To properly use the product, read this manual
thoroughly and retain for easy reference, inspection,
and maintenance. Ensure the end user receives this manual.
4 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 5
Nevertheless, Yaskawa assumes no responsibility for errors or omissions. Neither is any liability assumed for damages
resulting from the use of the information contained in this publication.
5 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 6
6 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 7
1Definition of Terms
+
+
+
Power
Supply Unit
CPU Unit
Power
Supply Unit
CPU UnitBase Unit
This section defines terms that have specific meanings in this manual.
Basic Units
“Basic Unit” is a collective term that refers to the three Units in the foll owing table.
Unit NamePrimary Function
Power Supply Unit
CPU Unit
Base UnitUsed to mount Optional Modules.
The Basic Units are typically connected as shown in the following examples.
Supplies the power that is needed for the operation of the Units that are connected to each other and to
any Optional Modules that ar e conn ect ed in the Contro ller.
Stores the module definitions and programs, and interprets the programs. The CPU Unit also controls
the Optional Modules.
1 Definition of Terms
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 5
Page 8
2 System Configuration Example
2System Configuration Example
The following figure shows a typical system configuration.
MotionWorks IEC version
2.4 or higher
Ethernet communications cables
MP3200iec
RLYOUT
components
connector cable
24-VDC power
supply, AC power
supply, or status
monitoring device
Power supply cable
24-VDC power
supply or AC
power supply
Another PLC
Ethernet
Battery
MECHATROLINK-III
Front cover
for unused slot
PC
Ethernet
MECHATROLINK-III Cable
Optional Modules
I/O Modules
IO-02
L
LIO-01
LIO-04
LIO-05
LIO-06
AI-01
DO-01
AO-01
Communications Modules
218IF-Y1
External outputs
External inputs
RS-232C
Ethernet
SERVOPACK with
MECHATROLINK-III
Communications
Servomotor
Servomotor
Servomotor
I/O Module with
MECHATROLINK-
Communications
I/O
III
Up to 62 stations, including I/O
6YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
PMC-U-MP32016CPU, MP3200iec, 16 axis
PMC-U-MP32032CPU, MP3200iec, 32 axis
PMC-U-MP32062CPU, MP3200iec, 62 axis
JEPMC-PSA3012-EPOWER SUPPLY, 100V/200V, MP3200
JEPMC-PSD3012-EPOWER SUPPLY, 24VDC, MP3200
JEPMC-BUB3003-EBASE UNIT, 3 SLOTS, MP3200
JEPMC-BUB3005-EBASE UNIT, 5 SLOTS, MP3200
JEPMC-BUB3008-EBASE UNIT, 8 SLOTS, MP3200
JAPMC-AN2300Analog Inputs (AI-01)
JAPMC-AN2310-EAnalog Outputs (AO-01)
JAPMC-DO2300Digital Output Modu le (DO-01)
JAPMC-IO2300-E Digital I/O Module (LIO-01)
JAPMC-IO2301-EDigital I/O Module (LIO-02)
JAPMC-IO2303Digital I/O Module (LIO-04)
JAPMC-IO2304Digital I/O Module (LIO-05)
JAPMC-IO2305-EDigital Multi-Function I/O Module (LIO-06)
JAPMC-CM2301-EEthernet & RS232C Communication (218IF-Y1)
JEPMC-MT2000-EHUB, MECHATROLINK-III NETWORK, 8 SLAVE PORTS
JEPMC-MT2020-EADAPTER, ETHERNET TO MECHATROLINK
JEPMC-MTD2310-EI/O MODULE, MECHATROLINK NETWORK, 64 IN, 64 OUT
JEPMC-MTA2900-EANALOG MODULE, MECHAT ROLINK NETWORK, 8 INPUT
JEPMC-MTA2910-EANALOG MODULE, MECHATROLINK NETWORK, 4 OUTPUT
JEPMC-W6012-A2-EMECHATROLINK-III CABLE, 0.2 M
JEPMC-W6012-A5-EMECHATROLINK-III CABLE, 0.5 M
JEPMC-W6012-01-EMECHATROLINK-III CABLE, 1.0 M
JEPMC-W6012-02-EMECHATROLINK-III CABLE, 2.0 M
JEPMC-W6012-03-EMECHATROLINK-III CABLE, 3.0 M
JEPMC-W6012-04-EMECHATROLINK-III CABLE, 4.0 M
JEPMC-W6012-05-EMECHATROLINK-III CABLE, 5.0 M
JEPMC-W6012-10-EMECHATROLINK-III CABLE, 10 M
JEPMC-W6012-20-EMECHATROLINK-III CABLE, 20 M
JEPMC-W6012-30-EMECHATROLINK-III CABLE, 30 M
JEPMC-W6012-40-EMECHATROLINK-III CABLE, 40 M
JEPMC-W6012-50-EMECHATROLINK-III CABLE, 50 M
JEPMC-BA3001Replacement Battery
JEPMC-OP2300Option Slot Cover
JEPMC-OP3001Replacement Power Supply Side Cover
JEPMC-OP3002Replacement Option Base Side Cover
3 Component Part Numbers
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 7
Page 10
4 Power Supply Units
Indicators
RLYOUT connector
Power connector
Unit connector
4Power Supply Uni ts
The Power Supply Unit supplies the connected Units and Optional Modules with the power needed to operate. There are
two Power Supply Units available: an AC Power Supply Unit and a DC Power Supply Unit.
This section shows the appearance and part names of the Power Supply Unit and describes the indicators and connectors.
Appearance and Part Names
The following figure shows the appearance of the Power Supply Unit and the part names.
Indicators
These indicators show the load on the Power Supply Unit.
Output Current8.9 A or less9.0 to 11.4 A11.5 to 13.9 A
Load
Green
Appendix
Indicator
<1> Reduce the number of Optional Mo dules that are connected.
Note: z: Lit, {: Not lit.
Yellow{zz{
Red{{z{
Normal: Within power supply
capacity
zzz{
<1>
Normal: Maximum power
supply capacity
14.0 A or more
Error: Over power supply
capacity
<1>
8YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 11
Connectors
The Power Supply Unit has three connectors: RLYOUT, power supply, and Unit connectors.
RLYOUT Connector
This connector outputs the operating status of the CPU Unit.
Model: 734-302
Pin Assignme n ts
No.Signal LabelDescription
1OUT
2OUT
Power Connector
Normal operation: Circuit closed.
Error: Circuit open.
Connect the power supply to this connector.
4 Power Supply Units
TypeModelColor
AC Power Supply Unit721-203/026-304Black
DC Power Supply Unit721-203/026-000White
Pin Assignments: AC Power Supply Unit
Pin No.Signal LabelDescription
3ACAC input
2ACAC input
1FGConnects to the frame ground. (Ground to 100 W max.)
Pin Assignments: DC Power Supply Unit
Pin No.Signal LabelDescription
324 VDCPower input wire for 24 VDC
20 VDCPower input wire for 0 VDC
1FGConnects to the frame gro und. (Ground to 100 W max.)
DC Power Supply UnitAC Power Supply Unit
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 9
Page 12
5 Power Supply Unit Specifications
5Power Supply Unit Specifications
The specifications of the Power Supply Unit are given in the following table.
Input Current4.0 A max. (at rated input/output)5.0 A max. (at rated input/output)
Inrush Current
Allowable Momentary
Power Loss Time
Rated Voltage5.15 V
Rated Current12.0 A
Output Current Range0 to 12.0 A0.2 to 12.0 A
Constant Voltage
Accuracy
85 to 132 VAC or 170 to 276 VAC19.2 to 28.8 VDC
47 to 63 Hz-
25 A, 10 ms max. (fully discharged, 132-VAC
input, rated output)
50 A, 10 ms max. (fully discharged, 276-VAC
input, rated output)
20 ms1 ms
5.15 V ±2% max. (5.05 t o 5.25 V)
If the Power Supply Unit is mounted on the Main Rack, this output functions as normally closed
contacts that are synchronized with the status of the CPU Unit.
• Normal operation: Circuit closed.
• Error: Circuit open.
Contact Ratings
AC Power Supply UnitDC Power Supply Unit
Specification
50 A, 10 ms max. (fully discharged,
28.8-VDC input, rated output)
Status Output
Connectors
Indicators
Input Conditions
Inrush Current
Rise Time
Drop Time
Leakage Current
Efficiency
Input VoltageCurrent Capacity
24 VDC
125 VAC
POWER: Power supply connector
RLY OUT: Relay contact connector
POWER
Refer to Indicators on page 12.
For Cold Start
50 A within 10 ms (fully discharged status)
275-VAC input, rated output
60,000 ms max. (The maximum time for the output control signals to maintain the specified timing
when the primary voltage rises linearly.)
60,000 ms max. (The maximum time that the controls, such as the power failure sequence, can be
maintained when the primary voltage drops linearly.)
276 VAC 61 Hz: 0.5 mA max.
132 VAC 61 Hz: 0.25 mA max.
70% minimum (for rated input voltage and
rated load)
0.5 A (resistive load)
0.25 A (inductive l oad)
0.4 A (resistive load)
0.2 A (inductive load)
For Cold Start
(Through rate at input voltage value increase from
10% to 90% is at 10 ms min.)
50 A within 10 ms (fully discharged status)
28.8-VDC input, rated output
65% minimum (for rat e d input voltage and ra ted
load)
10YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 13
5 Power Supply Unit Specifications
Protection
Safety
Status
Output
Power Sequences
Dielectric
Strength
Insulation
Resistance
(Measured at
500 VDC.)
External Wiring
Connector
Terminals
Connector Cable
Hot
Swapping
Item
AC Power Supply UnitDC Power Supply Unit
Specification
Low Input Protection
(Power Fail Detection
55 to 75 VAC or 150 VAC max.15.8 to 17.8 VDC
Level)
Overcurrent Protection
For rated curren t (12 A), the protection operates at 14.0 A min. (typical).
(The detection range is 13.0 to 15.0 A.)
Overvoltage ProtectionOperates at 5.75 to 6.75 V.
Allowable Power Loss
Time
The output voltage fluctuation range is
maintained for a 20-ms 100% dip momenta ry
power loss.
The output voltage fluctuatio n range is ma intained
for a 1-ms 100% dip momentary power loss.
Safety StandardsConforms to UL and CSA.
Fuse250 V/4 A250 V/6.3 A
Linked to the RDY indicator on the CPU Un it.
RDY indicator lit: Circuit closed.
RDY indicator not lit: Circuit open.
Contact Ratings
NO Contact Output (RLY
OUT)
Power ON
Power OFF
Input VoltageCurrent Capacity
24 VDC
125 VAC
0.5 A (resistive load)
0.25 A (inductive load)
0.4 A (resistive load)
0.2 A (inductive load)
AC ON - 5-V rise in 1 s max.
Output rise - POK signal in 0 s min.
AC OFF - POK signal for 20 ms min.
POK signal - 5-V drop in 2 ms min.
DC ON - 5-V rise in 1 s max.
Output rise - POK signal in 0 s min.
DC OFF - POK signal for 1 ms min.
POK signal - 5-V drop in 2 ms min.
Between primary and secondary sides: 1,500 VAC for 1 minute
Between primary side and FG (ground): 1,500 VAC for 1 minute
Between secondary s ide and FG (ground): 50 0 VAC for 1 minute
Between RLYOUT and primary side: 1,500 VAC for 1 minute
Between RLYOUT and secondary side: 1,500 VAC for 1 minute
Between primary and secondary sides: 10 MΩ min .
Between primary side and FG (ground): 10 MΩ min.
Between secondary s ide and FG (ground): 100 MΩ min.
Between RLYOUT and primary side: 100 MΩ min.
Between RLYOUT and secondary side: 100 MΩ min.
