i s g ene rat ed inside the panel
collects.
• Leave sufficient space above and below the Machine Controller, and maintain adequate distances from other devices,
cable ducts, and other objects to ensure suitable air circulation.
• Do not mount the Machine Controller in any direction other than the specified direction.
• Do not mount the Machine Controller on top of any device that generates a significant amount of heat.
• Do not subject the Machine Controller to direct sunlight.
Control Panels with Forced-air Cooling
Install a fan near the center of and at the top or bottom of the Machine Controller for either of the following methods.
• Forced draft method (A fan or a similar device is used to circulate the air in the interior and the exterior of the panel.).
• Forced circulation method (A fan or a similar device is mounted to the airtight panel to circulate the air inside.).
Note: 1. Use the following guideline when selecting the fan:
• 80 x 80 mm min., Maximum air flow: 0.9 m3/min, Maximum static pressure: 26.5 Pa or higher.
Figure 8
2. Adjust the fan installation location and the direction of air flow as shown in Figure 8.
14 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
Figure 8 Fan installation location and air flow direction
7Base Unit Specifications
The specifications of the Base Units are listed in Table 2.
Table 2 Base Unit Specifications
7 Base Unit Specifications
Item
ModelJEPMC-BU3304-EJEPMC-BU3303-EJEPMC-BU3302-EJEPMC-BU3301-E
AbbreviationMBU-304MBU-303MBU-302MBU-301
Number of Slots138
Mountable ModulesMP2000-series Optional Modules
Input Voltage24 VDC110/220 VAC
Allowable Input
Voltage Range
Input Current
Inrush Current40 A, 10 ms max.30 A, 10 ms max.40 A, 10 ms max.
Allowable Power Loss
Power Supply Section
RLY OUT
IndicatorsPOWER
Connectors
Time
Rated Voltage5.15 V5.0 V
Rated Current2.5 A4.5 A4.0 A8.0 A
Output Current Range 0 to 2.5 A0 to 4.5 A0.0 to 4.0 A0.0 to 8.0 A
Rated Voltage
Accuracy
Battery
1 slot3 slots8 slots DC8 slots AC
19.2 to 28.8 VDC
1.0 A max. (at rated
input/output)
1 ms20 ms
5.15 V ±2% max. (5.05 to 5.25 V)
You can mount a memory backup Battery for retained variables, absolute encoder offsets, and
alarm history.
A normally open relay output that is linked to the CPU Module status
Normal operation: Circuit closed .
Error: Circuit open.
Contact Ratings:
• 125 Vac, 0.4 A resistive load, 0.20 A inductive load
• 24 Vdc, 0.5 A resistive load, 0.25 A inductive load
POWER: Power supply connector
RLY OUT: Relay contact connector
1.5 A max. (at rated input/output)
Specification
85 to 132 VAC/ 198 to
276 VAC
3.0 A max. (at rated
input/output)
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 15
8 Switches
8Switches
The CPU Module has the following two types of switches.
• DIP switches: Mode switches
• STOP/SAVE switch
DIP Switches: Mode Switches
The SW1 and SW2 switches are checked at start-up, and their behavior is described in the following tables:
Table 3 SW1 Switches
SWDescription
STOPWhen ON, prevents PLC from running.
E-INITWhen ON, overrides Ethernet configuration according to Table 5.
INITWhen ON, the controller uses the fixed, default configuration
CNFGWhen ON, the controller creates Axes and I/O for all connected devices. (Auto-configuration)
Table 4 SW2 Switches
SWDescription
LOADWhen ON, load either the user project or firmware from the USB thumb dri ve. See Table 6 for details.
TESTWhen ON, the IP ad dress is scrolled across the seven segment display.
MNT
-- / DHCPDHCP Selection when E-INIT is ON.
When ON, controller starts up in supervisor mode. In this mode MECHA TROLINK III, PLC, Modbus/TCP and Ethernet/IP
do not start. The controller firmware can be updated, and clearing DOS FS alarms will repair the DOS FS.
E-INIT and - switches can override the Ethernet configuration according to Table 5.
Table 5 Operation of E-INIT, E-PM0 and E-PM1 for Configuring Ethernet
E-INIT-- / DHCP
Static ConfigurationOFFN/A
192.168.1.1ONOFF
DHCPONON
On start-up, the controller will aut omat ic ally l oad f ir mware or use r pr oje cts bas ed on t he LOAD and MNT swi tc hes . The
USB thumb drive is available in any other circumstances.
Table 6 Operation of LOAD and MNT for USB Thumb Drive
E-INIT-- / DHCP
Load user project from USB thumb driveONOFF
Install firmware and user project from USB
thumb drive
16YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
ONON
9 Display and Indicators
9Display and Indicators
The CPU Module has the following display and four types of indicators.
•Display
• Status indicators
•USB status indicator
• MECHATROLINK-III status indicators
• Ethernet status indicators
Display
The following situations use the seven segment display:
• Manufacturing: During programming the seven segment display outputs “FLASH...”. When finished, the seven
segment display outputs “donE”.
• Startup: If the controller cannot boot because of a bad firmware image check sum, the seven segment display outputs
“bOOt ERROR”
• IP Address: If the TEST switch is ON, then the seven segment display outputs the IP address.
• Firmware update: During programming the seven segment display outputs “FLASH...”. When finished, the seven
segment display outputs “donE”.
Status Indicators
These indicators show the status of the CPU Module.
Table 7 Status LED
LEDDescription
RDYON when the controller has detected valid firmware and has started.
RUNON when PLC is running.
ALMON when an alarm is active.
ERR
BATON when the battery needs replacing.
M-ALMON when JL100 (Mechatrolink Master) chip initialization fails.
ON at initial power up while firmware is loading. Turns off if firmware is valid.
ON when a critical error occurs requiring a power cycle to recover.
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 17
9 Display and Indicators
USB Status Indicator
This indicator shows the status of the USB memory.
Indicator NameIndicator StatusStatusDescription
Not litNo USB memory device
USB
ACTIVE
MECHATROLINK-III Status Indicators
LitUSB memory device insertedA USB memory device is inserted.
FlashingAccessing USB memoryThe USB memory is being accessed.
No USB memory device has been inserted ye t, or the
USB memory device is ready to be removed.
These indicators show the status of the MECHATROLINK-III communications.
Indicator NameColorStatus When Lit
Ethernet Status Indicators
CNGreen
LK1GreenMECHATROLINK-III communications are active on PORT1.
LK2GreenMECHATROLINK-III communications are active on PORT2.
MECHATROLINK-III communications is established with the CPU Module as a slave (i.e.,
the Connect command is ON).
These indicators show the status of Ethernet communications.
Indicator NameColorStatus When Not Lit, Lit, or Flashing
LINK/ACTYellow
100MGreen
Lit: Ethernet link established.
Flashing: Ethernet communications activity.
Not lit: 10 M connection
Lit: 100 M connection. We do not support GB connections.
18 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
10 Self-Configuration
10Self-Configuration
DIP Switch
Self-Configuration after Adding Devices such as Servopacks
The controller ca n aut omatica lly config ure a ll t he M echatr olink devi ces. Fi rst, co nnect and p ower up all the Mecha troli nk
nodes (making sure they all have unique station numbers). Then, set the CNFG switch to the ON position and power up
the controller. Wait for the RDY LED to come on and the controller will now have the new auto configuration.
