Yaskawa MP3300iec User Manual

MP3300iec
Machine Controller
Hardware Manual
Type: MP3300iec
To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance. Ensure the end user receives this manual.
YAI-SIA-IEC-7
Table of Contents
1. Basic Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2. System Configuration Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
3. Component Part Numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
4. Base Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
5. CPU Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
6. Installatio n and Usage Co n d itions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 3
7. Base Unit Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
8. Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
9. Display and Indi c at ors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
10. Self-Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
11. MECHATROLINK-III Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
12. MECHATROLINK-III Network Topologies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
13. MECHATROLINK-III Synchronization between Modules . . . . . . . . . . . . . . . . . . . . . .24
14. Devices Connectable via MECHATROLINK-III. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
15. Connecting the RLY OUT Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
16. Ethernet Connector Details. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
17. Option Module - AI-01 (Analog Input) Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
18. Option Module - AO-01 (Analog Output) Module . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
19. Option Module - DO-01 (Digital Output) Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
20. Option Module - LIO-01/02 Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
21. Option Module - LIO-04/05 Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
22. Option Module - LIO-06 Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
23. Option Module – 218IF-Y1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
24. Terminal Block Kit CBK-U-MP2A-xx. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
25. Terminal Block Kit CBK-U-MP2B-xx. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
26. Terminal Block Kit CBK-U-MP2C-xx. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
27. Cable Shielding, Segregation and Noise Immunity . . . . . . . . . . . . . . . . . . . . . . . . . .78
Copyright © 2014 YASKAWA AMERICA, INC. All rights reserved. No part of this publ ic at ion may be repr oduc ed, st ore d in a retrieval system, or transmitted, in any form, or by any means, mechanical, ele ct ron ic , ph oto copy ing , recording, or otherwise, without the prior written permission of Yaskawa. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, Yaskawa assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
4 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
1 Basic Units
CPU Module
+
Base Unit
“Basic Unit” is a collective term that refers to the modules in the following table.
Unit Name Primary Function
CPU Module Base Unit Contains the power supply and provides the backplane to which Modules are mounted.
The Basic Modules are typically connected as shown in the following examples.
Stores the module definitions and programs, and interprets the programs. The CPU Module also controls the Optional Modules.
1 Basic Units
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 5
2 System Configuration Example
2 System Configuration Example
The following figure shows a typical system configuration.
MotionWorks IEC version
3.0.0 or higher
RLYOUT
connector cable
24-VDC power supply, AC power supply, or status monitoring device
Power supply cable
24-VDC power supply or AC power supply
Another PLC
Ethernet communications cables
MP3300
Battery
MECHATROLINK-III
SERVOPACK with
MECHATROLINK-III
Communications
PC
HUB
Front cover for unused slot