External Power Supply
Terminals
Protective Ground
Terminal
AC, AC0 and 24 VDC
FG
RLY OUTRLYOUT
External Power Supply
Terminals (Twisted Pair)
AWG28 to AWG13 (0.08 to 2.6 mm
2
)
RLY OUT Connector Cable: AWG28 to AWG14 (0.08 to 2.0 mm2)
Not supported.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 11
Page 14
5 Power Supply Unit Specifications
Output Current (iout (typical)) POWER (Green) (No Label) (Yellow) (No Label) (Red)
i out ≤ 8.9 Az{{
9.0 A ≤ iout ≤ 11.4 Azz{
11.5 A ≤ iou t ≤ 13 .9 Azzz
14.0 A ≤ iout (OCP activation){{{
Item
POWER (green): Lights when the power is ON on the secondary side.
(No label) (yellow): Lights when the Overcurrent Warning 1 Status Output is ON.
(No label) (red): Lights when the Overcurrent Warning 2 Status Output is ON.
Indicators
z: Lit {: Not lit.
External
Dimensions
Weight350 g
Width: 60 mm, Height: 130 mm, De pth: 137 mm
Specification
AC Power Supply UnitDC Power Supply Unit
12 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 15
6 CPU Specifications
6CPU Specifications
The hardware specifications of the CPU Unit are given in the following table.
ItemSpecification
ModelPMC-U-MP320xx
AbbreviationMP3200iec
Flash MemoryCapacity: 40 MB (32 MB of user memory)
SDRAMCapacity: 128 MB
SRAMCapa city: 8 MB (ba ttery ba c kup)
CalendarSeconds, minutes, hour, day, week, month, year, day of week, and timing (battery backup)
Ethernet10Base-T or 100Base-TX x 2 ports (hub)
MECHATROLINKMECHATROLINK-III: 1 circuit with 2 ports
USB
Indicators and D i s plays
Switches
USB 2.0 Type A host, 1 port
Compatible devices: USB storage
Seven-segment display
Status indicators
USB status indicator
MECHATROLINK-III status indicators
Ethernet status indicators
DIP switch: Mode switch 1
DIP switch: Mode switch 2
Rotary switches
STOP/SAVE switch. Refer to DIP Switch Settings on page 27 for detailed switch information.
CPU Communications Specifications
The specifications of th e Communications Protocols built into the CPU Unit are given in the following table.
ProtocolModeDetail
Modbus TCP
Ethernet/IP
OPCread/write
Custom Protocoln/a
MP3200iec as Master (Client)Maximum Number of Data Blocks = 20
MP3200iec as Slave (Server)1000 registers in, 1000 registers out, 256 coils in, 256 coils out
MP3200iec as Master (Scanner)Maximum Number of Data Blocks = 100
MP3200iec as Slave (Adapter)
Total 16 instances in, 16 instances out, arranged as 3 instances of 256
bytes, 3 instances of 128 bytes, and 10 inst ances of 496 bytes.
Any Global variable can be configured, requires OPC Server running
on PC
Use the YDeviceComm firmware library to cre ate a custom
communication pro tocol.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 13
Page 16
7 CPU External Appearance and Indicators
7CPU External Appearance and Indicators
External Appearance
Indicators (LEDs)
MECHATROLINK-III connector CN1
MECHATROLINK-III connector CN2
Indicators
The following table describes the indicators that show the operating status and error information.
IndicatorIndicator NameColorMeaning When Lit
MECHATROLINK-III communications are established as a slave (i.e., the CONNECT
command is ON).
CN
LK1
LK2
CNGreen
LK1GreenPort 1 is performing MECHATROLINK-III communications.
LK2GreenPort 2 is performing MECHATROLINK-III communications.
14YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 17
8 Base Unit Installation and Operating Conditions
8Base Unit Installation and Operating Conditions
This section describes the specifications of the MP3200iec Series Machine Controllers.
Install the MP3200iec Series Controllers in an environment with the following conditions.
Environmental Conditions
ItemSpecification
Ambient Operating Temperature0 to 55°C (CPU-03: 0 to 50°C)
Ambient Storage Temperature-25 to 85°C
Ambient Operating Humidity30% to 95% RH (with no condensation)
Ambient Storage Humidity5% to 95% RH (with no condensation)
Pollution DegreeConforms to JIS B 3502 Pollution Degree 2.
Corrosive GasesThere must be no combustible or corrosive gases.
Operating Altitude2,000 m max.
Control Panel Cooling Method
The components that are used in the Machine Controller require the ambient operating temperature to be between 0 and
55°C. Use one of the methods described below to ensure adequate cooling in the control panel.
Note: If the ambient temperature exceeds 50°C, we recommend forced-ai r cooling.
Control Panels with Natural Cooling
• Do not mount the Machine Controller at the top of the control panel, where th e hot air that is genera ted inside the panel
collects.
• Leave sufficient spac e above and below the Units , and maintain ade quate dist ances from oth er devices, ca ble ducts, and
other objects to ensure suitable air circulation.
• Do not mount the Controller in any direction other than the specified direction.
• Do not mount the Controller on top of any device that generates a significant amount of heat.
• Do not subject the Controller to direct sunlight.
Control Panels with Forced-air Cooling
Use one of the following methods to ensure 0.03 m3/min average airflow below the CP U Unit.
• Forced draft method (A fan or a similar device is used to circulate the air in the interior and the exterior of the panel.)
• Forced circulation method (A fan or a similar device is mounted to the airtight panel to circulate the air inside.)
Note: Use the following guideline when selecting the fan: CPU Unit’s resistance to air flow: 6 x 106 (N×s2/m8)
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 15
Page 18
8 Base Unit Installation and Operating Conditions
Fan
CPU Unit’s internal resistance to
air flow: 6×10
6
(N⋅s2/m8)
40 mm min.
30 mm min.
Average airflow:
0.03 m
Mechanical Operating Conditions
ItemSpecification
Conforms to JIS B 3502.
Vibration Resistance
10 Hz ≤ f < 57 Hz with vibration amplitude of 0.075 mm
57 Hz ≤ f ≤ 150 Hz with fixed acceleration of 9.8 m/s
10 sweeps each in X, Y, Z directions (sweep: 1 octave/min)
Shock Resist ance
Electrical Operating Conditions
Conforms to JIS B 3502.
Peak acceleration of 147 m/s
ItemSpecification
Conforms to EN 61000-6- 2 and EN 55011 (Group 1 Class A).
Power supply noise (FT noise): 2 kV min. for 1 minute
Noise Resistance
Radiation noise (FT noise): 1 kV min., for 1 minute
Ground noise (impul se noise): ±1 kV min., for 10 minutes
Electrostatic noise (conducted): ±4 kV min ., 10 times
3
/min
2
2
twice for 11 ms each in the X, Y, and Z directions
30 mm min.
40 mm min.
Ground InformationGround to 100
ȍ
max.
16 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 19
9Installation
Screw Mounting Attachment
You can use either of the following methods to install an MP3200iec Series Controller.
•Screw mounting
• DIN rail mounting
Screw Mounting
You can install the Unit by using the Screw Mounting Attachment.
Note: You can install the Unit by using the Screw Mounting Attachment.
• JEPMC-OP3001
This Attachment is provided with the Power Supply Unit. It can be installed on the PMC-U-MP320**.
• JEPMC-OP3002
This Attachment is provided with the MBU-B03, MBU-B05, and MBU-B08. It can be purchased separately.
The installation procedure is as follows:
1. Attach the Screw Mounting Attachment to the right end of the Controller.
9 Installation
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 17
Page 20
9 Installation
2. Use screws to secure the 4 places shown in the following figure.
Note: 1. Recommended screws: M4 x 14 mm min.
2. Use a screwdriver wit h a shaft that is at least 13 cm long.
18 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 21
Lock release position
Locking position
DIN Rail Mounting
Carefully line up the DIN rail locks wit h the locking positions.
9 Installation
Note: Removal
You can remove t he Controller by revers ing the order of the mo unting procedure.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 19
Page 22
9 Installation
Connecting the CPU
Note: Before you connect the CPU, install the Battery. Refer to Installing and Replacing the Battery in the CPU on page 24.
1. Remove the rubber cap from the connector on the Power Supply Unit.
Note:
• When the connector is not in use, always cover it with the rubber cap.
• The left-side cap is marked with an L, and the right-side cap is marked with an R.
2. Connect the Power Supply Unit and the CPU Unit from left to right in this order.
20 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 23
3. Secure the connection by locking the slide locks at both the top and the bottom.
4
.;176
.
;17
6
;
#5-#9##5-#9#
/22
2
5#5#
%2727
2
19'41
9
'
4
#
%
&
#
%
&
4
&;&
;
4704
70
#./#
.
/
'44'4
4
$#6$
#6
/#.//
#
.
/
+
2#&&42
#
&
&
4
:
:
'2/
2/
'2/'2/
6'566'56
/06
5
99
5
9
9
.
&&
.
&
&
+
11
1
0
ψ
10
1
0
5
6126
1
2
'+0+6'
+
0
+
6
+0+6+
0
+
6
%0()%
0
(
)
.1#&.
1
#
&
&456&
4
5
6
7
5$5
$
#%6+8'#
%
6
+
8
'
5
6126
1
2
5#8'
5
#
8
'
%
0
.-
.
-
.-.
-
%
.+0-#%6.
+
0
-
#
%6
/
/
%
00
%
00
'
VJGTPGVV
J
G
T
P
G
V
*
7$7
$
1
2
/
+++
+
+
+
9 Installation
Installing Optional Modules
Use the following procedure to install Optional Modules.
1. Hold the top and bottom of the Optional Module to be installed, line up the Module with the left side of the guide rail
inside the option slot, and then insert the Module straight in.
Note: The FG bar inside and on the bottom may be damaged if the Module is not inserted along the guide rail.
2. After the Optional Module is completely inserted, place your hand on the front of the Optional Module and press the
Optional Module firmly until it mates with the Mounting Base connectors in the Unit. The front of the Optional
Module and the tabs will be aligned if the Optional Module has been installed properly.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 21
Page 24
9 Installation
;
#
5
-
#
9
#
2
5
#
2
19'4
88
/
2
%
2
7
:
+
2
#
&
&
4
'
2
/
'
2
/
6
'
5
6
/
0
6
5
6
12
'+
0+6
+0
+6
%0
()
.1#&
&45
6
75$
#
%6+8
'
5
612
5
#8'
12
'
V
J
G
T
P
G
V
%
0
%
0
%0
.
-
.
-
:
5
9
5
9
1
0
ψ
1
0
4
&
;
4
7
0
#
.
/
'
4
4
$
#
6
/
#
.
/
#
%
&
#
%
&
.
&
.
&
.
&
.
&
.
&
.
&
.
&
.
&
.
&
4
70
(
.
&
%
0
.
&
.
&
.
&
.
&
.&
.
&
/
1&'
.
+
1
+
%
0
*
7$
;#5-#9#
25#
219'4
88
/2
%27
:
+2#&&4
'2/
'2/
6'56
/06
5612
'+0+6
+0+6
%0()
.1#&
&456
75$
#%6+8'
5612
5#8'
12
'VJGTPGV
%0
%0
%0
%0
.-
.-
:
59
59
10
ψ10
4&;
470
#./
'44
$#6
/#./
#
%
&
#
%
&
.&
.&
.&
.+1
.+1
.&
.&
.&
.&
.&
.&
*7$
3. Place the hole on the bottom of the panel of the Optional Module onto the tab on the bottom of the Unit. Next, hook the
hole at the top of the panel of the Optional Module onto the tab on the Unit.