Note: Controllers with an existing saved configuration cannot be auto configured until the currect conf iguration is deleted.
MotionWorks IEC
The MotionWorks IEC (Express or Pro) configuration can detect the configuration and provide the user with
configuration choice s. If a S tar tUp Config urati on was alre ady save d on the controll er, the self-configure funct ion will not
allow new devices to be discovered. In this case, add them offline manually first.
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 19
11 MECHATROLINK-III Specifications
11MECHATROLINK-III Specifications
The specifications of the MECHATROLINK-III Network Master that is built into th e CPU Unit are given in the following
table.
ItemSpecificationRemarks
Communications ASICJL-100Number of Communications Lines1-
MECHATROLINK
communications
settings
Number of Communicat ions Ports
(Connectors)
Communications Method M-IIIBaud Rate100 Mbps-
Communications Cycle
Number of Connected
Master
Stations
Message RelayingNot Supported.C2 MessagesNot Supported.RetriesSupported.0 to 4 retries
Asynchronous Setting of
High-speed Scan Cycle
and Communications
Cycle
2-
250 μs/0.5 ms/
1 ms/1.5 ms/2 ms/2.5 ms/3 ms/
3.5 ms/4 ms
62 stations -
Not supported.An alarm will occur if setting is attempted.
-
CPU Unit Specifications
ItemSpecification
CalendarBattery backup accurate to 1 minute of error per month.
Ethernet
M-III1981386-1 ×2 (TycoAMP)
USB
ProtectionHardware watchdog timer (PLD): 0 to 510 ms (register setting)
Relay Output
Backup CircuitBattery: BR-1/2AA (Panasonic), 3.0 V
ConnectorDUSB-ARA42-T11A-FA (DDK), type A connector
FunctionUSB 2.0 ho st, 3 speeds (HS/FS/LS), 1 port
Contacts normally open for RUN status (RDY indicator lit), and OFF for WDT error status. The relay
is built into the Power Supply Unit.
20YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
12 MECHATROLINK-III Network Topologies
12MECHATROLINK-III Network Topologies
You can connect the MP3300iec Series Controller and drives or I/O with cascaded connections, star connections, or
mixed cascaded/star network topologies. The following figures show examples of these types of network topologies.
Cascaded Connection
Cascaded connections allow you to connect one or more series of slave stations from the CPU Unit MECHATROLINKIII ports. Regardless of whether a single MECHATROLINK-III port is used, as shown in Figure 9, or two CPU Unit
MECHATROLINK-III ports are used, as shown in Figure 10, these are called cascaded connections.
Figure 9
CPU Unit
Figure 10
Up to 32 stations, including Servos and I/O
Figure 9 Cascaded Connections Using Only One Port
CPU Unit
No terminating
resistor is
required.
Up to 32 Servo stations
Up to 62 stations, including I/O
No terminating resistor is required.
No terminating
resistor is required.
Figure 10 Cascaded Connections Using Two Ports
Note: 1. Do not connect more than 32 stations up to the final slave station to any one CPU Unit port.
2. The maximum number of stations that you can connect with cascaded co nnections depends on the c ommunications cycle.
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 21
12 MECHATROLINK-III Network Topologies
Star Connections
Star connections al low you to connect slave stations through Hub Modul es. Each port on a Hub Module connects to only
one slave station. You can also connect one additional Hub Module to the first Hub Module.
CPU Unit
Hub Module
Note: 1. Terminating resistors are not required.
2. The maximum number of stations that you can connect with star connections depends on the communications cycle.
Hub Module
22 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
Mixed Cascaded/Star Connections
You can combine both cascaded and star network topologies.
CPU Unit
Hub Module
12 MECHATROLINK-III Network Topologies
No terminating
resistor is required.
No terminating
resistor is required.
Note: 1. Do not connect more than 32 stations to a single CPU Unit port, including the Hub Modules.
2. The maximum number of stations that you can connect with a mixed cascaded/star connections depends on the communications cycle.
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 23
13 MECHATROLINK-III Synchronization between Modules
NOTICE
NOTICE
13MECHATROLINK-III Synchronization between Modules
Timing at Which Modules Are Synchronized
Modules are automatically synchronized when the power supply is cycled.
If you perform any of the following operations after turning ON the power supply, save the settings to flash memory and
then cycle the power supply again.
• When operation changes from asynchronized to synchronized as a result of changing the communications cycle
• When operation changes from synchronized to asynchronized or from asynchronized to synchronized as a result of
changing the high-speed scan setting
• When the minimum response time in the MPiec controller is changed.
Changing Synchronization Cycles
When the scan cycle is changed, MECHATROLINK communications with all slave stati ons conne ct ed to the SVC32 ar e
reset. Operation automatically changes to synchronized when communications are restored.
MECHATROLINK communications continue for all other Modules.
1. When you change the MECHATROLINK cycle, do so either with the CPU Function Module stopped or when motion commands are not being
executed. Otherwise, application operations may be affected.
2. When changing the MECHATROLINK setting, the following operation will occur because MECHATROLINK communications are reset.
• Position inform ation and zero point return completion information for Servo axes will be lost.
Changing the MECHATROLINK Communications Cycle
Operation is automatically synchronized as long as the high-speed scan setting is an integral multiple of the
communic ations cycle.
It is not necessary to cycle the power supply.
If asynchronous operation is set as a result of changing the communications cycle, an alarm will occur for the Servo
axis and an I/O error will occur for the I/O station. If this happens, change the setting back to synchronized, save the
settings to flash memory, and then cycle the power supply.
24YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
14 Devices Connectable via MECHATROLINK-III
14Devices Connectable via MECHATROLINK-III
Servopacks
The following table shows Servopacks that are compatible with MECHATROLINK-III and can be connected to the
controller.
ModelDetails
SGDV-
SGDV-
SGDV-
SGDV-
SGDV-
SGD7S-
SGD7W-
I/O Modules
ƑƑƑƑ
ƑƑƑ
ƑƑƑ
ƑƑƑ
ƑƑƑƑ
ƑƑƑ
ƑƑƑ
21
E21
H21A
J21A
25
A20A
A20A
Σ-V Series AC Servo amplifiers for rotary motors
Σ-V Series Mini AC Servo amplifiers for rotary motors
Σ-V Series 200 VAC Large Capacity AC Servo amplifiers for rotary motors
Σ-V Series 400 VAC Large Capacity AC Servo amplifiers for rotary motors
Σ-V Series AC Servo amplifiers for linear motors
Σ-7 Series 200 VAC Large Capacity AC Servo amplifiers
Σ-7 Series 200 VAC Large Capacity dual motor AC Servo amplifiers
The following table shows the module that is compatible with MECHATROLINK-III and can be connected to the
controller.
ModelDetails
JEPMC-MTD2310-E
64-point I/O Module
24VDC, 64 inputs, 64 outputs
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 25
15 Connecting the RLY OUT Connector
RLY OUT
24 VDC
0 VDC
POWER
Ground to 100 Ω max.
24-VDC
power supply
Power
supply
Error: OFF
Normal operation: ON
RLY OUT output
15Connecting the RLY OUT Connector
The RLY OUT connector connects the status output terminal. It is a normally open contact relay output. The RLY OUT
connector is linked to the operation of the RDY indicator: The contacts close when the indicator lights, and they open
when the indicator goes out.
