Yaskawa MP3200iec User Manual

MP3200iec
Machine Controller
Hardware Manual
Type: MP3200iec
To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance. Ensure the end user receives this manual.
YAI-SIA-IEC-5
Table of Contents
1. Definition of Terms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2. System Configuration Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3. Component Part Numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
4. Power Supply Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
5. Power Supply Unit Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
6. CPU Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
7. CPU External Appearance and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
8. Base Unit Installation and Operating Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
9. Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
10. DIP Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
11. LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
12. Self-Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
13. MECHATROLINK-III Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
14. MECHATROLINK-III Network Topologies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
15. MECHATROLINK-III Synchronization between Modules . . . . . . . . . . . . . . . . . . . . . .35
16. Devices Connectable via MECHATROLINK-III. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
17. Connecting the RLY OUT Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
18. Ethernet Connector Details. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
19. Option Module - AI-01 (Analog Input) Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
20. Option Module - AO-01 (Analog Output) Module . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
21. Option Module - DO-01 (Digital Output) Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
22. Option Module - LIO-01/02 Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
23. Option Module - LIO-04/05 Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
24. Option Module - LIO-06 Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
25. Option Module – 218IF-Y1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85
26. Terminal Block Kit CBK-U-MP2A-xx. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
27. Terminal Block Kit CBK-U-MP2B-xx. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
28. Terminal Block Kit CBK-U-MP2C-xx. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
29. Cable Shielding, Segregation and Noise Immunity . . . . . . . . . . . . . . . . . . . . . . . . . .90
Copyright © 2013 YASKAWA AMERICA, INC. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of Yaskawa. No patent liability is assumed with respect to the use of the information contained herein. Moreover, because Yaskawa is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual.
4 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Nevertheless, Yaskawa assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
5 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
6 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
1 Definition of Terms
+
+
+
Power
Supply Unit
CPU Unit
Power
Supply Unit
CPU Unit Base Unit
This section defines terms that have specific meanings in this manual.
Basic Units
“Basic Unit” is a collective term that refers to the three Units in the foll owing table.
Unit Name Primary Function
Power Supply Unit
CPU Unit Base Unit Used to mount Optional Modules.
The Basic Units are typically connected as shown in the following examples.
Supplies the power that is needed for the operation of the Units that are connected to each other and to any Optional Modules that ar e conn ect ed in the Contro ller.
Stores the module definitions and programs, and interprets the programs. The CPU Unit also controls the Optional Modules.
1 Definition of Terms
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 5
2 System Configuration Example
2 System Configuration Example
The following figure shows a typical system configuration.
MotionWorks IEC version
2.4 or higher
Ethernet communications cables
MP3200iec
RLYOUT
components
connector cable
24-VDC power supply, AC power supply, or status monitoring device
Power supply cable
24-VDC power supply or AC power supply
Another PLC
Ethernet
Battery
MECHATROLINK-III
Front cover