5#
2
&;
#5-#9#
19'4
88
470
#./
'44
$#6
/#./
27
2#&&4
612
2/
9
'+0+6
'2/
+0+6
6'56
%0()
/06
.1#&
&456
10
ψ
#%6+8'
612
5#8'
VJGTPGV
-
-
0
+1
&
&
&
&
&
&
&
&
9
7$
&
70
&
0
&
&
&
&
&
1&'
0
This completes the installation proce dure.
Note: Always use Option Covers (model: JEPMC-OP2300) to c over unused slots.
Replacing and Adding Optional Modules
Use the following procedure to replace or add Optional Modules.
Note: Always create a backup before replacing o r adding Optional Mo dules.
Use the Web Server to save the Application program image as an Archive.Zip.
1. Turn OFF the power supply and disconnect all cables from the MP3200iec.
2. Remove the tool from Base Unit.
22 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 25
9 Installation
;
#5-#9##
5
-
#9
#
2
5#5
#
2
19'41
9
'
4
88
8
8
/
22
%
272
7
:
+
2#&&42
#
&
&
4
'
2/
2
/
'2/'
2
/
6'566
'
5
6
/06/
0
6
5
6126
1
2
'+0+6'
+
0
+
6
+0+6+
0
+
6
%0()%0
(
)
.1#&.
1
#
&
&456&
4
5
6
75$5$
#%6+8'#%6+8'
5612612
5#8'5#8
'
12
*
7$7$
'VJGTPGVVJGT
PGV
%0
%
00
%
0
0
%00
.--
.--
:
5
99
5
99
1
0
1
0
4
&;&
;
4704
7
0
#./#
.
/
'44'
4
4
$#6$
#
6
/#.//
#
.
/
#
%
&
#
%
&
.+1+
1
.+1
+1
.
&&
.
&&
.
&&
.
&&
/
1&'
1
&
'
+
1
1
.
&&
.
&&
.
&&
.
&&
4
707
0
(
7
%
00
3. Insert the protruding part of the tool into the slot on top of the Optional Module panel to unhook the tab.
Unhook the bottom tab in the same way.
NOTICE: Use the same method to remove the Option Cover from an unused slot before adding an Optional Module.
25#
;#5-#9#
4.;1
/2
4&;
470
219'4
#
#
$
$
%
%
:
:
+2#&&4
5612
'2/
59
59
'+0+6
'2/
+0+6
6'56
%0()
/06
.1#&
10
&456
75$
ψ10
#%6+8'
5612
5#8'
12
'VJGTPGV
%0
.-
/+++
.-
%0
#./
'44
$#6
/#./
%27
.+1
.&
.&
.&
.&
/1&'
.+1
.&
.&
.&
.&
.&
.&
.&
.&
.&
.&
.&
.&
/1&'
+1
+1
4. Pull the top of the Optional Module panel toward you and remove it. A notch on the Optional Module will be visible
from the gap of the panel. Hook the round knob on the tool into the notch in the Optional Module.
5. Hold the center of the tool, and turn it around the round knob while pushing it toward the back to disconnect the
Module from the Mounting Base connectors. Then, pull the Module forward.
25#
/2
;#5-#9#
219'4
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 23
0&;&
4&;
470
#./
'44
$#6
/#./
%27
:
:
+2#&&4
612
5
'
+0+6
59
59
'+0+6
'
+0+6
+0+6
6
'56
%0()
/
06
.1#&
1
0
&456
1
0
7
5$
#
%6+8'
5
612
5
#8'
1
(
.+1
.&
.&
.&
.&
1&'
/
.+1
(7
.&
470
%0
.&
.&
.&
1
+
1
+
Page 26
9 Installation
CAUTION
4
.
;
17
6
;
#5
-#
9#
/
2
2
5
#
%
27
2
1
9
'
4
#
%
&
#
%
&
4
&
;
470
#
.
/
'4
4
$
#
6
/
#
.
/
+
2
#&&4
:
:
'
2/
'
2
/
6
'
5
6
/0
6
5
9
5
9
.
&
.
&
+
1
10
ψ
10
5
61
2
'+
0
+
6
+
0
+6
%
0(
)
.
1
#
&
&
4
5
6
7
5$
#
%
6
+
8
'
5
6
1
2
5
#
8
'
%0
.-
.
-
%
.
+
0
-
#%
6
/
%
0
%
0
'
V
J
G
T
P
G
V
*
7
$
1
2
/
+
+
+
6. Hold the Optional Module at the top and bottom and pull it straight out. Hold the edges of the Module and avoid
touching the components on the Module.
&
&;
470
#./
2
'44
$#6
5#
#5-#9#
19'4
/#./
27
9
612
2#&&4
9
'+0+6
+0+6
2/
%0()
'2/
.1#&
6'56
&456
/06
5$
#%6+8'
612
5#8'
.;176
Note: Put the Module that you removed into the bag that was supplied when you purchased it and store the Module in this bag.
Installing and Replacing the Battery in the CPU
Battery Installation
&
1
10
VJGTPGV
7$
.-
+++
.-
0
0
.+0-#%6
/
This Battery provides backup power for the SRAM data when the power supply to the MP3200iec Series CPU Unit is
turned OFF. The Battery provides backup power for the following data.
• Alarm history
• Calendar
• Retain Variables
Note: One Battery is provided with the CPU Unit. The Battery is not connected when the Unit is delivered.
Battery Replacement
When the total power OFF time exceeds 1 year, the voltage of the Battery will drop, and the BAT indicator on the CPU
Unit will light.
Replace the Battery within 2 weeks of when the BAT indicator first lights.
Battery Replacement Procedure
• Allow only qualified personnel trained in safety procedures to replace the Battery. Incorrect Battery
replacement may result in electric shock. Als o, ma chin e mal function may occur, possibly r esul t ing in i njur y or
machine damage.
• Replace the Battery only while power is supplied to the Basic Unit. Replacing the Battery while the power
supply to the Basic Unit is turned OFF may result in loss of the data stored in memory in the Unit.
• Do not touch the electrodes of the Battery. Static electricity may damage the electrodes.
• The Basic Module con tains a lithium battery. When you replace the Battery, separate the used Battery from
normal waste and dispose of it according to all local ordinances.
1. Back up the programs and data stored in the Basic Unit.
Note: The backup can be used to recover the data if the data accide ntally gets deleted during Battery replacement.
2. Confirm that the RDY indicato r on the CPU Unit is lit.
24 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 27
9 Installation
LiTHIUM
Black lead
Red lead
3. Open the battery holder on the bottom of the CPU Unit.
4. Disconnect the lead connector of the Battery from the connector on the CPU Unit, and remove the Battery from the
battery holder.
5. Insert the Replacement Battery into the battery holder, and securely connect the lead connector of the Battery to the
connector of the CPU Unit.
Connector on CPU Unit
Battery lead connector
Battery
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 25
Battery holder
Page 28
9 Installation
Press in.
6. Press the connector back into the CPU Unit.
7. Hold the connector, and while pressing it toward the CPU Unit’s internal circuit board (the board on the side of the
clamp), move the Battery and the battery holder into the CPU Unit.
Note: If this procedure is not follow ed, th e battery le ads may b e pinched b etween the Batte ry and the circuit boa rd, caus ing stress o n the
leads. If that occurs, the battery ho ld er will bulge after step 8 of the procedure.
Hold the connector
and press in.
2 battery leads
8. Close the battery holder and confirm that the BAT indicator on the CPU Unit is not lit.
This completes Battery replacement.
Clamp
CPU Unit internal circuit board
(on the side of the clamp)
Move the Battery.
26 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 29
10 DIP Switch Settings
SW
2
TEST
NO
MNT
E-PM0
E-PM1
10DIP Switch Setti ng s
The DIP switch settings are only referenced wh en the po wer is in itially t urned ON with t he exceptio n of the ST OP switc h,
which will immediately STOP IEC Application program execution.
SW1
STOP
E_INIT
INIT
CNFG
LOAD
D-RST
SwitchNameSettingOperating ModeDefaultDetails
S1-6STOP
S1-5E_INIT
S1-4INIT
S1-3CNFG
S1-2LOAD
S1-1D-RST
ONUser program stopped
OFFUser program running
ONUse default IP Address
OFF
ON
OFF
ONSelf-configuration Mode
OFFNormal Operation
ONUSB Mode
OFFInternal FLASH Mode
ONSystem Use
OFFNormal Operation
Use IP Address set in the
Configuration
For diagnostic
purposes only
For diagnostic
purposes only
SW
1
NO
OFFStops the user program execution.
OFF
OFF
OFF
OFF
OFFNot used.
When ON, overrides E thernet configuration according to
Table A.
The controller uses the fixed, default configuration.
For diagnostics only. Turning this switch ON may help
restore communications to the controller if the configuration
is corrupted or invalid.
The controller creates Axes and I/O for all connected
devices. (Auto-c on figu r ation)
When ON, load either the user project or firmware from t he
USB thumb drive. See Table B for details.
SW2
Sets the Ethernet port condition and other operating conditions.
The switch setting is read only when the module is first turned ON.
When E-INIT is ON and E-PM0 is ON,
overrides Ethernet configuration according to
T able A.
When E-INIT is ON and E-PM1 is ON,
overrides Ethernet configuration according to
T able A.
When ON, the IP address is scrolled across the
seven segment display.
When ON, controller starts up in supervisor
mode. In this mode MECHATROLINK III,
PLC, Modbus/T CP and Ethernet/IP do not
start. The controller firmware ca n be updated,
and clearing DOS FS alarms will repair the
DOS FS.
S2-4E-PM0
S2-3E-PM1
S2-2TEST
S2-1MNT
ON
OFF
ON
OFF
ONDisplay IP Address
OFFNormal Operation
ONMaintenance Mode
OFFNormal Operation
Use Default IP Address according to
Table A
Use Default IP Address according to
Table A
OFF
OFF
OFF
OFF
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 27
Page 30
10 DIP Switch Settings
Note: If the E-INIT switch is in the “ON” position when the controller is pow ered up , the IP addre ss of th e co ntroll er will be 19 2.16 8.1.1.
If the switch is in the “OFF” position at power on, then the IP address defined in the system configuration setup will be in effect.
E-INIT, E-PM0, E-PM1 and both Rotary Switches can override the Ethernet configuration. When E-INIT, E-PM0 and
E-PM1 are ON, ON, OFF, respectively, the upper nibble and lower nibbles of the last byte are given by the rotary
switches X16
Static ConfigurationOFFN/AN/A
192.168.1.1ONOFFOFF
192.168.1.RotarySwitchesONONOFF
DHCPONOFFON
1
and X160, respect i vely.
T able A Ethernet Overrides
E-INITE-PM0E-PM1
On startup, the controller will automatically load firmware or user projects based on the LOAD and MNT switches. The
USB thumb drive is not available in any other circumstances.
Table B Firmware and User Project Loading
LOADMNT
Load user project from USB thumb driv e.ONOFF
Install firmware and user project from USB thumb drive.ONON
28 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 31
11 LED Indicators
RDY
RUN
ALM
BAT
M-ALM
ERR
11LED Indicators
The following table shows the indicators that show the operating status of the controller and error information.
IndicatorColorStatus
RDYGreenLit during normal operation.
RUN GreenLit during execution of user program.
ALM RedLit/blinking when warning occurs.
ERRRed
BATRedLit during battery alarm.
M-ALMRedLit when a MECHATROLINK Communications Error occurs.
Seven Segment Display
The following situations use the seven segment display:
• Manufacturing: During programming the seven segment display outputs "FLASH...". When finished, the seven
segment display outputs "donE".
• Startup: If the controller cannot boot because of a bad firmware image check sum, the seven segment display outputs
"bOOt ERROR".
• IP Address: If the TEST switch is ON, then the seven segment display outputs the IP address.
• Firmware update: During programming the seven segment display outputs "FLASH...". When finished, the seven
segment display outputs "donE".