MECHATROLINK-III Cable
I/O Module with
MECHATROLINK-
Communications
Optional Modules I/O Modules
LIO-05
LIO-04
LIO-02
LIO-01
LIO-06
Communications Modules
218IF-Y1
III
AI-01
DO-01
AO-01
External outputs
External inputs
RS-232C
Ethernet
I/O
Servomotor
Servomotor
Servomotor
Up to 62 stations, including I/O
6 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
3 Component Part Numbers
System Components
Type Part Number Description
PMC-U-MP33004 CPU, MP3300, 4 axis, 400 MHz, 4MB SRAM PMC-U-MP33008 CPU, MP3300, 8 axis, 400 MHz, 4MB SRAM
CPU
Base Unit
Option Card
MECHATROLINK Network
MECHATROLINK Cables
Accessories
PMC-U-MP33020 CPU, MP3300, 20 axis, 40 0 MHz, 4MB SRAM PMC-U-MP33320 CPU, MP3300, 20 axis, 80 0 MHz, 8MB SRAM PMC-U-MP33332 CPU, MP3300, 32 axis, 80 0 MHz, 8MB SRAM JEPMC-BU3304-E Base Unit with DC Power Supply, 1 Slot, MP3300iec JEPMC-BU3303-E Base Unit with DC Power Supply, 3 Slots, MP3300iec JEPMC-BU3302-E Base Unit with DC Power Supply, 8 Slots, MP3300iec JEPMC-BU3301-E Base Unit with AC Power Supply, 8 Slots, MP3300iec JAPMC-AN2300 Analog Inputs (AI-01)
JAPMC-AN2310-E Analog Outputs (AO-01) JAPMC-DO2300 Digital Output Modul e (DO-01) JAPMC-IO2300-E Digital I/O Module (LIO-01) JAPMC-IO2301-E Digital I/O Module (LIO-02) JAPMC-IO2303 Digital I/O Module (LIO-04) JAPMC-IO2304 Digital I/O Module (LIO-05) JAPMC-IO2305-E Digital Multi-Function I/O Module (LIO-06) JAPMC-CM2301-E Ethernet & RS232C Communication (218IF-Y1) JEPMC-MT2000-E HUB, MECHATROLINK-III NETWORK, 8 SLAVE PORTS JEPMC-MT2020-E ADAPTER, ETHERNET TO MECHATROLINK JEPMC-MTD2310-E I/O MODULE, MECHATROLINK NETWORK, 64 IN, 64 OUT JEPMC-MTA2900-E ANALOG MODULE, MECHATROLINK NETWORK, 8 INPUT JEPMC-MTA2910-E ANALOG MODULE, MECHATROLINK NETWORK, 4 OUTPUT JEPMC-W6012-A2-E MECHATROLINK-III CABLE, 0.2 M JEPMC-W6012-A5-E MECHATROLINK-III CABLE, 0.5 M JEPMC-W6012-01-E MECHATROLINK-III CABLE, 1.0 M JEPMC-W6012-02-E MECHATROLINK-III CABLE, 2.0 M JEPMC-W6012-03-E MECHATROLINK-III CABLE, 3.0 M JEPMC-W6012-04-E MECHATROLINK-III CABLE, 4.0 M JEPMC-W6012-05-E MECHATROLINK-III CABLE, 5.0 M JEPMC-W6012-10-E MECHATROLINK-III CABLE, 10 M JEPMC-W6012-20-E MECHATROLINK-III CABLE, 20 M JEPMC-W6012-30-E MECHATROLINK-III CABLE, 30 M JEPMC-W6012-40-E MECHATROLINK-III CABLE, 40 M JEPMC-W6012-50-E MECHATROLINK-III CABLE, 50 M JEPMC-BA3001 Replacement Battery JEPMC-OP2300 Option Slot Cover JEPMC-OP3001 Replacement Power Supply Side Cover JEPMC-OP3002 Replacement Option Base Side Cover
3 Component Part Numbers
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 7
4 Base Units
4 Base Units
The Base Unit provides the backplane to which Modules are mounted and supplies the required power to the Modules. There are three models of Base Units, a one-slot model, a three-slot model, and an eight-slot model. This section shows the appearance and part names of the Base Unit and describes the connector.
Appearance and Part Names
Figure 1 illustrates the appearance of the Base Unit and a part name.
Figure 1
RLYOUT connector
Power connector
Figure 1 Base Unit
8 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
Connector
The Base Unit has two connectors: an RLYOUT connector and a power connector.
RLYOUT Connector
The RLYOUT connector outputs the status of the CPU Module.
Figure 2
Figure 2 RLYOUT Connector Model: 734-302
Pin Assignme n ts
No. Signal Label Description
1 OUT 2 OUT
Power Connector
Connect the power supply to this connector.
Figure 3
4 Base Units
Normal operation: Circuit closed. Error: Circuit open.
DC power supply 4-2013522-3 White
Pin Assignme n ts
Figure 3 RLYOUT Connector Model: 734-302
Type Model Color
No. Signal Label Description
3 24 VDC Power input wire for 24 VDC 2 0 VDC Power input wire for 0 VDC
1FG
Connects to the frame ground. (Ground to 100 W max.)
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 9
5 CPU Specifications
5 CPU Specifications
The hardware specifications of the CPU Unit are given in the following table.