for unused slot
PC
Ethernet
MECHATROLINK-III Cable
Optional Modules
I/O Modules
IO-02 L
LIO-01
LIO-04
LIO-05
LIO-06
AI-01
DO-01
AO-01
Communications Modules
218IF-Y1
External outputs
External inputs
RS-232C
Ethernet
SERVOPACK with
MECHATROLINK-III
Communications
Servomotor
Servomotor
Servomotor
I/O Module with
MECHATROLINK-
Communications
I/O
III
Up to 62 stations, including I/O
6 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
3 Component Part Numbers
System Components
Type Part Number Description
PMC-U-MP32004 CPU, MP3200iec, 4 axis PMC-U-MP32008 CPU, MP3200iec, 8 axis
CPU
Power Supply
Base Unit
Option Card
MECHATROLINK Network
MECHATROLINK Cables
Accessories
PMC-U-MP32016 CPU, MP3200iec, 16 axis PMC-U-MP32032 CPU, MP3200iec, 32 axis PMC-U-MP32062 CPU, MP3200iec, 62 axis JEPMC-PSA3012-E POWER SUPPLY, 100V/200V, MP3200 JEPMC-PSD3012-E POWER SUPPLY, 24VDC, MP3200 JEPMC-BUB3003-E BASE UNIT, 3 SLOTS, MP3200 JEPMC-BUB3005-E BASE UNIT, 5 SLOTS, MP3200 JEPMC-BUB3008-E BASE UNIT, 8 SLOTS, MP3200 JAPMC-AN2300 Analog Inputs (AI-01) JAPMC-AN2310-E Analog Outputs (AO-01) JAPMC-DO2300 Digital Output Modu le (DO-01) JAPMC-IO2300-E Digital I/O Module (LIO-01) JAPMC-IO2301-E Digital I/O Module (LIO-02) JAPMC-IO2303 Digital I/O Module (LIO-04) JAPMC-IO2304 Digital I/O Module (LIO-05) JAPMC-IO2305-E Digital Multi-Function I/O Module (LIO-06) JAPMC-CM2301-E Ethernet & RS232C Communication (218IF-Y1) JEPMC-MT2000-E HUB, MECHATROLINK-III NETWORK, 8 SLAVE PORTS JEPMC-MT2020-E ADAPTER, ETHERNET TO MECHATROLINK JEPMC-MTD2310-E I/O MODULE, MECHATROLINK NETWORK, 64 IN, 64 OUT JEPMC-MTA2900-E ANALOG MODULE, MECHAT ROLINK NETWORK, 8 INPUT JEPMC-MTA2910-E ANALOG MODULE, MECHATROLINK NETWORK, 4 OUTPUT JEPMC-W6012-A2-E MECHATROLINK-III CABLE, 0.2 M JEPMC-W6012-A5-E MECHATROLINK-III CABLE, 0.5 M JEPMC-W6012-01-E MECHATROLINK-III CABLE, 1.0 M JEPMC-W6012-02-E MECHATROLINK-III CABLE, 2.0 M JEPMC-W6012-03-E MECHATROLINK-III CABLE, 3.0 M JEPMC-W6012-04-E MECHATROLINK-III CABLE, 4.0 M JEPMC-W6012-05-E MECHATROLINK-III CABLE, 5.0 M JEPMC-W6012-10-E MECHATROLINK-III CABLE, 10 M JEPMC-W6012-20-E MECHATROLINK-III CABLE, 20 M JEPMC-W6012-30-E MECHATROLINK-III CABLE, 30 M JEPMC-W6012-40-E MECHATROLINK-III CABLE, 40 M JEPMC-W6012-50-E MECHATROLINK-III CABLE, 50 M JEPMC-BA3001 Replacement Battery JEPMC-OP2300 Option Slot Cover JEPMC-OP3001 Replacement Power Supply Side Cover JEPMC-OP3002 Replacement Option Base Side Cover
3 Component Part Numbers
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 7
4 Power Supply Units
Indicators
RLYOUT connector
Power connector
Unit connector
4 Power Supply Uni ts
The Power Supply Unit supplies the connected Units and Optional Modules with the power needed to operate. There are two Power Supply Units available: an AC Power Supply Unit and a DC Power Supply Unit.
This section shows the appearance and part names of the Power Supply Unit and describes the indicators and connectors.
Appearance and Part Names
The following figure shows the appearance of the Power Supply Unit and the part names.
Indicators
These indicators show the load on the Power Supply Unit.
Output Current 8.9 A or less 9.0 to 11.4 A 11.5 to 13.9 A
Load
Green
Appendix
Indicator
<1> Reduce the number of Optional Mo dules that are connected.
Note: z: Lit, {: Not lit.
Yellow {z z {
Red {{ z {
Normal: Within power supply
capacity
zz z {
<1>
Normal: Maximum power
supply capacity
14.0 A or more
Error: Over power supply
capacity
<1>
8 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Connectors
The Power Supply Unit has three connectors: RLYOUT, power supply, and Unit connectors.
RLYOUT Connector
This connector outputs the operating status of the CPU Unit.
Model: 734-302
Pin Assignme n ts
No. Signal Label Description
1 OUT 2 OUT
Power Connector
Normal operation: Circuit closed.
Error: Circuit open.
Connect the power supply to this connector.
4 Power Supply Units
Type Model Color
AC Power Supply Unit 721-203/026-304 Black DC Power Supply Unit 721-203/026-000 White
Pin Assignments: AC Power Supply Unit
Pin No. Signal Label Description
3AC AC input 2AC AC input 1 FG Connects to the frame ground. (Ground to 100 W max.)
Pin Assignments: DC Power Supply Unit
Pin No. Signal Label Description
3 24 VDC Power input wire for 24 VDC 2 0 VDC Power input wire for 0 VDC 1 FG Connects to the frame gro und. (Ground to 100 W max.)