ON at initial power-up while firmware is loading. Turns off if
firmware is valid. Lit/blinking when malfunction occurs.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 29
Page 32
12 Self-Configuration
STOP
SUP
INIT
CNFG
MON
TEST
1. Turn OFF the power supply
Turn OFF the 24 VDC power supply of the MP3200Siec.
2. Set DIP Switches
Turn ON CNFG in the DIP switch (SW1) of the MP3200Siec.
ࠉࠉࠉ
3. Turn ON the power supply
Turn ON the 24 VDC power supply of the MP3200Siec.
4. Check the LED Indicators
Check that LED display of the MP3200Siec basic module is
changed as follows:
5. DIP switch resetting
Turn the CNFG DIP switch (SW1) of the MP3200Siec to OFF.
ࠉࠉࠉ
STOP
SUP
INIT
CNFG
MON
TEST
RDY
RUN
ALM
ERR
BAT
M-ALM
RDY
RUN
ALM
ERR
BAT
M-ALM
: Lit : Unlit
12Self-Configuration
DIP Switch
Self-Configuration after Adding Devices such as Servopacks
By performing the following operation, a definition for devices detected on the MECHATROLINK-III network is
created. Before performing the operation, turn ON the power supply for each network node.
MotionWorks IEC
The MotionWorks IEC (Express or Pro) configuration can detect the configuration and provide the user with
configuration choices . If a S tart Up Configu rati on was alre ady saved on the cont rolle r, the self-configure functi on will not
allow new devices to be discovered. In this case, add them offline manually first.
30YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 33
13 MECHATROLINK-III Specifications
13MECHATROLINK-III Specifications
The specifications of the MECHA TROLINK-III Network Master that is built into the CPU Unit are given in the following
table.
ItemSpecificationRemarks
Communications ASICJL-100Number of Communications Lines1-
MECHATROLINK
communications
settings
Number of Communications Ports
(Connectors)
Communications MethodM-IIIBaud Rate100 Mbps-
Communications Cycle
Number of Connected
Master
Stations
Message RelayingNot Supported.C2 MessagesNot Supported.RetriesSupported.0 to 4 retries
Asynchronous Setting of
High-speed Scan Cycle
and Communications
Cycle
2-
250 μs/0.5 ms/
1 ms/1.5 ms/2 ms/2.5 ms/3 ms/
3.5 ms/4 ms
62 stations -
Not supported.An alarm will occur if setting is attempted.
-
CPU Unit Specifications
ItemSpecification
CalendarBattery backup accurate to 1 minute of error per month.
Ethernet
M-III1981386-1 ×2 (TycoAMP)
USB
RS-232C
/422
ProtectionHardware watchdog timer (PLD): 0 to 510 ms (register setting)
Relay Output
Backup CircuitBattery: BR-1/2AA (Panasoni c), 3.0 V
ConnectorDUSB-ARA42-T11A-FA (DDK), type A connector
FunctionUSB 2.0 host, 3 sp eeds (HS/FS/LS), 1 port
ConnectorHDR-EC14LFDTN-SLE+ (HONDA)
SOUT, SIN, RTS, CTS, and DTR
9,600 to 115K bps, UART built into CPU Unit is used.
Contacts normally open for RUN status (RDY indicator lit), and OFF for WDT error status. The relay
is built into the Power Supply Unit.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 31
Page 34
14 MECHATROLINK-III Network Topologies
CPU Unit
No terminating resistor is required.
Up to 32 stations, including Servos and I/O
14MECHATROLINK-III Network To pologies
You can connect the MP3200iec Series Controller and drives or I/O with cascaded connections, star connections, or
mixed cascaded/star network topologies. The following figures show examples of these types of network topologies.
Cascaded Connection
Cascaded connections allow you to connect one or more series of slave stations from the CPU Unit MECHATROLINKIII ports. Regardless of whether a single MECHATROLINK-III port is used, as shown in , or two CPU Unit
MECHATROLINK-III ports are used, as shown in Figure 1, these are called cascaded connections.
Figure 1
Figure 1 Cascaded Connections Using Only One Port
Figure 2
CPU Unit
No terminating
resistor is
required.
Up to 32 Servo stations
Up to 62 stations, including I/O
Figure 2 Cascaded Connections Using Two Ports
Note: 1. Do not connect more than 32 stations up to the final slave station to any one CPU Unit port.
2. The maximum number of stations that you can connect with cascaded connections depends on the communications cycle. Refer to
Communications Cycle and the Number of Slave Stations on page 35.
No terminating
resistor is required.
32YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 35
14 MECHATROLINK-III Network Topologies
Hub Module
Hub Module
Star Connections
Star connections allow you to connect slave stations through Hub Modul es. Each port on a Hub Module connects to only
one slave station. You can also connect one additional Hub Module to the first Hub Module.
CPU Unit
Note: 1. Terminating resistors are not required.
2. The maximum number of stations that you can connect with star connections depends on the communications cycle. Refer to
Communications Cycle and the Number of Slave Stations on page 35.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 33
Page 36
14 MECHATROLINK-III Network Topologies
CPU Unit
No terminating
resistor is required.
No terminating
resistor is required.
Hub Module
Mixed Cascaded/Star Connections
You can combine both cascaded and star network topologies.
Note: 1. Do not connect more than 32 st ations to a single CPU Unit port, incl uding the Hub Modules.
2. The maximum number of stations that you can connect with a mixed cascaded/star connections depends on the communications cycle.
Refer to Communications Cycle and the Number of Slave Stations on page 35.
34 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 37
15 MECHATROLINK-III Synchronization between Modules
15MECHATROLINK-III Synchronization between Modules
Communications Cycle and the Number of Slave Stations
The relationship between the MECHATROLINK communications cycle and the number of slave stations is given in the
following tables.
Cascaded Connections
Communications
Cycle
125 μs1 to 3–
250 μs1 to 7–
500 μs1 to 12–
1 ms1 to 21–
1.5 ms1 to 27–
2 ms1 to 32–
3 ms1 to 38
4 ms1 to 62
Star Connections
Communications CycleNumber of Connected Stations
Number of Connected
Stations
If more than 32 stations are connected, two ports must be used.
No more than 32 stat ions can be connected to a single port .
If no more than 32 stations are connected, two ports must be used.
No more than 32 stat ions can be connected to a single port .
125 μs1 to 4
250 μs1 to 8
500 μs1 to 14
1 ms1 to 32
1.5 ms1 to 62
2 ms1 to 62
3 ms1 to 62
4 ms1 to 62
Connection Conditions
Mixed Cascaded/Star Connections
Communications Cycle
125 μs1 to 4Only star connections can be used.
250 μs1 to 8A single cascaded connection series must consist o f no more than 2 stations.
500 μs1 to 14A single cascaded connection series must consist of no more than 6 stations.
1 ms1 to 29A single cascaded connection series must consist of no more than 7 stations.
1.5 ms 1 to 42A single cascaded connection series must consist of no more than 8 stations.
2 ms1 to 42A single cascaded connection series must consist of no more than 16 stations.
3 ms1 to 42A single cascaded connection series must consist of no more than 18 stations.
4 ms1 to 62A single cascaded connection series must consist of no more than 21 stations.
Note: The above connection conditions assume that the following conditions are met: Number of transmission bytes: 48, Distance
between stations: 100 m., Number of retries: 1.
NOTICE: If the SigmaWin+ is connected through a Machine Controller, the SigmaWin+ may not be usable if there are too many
SERVOPACK stations connected. If this occurs, either connect the SigmaWin+ to the SERVOPACK (CN7) directly, or increase the
communicat ions cycle.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 35
Number of
Connected Stations
Connection Conditions
Page 38
15 MECHATROLINK-III Synchronization between Modules
NOTICE
NOTICE
Timing at Which Modules Are Synchronized
Modules are automatically synchronized when the power supply is cycled.
If you perform any of the following operations after turning ON the power supply, save the settings to flash memory and
then cycle the power supply again.
• When operation changes from asynchronized to synchronized as a result of changing the communications cycle
• When operation changes from synchronized to asynchronized or from asynchronized to synchronized as a result of
changing the high-speed scan setting
• When the minimum response time in the MPiec controller is changed.
Changing Synchronization Cycles
When the scan cycle is changed, MECHATROLINK communications with all slave stati ons conne ct ed to the SVC32 ar e
reset. Operation automatically changes to synchronized when communications are restored.
MECHATROLINK communications continue for all other Modules.
1. When you change the MECHATROLINK cycle, do so either with the CPU Function Module stopped or when motion commands are not being
executed. Otherwise, application operations may be affected.
2. When changing the MECHATROLINK setting, the following operation will occur because MECHATROLINK communications are reset.
• Position information and zero point return comp letion information for Servo axes will be lost.
Changing the MECHATROLINK Communications Cycle
Operation is automatically synchronized as long as the high-speed scan setting is an integral multiple of the
communic ations cycle.
It is not necessary to cycle the power supply.
If asynchronous operation is set as a result of changing the communications cycle, an alarm will occur for the Servo
axis and an I/O error will occur for the I/O station. If this happens, change the setting back to synchronized, save the
settings to flash memory, and then cycle the power supply.
36 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 39
16 Devices Connectable via MECHATROLINK-III
16Devices Connectable via MECHATROLINK-III
Servopacks
The following table shows Servopacks that are compatible with MECHATROLINK-III and can be connected to the
controller.
ModelDetails
SGDV-21 Σ-V Series AC Servo amplifiers for rotary motors
SGDV-E21Σ-V Series Mini AC Servo amplifiers for rotary motors
SGDV-H21AΣ-V Series 200 VAC Large Capacity AC Servo amplifiers for rotary motors
SGDV-J21AΣ-V Series 400 VAC Large Capacity AC Servo amplifiers for rotary motors
SGDV-25Σ-V Series AC Servo amplifiers for linear motors
I/O Modules
The following table shows the module that is compatible with MECHATROLINK-III and can be connected to the
controller.
ModelDetails
JEPMC-MTD2310-E
64-point I/O Module
24VDC, 64 inputs, 64 outputs
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 37
Page 40
17 Connecting the RLY OUT Connector
RLY OUT
24 VDC
0 VDC
POWER
Ground to 100 Ω max.
24-VDC
power supply
Power
supply
Error: OFF
Normal operation: ON
RLY OUT output
17Connectin g th e RLY OUT Connector
The RLY OUT connector connects the status output terminal. It is a normally open contact relay output. The RLY OUT
connector is linked to the operation of the RDY indicator: The contacts close when the indicator lights, and they open
when the indicator goes out.
Note: When the RDY indicator is lit, the Controller is operating normally. It does not necessarily mean that the user programs are being
executed.
RLY OUT Connector Specifications
The operation of the RLY OUT connector is linked to the operation of the RDY indicator on the CPU Unit.
RDY indicator lit: Circuit closed
RDY indicator not lit: Circuit open
Contact Ratings
Input
Voltage
24 VDC
125 VAC
RLY OUT Connector Connection Cable
Current Capacity
0.5 A (resistive load)
0.25 A (inductive load)
0.4 A (resistive load)
0.2 A (inductive load)
To connect the RLY OUT connector, use a cable with a wire size of AWG28 to AWG14 (0.08 to 2.0 mm2) and a
maximum outer diameter of 3.4 mm.
The procedure to make the RLY OUT connector cable is the same as for the 24-VDC power supply cable.
Note: You can use the RLY connector on the Power Supply Unit only on the Rack to which the CPU Unit is mounted. On Racks without
the CPU Unit, the power supply circuit is always open.
RLY OUT Connector Connection Example
Refer to the following figure for an example of connecting the RLY OUT connector.
38YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 41
18Ethernet Connector Details
'VJGTPGV
.+0-
/
Connects to other devices by Ethernet (100Base-TX/10Base-T).