Item CPU Specification
Model PMC-U-MP330xx
PMC-U-MP33004: CPU, MP3300, 4 axis, 400 MHz, 4MB SRAM
PMC-U-MP33008: CPU, MP3300, 8axis, 400 MHz , 4MB SRAM
Part Number: Description
Flash Memory Capacit y: 40 MB (32 MB of user me mo ry ) SDRAM Capacity: 128 MB SRAM Capacity: 8 MB (battery backup) Calendar Seconds, minutes, hour, day, week, month, year, day of week, and timing (battery backup) Ethernet 10Base-T or 100Base -TX MECHATROLINK MECHATROLINK-III: 1 circuit with 2 ports
USB
Indicators and Displays
Switches
PMC-U-MP33020: CPU, MP3300, 20 axis, 400 MHz, 4MB SRAM
PMC-U-MP33320: CPU, MP3300, 20 axis, 800 MHz, 8MB SRAM
PMC-U-MP33332: CPU, MP3300, 32 axis, 800 MHz, 8MB SRAM
USB 2.0 Type A host, 1 port Compatible devices: USB storage
Seven-segment disp lay Status indicators USB status indicator MECHATROLINK-III status indicators Ethernet status indicators
DIP switch: Mode switch STOP/SAVE switch. Refer to Switches on page 16 for detailed switch information.
CPU Communications Specifications
The specifications of the Communications Protocols built into the CPU Module are given in the following table.
Protocol Mode Detail
Modbus TCP
Ethernet/IP
OPC read/write
Custom Protocol n/ a
Network Variables read/writ e
MP3300iec as Master (Client) Maximum Number of Data Bl ocks = 20 MP3300iec as Slave (Server) 1000 registers in, 1000 registers out, 256 coils in, 256 coils out MP3300iec as Master (Scanner) Maximum Number of Data Blocks = 10 0
MP3300iec as Slave (Adapter)
Total of 16 instances in, 16 instances out, arranged as 3 instances of
256 bytes, 3 instances of 128 bytes, and 10 instances of 496 bytes.
Any Global variable can be configured, requires OPC Server running
on PC
Use the YDeviceComm firmware library to create a cu stom
communication protocol.
Variables configured with MotionWorks IEC software that allow
automatic data transfer from controller to controller.
10 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
Display
MECHATROLINK-III status indicators
MECHATROLINK-III connectors
Status indicators
Mode switches
Ethernet status indicators
Ethernet connector
USB status indicator
CPU Module Appearance and Component Names
Figure 4 shows the appearance of the CPU Module and the compnent names.
Figure 4
5 CPU Specifications
Figure 4 CPU Module Component Names
CPU Module Connectors
The CPU Module has three types of connectors: MECHATROLINK-III, Ethernet, and USB.
MECHATROLINK-III Connectors
Figure 5 illustrates connectors used to connect MECHATROLINK-III communications devices.
Figure 5
Figure 5 MECHATROLINK-III Connectors
Ethernet Connectors
Figure 6 illustrates the connector used to connect Ethernet communications devices.
Figure 6
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 11
Figure 6 Ethernet Connector
5 CPU Specifications
r
USB Connector
Figure 5 illustrates the connector used to connect a USB memory device.
Figure 7
USB connecto
Open the cover.
Figure 7 USB Connector
NOTICE: Equipment Hazard. Before removing the USB memory device, press the STOP/SAVE switch and wait until the USB status
indicator goes out. If the USB memory device is removed while the USB status indicator is lit or flashing, the data may become corrupted.
12 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
6 Installation and Usage Conditions
6 Installation and Usage Conditions
This section describes installation and usage conditions for the MP3300iec Series Machine Controllers. Install the MP3300iec Series Controllers in an environment with the following conditions.
Installation and Usage Conditions
Ta ble 1 MP3300iec Installation and Usage Conditions
Item Specification
Environmental Conditions
Mechanical Operating Conditions
Electrical Operating Conditions
Installation Conditions
Ambient Operating Temperature
Ambient Storage Temperature -25 to 85°C Ambient Operating Humidity 10% to 95% RH (with no condensation) Ambient Storage Humidity 10% to 95% RH (with no condensation) Pollution Level Conforms to JIS B 3502 Pollution Degree 2. Corrosive Gas There must be no combustible or corrosive gas. Operating Altitude 2,000 m max.