DC Power Supply UnitAC Power Supply Unit
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 9
5 Power Supply Unit Specifications
5 Power Supply Unit Specifications
The specifications of the Power Supply Unit are given in the following table.
Item
Model JEPMC-PSA3012-E JEPMC-PSD3012-E Abbreviation PSA-12 PSD-12
Input Voltage 100/200 VAC 24 VDC
Power Supply Section
Allowable Input Voltage Range
Allowable Frequency Range
Input Current 4.0 A max. (at rated input/output) 5.0 A max. (at rated input/output)
Inrush Current
Allowable Momentary Power Loss Time
Rated Voltage 5.15 V Rated Current 12.0 A Output Current Range 0 to 12.0 A 0.2 to 12.0 A Constant Voltage
Accuracy
85 to 132 VAC or 170 to 276 VAC 19.2 to 28.8 VDC
47 to 63 Hz -
25 A, 10 ms max. (fully discharged, 132-VAC input, rated output)
50 A, 10 ms max. (fully discharged, 276-VAC input, rated output)
20 ms 1 ms
5.15 V ±2% max. (5.05 t o 5.25 V) If the Power Supply Unit is mounted on the Main Rack, this output functions as normally closed
contacts that are synchronized with the status of the CPU Unit.
• Normal operation: Circuit closed.
• Error: Circuit open.
Contact Ratings
AC Power Supply Unit DC Power Supply Unit
Specification
50 A, 10 ms max. (fully discharged,
28.8-VDC input, rated output)
Status Output
Connectors
Indicators
Input Conditions
Inrush Current
Rise Time
Drop Time
Leakage Current
Efficiency
Input Voltage Current Capacity
24 VDC
125 VAC
POWER: Power supply connector RLY OUT: Relay contact connector
POWER
Refer to Indicators on page 12.
For Cold Start 50 A within 10 ms (fully discharged status) 275-VAC input, rated output
60,000 ms max. (The maximum time for the output control signals to maintain the specified timing when the primary voltage rises linearly.)
60,000 ms max. (The maximum time that the controls, such as the power failure sequence, can be maintained when the primary voltage drops linearly.)
276 VAC 61 Hz: 0.5 mA max. 132 VAC 61 Hz: 0.25 mA max.
70% minimum (for rated input voltage and rated load)
0.5 A (resistive load)
0.25 A (inductive l oad)
0.4 A (resistive load)
0.2 A (inductive load)
For Cold Start (Through rate at input voltage value increase from 10% to 90% is at 10 ms min.) 50 A within 10 ms (fully discharged status)
28.8-VDC input, rated output
­65% minimum (for rat e d input voltage and ra ted
load)
10 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
5 Power Supply Unit Specifications
Protection
Safety
Status Output
Power Sequences
Dielectric Strength
Insulation Resistance (Measured at 500 VDC.)
External Wiring Connector Terminals
Connector Cable
Hot Swapping
Item
AC Power Supply Unit DC Power Supply Unit
Specification
Low Input Protection (Power Fail Detection
55 to 75 VAC or 150 VAC max. 15.8 to 17.8 VDC
Level) Overcurrent Protection
For rated curren t (12 A), the protection operates at 14.0 A min. (typical). (The detection range is 13.0 to 15.0 A.)
Overvoltage Protection Operates at 5.75 to 6.75 V. Allowable Power Loss
Time
The output voltage fluctuation range is maintained for a 20-ms 100% dip momenta ry power loss.
The output voltage fluctuatio n range is ma intained for a 1-ms 100% dip momentary power loss.
Safety Standards Conforms to UL and CSA. Fuse 250 V/4 A 250 V/6.3 A
Linked to the RDY indicator on the CPU Un it. RDY indicator lit: Circuit closed. RDY indicator not lit: Circuit open. Contact Ratings
NO Contact Output (RLY OUT)
Power ON
Power OFF
Input Voltage Current Capacity
24 VDC
125 VAC
0.5 A (resistive load)
0.25 A (inductive load)
0.4 A (resistive load)
0.2 A (inductive load)
AC ON - 5-V rise in 1 s max. Output rise - POK signal in 0 s min.
AC OFF - POK signal for 20 ms min. POK signal - 5-V drop in 2 ms min.
DC ON - 5-V rise in 1 s max. Output rise - POK signal in 0 s min.
DC OFF - POK signal for 1 ms min. POK signal - 5-V drop in 2 ms min.