Ethernet Connector Specification and Pin Array/Indicator Light
The following table provides the Ethernet connector specifications.
The following table provides Ethernet connector pin array / indicator light details.
Pin NumberSignal NameDescription
1TXD+Transmitted data + side
2TXD-Transmitted data – side
3RXD+Received data + side
4––
5––
6RXD-Received data – side
7––
8––
Display NameDisplay ColorDescription
LINKYellow
100MGreen
Ethernet Cable
Lit: Connect
Unlit: Unconnected
Lit: Connected at 100Mbps, or automatically negotiating
Unlit: Connected at 10Mbps
For the Ethernet cable, use a twisted pair cable with RJ-45 connector. Yaskawa strongly recommends the use of shielded
ethernet cables.
Ethernet
Type
10Base-TCategory 3 or more
100Base-TCategory 5 or more
CategoryRemarks
• When connecting to remote equipment through a hub: Straight cable
• When connecting to remote equipment without using a hub: Cross cable
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 39
Page 42
18 Ethernet Connector Details
Hub
or Switch
MP3200iec
Hub
or Switch
10Base-T
(Straight cable)
Station
StationStation
Up to 100mUp to 100m
Up to 100m
Up to 100m
Up to 100m
Station
Up to 100m
When connecting to a HUB without using the
auto-negotiation function, set the HUB side to
half-duplex mode.
10 Base-T (crossover cable, up to 100m)
MP3200iec
Ethernet Connection Examples
The following are examples of Ethernet network connections via 10Base-Tx cable:
Connection Example 1 (When using a hub or switch)
Specification
ItemWhen Connecting to a Repeater HUBWhen Connecting to a Switching HUB
Cable Length between Node-HUB100m or less100 m or less
Cable Length between HUBs100m or less100 m or less
Number of HUBs between NodesUp to fourUnlimited
Connection Example 2
40 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 43
18 Ethernet Connector Details
CAUTION
Hub
or Switch
MotionWorks IEC
MP3200iec
YASKAWA SERVOPACK
200V
SGDS-01A12A
SW1
CHARGE
C
N
3
A/B
C
N
1
C
N
2
C
N
4
L1
L2
L2C
L1C
B1/
B2
U
V
W
C
N
6
SERVOPACK
Core
Core
Core
100Base-T
(straight cable)
Servomotor
Other station
The following are examples of Ethernet network connections via 100Base-Tx cable:
High frequency wave noise from other devices in the installation environment may cause errors in
communications using Ethe rnet or MECHATROLINK-III connections. Wh en designi ng a syst em, use pr otectiv e
measures to avoid the influence of high frequency wave noise as follows:
1. Wiring
2. Communication system (Ethernet)
Wire Ethernet or MECHATROLINK-III cables so that they are well-separated from other cable systems such as the main circuit or
power lines.
• Communicate data to a remote device through TCP/IP communication.
• If necessary, increase the number of communication retries.
• Yaskaw a strongly recommends shielded Ethernet cables.
3. Attach a ferrite core.
Ethernet: Attach it to the communication port side and the external equipm ent side of the MP3200iec unit.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 41
Note: Recommended ferrite core.
ModelManufacturer
E04SR301334Seiwa Electric Mfg. Co., Ltd
Page 44
19 Option Module - AI-01 (Analog Input) Module
AI-01
LED indicator
Analog input
connector CN1
RUN
CN1
CN2
Analog input
connector CN2
125 mm
95 mm
19.3 mm
19Option Module - AI-01 (Analog Input) Module
Appearance
Module Functions
The AI-01 module is an analog input module with voltage and/or current input modes.
Module Specifications
The following table shows the AI-01 Module hardware specifications.
ItemSpecifications
ClassificationI/O Module
NameAI-01
ModelJAPMC-AN2300
Analog Input
Accuracy
Analog Input Range-10 to +10V0 to +10V0 to 20 mA
Number of Channels8 ((4/ connector)×2)
Number of Channels to be UsedAny number from 1 to 8
Isolation
Max. Rated Input±15V±30 mA
Input Impedance20 kΩ250 kΩ
Resolution16-bit (-31276 to +31276)15-bit (0 to +31276)
Absolute Accuracy100 mV Max0.3 mA Max
Input Conversion Time1.4 msec Max
Connectors
LED IndicatorRUN (green)
25°C±0.1% (±10 mV)±0.1% (± 0.02 mA)
0 to 55°C±0.3% (±30 mV)±0.3% (±0.06 m A )
Between input connector and system power supply: Photocoupler isolation
Between channels: Not isolated.
CN1: Input connector
CN2: Input connector
42YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 45
L150 mm
26-core
Loose wires
NP JEPMC-W6080-05
Marking tube (Label)
LED Indicator
19 Option Module - AI-01 (Analog Input) Module
ItemSpecifications
Current Consumption500 mA Max
Dimensions125×95 (H×D)
Mass100 g
Indicator
RUNGreenNormal operationOperation stopped (no access from CPU)
Connector Specifications
Connector Name # of Pins
CN1/CN22610226-52A3PL
Indicator
Color
Status when LitStatus when not Lit
Module SideCable SideManufacturer
Applicable Cable: JEPMC-W6080-oo
Standard Cable Model and External Appearance
ModelLengthExternal Appearance (JEPMC-W6080-oo)
JEPMC-W6080- 050.5 m
Connector Model
• Connector
10126-3000VE
•Shell
10326-52A0-008
(Screw locking), or
10326-52F0-008
(One-touch lock ing)
Sumitomo 3M Corporation
JEPMC-W6080- 101.0 m
JEPMC-W6080- 303.0 m
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 43
Page 46
19 Option Module - AI-01 (Analog Input) Module
25
26
13
12
15
1
2
14
1
V1
14
MDP1
2
G1
15
G1
3A116MDN1
4V217MDP2
5G218G2
6A219MDN2
7V320MDP3
8G321G3
9A322MDN3
10V423MDP4
11G424G4
12A425MDN4
1326
25
26
13
12
15
1
2
14
1
V5
14
MDP5
2
G5
15
G5
3A516MDN5
4V617MDP6
5G618G6
6A619MDN6
7V720MDP7
8G721G7
9A722MDN7
10V823MDP8
11G824G8
12A825MDN8
1326
Connector Pin Arrangement
The AI-01 Module Connector (CN1/CN2) pin arrangement is shown below.
CN1 Connector Pin Arrangement
Pin Arrangement Viewed from Wiring Side
CN2 Connector Pin Arrangement
Pin Arrangement Viewed from Wiring Side
Standard Cable Wiring Table
The wiring table for the standard cable JEPMC-W6080- is shown below.
PinWire Color
1
2
3
14
16
4
5
44 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Columns “Label on M arkin g T u be”, “Si gnal Name”, and “Fu nction ” dis play t he val ues f or conn ector s CN1 and CN2 in
the format “CN1 /CN2”, respectively.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 45
Page 48
19 Option Module - AI-01 (Analog Input) Module
DC/DC
Converter
+5V
0V
+15V
-15V
0V
D/A
Converter
Internal circuit
+5V
Photocoupler
Voltage input
Current input
Mode
10
12
25
23
-
+
GND
CH8
11
Multiplexer
Ground
Voltage input
Current input
Mode
4
6
19
17
-
+
GND
CH2
5
Voltage input
Current input
Mode
Ground
1
3
16
14
2
-
+
GND
CH1
Ground
Shell
RR
R
RR
R
RR
R
10k
10k
256.5
10k
10k
256.5
10k
10k
256.5
Circuit Configuration
46 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 49
DANGER
DC/DC
Converter
+5V
0V
+15V
-15V
0V
D/A
Converter
Internal circuit
+5V
Photocoupler
Voltage input
Current input
Mode
10
12
25
23
-
+
GND
CH8
11
Multiplexer
Ground
Voltage input
Current input
Mode
4
6
19
17
-
+
GND
CH2
5
Voltage input
Current input
Mode
Ground
1
3
16
14
2
-
+
GND
CH1
Ground
Shell
RR
R
RR
R
RR
R
10k
10k
256.5
10k
10k
256.5
10k
10k
256.5
CN1 Connector Connection Example
19 Option Module - AI-01 (Analog Input) Module
• Use the standard cable (J EPMC-W6080- ) for AI-01 Modules to connect to ex te rnal de vices . Use a relay termina l
block to connect the AI-01 module to external devices because the wiring distance varies between the AI-01 module
and each external device.
• Ground the cable shield between an external device and the relay terminal block on the external device side.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 47
Page 50
20 Option Module - AO-01 (Analog Output) Module
A
O
-01
LED indicator
Analog output
connector CN1
RUN
CN1
125 mm
95 mm
19.3 mm
20Option Module - AO-01 (Analog Output) Module
Appearance
Module Functions
The AO-01 module has four channels for anal og output. Two types of analog outpu t ranges a re availabl e; -10 t o +10V and
0 to +10V.
Module Specifications
The following table shows the AO-01 Module hardware specifications.
ItemSpecifications
NameAO-01
ModelJAPMC-AN2310-E
Number of Channels4
Isolation
Analog Output Rang e±10V0 to +10V
Resolution16-bit (-31276 to +31276)15-bit (0 to +31276)
Absolute Accuracy100 mV Max0.3 mA Max
Analog Output
Accuracy
Input Conver sion Time1.2 msec Max
ConnectorsCN1: Output connector
LED IndicatorRUN (green)
Current Consum ption500 mA Max
Dimensions125 × 95 (H×D)
Mass90 g
Indicators
25°C±0.1% (±10 mV)
0 to 55°C±0.3% (±30 mV)
Between channels: Not isolated.
Between output connector and system power supply: Photocoupler isolation
Indicator
RUNGreenNormal operationOperation stopped (no access from CPU)
48YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Indicator
Color
Status when LitStatus when not Lit
Page 51
Connector Specifications
20 Option Module - AO-01 (Analog Output) Module
Name
Analog Output
Connector
Connector
Name
CN12010220-52A3PL
# of Pins
Module SideCable SideManufacturer
Applicable Cable: JEPMC-W6090-oo
Standard Cable Model and External Appearance
ModelLengthExternal Appearance (JEPMC-W6090-oo)
JEPMC-W6090-050.5 m
JEPMC-W6090-101.0 m
JEPMC-W6090-303.0 m
CN1 Pin Layout Diagram
Connector Model
• Connector 10126-30 00VE
• Shell 10326-52A0-008
(Screw locking), or
10326-52F0-008
(One-touch locking)
Sumitomo 3M
Corporation
Standard Cable Wiring Table
The following shows the pin arrangement for standard cable JEPMC-W6090.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 49
OrangeBlackGround 0
GrayBlackA_Pulse+
YellowRed(-)
YellowBlackC-Phase latch input common (5V)
Marking
Color
Function
Page 52
20 Option Module - AO-01 (Analog Output) Module
DANGER
AO-01 Module Connector Connection Example
CN1 Connector Connection Example
• Use the AO-01 standard cable (JEPMC-W6090-) for the connection to the external device. Use the junction
terminal block because the distance between the external devices and the module are different as seen on the above
diagram.
• Ground the cable shield between the external devices and the junction terminal block by the external device side.
50 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 53
21 Option Module - DO-01 (Digital Output) Module
DANGER
0
24
DO_24V
Output
register
DO_OUT
DO_COM
+24V
R
Photocoupler
R
Transistor
21Option Module - DO-01 (Digital Output) Module
Appearance/Indicators
Module Functions
The DO–01 module is equipped with 64 digital outputs.
Output Circuit Specifications
The following table shows the DO-01 Module output circuit specifications.