Vibration Resistance
Shock Resistance
Noise Resistance
Ground Ground to 100 Ω max. Cooling Method Natural cooling or forced-air cooling. Refer to Control Panel Cooling Method on page 14
0 to 60°C (Forced cooling is required if 55°C is exceeded.)
Conforms to JIS B 3502. Continuous vibration: 5 to 9 Hz with single-amplitude of 1.75 mm 9 to 150 Hz with fixed acceleration of 4.9 m/s Intermittent vibration: 5 to 9 Hz with single-amplitude of 3.5 mm 9 to 150 Hz with fixed acceleration of 9.8 m/s 10 sweeps each in X, Y, and Z directions for both intermittent and continuous vibration
Size of shock: Peak accel eration of 147 m/s Duration: 11 ms 3 times each in X, Y, and Z directions
Conforms to EN 61000-6-2, EN 61000-6-4, and EN 55011 (Group 1 Class A). Power supply noise (FT noise): ±2 kV min. for one minute Radiation nois e (F T noise): ±1 kV min. for one minute Ground noise (impulse noise): ±1 kV min. for 10 minutes Electrostatic noise (contact disch a rge method): ±6 kV or more, 10 times
2
2
2
(15 G)
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 13
6 Installation and Usage Conditions
Fan
Fan
40 mm min.
10 mm
min.*
* For a control panel with natural cooling with the MBU-303 Base Unit: 30 mm min.
10 mm
min.*
40 mm min.
Approx. 40 mm
Direction of air ow
Direction of air ow
Approx. 40 mm
Control Panel Cooling Method
The components that are used in the Machine Controller require the ambient operating temperature to be between 0 and 60 °C. Use one of the methods described below to ensure adequate cooling in the control panel.
NOTICE: Equipment Damage. Use forced-air cooling if the ambient temperature exceeds 55°C.
Control Panels with Natural Cooling
• Do not mount t h e Mac hi ne Controller at the top of the control panel, where the hot a ir t hat i s g ene rat ed inside the panel collects.
• Leave sufficient space above and below the Machine Controller, and maintain adequate distances from other devices, cable ducts, and other objects to ensure suitable air circulation.
• Do not mount the Machine Controller in any direction other than the specified direction.
• Do not mount the Machine Controller on top of any device that generates a significant amount of heat.
• Do not subject the Machine Controller to direct sunlight.
Control Panels with Forced-air Cooling
Install a fan near the center of and at the top or bottom of the Machine Controller for either of the following methods.
• Forced draft method (A fan or a similar device is used to circulate the air in the interior and the exterior of the panel.).
• Forced circulation method (A fan or a similar device is mounted to the airtight panel to circulate the air inside.).
Note: 1. Use the following guideline when selecting the fan:
• 80 x 80 mm min., Maximum air flow: 0.9 m3/min, Maximum static pressure: 26.5 Pa or higher.
Figure 8
2. Adjust the fan installation location and the direction of air flow as shown in Figure 8.
14 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
Figure 8 Fan installation location and air flow direction
7 Base Unit Specifications
The specifications of the Base Units are listed in Table 2.
Table 2 Base Unit Specifications
7 Base Unit Specifications
Item
Model JEPMC-BU3304-E JEPMC-BU3303-E JEPMC-BU3302-E JEPMC-BU3301-E Abbreviation MBU-304 MBU-303 MBU-302 MBU-301 Number of Slots 138
Mountable Modules MP2000-series Optional Modules
Input Voltage 24 VDC 110/220 VAC Allowable Input
Voltage Range Input Current Inrush Current 40 A, 10 ms max. 30 A, 10 ms max. 40 A, 10 ms max.
Allowable Power Loss
Power Supply Section
RLY OUT
Indicators POWER Connectors
Time Rated Voltage 5.15 V 5.0 V Rated Current 2.5 A 4.5 A 4.0 A 8.0 A Output Current Range 0 to 2.5 A 0 to 4.5 A 0.0 to 4.0 A 0.0 to 8.0 A Rated Voltage
Accuracy Battery
1 slot 3 slots 8 slots DC 8 slots AC
19.2 to 28.8 VDC
1.0 A max. (at rated input/output)
1 ms 20 ms
5.15 V ±2% max. (5.05 to 5.25 V) You can mount a memory backup Battery for retained variables, absolute encoder offsets, and
alarm history. A normally open relay output that is linked to the CPU Module status
Normal operation: Circuit closed . Error: Circuit open.