Between primary and secondary sides: 1,500 VAC for 1 minute Between primary side and FG (ground): 1,500 VAC for 1 minute Between secondary s ide and FG (ground): 50 0 VAC for 1 minute Between RLYOUT and primary side: 1,500 VAC for 1 minute Between RLYOUT and secondary side: 1,500 VAC for 1 minute
Between primary and secondary sides: 10 MΩ min . Between primary side and FG (ground): 10 MΩ min. Between secondary s ide and FG (ground): 100 MΩ min. Between RLYOUT and primary side: 100 MΩ min. Between RLYOUT and secondary side: 100 MΩ min.
External Power Supply Terminals
Protective Ground Terminal
AC, AC 0 and 24 VDC
FG
RLY OUT RLYOUT External Power Supply
Terminals (Twisted Pair)
AWG28 to AWG13 (0.08 to 2.6 mm
2
) RLY OUT Connector Cable: AWG28 to AWG14 (0.08 to 2.0 mm2) Not supported.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 11
5 Power Supply Unit Specifications
Output Current (iout (typical)) POWER (Green) (No Label) (Yellow) (No Label) (Red)
i out 8.9 A z{{
9.0 A iout 11.4 A zz{
11.5 A iou t 13 .9 A zzz
14.0 A iout (OCP activation) {{{
Item
POWER (green): Lights when the power is ON on the secondary side. (No label) (yellow): Lights when the Overcurrent Warning 1 Status Output is ON.
(No label) (red): Lights when the Overcurrent Warning 2 Status Output is ON.
Indicators
z: Lit {: Not lit.
External Dimensions
Weight 350 g
Width: 60 mm, Height: 130 mm, De pth: 137 mm
Specification
AC Power Supply Unit DC Power Supply Unit
12 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
6 CPU Specifications
6 CPU Specifications
The hardware specifications of the CPU Unit are given in the following table.
Item Specification
Model PMC-U-MP320xx Abbreviation MP3200iec Flash Memory Capacity: 40 MB (32 MB of user memory) SDRAM Capacity: 128 MB SRAM Capa city: 8 MB (ba ttery ba c kup) Calendar Seconds, minutes, hour, day, week, month, year, day of week, and timing (battery backup) Ethernet 10Base-T or 100Base-TX x 2 ports (hub) MECHATROLINK MECHATROLINK-III: 1 circuit with 2 ports
USB
Indicators and D i s plays
Switches
USB 2.0 Type A host, 1 port Compatible devices: USB storage
Seven-segment display Status indicators USB status indicator MECHATROLINK-III status indicators Ethernet status indicators
DIP switch: Mode switch 1 DIP switch: Mode switch 2 Rotary switches STOP/SAVE switch. Refer to DIP Switch Settings on page 27 for detailed switch information.
CPU Communications Specifications
The specifications of th e Communications Protocols built into the CPU Unit are given in the following table.
Protocol Mode Detail
Modbus TCP
Ethernet/IP
OPC read/write
Custom Protocol n/a
MP3200iec as Master (Client) Maximum Number of Data Blocks = 20 MP3200iec as Slave (Server) 1000 registers in, 1000 registers out, 256 coils in, 256 coils out MP3200iec as Master (Scanner) Maximum Number of Data Blocks = 100
MP3200iec as Slave (Adapter)
Total 16 instances in, 16 instances out, arranged as 3 instances of 256 bytes, 3 instances of 128 bytes, and 10 inst ances of 496 bytes.
Any Global variable can be configured, requires OPC Server running on PC
Use the YDeviceComm firmware library to cre ate a custom communication pro tocol.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 13
7 CPU External Appearance and Indicators
7 CPU External Appearance and Indicators
External Appearance
Indicators (LEDs)
MECHATROLINK-III connector CN1
MECHATROLINK-III connector CN2
Indicators
The following table describes the indicators that show the operating status and error information.
Indicator Indicator Name Color Meaning When Lit
MECHATROLINK-III communications are established as a slave (i.e., the CONNECT command is ON).
CN
LK1 LK2
CN Green LK1 Green Port 1 is performing MECHATROLINK-III communications.
LK2 Green Port 2 is performing MECHATROLINK-III communications.
14 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
8 Base Unit Installation and Operating Conditions
8 Base Unit Installation and Operating Conditions
This section describes the specifications of the MP3200iec Series Machine Controllers. Install the MP3200iec Series Controllers in an environment with the following conditions.