ItemSpecifications
Outputs64 points
Output FormatTransistor/open collector, sink mode outpu t
Isolation MethodPhotocoupler
Output Voltage+ 24VDC (+19.2 to +28.8V)
Output Current100 mA Max
Leakage Current When OFF0.1 mA Max
ON Time/OFF Time
Number of Commons8 points
Protection CircuitFuse connected to each common line
Fuse Rating1A
Error DetectionFuse blowout detection
ON: 0.5 ms Max
OFF: 1 ms Max
DO-01 Digital Output Circuit (Sink Mode Output) Connection Example
A fuse is inserted into the output commo n line of th e DO-01 Module for circuit protection. However , the fuse may not
be blown out in the cases such as layer shorts in outputs. To ensure the circuit protection, provide a protective element
such as fuse in each output as shown in the above diagram.
DO-01 Module Connections
Connects the DO-01 Module to external output signals.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 51
Columns “Signal Name” and “Function” display the values for connectors CN1 and CN2 in the format “CN1/CN2”
respectively.
54 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 57
22 Option Module - LIO-01/02 Module
LIO-01
LED indicators
Switch
I/O connector
22Option Module - LIO-01/02 Module
Appearance
External Appearance
The following figure shows the external appearance of the LIO-01/02 Modules
The LIO-01 Module provides digital I/O and encoder input functions. There are 16 digital inputs (DI) and 16 digital
outputs (DO) for the digital I/O function. There is also one encoder input.
The following diagra m giv es an outli ne of the LI O-01 Mo dule f uncti ons. The only f unctiona l d iff erenc e betwe en the LIO01 and the LIO-02 is the active state of the output circuits
Refer to LIO-01 Digital Output Circuit (Sink Mode Output) Connection Example on page 58 and Refer to LIO-02
Digital Output Circuit (Source Mode Output) Connection Example on page 58.
The LIO-02 Module status display LED indicators (LD1 to LD8) change based on the SW1 rotary switch settings. The
following table shows the ON/OFF indicator display for digital input and digital output.
Outline of Functions
LED Indicators and Switch Settings
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 55
Page 58
22 Option Module - LIO-01/02 Module
LD3
LD2
LD1
LD4
LD7
LD6
LD5
LD8
SW1
0
5
1
2
3
4
6
7
8
9
Indicators
IndicatorColorSW1Status when Lit
Board Status Indicators
LD1Normal operation: Lit, Error: Not lit
LD2DI-00 to DI-07 status. Lit when any digital input is turned ON.
LD3DO-00 to DO-07 status. Lit when any digital output is turned ON.
0
LD1 to LD8G re en
1Digital input indicators: When DI00 to DI07 turn ON, corresponding indicators (LD1 to LD8) are lit.
2Digital input indicators: When DI08 to DI15 turn ON, corresponding indicators (LD1 to LD8) are lit.
3Digital output indicators: When DO00 to DO07 turn ON, corresponding indicators (LD1 to LD8) are lit.
4Digital output indicators: When DO08 to DO15 turn ON, corresponding indicators (LD1 to LD8) are lit.
5
LD4Pulse A/B input. Lit when phase A/B is turned ON.
LD5Normal operation: Lit, Error: Not lit
LD6DI-08 to DI-15 status. Lit when any digital input is turned ON.
LD7DO-08 to DO-15 status. Lit when any digital output is turned ON.
LD8Pulse Z input. Lit when phase Z is turned ON.
PI input Indicators
LD1
LD2
LD3
LD4
Pulse A input
Pulse B input
Pulse Z input
-
LD5
LD6
LD7
LD8
High speed output set
Phase-Z latch
Digital input latch
-
Specifications
Module Specifications
ItemSpecifications
NameLIO-01/02
ModelJAPMC-IO2300/JAPMC-IO2301
16 inputs
Digital Inputs
24VDC, 4.1 mA, combined sink mode/source mode i nputs
(DI_01 also used for position registation latch.)
Phase A/B/Z inputs
Phase-A/B: 5V differential input, not isolated, Max frequency: 4 M H z
Encoder Input
Phase-Z: 5V/12V photocoupler input, Max frequency: 500 kHz
Latch input
Position registration latch on phase-C or DI _0 1.
SwitchesRotary switch (SW1)
Dimensions (mm)125 x 95 (H x D)
Mass80 g
56 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 59
22 Option Module - LIO-01/02 Module
5.6k Ω/0.5 W
Vcc
DI_COM
+24 V
DI_IN
Input register
0
24
R
R
R
R
5.6 k
Ω/ 0.5 W
Vcc
680 Ω
DI_COM
+24 V
DI_IN
22 kΩ
1 k
Ω
2200PF
0.01 μF
Input register
0
24
R
R
R
R
Input Circuit Specifications
ItemSpecifications
Inputs16 points
Input FormatSink mode/Sourc e mode input
Isolation MethodPhotocoupler
Input Voltage±24VDC, ±20mv
Input Current4.1 mA (typ.)
ON Voltage/Current15V min./2.0 mA min.
OFF Voltage/Current5V Max/1.0 mA Max
ON Time/OFF Time
Number of Commons8 points (DI_COM0: DI_00 to DI_07, DI_COM1: DI_08 to DI_15)
Other Functions
Digital Input Circuit (Sink Mode Input) Connection Example
ON: 0.5 ms Max
OFF: 0.5 ms Max
DI_01 is shared with position registration latch. If DI_01 is turned ON while position registration latch
inputs are enabled, the encoder position will be latched.
Digital Input Circuit (Source Mode Input) Connection Example
Output Circuit
The following table shows the LIO-01/02 Module output circuit specifications.
ItemSpecifications
Outputs16 p oints
Output Format
Isolation MethodPhotocoupler
Output Voltage+24VDC, ±20mv
Output Current100 mA Max
Leakage Current When OFF0.1 mA Max
ON Time/OFF Time
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 57
LIO-01Transistor, open collector sink mode outputs
LIO-02Transistor, open collector source mode outputs
ON: 1 ms Max
OFF: 1 ms Max
Page 60
22 Option Module - LIO-01/02 Module
R
R
R
0
24
DO_24V
Output
register
DO_OUT
DO_COM
+24 V
0
24
+24V
DO_24V
Output
register
DO_OUT
DO_COM
R
R
R
ItemSpecifications
Number of Commons16 points
Protection Circuit
Error DetectionBlown fuse detection
Other FunctionsDO_01 is shared with encoder position detection
LIO-01 Digital Output Circuit (Sink Mode Output) Connection Example
The fuses are not for circuit protection. Th ey are for fire protection at output shorts. Attach a fu se
externally to each output if circuit protection is required.
LIO-02 Digital Output Circuit (Source Mode Output) Connection Example
Pulse Input Circuit
The following table shows the LIO-01/02 Module encoder circuit specifications.
ItemSpecifications
Number of Encoders1 (Phase-A /B/Z input)
Encoder Circuit
Input ModePhase-A/B, signed, incrementa l/decremental
Latch Input
Phase-AB: 5V differential input, not isolated, Max frequency: 4 MHz
Phase-Z: 5V/12V photocoupler input, Max frequency: 500 kHz
Position registration latch on phase-Z or DI_01.
Response time: 5 ms Max for phase-Z input; 60 ms Max for DI_01 input.
58 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 61
22 Option Module - LIO-01/02 Module
+5 V
0 V
Phase-A
A1
220Ω
Pulse Generator
Phase-B
PA
PAL
PB
PBL
GND
B1
A2
B2
B3
B4
A4
A3
+5 V
Latch input or
phase-Z pulse
PC
PCL5
PCL12
R
R
R
220Ω
R
B1A1
B24A24
Encoder Circuit Connection Example
LIO–01/02 Standard Cable Wiring Table
Connector Pin Arrangement
The following table shows the connector pin arrangement for LIO-01/02 Modules viewed from the wiring side.
• Connect a fuse suit able for the load specifica t ions in the output signal circuit in series with the load. If an external
fuse is not connected, load shorts or overloads could result in fire, destruction of the load device, or damage to the
output element.
• The pins A5 and B5, and the pins A6 and B6 are internally connected. Connect them externally as well.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 61
Page 64
22 Option Module - LIO-01/02 Module
+5V
0V
Phase-A
Pulse generator
+5V
Pulse input
Latch input
or phase-Z
pulse
Latch input or
phase-Z pulse
Phase-B
5V
A2
B2
A4
PB
PBL
GND
PC
PCL5
PCL12
A3
A24
B24
B3
B4
PA
PAL
A1
B1
External input
signals
DI_COM0
DI_01
DI_02
DI_03
DI_04
DI_05
DI_06
DI_07
DI_00
A23
B22
A22
B21
A21
B20
A20
B19
A19
24 VDC
Digital input
R
R
External input
signals
DI_COM1
DI_09
DI_10
DI_11
DI_12
DI_13
DI_14
DI_15
DI_08
B23
B18
A18
B17
A17
B16
A16
B15
A15
24 VDC
Digital input
R
R
R
R
R
R
R
L
L
L
L
L
L
L
Digital output
External output
signals
L
L
L
L
L
L
L
L
L
Fuse open
detection circuit
Fuse
24 VDC
Fuse
DO_24V
DO_24V
DO_00
DO_01
DO_02
DO_03
DO_04
DO_05
DO_06
DO_07
DO_08
DO_09
DO_10
DO_11
DO_12
DO_13
DO_14
DO_15
DO_COM
DO_COM
B6
A6
B14
A14
B13
A13
B12
A12
B11
A11
B10
A10
B9
A9
B8
A8
B7
A7
A5
B5
R
L
Load
External Fuse
LIO-02 Module Connections
62 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 65
23 Option Module - LIO-04/05 Modules
DANGER
LED indicators
I/O connector
(CN1)
LIO-04
RUN
FU
CN2
CN1
I/O connector
(CN2)
FURUN
23Option Module - LIO-04/05 Modules
External Appearance
The following figure shows the external appearance of the LIO-04/05 Modules.
The LIO-04/05 Modules are Optional Boards for the MP2300Siec which provide a digital I/O function. There are 32
digital inputs (DI) and 32 digital outputs (DO) (sink mode outputs) for the digital I/O function.
The following table shows the status of LIO-04/05 Module LED indicators.
The burnout detection circuit will not function when there is no external 24V power supply.
Outline of Functions
Indicators
Indicator Name Indicator ColorStatus
RUNGreen
FURed
Lit: Module normal
Not lit: Module error
Lit: One of the output protection fuses is blown.
Not lit: All of the output protection fuses are normal.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 63
Page 66
23 Option Module - LIO-04/05 Modules
LD3
LD2
LD1
LD4
LD7
LD6
LD5
LD8
SW1
0
5
1
2
3
4
6
7
8
9
Indicators
Switch Settings
The LIO-04/05 Module status display the LED indicators (LD1 to LD8) change based on the SW1 rotary switch setting.
The following table shows the ON/OFF indicator display for digital input and digital output.
IndicatorColorSW1Status when Lit
Board Status Indicators
LD1Normal operation: Lit, Error: Not lit
LD2DI_00 to DI_07 status. Lit when any digital input is turned ON.
LD3DO_00 to DO_07 status. Lit when any digital output is turned ON.
LD4Pulse A/B input. Lit when phase A/B is turned ON.
0
LD5Normal operation: Lit, Error: Not lit
LD6DI_08 to DI_15 status. Lit when any digital input is turned ON.
LD7DO_08 to DO_15 status. Lit when any digital output is turned ON.
LD1 to LD8Green
LD8Pulse Z input. Lit when phase Z is turned ON.
1Digital input indicators: When DI_00 to DI_07 turn ON, corresponding indicators LD1 to LD8 are lit.
2Digital input indicators: When DI_08 to DI_15 turn ON, corresponding indicators LD1 to LD8 are lit.
3Digital output indicators: When DO _ 00 to DO _07 turn ON, corresponding indicators LD1 to LD8 are lit.