Contact Ratings:
• 125 Vac, 0.4 A resistive load, 0.20 A inductive load
• 24 Vdc, 0.5 A resistive load, 0.25 A inductive load
POWER: Power supply connector RLY OUT: Relay contact connector
1.5 A max. (at rated input/output)
Specification
85 to 132 VAC/ 198 to 276 VAC
3.0 A max. (at rated input/output)
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 15
8 Switches
8Switches
The CPU Module has the following two types of switches.
• DIP switches: Mode switches
• STOP/SAVE switch
DIP Switches: Mode Switches
The SW1 and SW2 switches are checked at start-up, and their behavior is described in the following tables:
Table 3 SW1 Switches
SW Description
STOP When ON, prevents PLC from running.
E-INIT When ON, overrides Ethernet configuration according to Table 5.
INIT When ON, the controller uses the fixed, default configuration
CNFG When ON, the controller creates Axes and I/O for all connected devices. (Auto-configuration)
Table 4 SW2 Switches
SW Description
LOAD When ON, load either the user project or firmware from the USB thumb dri ve. See Table 6 for details.
TEST When ON, the IP ad dress is scrolled across the seven segment display.
MNT
-- / DHCP DHCP Selection when E-INIT is ON.
When ON, controller starts up in supervisor mode. In this mode MECHA TROLINK III, PLC, Modbus/TCP and Ethernet/IP do not start. The controller firmware can be updated, and clearing DOS FS alarms will repair the DOS FS.
E-INIT and - switches can override the Ethernet configuration according to Table 5.
Table 5 Operation of E-INIT, E-PM0 and E-PM1 for Configuring Ethernet
E-INIT -- / DHCP
Static Configuration OFF N/A
192.168.1.1 ON OFF DHCP ON ON
On start-up, the controller will aut omat ic ally l oad f ir mware or use r pr oje cts bas ed on t he LOAD and MNT swi tc hes . The USB thumb drive is available in any other circumstances.
Table 6 Operation of LOAD and MNT for USB Thumb Drive
E-INIT -- / DHCP
Load user project from USB thumb drive ON OFF
Install firmware and user project from USB
thumb drive
16 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
ON ON
9 Display and Indicators
9 Display and Indicators
The CPU Module has the following display and four types of indicators.
•Display
• Status indicators
•USB status indicator
• MECHATROLINK-III status indicators
• Ethernet status indicators
Display
The following situations use the seven segment display:
• Manufacturing: During programming the seven segment display outputs “FLASH...”. When finished, the seven segment display outputs “donE”.
• Startup: If the controller cannot boot because of a bad firmware image check sum, the seven segment display outputs “bOOt ERROR”
• IP Address: If the TEST switch is ON, then the seven segment display outputs the IP address.
• Firmware update: During programming the seven segment display outputs “FLASH...”. When finished, the seven segment display outputs “donE”.
Status Indicators
These indicators show the status of the CPU Module.
Table 7 Status LED
LED Description
RDY ON when the controller has detected valid firmware and has started. RUN ON when PLC is running. ALM ON when an alarm is active.
ERR BAT ON when the battery needs replacing.
M-ALM ON when JL100 (Mechatrolink Master) chip initialization fails.
ON at initial power up while firmware is loading. Turns off if firmware is valid. ON when a critical error occurs requiring a power cycle to recover.
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 17
9 Display and Indicators
USB Status Indicator
This indicator shows the status of the USB memory.
Indicator Name Indicator Status Status Description
Not lit No USB memory device
USB ACTIVE
MECHATROLINK-III Status Indicators
Lit USB memory device inserted A USB memory device is inserted.
Flashing Accessing USB memory The USB memory is being accessed.
No USB memory device has been inserted ye t, or the USB memory device is ready to be removed.