Environmental Conditions
Item Specification
Ambient Operating Temperature 0 to 55°C (CPU-03: 0 to 50°C) Ambient Storage Temperature -25 to 85°C Ambient Operating Humidity 30% to 95% RH (with no condensation) Ambient Storage Humidity 5% to 95% RH (with no condensation) Pollution Degree Conforms to JIS B 3502 Pollution Degree 2. Corrosive Gases There must be no combustible or corrosive gases. Operating Altitude 2,000 m max.
Control Panel Cooling Method
The components that are used in the Machine Controller require the ambient operating temperature to be between 0 and 55°C. Use one of the methods described below to ensure adequate cooling in the control panel.
Note: If the ambient temperature exceeds 50°C, we recommend forced-ai r cooling.
Control Panels with Natural Cooling
• Do not mount the Machine Controller at the top of the control panel, where th e hot air that is genera ted inside the panel collects.
• Leave sufficient spac e above and below the Units , and maintain ade quate dist ances from oth er devices, ca ble ducts, and other objects to ensure suitable air circulation.
• Do not mount the Controller in any direction other than the specified direction.
• Do not mount the Controller on top of any device that generates a significant amount of heat.
• Do not subject the Controller to direct sunlight.
Control Panels with Forced-air Cooling
Use one of the following methods to ensure 0.03 m3/min average airflow below the CP U Unit.
• Forced draft method (A fan or a similar device is used to circulate the air in the interior and the exterior of the panel.)
• Forced circulation method (A fan or a similar device is mounted to the airtight panel to circulate the air inside.)
Note: Use the following guideline when selecting the fan: CPU Unit’s resistance to air flow: 6 x 106 (N×s2/m8)
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 15
8 Base Unit Installation and Operating Conditions
Fan
CPU Unit’s internal resistance to
air flow: 6×10
6
(N⋅s2/m8)
40 mm min.
30 mm min.
Average airflow:
0.03 m
Mechanical Operating Conditions
Item Specification
Conforms to JIS B 3502.
Vibration Resistance
10 Hz f < 57 Hz with vibration amplitude of 0.075 mm 57 Hz f 150 Hz with fixed acceleration of 9.8 m/s 10 sweeps each in X, Y, Z directions (sweep: 1 octave/min)
Shock Resist ance
Electrical Operating Conditions
Conforms to JIS B 3502. Peak acceleration of 147 m/s
Item Specification
Conforms to EN 61000-6- 2 and EN 55011 (Group 1 Class A). Power supply noise (FT noise): 2 kV min. for 1 minute
Noise Resistance
Radiation noise (FT noise): 1 kV min., for 1 minute Ground noise (impul se noise): ±1 kV min., for 10 minutes Electrostatic noise (conducted): ±4 kV min ., 10 times
3
/min
2
2
twice for 11 ms each in the X, Y, and Z directions
30 mm min.
40 mm min.
Ground Information Ground to 100
ȍ
max.
16 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
9 Installation
Screw Mounting Attachment
You can use either of the following methods to install an MP3200iec Series Controller.
•Screw mounting
• DIN rail mounting
Screw Mounting
You can install the Unit by using the Screw Mounting Attachment.
Note: You can install the Unit by using the Screw Mounting Attachment.
• JEPMC-OP3001 This Attachment is provided with the Power Supply Unit. It can be installed on the PMC-U-MP320**.
• JEPMC-OP3002 This Attachment is provided with the MBU-B03, MBU-B05, and MBU-B08. It can be purchased separately.
The installation procedure is as follows:
1. Attach the Screw Mounting Attachment to the right end of the Controller.
9 Installation
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 17
9 Installation
2. Use screws to secure the 4 places shown in the following figure.
Note: 1. Recommended screws: M4 x 14 mm min.
2. Use a screwdriver wit h a shaft that is at least 13 cm long.
18 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Lock release position
Locking position
DIN Rail Mounting
Carefully line up the DIN rail locks wit h the locking positions.
9 Installation
Note: Removal
You can remove t he Controller by revers ing the order of the mo unting procedure.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 19
9 Installation
Connecting the CPU
Note: Before you connect the CPU, install the Battery. Refer to Installing and Replacing the Battery in the CPU on page 24.
1. Remove the rubber cap from the connector on the Power Supply Unit.
Note:
• When the connector is not in use, always cover it with the rubber cap.
• The left-side cap is marked with an L, and the right-side cap is marked with an R.
2. Connect the Power Supply Unit and the CPU Unit from left to right in this order.
20 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
3. Secure the connection by locking the slide locks at both the top and the bottom.
4
.;176
.