Note: When the RDY indicator is lit, the Controller is operating normally. It does not necessarily mean that the user programs are being
executed.
RLY OUT Connector Specifications
The operation of the RLY OUT connector is linked to the operation of the RDY indicator on the CPU Unit.
RDY indicator lit: Circuit closed
RDY indicator not lit: Circuit open
Contact Ratings
Input
Voltage
24 VDC
125 VAC
RLY OUT Connector Connection Cable
Current Capacity
0.5 A (resistive load)
0.25 A (inductive load)
0.4 A (resistive load)
0.2 A (inductive load)
To connect the RLY OUT connector, use a cable with a wire size of AWG 28 to AWG 14 (0.08 to 2.0 mm2) and a
maximum outer diameter of 3.4 mm.
The procedure to make the RLY OUT connector cable is the same as for the 24-VDC power supply cable.
Note: You can use the RLY connector on the Power Supply Unit only on the Rack to which the CPU Unit is mounted. On Racks without
the CPU Unit, the power supply circuit is always open.
RLY OUT Connector Connection Example
Refer to the following figure for an example of connecting the RLY OUT connector.
26YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
16Ethernet Connector Details
'VJGTPGV
.+0-
/
Connects to other devices by Ethernet (100Base-TX/10Base-T).
Ethernet Connector Specification and Pin Array/Indicator Light
The following table provides the Ethernet connector specifications.
The following table provides Ethernet connector pin array / indicator light details.
Pin NumberSignal NameDescription
1TXD+Transmitted data + side
2TXD-Transmitted data – side
3RXD+Received data + side
4––
5––
6RXD-Received data – side
7––
8––
Display NameDisplay ColorDescription
LINKYellow
100MGreen
Ethernet Cable
Lit: Connect
Unlit: Unconnected
Lit: Connected at 100Mbps, or automatically negotiating
Unlit: Connected at 10Mbps
For the Ethernet cable, use a twisted pair cable with RJ-45 connector. Yaskawa strongly recommends the use of shielded
ethernet cables.
Ethernet
Type
10Base-TCategory 3 or more
100Base-TCategory 5 or more
Ethernet Connection Examples
CategoryRemarks
• When connecting to remote equipment through a hub: Straight cable
• When connecting to remote equipment without using a hub: Cross cable
The following are examples of Ethernet network connections via 10Base-Tx cable:
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 27
16 Ethernet Connector Details
Hub
or Switch
MP3300iec
Hub
or Switch
10Base-T
(Straight cable)
Station
StationStation
Up to 100mUp to 100m
Up to 100m
Up to 100m
Up to 100m
Station
Up to 100m
When connecting to a HUB without using the
auto-negotiation function, set the HUB side to
half-duplex mode.
10 Base-T (crossover cable, up to 100m)
MP3300iec
Connection Example 1 (When using a hub or switch)
Specification
ItemWhen Connecting to a Repeater HUBWhen Connecting to a Switching HUB
Cable Length between Node-HUB100m or less100 m or less
Cable Length between HUBs100m or less100 m or less
Number of HUBs between NodesUp to fourUnlimited
Connection Example 2
The following are examples of Ethernet network connections via 100Base-Tx cable:
28 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
16 Ethernet Connector Details
CAUTION
Hub
or Switch
MotionWorks IEC
MP3300iec
YASKAWA SERVOPACK
200V
SGDS-01A12A
SW1
CHARGE
C
N
3
A/B
C
N
1
C
N
2
C
N
4
L1
L2
L2C
L1C
B1/
B2
U
V
W
C
N
6
SERVOPACK
Core
Core
Core
100Base-T
(straight cable)
Servomotor
Other station
High frequency wave noise from other devices in the installation environment may cause errors in
communications using Ethe rnet or MECHATROLINK-III connections. Wh en designi ng a syst em, use pr otectiv e
measures to avoid the influence of high frequency wave noise as follows:
1. Wiring
2. Communication system (Ethernet)
Wire Ethernet or MECHATROLINK-III cables so that they are well-separated from other cable systems such as the main circuit or
power lines.
• Communicate data to a remote device through TCP/IP communication.
• If necessary, increase the number of communication retries.
Columns “Label on M arkin g T u be”, “Si gnal Name”, and “Fu nction ” dis play t he val ues f or conn ector s CN1 and CN2 in
the format “CN1 /CN2”, respec tively.
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 33
17 Option Module - AI-01 (Analog Input) Module
DC/DC
Converter
+5V
0V
+15V
-15V
0V
D/A
Converter
Internal circuit
+5V
Photocoupler
Voltage input
Current input
Mode
10
12
25
23
+
GND
CH8
11
Multiplexer
Ground
Voltage input
Current input
Mode
4
6
19
17
+
GND
CH2
5
Voltage input
Current input
Mode
Ground
1
3
16
14
2
+
GND
CH1
Ground
Shell
RR
R
RR
R
RR
R
10k
10k
256.5
10k
10k
256.5
10k
10k
256.5
Circuit Configuration
34 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
DANGER
DC/DC
Converter
+5V
0V
+15V
-15V
0V
D/A
Converter
Internal circuit
+5V
Photocoupler
Voltage input
Current input
Mode
10
12
25
23
-
+
GND
CH8
11
Multiplexer
Ground
Voltage input
Current input
Mode
4
6
19
17
-
+
GND
CH2
5
Voltage input
Current input
Mode
Ground
1
3
16
14
2
-
+
GND
CH1
Ground
Shell
RR
R
RR
R
RR
R
10k
10k
256.5
10k
10k
256.5
10k
10k
256.5
CN1 Connector Connection Example
17 Option Module - AI-01 (Analog Input) Module
• Use the standar d cable (JEPMC- W6080- ) f or AI -01 Mo dules t o connec t to ex te rnal de vices . Use a rel ay termina l
block to connect the AI-01 module to external devices because the wiring distance varies between the AI-01 module
and each external device.
• Ground the cable shield between an external device and the relay terminal block on the external device side.
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 35
18 Option Module - AO-01 (Analog Output) Module
A
O
-01
LED indicator
Analog output
connector CN1
RUN
CN1
125 mm
95 mm
19.3 mm
18Option Module - AO-01 (Analog Output) Module
Appearance
Module Functions
The AO-01 module has four channels for anal og output. Two types of analog outpu t ranges a re availabl e; -10 to +10V and
0 to +10V.
Module Specifications
The following table shows the AO-01 Module hardware specifications.
ItemSpecifications
NameAO-01
ModelJAPMC-AN2310-E
Number of Channels4
Isolation
Analog Output Rang e±10V0 to +10V
Resolution16-bit (-31276 to +31276)15-bit (0 to +31276)
Absolute Accuracy100 mV Max0.3 mA Max
Analog Output
Accuracy
Input Conver sion Time1.2 msec Max
ConnectorsCN1: Out put connector
LED IndicatorRUN (green)
Current Consum ption500 mA Max
Dimensions125 × 95 (H×D)
Mass90 g
Indicators
25°C±0.1% (±10 mV)
0 to 55°C±0.3% (±30 mV)
Between channels: Not isolated.