These indicators show the status of the MECHATROLINK-III communications.
Indicator Name Color Status When Lit
Ethernet Status Indicators
CN Green LK1 Green MECHATROLINK-III communications are active on PORT1.
LK2 Green MECHATROLINK-III communications are active on PORT2.
MECHATROLINK-III communications is established with the CPU Module as a slave (i.e., the Connect command is ON).
These indicators show the status of Ethernet communications.
Indicator Name Color Status When Not Lit, Lit, or Flashing
LINK/ACT Yellow
100M Green
Lit: Ethernet link established. Flashing: Ethernet communications activity.
Not lit: 10 M connection Lit: 100 M connection. We do not support GB connections.
18 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
10 Self-Configuration
10 Self-Configuration
DIP Switch
Self-Configuration after Adding Devices such as Servopacks
The controller ca n aut omatica lly config ure a ll t he M echatr olink devi ces. Fi rst, co nnect and p ower up all the Mecha troli nk nodes (making sure they all have unique station numbers). Then, set the CNFG switch to the ON position and power up the controller. Wait for the RDY LED to come on and the controller will now have the new auto configuration.
Note: Controllers with an existing saved configuration cannot be auto configured until the currect conf iguration is deleted.
MotionWorks IEC
The MotionWorks IEC (Express or Pro) configuration can detect the configuration and provide the user with configuration choice s. If a S tar tUp Config urati on was alre ady save d on the controll er, the self-configure funct ion will not allow new devices to be discovered. In this case, add them offline manually first.
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 19
11 MECHATROLINK-III Specifications
11 MECHATROLINK-III Specifications
The specifications of the MECHATROLINK-III Network Master that is built into th e CPU Unit are given in the following table.
Item Specification Remarks
Communications ASIC JL-100 ­Number of Communications Lines 1 -
MECHATROLINK communications settings
Number of Communicat ions Ports (Connectors)
Communications Method M-III ­Baud Rate 100 Mbps -
Communications Cycle
Number of Connected
Master
Stations Message Relaying Not Supported. ­C2 Messages Not Supported. ­Retries Supported. 0 to 4 retries Asynchronous Setting of
High-speed Scan Cycle and Communications Cycle
2-
250 μs/0.5 ms/ 1 ms/1.5 ms/2 ms/2.5 ms/3 ms/
3.5 ms/4 ms 62 stations -
Not supported. An alarm will occur if setting is attempted.
-
CPU Unit Specifications
Item Specification
Calendar Battery backup accurate to 1 minute of error per month. Ethernet M-III 1981386-1 ×2 (TycoAMP) USB
Protection Hardware watchdog timer (PLD): 0 to 510 ms (register setting) Relay Output Backup Circuit Battery: BR-1/2AA (Panasonic), 3.0 V
Connector DUSB-ARA42-T11A-FA (DDK), type A connector Function USB 2.0 ho st, 3 speeds (HS/FS/LS), 1 port
10BASE-T, 100BASE-TX Auto-Negotiation / Baseline Wander Correction / Auto-MDIX
Contacts normally open for RUN status (RDY indicator lit), and OFF for WDT error status. The relay is built into the Power Supply Unit.
20 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
12 MECHATROLINK-III Network Topologies
12 MECHATROLINK-III Network Topologies
You can connect the MP3300iec Series Controller and drives or I/O with cascaded connections, star connections, or mixed cascaded/star network topologies. The following figures show examples of these types of network topologies.
Cascaded Connection
Cascaded connections allow you to connect one or more series of slave stations from the CPU Unit MECHATROLINK­III ports. Regardless of whether a single MECHATROLINK-III port is used, as shown in Figure 9, or two CPU Unit MECHATROLINK-III ports are used, as shown in Figure 10, these are called cascaded connections.
Figure 9
CPU Unit
Figure 10
Up to 32 stations, including Servos and I/O
Figure 9 Cascaded Connections Using Only One Port
CPU Unit
No terminating resistor is required.
Up to 32 Servo stations
Up to 62 stations, including I/O
No terminating resistor is required.
No terminating
resistor is required.