;17
6
;
#5-#9##5-#9#
/22

2
5#5#

%2727

2
19'41
9
'
4
#
%
&
#
%
&
4
&;&
;
4704
70
#./#
.
/
'44'4
4
$#6$
#6
/#.//
#
.
/
+
2#&&42
#
&
&
4
:

:
'2/
2/
'2/'2/
6'566'56
/06
5
99
5
9
9
.
&&
.
&
&

+
11
1
0
ψ
10
1
0
5
6126
1
2
'+0+6'
+
0
+
6
+0+6+
0
+
6
%0()%
0
(
)
.1#&.
1
#
&
&456&
4
5
6
7
5$5
$
#%6+8'#
%
6
+
8
'
5
6126
1
2
5#8'
5
#
8
'
%
0 .-
.
-
.-.
-
%
.+0-#%6.
+
0
-
#
%6
/
/
%
00
%
00
'
VJGTPGVV
J
G
T
P
G
V
*
7$7
$
1
2
/
+++
+
+
+
9 Installation
Installing Optional Modules
Use the following procedure to install Optional Modules.
1. Hold the top and bottom of the Optional Module to be installed, line up the Module with the left side of the guide rail inside the option slot, and then insert the Module straight in.
Note: The FG bar inside and on the bottom may be damaged if the Module is not inserted along the guide rail.
2. After the Optional Module is completely inserted, place your hand on the front of the Optional Module and press the Optional Module firmly until it mates with the Mounting Base connectors in the Unit. The front of the Optional Module and the tabs will be aligned if the Optional Module has been installed properly.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 21
9 Installation
;
#
5
-
#
9
#
2
5
#
2
19'4
88
/
2
%
2
7
:
+
2
#
&
&
4
'
2
/
'
2
/
6
'
5
6
/
0
6
5
6
12
'+
0+6
+0
+6
%0
() .1#& &45
6
75$
#
%6+8
'
5
612
5
#8'
12
'
V
J
G
T
P
G
V
%
0
%
0
%0
.
-
.
-
:
5
9
5
9
1
0
ψ
1
0
4
&
;
4
7
0
#
.
/
'
4
4
$
#
6
/
#
.
/
#
%
&
#
%
&
.
&
.
&
.
&
.
&
.
&
.
&
.
&
.
&
.
&
4
70
(
.
&
%
0
.
&
.
&
.
&
.
&
.&
.
&
/
1&'
.
+
1
+
%
0
*
7$
;#5-#9#
25#
219'4
88
/2
%27
:
+2#&&4
'2/ '2/
6'56 /06
5612
'+0+6
+0+6 %0() .1#& &456
75$
#%6+8'
5612 5#8'
12
'VJGTPGV
%0
%0
%0
%0
.- .-
:
59
59
10
ψ10
4&; 470 #./ '44 $#6
/#./
#
%
&
#
%
&
.&
.&
.&
.+1
.+1
.&
.&
.&
.&
.&
.&
*7$
3. Place the hole on the bottom of the panel of the Optional Module onto the tab on the bottom of the Unit. Next, hook the hole at the top of the panel of the Optional Module onto the tab on the Unit.
5#
2
&;
#5-#9#
19'4
88
470 #./ '44 $#6
/#./
27


2#&&4
612
2/
9
'+0+6
'2/
+0+6
6'56
%0()
/06
.1#& &456
10
ψ
#%6+8'
612
5#8'
VJGTPGV
-
-
0
+1
&
&
&
&
&
&
&
&
9
7$
&
70
&
0
&
&
&
&
&
1&'
0
This completes the installation proce dure.
Note: Always use Option Covers (model: JEPMC-OP2300) to c over unused slots.
Replacing and Adding Optional Modules
Use the following procedure to replace or add Optional Modules.
Note: Always create a backup before replacing o r adding Optional Mo dules.
Use the Web Server to save the Application program image as an Archive.Zip.
1. Turn OFF the power supply and disconnect all cables from the MP3200iec.
2. Remove the tool from Base Unit.
22 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
9 Installation
;
#5-#9##
5
-
#9
#
2
5#5
#
2
19'41
9
'
4
88
8
8
/
22
%
272
7
:

+
2#&&42
#
&
&
4
'
2/
2
/
'2/'
2
/
6'566
'
5
6
/06/
0
6
5
6126
1
2
'+0+6'
+
0
+
6
+0+6+
0
+
6
%0()%0
(
)
.1#&.