Between output connector and system power supply: Photo c oupler isolation
Indicator
RUNGreenNormal operationOperation stopped (no access from CPU)
36YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
Indicator
Color
Status when LitStatus when not Lit
Connector Specifications
18 Option Module - AO-01 (Analog Output) Module
Name
Analog Output
Connector
Connector
Name
CN12010220-52A3PL
# of Pins
Module SideCable SideManufacturer
Applicable Cable: JEPMC-W6090-oo
Standard Cable Model and External Appearance
ModelLengthExternal Appearance (JEPMC-W6090-oo)
JEPMC-W6090-050.5 m
JEPMC-W6090-101.0 m
JEPMC-W6090-303.0 m
CN1 Pin Layout Diagram
Connector Model
• Connector 10 126-3000VE
• Shell 10326-52 A 0-0 08
(Screw locking), or
10326-52F0-008
(One-touch locking)
Sumitomo 3M
Corporation
Standard Cable Wiring Table
The following shows the pin arrangement for standard cable JEPMC-W6090.
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 37
OrangeBlackGround 0
GrayBlackA_Pulse+
YellowRed(-)
YellowBlackC-Phase latch input common (5V)
Marking
Color
Function
18 Option Module - AO-01 (Analog Output) Module
DANGER
AO-01 Module Connector Connection Example
CN1 Connector Connection Example
• Use the AO-01 standard cable (JEPMC-W6090-) for the connection to the external device. Use the junction
terminal block because the distance between the external devices and the module are different as seen on the above
diagram.
• Ground the cable shield between the external devices and the junction terminal block by the external device side.
38 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
19 Option Module - DO-01 (Digital Output) Module
DANGER
0
24
DO_24V
Output
register
DO_OUT
DO_COM
+24V
R
Photocoupler
R
Transistor
19Option Module - DO-01 (Digital Output) Module
Appearance/Indicators
Module Functions
The DO–01 module is equipped with 64 digital outputs.
Output Circuit Specifications
The following table shows the DO-01 Module output circuit specifications.
ItemSpecifications
Outputs64 points
Output FormatTransistor/open collector, sink mode output
Isolation MethodPhotocoupler
Output Voltage+ 24VDC (+19.2 to +28.8V)
Output Current100 mA Max
Leakage Current When OFF0.1 mA Max
ON Time/OFF Time
Number of Commons8 points
Protection CircuitFuse connected to each common line
Fuse Rating1A
Error DetectionFuse blowout detection
ON: 0.5 ms Max
OFF: 1 ms Max
DO-01 Digital Output Circuit (Sink Mode Output) Connection Example
A fuse is inserted into the output commo n line of th e DO-01 Module for circuit protection. However , the fuse may not
be blown out in the cases such as layer shorts in outputs. To ensure the circuit protection, provide a protective element
such as fuse in each output as shown in the above diagram.
DO-01 Module Connections
Connects the DO-01 Module to external output signals.
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 39
Columns “Signal Name” and “Function” display the values for connectors CN1 and CN2 in the format “CN1/CN2”
respectively.
42 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
20 Option Module - LIO-01/02 Module
LIO-01
LED indicators
Switch
I/O connector
20Option Module - LIO-01/02 Module
Appearance
External Appearance
The following figure shows the external appearance of the LIO-01/02 Modules
The LIO-01 Module provides digital I/O and encoder input functions. There are 16 digital inputs (DI) and 16 digital
outputs (DO) for the digital I/O function. There is also one encoder input.
The following diagra m giv es an outli ne of the LI O-01 Mo dule f uncti ons. The only f unctiona l d iff erenc e betwe en the LIO01 and the LIO-02 is the active state of the output circuits
Refer to LIO-01 Digital Output Circuit (Sink Mode Output) Connection Example on page 46 and Refer to LIO-02
Digital Output Circuit (Source Mode Output) Connection Example on page 46.
The LIO-02 Module status display LED indicators (LD1 to LD8) change based on the SW1 rotary switch settings. The
following table shows the ON/OFF indicator display for digital input and digital output.
Outline of Functions
LED Indicators and Switch Settings
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 43
20 Option Module - LIO-01/02 Module
LD3
LD2
LD1
LD4
LD7
LD6
LD5
LD8
SW1
0
5
1
2
3
4
6
7
8
9
Indicators
IndicatorColorSW1Status when Lit
Board Status Indicators
LD1Normal operation: Lit, Error: Not lit
LD2DI-00 to DI-07 status. Lit when any digital input is turned ON.
LD3DO-00 to DO-07 status. Lit when any digital output is turned ON.
0
LD1 to LD8Green
1Digital input indicators: When DI00 to DI07 turn ON, corresponding indicators (LD1 to LD8) are lit.
2Digital input indicators: When DI08 to DI15 turn ON, corresponding indicators (LD1 to LD8) are lit.
3Digital output indicators: When DO00 to DO07 turn ON, corresponding indicators (LD1 to LD8) are lit.
4Digital output indicators: When DO08 to DO15 turn ON, corresponding indicators (LD1 to LD8) are lit.
5
LD4Pulse A/B input. Lit when phase A/B is turned ON.
LD5Normal operation: Lit, Error: Not lit
LD6DI-08 to DI-15 status. Lit when any digital input is turned ON.
LD7DO-08 to DO-15 status. Lit when any digital output is turned ON.
LD8Pulse Z input. Lit when phase Z is turned ON.
PI input Indicators
LD1
LD2
LD3
LD4
Pulse A input
Pulse B input
Pulse Z input
-
LD5
LD6
LD7
LD8
High speed output set
Phase-Z latch
Digital input latch
-
Specifications
Module Specifications
ItemSpecifications
NameLIO-01/02
ModelJAPMC-IO2300/JAPMC-IO2301
16 inputs
Digital Inputs
24VDC, 4.1 mA, combined sink mode/source mode inputs
(DI_01 also used for position registation latch.)
Position registration latch on phase-C or DI _0 1.
SwitchesRotary switch (SW1)
Dimensions (mm)125 x 95 (H x D)
Mass80 g
44 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
20 Option Module - LIO-01/02 Module
5.6k Ω/0.5 W
Vcc
DI_COM
+24 V
DI_IN
Input register
0
24
R
R
R
R
5.6 k
Ω/ 0.5 W
Vcc
680 Ω
DI_COM
+24 V
DI_IN
22 kΩ
1 k
Ω
2200PF
0.01 μF
Input register
0
24
R
R
R
R
Input Circuit Specifications
ItemSpecifications
Inputs16 points
Input FormatSink mode/Source mode input
Isolation MethodPhotocoupler
Input Voltage±24VDC, ±20mv
Input Current4.1 mA (typ.)
ON Voltage/Current15V min./2.0 mA min.
OFF Voltage/Current5V Max/1.0 mA Max
ON Time/OFF Time
Number of Commons8 points (DI_COM0: DI_00 to DI_07, DI_COM1: DI_08 t o DI _15)
Other Functions
Digital Input Circuit (Sink Mode Input) Connection Example
ON: 0.5 ms Max
OFF: 0.5 ms Max
DI_01 is shared with position registration latch. If DI_01 is turned ON while position registration latch
inputs are enabled, the encoder position will be latched.
Digital Input Circuit (Source Mode Input) Connection Example
Output Circuit
The following table shows the LIO-01/02 Module output circuit specifications.