4Digital output indicators: When DO _ 08 to DO _15 turn ON, corresponding indicators LD1 to LD8 are lit.
PI Input Indicators
LD1
5
LD2
LD3
LD4
Pulse A input
Pulse B input
Pulse Z input
-
LD5
LD6
LD7
LD8
Coincidence detection
Phase-Z latch
Digital input latch
-
Module Specifications
The following table shows the hardware specifications of the LIO-04/05 Module.
ItemSpecifications
NameLIO-04/LIO-05
ModelJAPMC-IO2303/JAPMC-IO2304
32 inputs
24VDC, 4.1 mA, combined sink mode/source mode inputs
(DI_00, 01, 16, and 17 also used for interrupts.)
Digital Inputs
Digital Outputs
Indicators
Dimensions (mm)125 x 95 (H x D)
Mass80 g
64 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Simultaneously ON Inputs
16 points (8 inputs/common): At ambient temperatur e of 55°C and 24VDC
10 points (5 inputs/common): At ambient temperat ure of 55°C and 28.8VDC
Refer to the following characteristics graph for details.
The following table shows the LIO-04/05 Modules input circuit specifications.
ItemSpecifications
Inputs32 points
Input FormatSink mode, source mode input
Isolation MethodPhotocoupler (PS2805-4)
Input V oltage±24VDC (+19.2 to +28.8V)
Input Current4.1 mA (typ.)
ON Voltage/Current15VDC min./2.0 mA min.
OFF Voltage/Current5VDC min./1.0 mA min.
ON Time/OFF Time
Number of Commons8 points
Digital Input Circuit (Sink Mode Input) Connection Example
ON: 0.5 ms Max
OFF: 0.5 ms Max
Digital Input Circuit (Source Mode Input) Connection Example
Output Circuit
The following table shows the LIO-04/05 Module’s output circuit specifications.
ItemSpecifications
Outputs32 points
Output Format
Isolation MethodPhotocoupler
Output Voltage+24VDC (+19.2 to +28.8VDC)
Output Current100 mA Max
Leakage Current When OFF0.1 mA Max
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 65
Page 68
23 Option Module - LIO-04/05 Modules
0
24
+24V
Output
register
DO_OUT
0V
+24V
R
Photocoupler
R
Transistor
ItemSpecifications
ON Time/ OFF Time
Number of Commons1 per 8 outputs
Protection Circuit
Fuse Rating1A
Error DetectionFuse blowout detection
LIO-04 Digital Output Circuit (Sink Mode Output) Connection Example
ON: 0.5 ms Max
OFF: 1 ms Max
The fuses are not for circuit protection. They are for fire protection at output sho rts. Attach a fuse
externally to each output if circuit prote ctio n is requ ired.
LIO-05 Digital Output Circuit (Source Mode Output) Connection Example
+24V
DO_OUT
0V
Output
register
R
R
R
Photocoupler
Transistor
+24V
0
24
66 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 69
23 Option Module - LIO-04/05 Modules
1
3
5
7
9
11
13
15
17
19
21
23
25
DICOM_3
DI_18
DI_22
DI_24
DI_28
N.C.
DO_18
+24V_3
DO_22
DO_24
N.C.
DO_28
N.C.
26
28
30
32
34
36
38
40
42
44
46
48
50
N.C.
DI_19
DI_23
DI_25
DI_29
N.C.
DO_19
N.C.
DO_23
DO_25
OV_4
DO_29
OV_4
27
29
31
33
35
37
39
41
43
45
47
49
DI_17
DI_21
N.C.
DI_27
DI_31
DO_17
OV_3
DO_21
N.C.
DO_27
N.C.
DO_31
50
49
25
24
26
27
1
2
Pin Arrangement Viewed from Wiring Side
2
4
6
8
10
12
14
16
18
20
22
24
DI_16
DI_20
DICOM_4
DI_26
DI_30
DO_16
N.C.
DO_20
N.C.
DO_26
+24V_4
DO_30
LIO-04 Module Connector Pin Arrangement
The LIO-04 Module Connector (CN1 and CN2) pin arrangements are shown below.
CN1 Connector Pin Arrangement
Pin Arrangement Viewed from Wiring Side
1
26
27
2
49
24
50
25
10
12
14
16
18
20
22
24
2
4
6
8
DI_00
DI_04
DICOM_2
DI_10
DI_14
DO_00
N.C.
DO_04
N.C.
DO_10
+24V_2
DO_14
1
3
5
7
9
11
13
15
17
19
21
23
25
DICOM_1
DI_02
DI_06
DI_08
DI_12
N.C.
DO_02
+24V_1
DO_06
DO_08
N.C.
DO_12
N.C.
DI_01
27
29
DI_05
N.C.
31
33
DI_11
35
DI_15
DO_01
37
39
OV_1
DO_05
41
43
N.C.
DO_11
45
47
N.C.
DO_15
49
26
N.C.
DI_03
28
30
DI_07
DI_09
32
34
DI_13
N.C.
36
38
DO_03
N.C.
40
DO_07
42
44
DO_09
OV_2
46
48
DO_13
OV_2
50
CN2 Connector Pin Arrangement
• P: Power supply input, I: Input signal, O: Open collector output
Standard Cable Wiring Table
The wiring table for the standard cable JEPMC-W6060- is shown below.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 67
PinWire ColorMarkingsSignal NameI/OFunction
1
2
3White—DI_02/18I/IDigital input 2/18
4
5Pink—DI_06/22I/IDigital input 6/22
Orange—DICOM_1/3P/PDigital Input common 1/3
Gray—DI_00/16I/I
Yellow—DI_04/20I/IDigital input 4/20
Digital input 0/16
(shared with interrupt input)
Page 70
23 Option Module - LIO-04/05 Modules
DANGER
PinWire ColorMarkingsSignal NameI/OFunction
6Orange— —DICOM_2/4P/PDigital Input common 2/4
7
8White— —DI_10/26I/IDigital input 10/26
Orange————————0V_2/4Digital Output 0VDC common 2/4
47
Gray————————+24V_2/4Digital Output 24V supply 2/4
48White————————DO_13/29O/ODigital output 13/29
49
Yellow————————DO_15/31O/ODigital output 15/31
50Pink————————N.C.
Columns “Signal Name”, “I/O”, and “Function” display the values for connectors CN1 and CN2 in the format “CN1/
CN2” respectively.
70 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 73
DANGER
JEPMC-IO2303
+5V
+-
+-
24 VDC
Input 0
Input 1
Input 6
Input 7
+-
+-
24 VDC
6
7
32
10
35
1
2
27
5
30
CN1 connector
pin No.
Common 1
Common 2
Input 8
Input 9
Input 14
Input 15
Internal circuit
5.6 kW
Photocoupler
R
R
Photocoupler
Fuse blowout
detection circuit
38
12
13
41
17
42
16
L
L
L
L
L
24 VDC
+-
43
37
L
Output 0
39
15
Output 1
Output 2
Output 4
Output 5
Output 6
Output 7
Output 3
R
L
L
Photocoupler
45
19
20
48
24
49
23
L
L
L
L
L
24 VDC
+-
50
44
L
Output 8
46
22
Output 9
Output 10
Output 12
Output 13
Output 14
Output 15
Output 11
R
L
L
Fuse blowout
detection circuit
L
Load
External Fuse
(Installed by customer)
LIO-04 Module Connector Connection Examples
CN1 Connector Connection Example
23 Option Module - LIO-04/05 Modules
• Check the polarity of the external power supply when wiring. An adverse connection may cause a load malfunction.
• The pins 39 and 43 and the pins 46 and 50 are internally connected. Connect them externally as well.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 71
Page 74
23 Option Module - LIO-04/05 Modules
DANGER
CN2 Connector Connection Example
24 VDC
+-
Common 3
+-
Input 16
Input 17
Input 22
Input 23
24 VDC
+-
Common 4
+-
Input 24
Input 25
Input 30
Input 31
L
Load
External Fuse
(Installed by customer)
CN2 connector
pin No.
1
5.6 kW
2
R
27
5
30
6
Photocoupler
7
32
10
35
JEPMC-IO2303
Photocoupler
R
Photocoupler
+5V
R
Fuse blowout
detection circuit
R
Fuse blowout
detection circuit
Internal circuit
15
12
37
13
38
16
41
17
42
43
39
22
19
44
20
45
23
48
24
49
50
46
Output 16
Output 17
Output 18
Output 19
Output 20
Output 21
Output 22
Output 23
Output 24
Output 25
Output 26
Output 27
Output 28
Output 29
Output 30
Output 31
24 VDC
+-
L
L
L
L
L
L
L
L
24 VDC
+-
L
L
L
L
L
L
L
L
• Check the polarity of the external power supply when wiring. An adverse connection may cause a load malfunction.
• The pins 39 and 32 and the pins 46 and 50 are internally connected. Connect them externally as well.
72 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 75
DANGER
+
-
-
+
24 VDC
Common 1
Common 2
1
CN1 connector
pin No.
Input 0
Input 1
2
27
Input 6
Input 7
5
30
6
7
32
Input 8
Input 9
10
35
Input 14
Input 15
JEPMC-IO2304
+
-
-
+
DC24V
+5V
5.6 kΩ
Photocoupler
Internal
circuit
R
R
L
L
L
L
L
L
15
12
Output 0
37
Output 1
13
Output 2
38
24 VDC
+
-
41
17
42
16
39
Output 4
Output 5
Output 6
Output 7
Photocoupler
L
Output 3
R
R
L
L
L
L
L
L
L
22
19
Output 8
44
Output 9
20
Output 10
45
24 VDC
+
-
48
24
49
23
46
Output 12
Output 13
Output 14
Output 15
Photocoupler
L
Output 11
R
R
L
Fuse blowout
detection circuit
Fuse blowout
detection circuit
L
Load
External Fuse
(Installed by customer)
LIO-05 Module Connector Connection Examples
CN1 Connector Connection Example
23 Option Module - LIO-04/05 Modules
Check the polarity of the external power supply when wiring. An adverse connection may cause a load malfunction.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 73
Page 76
23 Option Module - LIO-04/05 Modules
DANGER
࣭
࣭
࣭
࣭
࣭
࣭
+
-
-
+
24 VDC
Common 3
Common 4
1
CN2 connector
pin No.
Input 16
Input 17
2
27
Input 22
Input 23
5
30
6
7
32
Input 24
Input 25
10
35
Input 30
Input 31
JEPMC-IO2304
+
-
-
+
24 VDC
+5V
5.6 kW
Photocoupler
Internal
circuit
R
R
L
L
L
L
L
L
15
12
Output 16
37
Output 17
13
Output 18
38
24 VDC
+
-
41
17
42
16
39
Output 20
Output 21
Output 22
Output 23
Photocoupler
L
Output 19
R
R
L
L
L
L
L
L
L
22
19
Output 24
44
Output 25
20
Output 26
45
24 VDC
+
-
48
24
49
23
46
Output 28
Output 29
Output 30
Output 31
Photocoupler
L
Output 27
R
R
L
Fuse blowout
detection circuit
Fuse blowout
detection circuit
L
Load
External Fuse
(Installed by customer)
CN2 Connector Connection Example
Check the polarity of the external power supply when wiring. An adverse connection may cause a load malfunction.
74 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 77
24Option Module - LIO-06 Module
DANGER
LIO-06
ALMRUN
CN1
Module External Appearance
24 Option Module - LIO-06 Module
Outline of Functions
The LIO-06 Module has digital I/O, analog I/O, and pulse encoder functionality, including a registration latch input. The
LIO-06 Module is fully compatible with the MP940 I/O connector.
When converting equipment from the prior generation MP940 controller, users should bear in mind that the analog
inputs that had previo usly bee n wired to the V-REF and T- REF inputs on the SGDH must now be co nnected directl y to
the LIO-06 option module.