1
#
&
&456&
4
5
6
75$5$
#%6+8'#%6+8'
5612612 5#8'5#8
'
12
*
7$7$
'VJGTPGVVJGT
PGV
%0
%
00
%
0
0
%00
.-- .--
:

5
99
5
99
1
0
1
0
4
&;&
;
4704
7
0
#./#
.
/
'44'
4
4
$#6$
#
6
/#.//
#
.
/
#
%
&
#
%
&
.+1+
1

.+1
+1
.
&&
.
&&
.
&&
.
&&
/
1&'
1
&
'
+
1
1
.
&&
.
&&
.
&&
.
&&
4
707
0
(
7
%
00
3. Insert the protruding part of the tool into the slot on top of the Optional Module panel to unhook the tab. Unhook the bottom tab in the same way.
NOTICE: Use the same method to remove the Option Cover from an unused slot before adding an Optional Module.
25#
;#5-#9#
4.;1
/2
4&; 470
219'4
#
#
$
$
%
%
:
: +2#&&4
5612
'2/
59
59
'+0+6
'2/
+0+6
6'56
%0()
/06
.1#&
10
&456
75$
ψ10
#%6+8'
5612 5#8'
12
'VJGTPGV
%0
.-
/+++
.-
%0
#./ '44 $#6
/#./
%27
.+1
.&
.&
.&
.&
/1&'
.+1
.&
.&
.&
.&
.&
.&
.&
.&
.&
.&
.&
.&
/1&'
+1
+1
4. Pull the top of the Optional Module panel toward you and remove it. A notch on the Optional Module will be visible from the gap of the panel. Hook the round knob on the tool into the notch in the Optional Module.
5. Hold the center of the tool, and turn it around the round knob while pushing it toward the back to disconnect the Module from the Mounting Base connectors. Then, pull the Module forward.
25#
/2
;#5-#9#
219'4
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 23
0&;&
4&; 470 #./ '44 $#6
/#./
%27

:

:
+2#&&4
612
5
'
+0+6
59
59
'+0+6
'
+0+6
+0+6
6
'56
%0()
/
06
.1#&
1
0
&456
1
0
7
5$
#
%6+8'
5
612
5
#8'
1
(
.+1
.&
.&
.&
.&
1&'
/
.+1
(7
.&
470
%0
.&
.&
.&
1
+
1
+
9 Installation
CAUTION
4
.
;
17
6
;
#5
-#
9#
/
2
2
5
#
%
27

2
1
9
'
4
#
%
&
#
%
&
4
&
;
470
#
.
/
'4
4
$
#
6
/
#
.
/
+
2
#&&4
:
:
'
2/
'
2
/
6
'
5
6 /0
6
5
9
5
9
.
&
.
&
+
1
10
ψ
10
5
61
2
'+
0
+
6
+
0
+6
%
0(
)
.
1
#
&
&
4
5
6
7
5$
#
%
6
+
8
'
5
6
1
2
5
#
8
'
%0
.-
.
-
%
.
+
0
-
#%
6
/
%
0
%
0
'
V
J
G
T
P
G
V
*
7
$
1
2
/
+
+
+
6. Hold the Optional Module at the top and bottom and pull it straight out. Hold the edges of the Module and avoid touching the components on the Module.
&
&; 470
#./
2
'44 $#6
5#
#5-#9#
19'4
/#./
27
9
612
2#&&4
9
'+0+6
+0+6
2/
%0()
'2/
.1#&
6'56
&456
/06
5$
#%6+8'
612 5#8'
.;176
Note: Put the Module that you removed into the bag that was supplied when you purchased it and store the Module in this bag.
Installing and Replacing the Battery in the CPU
Battery Installation
&
1
10
VJGTPGV
7$
.-
+++
.-
0
0
.+0-#%6
/
This Battery provides backup power for the SRAM data when the power supply to the MP3200iec Series CPU Unit is turned OFF. The Battery provides backup power for the following data.
• Alarm history
• Calendar
• Retain Variables
Note: One Battery is provided with the CPU Unit. The Battery is not connected when the Unit is delivered.
Battery Replacement
When the total power OFF time exceeds 1 year, the voltage of the Battery will drop, and the BAT indicator on the CPU Unit will light.
Replace the Battery within 2 weeks of when the BAT indicator first lights.