ItemSpecifications
Outputs16 points
Output Format
Isolation MethodPhotocoupler
Output Voltage+24VDC, ±20mv
Output Current100 mA Ma x
Leakage Current When OFF0.1 mA Max
ON Time/OFF Time
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 45
LIO-01Transistor, open collector sink mode outputs
LIO-02Transistor, open collector source m ode outputs
ON: 1 ms Max
OFF: 1 ms Max
20 Option Module - LIO-01/02 Module
R
R
R
0
24
DO_24V
Output
register
DO_OUT
DO_COM
+24 V
0
24
+24V
DO_24V
Output
register
DO_OUT
DO_COM
R
R
R
ItemSpecifications
Number of Commons16 points
Protection Circuit
Error DetectionBlown fuse detection
Other FunctionsDO_01 is shared with encoder position detection
LIO-01 Digital Output Circuit (Sink Mode Output) Connection Example
The fuses are not for circuit protection. Th ey are for fire protection at output shorts. Attach a fuse
externally to each output if circuit protection is required.
LIO-02 Digital Output Circuit (Source Mode Output) Connection Example
Pulse Input Circuit
The following table shows the LIO-01/02 Module encoder circuit specifications.
ItemSpecifications
Number of Encoders1 (Phase-A/B/Z input)
Encoder Circuit
Input ModePhase-A/B, signed, incremental /d ecremental
Latch Input
Phase-AB: 5V differential input, not isolated, Max frequency: 4 MHz
Phase-Z: 5V/12V photocoupler input, Max frequency: 500 kHz
Position registration latch on phase-Z or DI_01.
Response time: 5 ms Max for phase-Z input; 60 ms Max for DI_01 input.
46 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
20 Option Module - LIO-01/02 Module
+5 V
0 V
Phase-A
A1
220Ω
Pulse Generator
Phase-B
PA
PAL
PB
PBL
GND
B1
A2
B2
B3
B4
A4
A3
+5 V
Latch input or
phase-Z pulse
PC
PCL5
PCL12
R
R
R
220Ω
R
B1A1
B24A24
Encoder Circuit Connection Example
LIO–01/02 Standard Cable Wiring Table
Connector Pin Arrangement
The following table shows the connector pin arrangement for LIO-01/02 Modules viewed from the wiring side.
• Connect a fuse suitable for the load specif ications in the output signal circuit in series with the load. If an external
fuse is not connected, load shorts or overloads could result in fire, destruction of the load device, or damage to the
output element.
• The pins A5 and B5, and the pins A6 and B6 are internally connected. Connect them externally as well.
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 49
20 Option Module - LIO-01/02 Module
+5V
0V
Phase-A
Pulse generator
+5V
Pulse input
Latch input
or phase-Z
pulse
Latch input or
phase-Z pulse
Phase-B
5V
A2
B2
A4
PB
PBL
GND
PC
PCL5
PCL12
A3
A24
B24
B3
B4
PA
PAL
A1
B1
External input
signals
DI_COM0
DI_01
DI_02
DI_03
DI_04
DI_05
DI_06
DI_07
DI_00
A23
B22
A22
B21
A21
B20
A20
B19
A19
24 VDC
Digital input
R
R
External input
signals
DI_COM1
DI_09
DI_10
DI_11
DI_12
DI_13
DI_14
DI_15
DI_08
B23
B18
A18
B17
A17
B16
A16
B15
A15
24 VDC
Digital input
R
R
R
R
R
R
R
L
L
L
L
L
L
L
Digital output
External output
signals
L
L
L
L
L
L
L
L
L
Fuse open
detection circuit
Fuse
24 VDC
Fuse
DO_24V
DO_24V
DO_00
DO_01
DO_02
DO_03
DO_04
DO_05
DO_06
DO_07
DO_08
DO_09
DO_10
DO_11
DO_12
DO_13
DO_14
DO_15
DO_COM
DO_COM
B6
A6
B14
A14
B13
A13
B12
A12
B11
A11
B10
A10
B9
A9
B8
A8
B7
A7
A5
B5
R
L
Load
External Fuse
LIO-02 Module Connections
50 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
21 Option Module - LIO-04/05 Modules
DANGER
LED indicators
I/O connector
(CN1)
LIO-04
RUN
FU
CN2
CN1
I/O connector
(CN2)
FURUN
21Option Module - LIO-04/05 Modules
External Appearance
The following figure shows the external appearance of the LIO-04/05 Modules.
Outline of Functions
The LIO-04/05 Modules are Optional Boards for the MP2300Siec which provide a digital I/O function. There are 32
digital inputs (DI) and 32 digital outputs (DO) (sink mode outputs) for the digital I/O function.
Indicators
The following table shows the status of LIO-04/05 Module LED indicators.
Indicator Name Indicator ColorStatus
RUNGreen
FURed
Lit: Module normal
Not lit: Module error
Lit: One of the output protection fuses is blown.
Not lit: All of the output protection fuses are normal.
The burnout detection circuit will not function when there is no external 24V power supply.
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 51
21 Option Module - LIO-04/05 Modules
LD3
LD2
LD1
LD4
LD7
LD6
LD5
LD8
SW1
0
5
1
2
3
4
6
7
8
9
Indicators
Switch Settings
The LIO-04/05 Module status display the LED indicators (LD1 to LD8) change based on the SW1 rotary switch setting.
The following table shows the ON/OFF indicator display for digital input and digital output.
IndicatorColorSW1Status when Lit
Board Status Indicators
LD1Normal operation: Lit, Error: Not lit
LD2DI_00 to DI_07 status. Lit when any digital input is turned ON.
LD3DO_00 to DO_07 status. Lit when any digital output is turned ON.
LD4Pulse A/B input. Lit when phase A/B is turned ON.
0
LD5Normal operation: Lit, Error: Not lit
LD6DI_08 to DI_15 status. Lit when any digital input is turned ON.
LD7DO_08 to DO_15 status. Lit when any digital output is turned ON.
LD1 to LD8Green
LD8Pulse Z input. Lit when phase Z is turned ON.
1Digital input indicators: When DI_00 to DI_07 turn ON, corresponding indicators LD1 to LD8 are lit.
2Digital input indicators: When DI_08 to DI_15 turn ON, corresponding indicators LD1 to LD8 are lit.
3Digital output indicators: When DO_00 to D O _07 tur n ON , corre spo ndin g in d icators LD 1 to LD8 a re lit.
4Digital output indicators: When DO_08 to D O _15 tur n ON , corre spo ndin g in d icators LD 1 to LD8 a re lit.
PI Input Indicators
LD1
5
LD2
LD3
LD4
Pulse A input
Pulse B input
Pulse Z input
-
LD5
LD6
LD7
LD8
Coincidence detection
Phase-Z latch
Digital input latch
-
Module Specifications
The following table shows the hardware specifications of the LIO-04/05 Module.
ItemSpecifications
NameLIO-04/LIO-05
ModelJAPMC-IO2303/JAPMC-IO2304
32 inputs
24VDC, 4.1 mA, combined sink mode/source mode inputs
(DI_00, 01, 16, and 17 also used for interrupts.)
Digital Inputs
Digital Outputs
Indicators
Dimensions (mm)125 x 95 (H x D)
Mass80 g
52 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
Simultaneously ON Inputs
16 points (8 inputs/common): At ambient temperature of 55°C and 24VDC
10 points (5 inputs/common): At ambient temperature of 55°C and 28.8VDC
Refer to the following characteristics graph for details.
The following table shows the LIO-04/05 Modules input circuit specifications.