LED Indicators and Switch Settings
Display NameColorStatus when LitStaus when OFF
RUNGreenNormalStopped. (No access by CPU)
ALMRedFaultNormal operation
The ALM light indicates the following conditions
• Fuse fault
•ASIC error
• A-phase disconnect
• B-phase disconnect
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 75
Page 78
24 Option Module - LIO-06 Module
DANGER
Option Board Specifications
ItemSpecification
Number of Inputs8/Common
Input MethodSink/Source
IsolationPhotocoupler Isolation
Input VoltageDC24V±20% (DC19.2 to 28.8V)
Digital Input
Digital Output
Analog
Input
Analog
Output
Input Current4.1mA (TYP)
ON Voltage/CurrentAt least 15V/At least 2mA
OFF Voltage/Current5V Max/1mA Max
ON/OFF TimeON= 0.5ms Max/OFF= 0.5ms Max
Interrupt1 (used together with DI_00)
Number of Outputs8/ Common
Output MethodTransistor Sink Output
IsolationPhotocoupler Isolation
External Power Sup ply VoltageDC24V±20% (DC19.2 to 28.8V)
Output Current100mA (Max)
ON Voltage1V Max
Leak Current at OFF0.1mA Max
ON/OFF TimeON= 0. 25ms Max/OFF= 1ms Max
Protection Classi ficationUnprotected output
Error DetectionBlown fuse detection
Number of Channels1
IsolationNon-isolated
Analog Input Range-10 to +10V
Maximum Rated In pu t±15V
Input ImpedanceApprox. 20kΩ
Resolution16bit (-31276 to +31276)
Absolute Accuracy100mV Max
Accuracy
Input Filter
Input Conversion Speed50μs
Number of Channels1
IsolationNon-isolated
Analog Output Rang e-10 to +10V
Output Impedance20Ω Max
Resolution16bit (-31276 to +31276)
Accuracy
Maximum Permissible Load Current±5mA
Output Delay Time1.2ms (Time of change from -10+10V)
25ºC±0.1% (±10mV)
0 to 55ºC±0.3% (±30mV)
25ºC±0.1% (±10mV)
0 to 55ºC±0.3% (±30mV)
Time Constant
Delay Time1ms(Max) (when -10 to 10V)
0.2×10
–3
The time constant shows th e characte ristic s according to the input f ilter equ ivalent t o the time to reach 0.632 × the in put
voltage.
76 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 79
24 Option Module - LIO-06 Module
ItemSpecification
Number of Channels1
Input Method5V Differential Max Frequency 4MHz
IsolationNon-isolated
A/B Phase
Counting System
Encoder Input
Number of Input Circuits
Input MethodSource Photocoupler I/FSink/Source Photocoupl er I/F
IsolationPhotocoupler IsolationPhotocoupler Isolation
Encoder
Input
Current Consumption5V, 1A Max
Hot Swapping (Modul es)Not Possible
ConnectorCN1: Digital I/O, Analog I/O, Encoder Input
IndicatorsRUN (Green), ALM (Red)
Input Voltage
Input Current
Latch Input
ON Voltage
OFF Voltage
Response Time1μs Max60μs Max
Minimum ON Pulse Width1μs60μs
COIN Output
Pulse/Direction
UP/DOWN Counter
2 (C-Phase latch or digital input latch)
The digital input latch is used in conjunction with DI-01 on pin 39.
C-Phase LatchDigital Input Latch
24VDC±20%
12VDC±20%
5VDC±20%
24VDC/12VDC/5VDC are switched by
connector wiring
1, digital output
Used together with DO-07 (software switching)
DC24V±20%
4.1mA (TYP)
15V Min
5V Max
Digital Input Circuit
The specifications of the LIO-06 module digital input circuit are shown below.
ItemSpecification
Number of Inputs8
Input MethodSink/Source
IsolationPhotocoupler Isolation
Input VoltageDC24V±20%
Input Current4.1mA (TYP )
ON Voltage/CurrentAt least 15V/2.0mA
OFF Voltage/Curr e nt5V Max/1.0mA Max
ON Time/OFF TimeON=0.5ms Max/OFF=0.5ms Max
Number of Commons1
Other Functions
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 77
DI_01 is used together with the position registration latch input, and when enabled, the position
registration latch input latches with the pulse encoder when SI_01 is "ON".
Page 80
24 Option Module - LIO-06 Module
Digital Input Circuit Connection Example
Common
750
5.6
DI
Internal Circuitry
Digital Output Circuit Connection Example
Output
Register
1.2k䃈
R
0.5
Photocoupler
PS280䠍䠉䠐
33k䃈
1000PF
PS2805-4
R
1000PF
Transistor
DTDS14GP
FU
Input Circuitry
Input
Register
Vin
DO
0䠲
Digital Output Circuit
The specifications of the LIO-06 digital output circuit are shown below.
ItemSpecification
Number of Outputs8
Output MethodTransistor Open Collector Sink Output
IsolationPhotocoupler Isolation
External Power Supply VoltageDC24V±20%
Output Current100mA Max
Leak Current at OFF0.1mA Max
ON Time/OFF TimeON=0.25ms Max/OFF =1ms Max
Number of Commons1
Protection Circuit
Fuse Rating1A
Error DetectionBlown fuse detection
78 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
The fuses are not for circuit protection. They are for fire protection at output sho rts. A fuse
should be attached outside each output when a protective ci rcuit is necessary.
Page 81
24 Option Module - LIO-06 Module
DANGER
Analog Input Circuit
The specifications of the LIO-06 analog input circuit are shown below.
ItemSpecification
Analog Input Range-10 to +10V
Number of Input Chan ne ls1
IsolationNon-isolated
Maximum Rated Input±15V
Input Impeda nceApprox. 20kΩ
Resolution16-bit (-31276 to +31276)
Accuracy
Input Filter
Conversion Speed50μs
25ºC±0.1%(±10mV)
0 to 55ºC±0.3%(±30mV)
Time Constant
Delay Ti me1 ms (M a x) ( Whe n -1 0+ 1 0V )
0.2×10
–2
The time constant shows t he charact eristic s accordin g to the input filter eq uivalent to the time to re ach 0.632 × t he input
voltage.
Analog Input Circuit Connection Example
To A/D
Conversion
Ground
Internal Circuitry
Analog Input Characteristics Response Chart
The following shows an analog input response chart and input characteristics diagram for the LIO-06 module.
Input Characteristics Response Chart
Analog Input ValueInput Register Value
-10.5V-32768
-10.0V-31276
-5.0V-15638
0.0V0
+5.0V15638
+10.0V31276
+10.5V32767
• Minimum linearity of +10.0V cannot be assured.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 79
Page 82
24 Option Module - LIO-06 Module
Voltage Input Characteristics Diagram
Analog Output Circuit
Analog Input
Value
The specifications of the LIO-06 analog output circuit are shown below.
ItemSpecification
Output Range-10 to +10V
Number of Output Channels1
IsolationNon-isolated
Maximum Permissible Load Current±5mA
Resolution16-Bit (-31276 to +31276)
Absolute
Output Delay Time1.2ms (Time of change from -10+10V)
Analog Output Circuit Connection Example
25ºC±0.1% (±10mV)
0 to 55ºC±0.3% (±30mV)
80 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 83
24 Option Module - LIO-06 Module
Analog Output Characteristics Response Chart
The following shows an analog output response chart and output characteristics diagram for the LIO-06 module.
Output Characteristics Response Chart
Analog Output ValueOutput Register Va lue
-10.5V-32768
-10.0V-31276
-5.0V-15638
0.0V0
+5.0V15638
+10.0V31276
+10.5V32767
Voltage Output Charac teristics Diagram
Output Register Value
Analog Output
Value
Encoder Circuit
The specifications of the LIO-06 encoder circuit are shown below.
ItemSpecification
Number of Encode rs1 channel (A/B/C-Phase Input)
Input Circuits
Input ModeA/B-phase, code, UP/DOWN counter, pulse, and direction
Latch Input
A/B-phase: 5V differential input, non-isolated, max frequency 4MHz
C-Phase: 5V/12V /2 4V ph oto c ou pler input, max frequency 500k H z
Position registration latch with C-Phase of DI_01
Response Time: Max 5μs during C-Phase input, During DI_01 Input: Max 60μs
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 81
Page 84
24 Option Module - LIO-06 Module
50-core
Loose wires
Encoder Input Circuit Connection Example
Pulse Generator
A-phase
B-phase
LIO-06 Connectors and Pin Layouts
• Connectors
ItemDescription
Use Connector10250-52A3PL (Sumitomo 3M)LIO- 06 Connector (RoHS-compatible)
JEPMC-W2064-A5-E0.5 m
Cable for LIO-06
Module
(Single loose wire)
Standard Cable Wiring Table
JEPMC-W2064-01-E1 m
JEPMC-W2064-03-E3 m
10150-3000PE (Sumitomo 3M)Connector Unit (RoHS-compatible)
10350-52A0-008 ( Sumitomo 3M)Shell screw lock typ e
10350-52F0-00 8 (Sumitomo 3M)One-touch lock type
The following shows the standard cable wiring for the JEPMC-W2064 cable.
YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5 83
Page 86
24 Option Module - LIO-06 Module
DANGER
L
LoadExternal Fuse
(Installed bycustomer)
LIO-06 Module Connector Connection Example
An example of LIO-06 module connector connection is shown below.
Relay Terminal Block
+15
V
-15V
Analog Output
Analog Input
Pulse Input
+
+15
V
-15V
+
AO
1
AO_GND
26
AI
2
AI_GND
27
PA+
4
PA-
5
PB+
29
PB-
30
GND
6
GND
31
External Device
L
-10
+10V
FG
External Device
V
-10 +10V
FG
Pulse Generator
+5V
0V
FG
L
L
L
L
L
L
L
L
L
Load
External Fuse
(Installed by customer)
Signal
External Input
Signal
External Output
Z-phase Latch
Input
Digital Input
Digital Output
PILC(24V)
10
PILC(12V)
34
PILC(5V)
9
PIL
35
+5V
Fuse Break
Detection
Circuit
FG Connector
Shell)
13
38
14
39
15
40
16
41
17
42
20
45
21
46
22
47
23
48
24
49
25
50
DICOM
DICOM
DI_00
DI_01
DI_02
DI_03
DI_04
DI_05
DI_06
DI_07
DO_24V
DO_24V
DO_00
DO_01
DO_02
DO_03
DO_04
DO_05
DO_06
DO_07
DO_GND
DO_GND
The cable shield between the external equipment and the junction terminal block should be installed on the external
device side.
84 YASKAWA America, Inc. MP3200iec Hardware Manual YAI-SIA-IEC-5
Page 87
25 Option Module – 218IF-Y1
25Option Module – 218IF-Y1
Outline of Functions
The 218IF-01 Module has an RS-232C serial interface and an Ethernet interface mounted in it. Pe rs onal computers, HMI
devices, and controllers manufactured by other companies can be connected to the 218IF-01 Module via the serial or
Ethernet connectors.
YASKAWA ELECTRIC (SHANGHAI) CO., LTD. BEIJING OFFICE
Room 1011, Tower W3 Oriental Plaza, No.1 East Chang An Ave.,
Dong Cheng District, Beijing 100738, China
Phone 86-10-8518-4086 Fax 86-10-8518-4082
YASKAWA ELECTRIC TAIWAN CORPORATION
9F, 16, Nanking E. Rd., Sec. 3, Taipei 104, Taiwan
Phone 886-2-2502-5003 Fax 886-2-2505-1280
YASKAWA AMERICA, INC.
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture
thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulation s. Therefore, be sure
to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may ap ply.
Specifications are subject to change without notice for ongoing product modifications and improvements.