Battery Replacement Procedure
Allow only qualified personnel trained in safety procedures to replace the Battery. Incorrect Battery replacement may result in electric shock. Als o, ma chin e mal function may occur, possibly r esul t ing in i njur y or machine damage.
Replace the Battery only while power is supplied to the Basic Unit. Replacing the Battery while the power supply to the Basic Unit is turned OFF may result in loss of the data stored in memory in the Unit.
Do not touch the electrodes of the Battery. Static electricity may damage the electrodes.
The Basic Module con tains a lithium battery. When you replace the Battery, separate the used Battery from
normal waste and dispose of it according to all local ordinances.
1. Back up the programs and data stored in the Basic Unit.
Note: The backup can be used to recover the data if the data accide ntally gets deleted during Battery replacement.
2. Confirm that the RDY indicato r on the CPU Unit is lit.
24 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
9 Installation
LiTHIUM
Black lead
Red lead
3. Open the battery holder on the bottom of the CPU Unit.
4. Disconnect the lead connector of the Battery from the connector on the CPU Unit, and remove the Battery from the battery holder.
5. Insert the Replacement Battery into the battery holder, and securely connect the lead connector of the Battery to the connector of the CPU Unit.
Connector on CPU Unit
Battery lead connector
Battery
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 25
Battery holder
9 Installation
Press in.
6. Press the connector back into the CPU Unit.
7. Hold the connector, and while pressing it toward the CPU Unit’s internal circuit board (the board on the side of the clamp), move the Battery and the battery holder into the CPU Unit.
Note: If this procedure is not follow ed, th e battery le ads may b e pinched b etween the Batte ry and the circuit boa rd, caus ing stress o n the
leads. If that occurs, the battery ho ld er will bulge after step 8 of the procedure.
Hold the connector and press in.
2 battery leads
8. Close the battery holder and confirm that the BAT indicator on the CPU Unit is not lit. This completes Battery replacement.
Clamp
CPU Unit internal circuit board (on the side of the clamp)
Move the Battery.
26 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
10 DIP Switch Settings
SW
2
TEST
NO
MNT
E-PM0 E-PM1
10 DIP Switch Setti ng s
The DIP switch settings are only referenced wh en the po wer is in itially t urned ON with t he exceptio n of the ST OP switc h, which will immediately STOP IEC Application program execution.
SW1
STOP
E_INIT
INIT
CNFG
LOAD
D-RST
Switch Name Setting Operating Mode Default Details
S1-6 STOP
S1-5 E_INIT
S1-4 INIT
S1-3 CNFG
S1-2 LOAD
S1-1 D-RST
ON User program stopped
OFF User program running
ON Use default IP Address
OFF
ON
OFF
ON Self-configuration Mode
OFF Normal Operation
ON USB Mode
OFF Internal FLASH Mode
ON System Use
OFF Normal Operation
Use IP Address set in the
Configuration
For diagnostic
purposes only
For diagnostic
purposes only
SW
1
NO
OFF Stops the user program execution.
OFF
OFF
OFF
OFF
OFF Not used.
When ON, overrides E thernet configuration according to
Table A.
The controller uses the fixed, default configuration. For diagnostics only. Turning this switch ON may help restore communications to the controller if the configuration is corrupted or invalid.
The controller creates Axes and I/O for all connected devices. (Auto-c on figu r ation)
When ON, load either the user project or firmware from t he USB thumb drive. See Table B for details.
SW2
Sets the Ethernet port condition and other operating conditions. The switch setting is read only when the module is first turned ON.
Switch Switch Name State Operation Mode Default Description
When E-INIT is ON and E-PM0 is ON, overrides Ethernet configuration according to
T able A.
When E-INIT is ON and E-PM1 is ON, overrides Ethernet configuration according to
T able A.
When ON, the IP address is scrolled across the seven segment display.
When ON, controller starts up in supervisor mode. In this mode MECHATROLINK III, PLC, Modbus/T CP and Ethernet/IP do not start. The controller firmware ca n be updated, and clearing DOS FS alarms will repair the DOS FS.
S2-4 E-PM0
S2-3 E-PM1
S2-2 TEST
S2-1 MNT
ON
OFF
ON
OFF
ON Display IP Address
OFF Normal Operation
ON Maintenance Mode
OFF Normal Operation
Use Default IP Address according to
Table A
Use Default IP Address according to
Table A
OFF
OFF
OFF
OFF
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 27
Loading...
+ 67 hidden pages