ItemSpecifications
Inputs32 points
Input FormatSink mode, source mode input
Isolation MethodPhotocoupler (PS2805-4)
Input V oltage±24VDC (+19.2 to +28.8V)
Input Current4.1 mA (typ.)
ON Voltage/Current15VDC min./2.0 mA min.
OFF Voltage/Current5VDC min./1.0 mA min.
ON Time/OFF Time
Number of Commons8 points
Digital Input Circuit (Sink Mode Input) Connection Example
ON: 0.5 ms Max
OFF: 0.5 ms Max
Digital Input Circuit (Source Mode Input) Connection Example
Output Circuit
The following table shows the LIO-04/05 Module’s output circuit specifications.
ItemSpecifications
Outputs32 points
Output Format
Isolation MethodPhotocoupler
Output Voltage+24VDC (+19.2 to +28.8VDC)
Output Current100 mA Max
Leakage Current When OFF0.1 mA Max
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 53
21 Option Module - LIO-04/05 Modules
0
24
+24V
Output
register
DO_OUT
0V
+24V
R
Photocoupler
R
Transistor
ItemSpecifications
ON Time/OFF Tim e
Number of Commons1 per 8 outputs
Protection Circuit
Fuse Rating1A
Error DetectionFuse blowout detection
LIO-04 Digital Output Circuit (Sink Mode Output) Connection Example
ON: 0.5 ms Max
OFF: 1 ms Max
The fuses are not for circuit protection. They are for fire protection at output shor ts. Attach a fuse
externally to each output if circuit prote ctio n is requ ired.
LIO-05 Digital Output Circuit (Source Mode Output) Connection Example
+24V
DO_OUT
0V
Output
register
R
R
R
Photocoupler
Transistor
+24V
0
24
54 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
21 Option Module - LIO-04/05 Modules
1
3
5
7
9
11
13
15
17
19
21
23
25
DICOM_3
DI_18
DI_22
DI_24
DI_28
N.C.
DO_18
+24V_3
DO_22
DO_24
N.C.
DO_28
N.C.
26
28
30
32
34
36
38
40
42
44
46
48
50
N.C.
DI_19
DI_23
DI_25
DI_29
N.C.
DO_19
N.C.
DO_23
DO_25
OV_4
DO_29
OV_4
27
29
31
33
35
37
39
41
43
45
47
49
DI_17
DI_21
N.C.
DI_27
DI_31
DO_17
OV_3
DO_21
N.C.
DO_27
N.C.
DO_31
50
49
25
24
26
27
1
2
Pin Arrangement Viewed from Wiring Side
2
4
6
8
10
12
14
16
18
20
22
24
DI_16
DI_20
DICOM_4
DI_26
DI_30
DO_16
N.C.
DO_20
N.C.
DO_26
+24V_4
DO_30
LIO-04 Module Connector Pin Arrangement
The LIO-04 Module Connector (CN1 and CN2) pin arrangements are shown below.
CN1 Connector Pin Arrangement
Pin Arrangement Viewed from Wiring Side
1
26
27
2
49
24
50
25
10
12
14
16
18
20
22
24
2
4
6
8
DI_00
DI_04
DICOM_2
DI_10
DI_14
DO_00
N.C.
DO_04
N.C.
DO_10
+24V_2
DO_14
1
3
5
7
9
11
13
15
17
19
21
23
25
DICOM_1
DI_02
DI_06
DI_08
DI_12
N.C.
DO_02
+24V_1
DO_06
DO_08
N.C.
DO_12
N.C.
DI_01
27
29
DI_05
N.C.
31
33
DI_11
35
DI_15
DO_01
37
39
OV_1
DO_05
41
43
N.C.
DO_11
45
47
N.C.
DO_15
49
26
N.C.
DI_03
28
30
DI_07
DI_09
32
34
DI_13
N.C.
36
38
DO_03
N.C.
40
DO_07
42
44
DO_09
OV_2
46
48
DO_13
OV_2
50
CN2 Connector Pin Arrangement
• P: Power supply input, I: Input signal, O: Open collector output
Standard Cable Wiring Table
The wiring table for the standard cable JEPMC-W6060- is shown below.
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 55
PinWire ColorMarkingsSignal NameI/OFunction
1
2
3White—DI_02/18I/IDigital input 2/18
4
5Pink—DI_06/22I/IDigital input 6/22
Orange—DICOM_1/3P/PDigital Input common 1/3
Gray—DI_00/16I/I
Yellow—DI_04/20I/IDigital input 4/20
Digital input 0/16
(shared with interrupt input)
21 Option Module - LIO-04/05 Modules
DANGER
PinWire ColorMarkingsSignal NameI/OFunction
6Orange— —DICOM_2/4P/PDigital Input common 2/4
7
8White— —DI_10/26I/IDigital input 10/26
Orange————————0V_2/4Digital Output 0VDC common 2/4
47
Gray————————+24V_2/4Digital Output 24V supply 2/4
48White————————DO_13/29O/ODigital output 13/29
49
Yellow————————DO_15/31O/ODigital output 15/31
50Pink————————N.C.
Columns “Signal Name”, “I/O”, and “Function” display the values for connectors CN1 and CN2 in the format “CN1/
CN2” respectively.
58 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
DANGER
JEPMC-IO2303
+5V
+-
+-
24 VDC
Input 0
Input 1
Input 6
Input 7
+-
+-
24 VDC
6
7
32
10
35
1
2
27
5
30
CN1 connector
pin No.
Common 1
Common 2
Input 8
Input 9
Input 14
Input 15
Internal circuit
5.6 kW
Photocoupler
R
R
Photocoupler
Fuse blowout
detection circuit
38
12
13
41
17
42
16
L
L
L
L
L
24 VDC
+-
43
37
L
Output 0
39
15
Output 1
Output 2
Output 4
Output 5
Output 6
Output 7
Output 3
R
L
L
Photocoupler
45
19
20
48
24
49
23
L
L
L
L
L
24 VDC
+-
50
44
L
Output 8
46
22
Output 9
Output 10
Output 12
Output 13
Output 14
Output 15
Output 11
R
L
L
Fuse blowout
detection circuit
L
Load
External Fuse
(Installed by customer)
LIO-04 Module Connector Connection Examples
CN1 Connector Connection Example
21 Option Module - LIO-04/05 Modules
• Check the polarity of the external power supply when wiring. An adverse connection may cause a load malfunction.
• The pins 39 and 43 and the pins 46 and 50 are internally connected. Connect them externally as well.
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 59
21 Option Module - LIO-04/05 Modules
DANGER
CN2 Connector Connection Example
24 VDC
+-
Common 3
+-
Input 16
Input 17
Input 22
Input 23
24 VDC
+-
Common 4
+-
Input 24
Input 25
Input 30
Input 31
L
Load
External Fuse
(Installed by customer)
CN2 connector
pin No.
1
5.6 kW
2
R
27
5
30
6
Photocoupler
7
32
10
35
JEPMC-IO2303
Photocoupler
R
Photocoupler
+5V
R
Fuse blowout
detection circuit
R
Fuse blowout
detection circuit
Internal circuit
15
12
37
13
38
16
41
17
42
43
39
22
19
44
20
45
23
48
24
49
50
46
Output 16
Output 17
Output 18
Output 19
Output 20
Output 21
Output 22
Output 23
Output 24
Output 25
Output 26
Output 27
Output 28
Output 29
Output 30
Output 31
24 VDC
+-
L
L
L
L
L
L
L
L
24 VDC
+-
L
L
L
L
L
L
L
L
• Check the polarity of the external power supply when wiring. An adverse connection may cause a load malfunction.