Figure 10 Cascaded Connections Using Two Ports
Note: 1. Do not connect more than 32 stations up to the final slave station to any one CPU Unit port.
2. The maximum number of stations that you can connect with cascaded co nnections depends on the c ommunications cycle.
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 21
12 MECHATROLINK-III Network Topologies
Star Connections
Star connections al low you to connect slave stations through Hub Modul es. Each port on a Hub Module connects to only one slave station. You can also connect one additional Hub Module to the first Hub Module.
CPU Unit
Hub Module
Note: 1. Terminating resistors are not required.
2. The maximum number of stations that you can connect with star connections depends on the communications cycle.
Hub Module
22 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
Mixed Cascaded/Star Connections
You can combine both cascaded and star network topologies.
CPU Unit
Hub Module
12 MECHATROLINK-III Network Topologies
No terminating
resistor is required.
No terminating
resistor is required.
Note: 1. Do not connect more than 32 stations to a single CPU Unit port, including the Hub Modules.
2. The maximum number of stations that you can connect with a mixed cascaded/star connections depends on the communications cycle.
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 23
13 MECHATROLINK-III Synchronization between Modules
NOTICE
NOTICE
13 MECHATROLINK-III Synchronization between Modules
Timing at Which Modules Are Synchronized
Modules are automatically synchronized when the power supply is cycled. If you perform any of the following operations after turning ON the power supply, save the settings to flash memory and
then cycle the power supply again.
• When operation changes from asynchronized to synchronized as a result of changing the communications cycle
• When operation changes from synchronized to asynchronized or from asynchronized to synchronized as a result of changing the high-speed scan setting
• When the minimum response time in the MPiec controller is changed.
Changing Synchronization Cycles
When the scan cycle is changed, MECHATROLINK communications with all slave stati ons conne ct ed to the SVC32 ar e reset. Operation automatically changes to synchronized when communications are restored.
MECHATROLINK communications continue for all other Modules.
1. When you change the MECHATROLINK cycle, do so either with the CPU Function Module stopped or when motion commands are not being executed. Otherwise, application operations may be affected.
2. When changing the MECHATROLINK setting, the following operation will occur because MECHATROLINK communications are reset.
• Position inform ation and zero point return completion information for Servo axes will be lost.
Changing the MECHATROLINK Communications Cycle
Operation is automatically synchronized as long as the high-speed scan setting is an integral multiple of the communic ations cycle.
It is not necessary to cycle the power supply.
If asynchronous operation is set as a result of changing the communications cycle, an alarm will occur for the Servo axis and an I/O error will occur for the I/O station. If this happens, change the setting back to synchronized, save the settings to flash memory, and then cycle the power supply.
24 YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7
14 Devices Connectable via MECHATROLINK-III
14 Devices Connectable via MECHATROLINK-III
Servopacks
The following table shows Servopacks that are compatible with MECHATROLINK-III and can be connected to the controller.
Model Details
SGDV-
SGDV-
SGDV-
SGDV-
SGDV-
SGD7S-
SGD7W-
I/O Modules
ƑƑƑƑ
ƑƑƑ
ƑƑƑ
ƑƑƑ
ƑƑƑƑ
ƑƑƑ
ƑƑƑ
21
E21
H21A
J21A
25
A20A
A20A
Σ-V Series AC Servo amplifiers for rotary motors Σ-V Series Mini AC Servo amplifiers for rotary motors Σ-V Series 200 VAC Large Capacity AC Servo amplifiers for rotary motors Σ-V Series 400 VAC Large Capacity AC Servo amplifiers for rotary motors Σ-V Series AC Servo amplifiers for linear motors Σ-7 Series 200 VAC Large Capacity AC Servo amplifiers Σ-7 Series 200 VAC Large Capacity dual motor AC Servo amplifiers
The following table shows the module that is compatible with MECHATROLINK-III and can be connected to the controller.
Model Details
JEPMC-MTD2310-E
64-point I/O Module 24VDC, 64 inputs, 64 outputs
YASKAWA America, Inc. MP3300iec Hardware Manual YAI-SIA-IEC-7 25
Loading...
+ 57 hidden pages