• The pins 39 and 32 and the pins 46 and 50 are internally connected. Connect them externally as well.
60 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
DANGER
+
-
-
+
24 VDC
Common 1
Common 2
1
CN1 connector
pin No.
Input 0
Input 1
2
27
Input 6
Input 7
5
30
6
7
32
Input 8
Input 9
10
35
Input 14
Input 15
JEPMC-IO2304
+
-
-
+
DC24V
+5V
5.6 kΩ
Photocoupler
Internal
circuit
R
R
L
L
L
L
L
L
15
12
Output 0
37
Output 1
13
Output 2
38
24 VDC
+
-
41
17
42
16
39
Output 4
Output 5
Output 6
Output 7
Photocoupler
L
Output 3
R
R
L
L
L
L
L
L
L
22
19
Output 8
44
Output 9
20
Output 10
45
24 VDC
+
-
48
24
49
23
46
Output 12
Output 13
Output 14
Output 15
Photocoupler
L
Output 11
R
R
L
Fuse blowout
detection circuit
Fuse blowout
detection circuit
L
Load
External Fuse
(Installed by customer)
LIO-05 Module Connector Connection Examples
CN1 Connector Connection Example
21 Option Module - LIO-04/05 Modules
Check the polarity of the external power supply when wiring. An adverse connection may cause a load malfunction.
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 61
21 Option Module - LIO-04/05 Modules
DANGER
࣭
࣭
࣭
࣭
࣭
࣭
+
-
-
+
24 VDC
Common 3
Common 4
1
CN2 connector
pin No.
Input 16
Input 17
2
27
Input 22
Input 23
5
30
6
7
32
Input 24
Input 25
10
35
Input 30
Input 31
JEPMC-IO2304
+
-
-
+
24 VDC
+5V
5.6 kW
Photocoupler
Internal
circuit
R
R
L
L
L
L
L
L
15
12
Output 16
37
Output 17
13
Output 18
38
24 VDC
+
-
41
17
42
16
39
Output 20
Output 21
Output 22
Output 23
Photocoupler
L
Output 19
R
R
L
L
L
L
L
L
L
22
19
Output 24
44
Output 25
20
Output 26
45
24 VDC
+
-
48
24
49
23
46
Output 28
Output 29
Output 30
Output 31
Photocoupler
L
Output 27
R
R
L
Fuse blowout
detection circuit
Fuse blowout
detection circuit
L
Load
External Fuse
(Installed by customer)
CN2 Connector Connection Example
Check the polarity of the external power supply when wiring. An adverse connection may cause a load malfunction.
62 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
22Option Module - LIO-06 Module
DANGER
LIO-06
ALMRUN
CN1
Module External Appearance
22 Option Module - LIO-06 Module
Outline of Functions
The LIO-06 Module has digital I/O, analog I/O, and pulse encoder functionality, including a registration latch input. The
LIO-06 Module is fully compatible with the MP940 I/O connector.
When converting equipment from the prior generation MP940 controller, users should bear in mind that the analog
inputs that had previo usly bee n wired to the V-REF and T- REF inputs on the SGDH must now be co nnected directl y to
the LIO-06 option module.
LED Indicators and Switch Settings
Display NameColorStatus when LitStaus wh en OFF
RUNGreenNormalStopped. (No access by CPU)
ALMRedFaultNormal opera tion
The ALM light indicates the following conditions
• Fuse fault
•ASIC error
• A-phase disconnect
• B-phase disconnect
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 63
22 Option Module - LIO-06 Module
DANGER
Option Board Specifications
ItemSpecification
Number of Inputs8/Common
Input MethodSink/Source
IsolationPhotocoupler Isolation
Input VoltageDC24V±20% (DC19.2 to 28.8V)
Digital Input
Digital Output
Analog
Input
Analog
Output
Input Current4.1mA (TYP)
ON Voltage/CurrentAt least 15V/At least 2mA
OFF Voltage/Current5V Max/1mA Max
ON/OFF TimeON= 0.5ms Max/OFF= 0.5ms Max
Interrupt1 (used together with DI_00)
Number of Outputs8/Common
Output MethodTransistor Sink Output
IsolationPhotocoupler Isolation
External Power Sup ply VoltageDC24 V±20% (DC19.2 to 28.8V)
Output Current100mA (Max)
ON Voltage1V Max
Leak Current at OFF0.1mA Max
ON/OFF TimeON= 0.25ms Max/OFF= 1ms Max
Protection Classi ficationUnprotected output
Error DetectionBlown fuse detection
Number of Channels1
IsolationNon-isolated
Analog Input Range-10 to +10V
Maximum Rated In pu t±15V
Input ImpedanceApprox. 20kΩ
Resolution16bit (-31276 to +31276)
Absolute Accuracy100mV Max
Accuracy
Input Filter
Input Conversion Speed50μs
Number of Channels1
IsolationNon-isolated
Analog Output Rang e-10 to +10V
Output Impedance20Ω Max
Resolution16bit (-31276 to +31276)
Accuracy
Maximum Permissible Load Current±5mA
Output Delay Time1.2ms ( Time of change from -10+10V)
25ºC±0.1% (±10mV)
0 to 55ºC±0.3% (±30mV)
25ºC±0.1% (±10mV)
0 to 55ºC±0.3% (±30mV)
Time Constant
Delay Time1ms(Max) (when -10 to 10V)
0.2×10
–3
The time constant shows th e characte ristic s according to the input f ilter equ ivalent t o the time to reach 0.632 × the in put
voltage.
64 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
22 Option Module - LIO-06 Module
ItemSpecification
Number of Channels1
Input Method5V Differential Max Frequency 4M Hz
IsolationNon-isolated
Current Consumption5V, 1A Max
Hot Swapping (Modul es)Not Possible
ConnectorCN1: Digital I/O, Analog I/O, Encoder Input
IndicatorsRUN (Green), ALM (Red)
Input Voltage
Input Current
Latch Input
ON Voltage
OFF Voltage
Response Time1μs Max60μs Max
Minimum ON Pulse Width1μs60μs
COIN Output
Pulse/Direction
UP/DOWN Counter
2 (C-Phase latch or digital input latch)
The digital input latch is used in conjunction with DI-01 on pin 39.
C-Phase LatchDigital Input Latch
24VDC±20%
12VDC±20%
5VDC±20%
24VDC/12VDC/5VDC are switched by
connector wiring
1, digital output
Used together with DO-07 (software switching)
DC24V±20%
4.1mA (TYP)
15V Min
5V Max
Digital Input Circuit
The specifications of the LIO-06 module digital input circuit are shown below.
ItemSpecification
Number of Inputs8
Input MethodSink/Source
IsolationPhotocoupler Isolation
Input VoltageDC24V±20%
Input Current4.1mA (TYP )
ON Voltage/CurrentAt least 15V/2.0mA
OFF Voltage/Curr e nt5V Max/1.0mA Max
ON Time/OFF TimeON=0.5ms Max/OFF=0.5ms Max
Number of Commons1
Other Functions
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 65
DI_01 is used together with the position registration latch input, and when enabled, the position
registration latch input latches with the pulse encoder when SI_01 is "ON".
22 Option Module - LIO-06 Module
Digital Input Circuit Connection Example
Common
750
5.6
DI
Internal Circuitry
Digital Output Circuit Connection Example
Output
Register
1.2k䃈
R
0.5
Photocoupler
PS280䠍䠉䠐
33k䃈
1000PF
PS2805-4
R
1000PF
Transistor
DTDS14GP
FU
Input Circuitry
Input
Register
Vin
DO
0䠲
Digital Output Circuit
The specifications of the LIO-06 digital output circuit are shown below.
ItemSpecification
Number of Outputs8
Output MethodTransistor Open Collector Sink Output
IsolationPhotocoupler Isolation
External Power Supply VoltageDC24V±20%
Output Current100mA Max
Leak Current at OFF0.1mA Max
ON Time/OFF TimeON=0.25ms Max/OFF=1ms Max
Number of Commons1
Protection Circuit
Fuse Rating1A
Error DetectionBlown fuse detection
66 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
The fuses are not for circuit protection. They are for fire protection at output shor ts. A fuse
should be attached outside each output when a protective circui t is necessary.
22 Option Module - LIO-06 Module
DANGER
Analog Input Circuit
The specifications of the LIO-06 analog input circuit are shown below.
ItemSpecification
Analog Input Range-10 to +10V
Number of Input Chan ne ls1
IsolationNon-isolated
Maximum Rated Input±15V
Input Impeda nceApprox. 20kΩ
Resolution16-bit (-31276 to +31276)
Accuracy
Input Filter
Conversion Speed50μs
25ºC±0.1%(±10mV)
0 to 55ºC±0.3%(±30mV)
Time Constant
Delay Ti me1 ms (Max) (When -10+10V)
0.2×10
–2
The time constant shows t he charact eristic s accordin g to the input filter eq uivalent to the time to re ach 0.632 × t he input
voltage.
Analog Input Circuit Connection Example
To A/D
Conversion
Ground
Internal Circuitry
Analog Input Characteristics Response Chart
The following shows an analog input response chart and input characteristics diagram for the LIO-06 module.
Input Characteristics Response Chart
Analog Input ValueInput Register Value
-10.5V-32768
-10.0V-31276
-5.0V-15638
0.0V0
+5.0V15638
+10.0V31276
+10.5V32767
• Minimum linearity of +10.0V cannot be assured.
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 67
22 Option Module - LIO-06 Module
Voltage Input Characteristics Diagram
Analog Output Circuit
Analog Input
Value
The specifications of the LIO-06 analog output circuit are shown below.
ItemSpecification
Output Range-10 to +10V
Number of Output Channels1
IsolationNon-isolated
Maximum Permissible Load Current±5mA
Resolution16-Bit (-31276 to +31276)
Absolute
Output Delay Time1.2ms (Time of change from -10+10V)
Analog Output Circuit Connection Example
25ºC±0.1% (±10mV)
0 to 55ºC±0.3% (±30mV)
68 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
22 Option Module - LIO-06 Module
Analog Output Characteristics Response Chart
The following shows an analog output response chart and output characteristics diagram for the LIO-06 module.
Output Characteristics Response Chart
Analog Output ValueOutput Register Va lue
-10.5V-32768
-10.0V-31276
-5.0V-15638
0.0V0
+5.0V15638
+10.0V31276
+10.5V32767
Voltage Output Charac teristics Diagram
Output Register Value
Analog Output
Value
Encoder Circuit
The specifications of the LIO-06 encoder circuit are shown below.
ItemSpecification
Number of Encode rs1 channel (A/B/C-Phase Input)
Input Circuits
Input ModeA/B-phase, code, UP/DOWN counter, pulse, and direction
Latch Input
A/B-phase: 5V differential input, non-isolated, max frequency 4MHz
C-Phase: 5V/12V /2 4V ph oto c ou pler input, max frequency 500k H z
Position registration latch with C-Phase of DI_01
Response Time: Max 5μs during C-Phase input, During DI_01 Input: Max 60μs
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 69
22 Option Module - LIO-06 Module
50-core
Loose wires
Encoder Input Circuit Connection Example
Pulse Generator
A-phase
B-phase
LIO-06 Connectors and Pin Layouts
• Connectors
ItemDescription
Use Connector10250-52A3PL (Sumitomo 3M)LIO-06 Connector (RoHS-compatible)
JEPMC-W2064-A5-E0.5 m
Cable for LIO-06
Module
(Single loose wire)
Standard Cable Wiring Table
JEPMC-W2064-01-E1 m
JEPMC-W2064-03-E3 m
10150-3000PE (Sumitomo 3M)Connector Unit (RoHS-compatible)
10350-52A0-008 ( Sumitomo 3M)Shell screw lock type
10350-52F0-00 8 (Sumitomo 3M)On e -touch lock type
The following shows the standard cable wiring for the JEPMC-W2064 cable.
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 71
22 Option Module - LIO-06 Module
DANGER
L
LoadExternal Fuse
(Installed bycustomer)
LIO-06 Module Connector Connection Example
An example of LIO-06 module connector connection is shown below.
Relay Terminal Block
+15
V
-15V
Analog Output
Analog Input
Pulse Input
+
+15
V
-15V
+
1
26
2
27
4
5
29
30
6
31
AO
AO_GND
AI
AI_GND
PA+
PA-
PB+
PB-
GND
GND
External Device
L
-10
+10V
FG
External Device
V
-10 +10V
FG
Pulse Generator
+5V
0V
FG
L
L
L
L
L
L
L
L
L
Load
External Fuse
(Installed by customer)
Signal
External Input
Signal
External Output
Z-phase Latch
Input
Digital Input
Digital Output
PILC(24V)
10
PILC(12V)
34
PILC(5V)
9
PIL
35
+5V
Fuse Break
Detection
Circuit
FG Connector
Shell)
13
38
14
39
15
40
16
41
17
42
20
45
21
46
22
47
23
48
24
49
25
50
DICOM
DICOM
DI_00
DI_01
DI_02
DI_03
DI_04
DI_05
DI_06
DI_07
DO_24V
DO_24V
DO_00
DO_01
DO_02
DO_03
DO_04
DO_05
DO_06
DO_07
DO_GND
DO_GND
The cable shield between the external equipment and the junction terminal block should be installed on the external
device side.
72 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
23 Option Module – 218IF-Y1
23Option Module – 218IF-Y1
Outline of Functions
The 218IF-01 Module has an RS-232C serial interface and an Et her net interface mounted in it. Pers onal co mp ute rs , HMI
devices, and controllers manufactured by other companies can be connected to the 218IF-01 Module via the serial or
Ethernet connectors.
YASKAWA ELECTRIC (SHANGHAI) CO., LTD. BEIJING OFFICE
Room 1011, Tower W3 Oriental Plaza, No.1 East Chang An Ave.,
Dong Cheng District, Beijing 100738, China
Phone 86-10-8518-4086 Fax 86-10-8518-4082
YASKAWA ELECTRIC TAIWAN CORPORATION
9F, 16, Nanking E. Rd., Sec. 3, Taipei 104, Ta iwan
Phone 886-2-2502-5003 Fax 886-2-2505-1280
YASKAWA AMERICA, INC.
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture
thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be sure
to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.