Xantrex Technology Inc. is a world-leading supplier of advanced power electronics and controls with products from
50 watt mobile units to one MW utility-scale systems for wind, solar, batteries, fuel cells, microturbines, and backup
power applications in both grid-connected and stand-alone systems. Xantrex products include inverters, battery
chargers, programmable power supplies, and variable speed drives that convert, supply, control, clean, and distribute
electrical power.
Trademarks
PV100S 100 kW Grid-Tied Photovoltaic Inverter is a trademark of Xantrex International. Xantrex is a registered
trademark of Xantrex International.
Other trademarks, registered trademarks, and product names are the property of their respective owners and are used
herein for identification purposes only.
UNLESS SPECIFICALLY AGREED TO IN WRITING, XANTREX TECHNOLOGY INC. (“XANTREX”)
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY
TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT,
INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH
INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK.
Date and Revision
May 2005 Revision C
Part Number
152379 Rev C
Contact Information
Telephone: 1 800 670 0707 (toll free North America)
Fax:1 360 925 5143 (direct)
Email:customerservice@xantrex.com
Web:www.xantrex.com
1 360 925 5097 (direct)
About This Manual
Purpose
The purpose of this Operation and Maintenance Manual is to provide explanations
and procedures for operating, maintaining, and troubleshooting the PV100S 100
kW Grid-Tied Photovoltaic Inverter. Installation instructions are available in the
PV100S 100 kW Grid-tied Photovoltaic Inverter Planning and Installation
Manual.
Scope
This Manual provides safety guidelines and information about operating and
troubleshooting the unit.
Audience
This Manual is intended for anyone who needs to operate the PV100S 100 kW
Grid-Tied Photovoltaic Inverter. Operators must be familiar with all the safety
regulations pertaining to operating high-voltage equipment as dictated by local
code. Operators must also have a complete understanding of this equipment’s
features and functions.
Organization
This Manual is organized into five chapters and one appendix.
Chapter 1, “Introduction” contains information about the features and functions of
the PV100S 100 kW Grid-Tied Photovoltaic Inverter.
Chapter 2, “Operation” contains information on the basic operation of the
PV100S 100 kW Grid-Tied Photovoltaic Inverter.
Chapter 3, “Commissioning” contains information on safely commissioning the
PV100S 100 kW Grid-Tied Photovoltaic Inverter.
Chapter 4, “Troubleshooting” contains information and procedures for
troubleshooting the PV100S 100 kW Grid-Tied Photovoltaic Inverter. It provides
descriptions of common situations and errors that may occur and provides
possible solutions for resolving fault conditions. It also provides instructions for
clearing faults manually, if required.
Chapter 5, “Preventative Maintenance” contains information and procedures for
performing preventative maintenance on the PV100S 100 kW Grid-Tied
Photovoltaic Inverter.
Appendix A provides the environmental and electrical specifications for the
PV100S 100 kW Grid-Tied Photovoltaic Inverter.
152379 Rev Ciii
About This Manual
Conventions Used
The following conventions are used in this guide.
WARNING
Warnings identify conditions or practices that could result in personal injury or loss of life.
CAUTION
Cautions identify conditions or practices that could result in damage to the unit or other
equipment.
Important:
serious as a caution or warning.
This Manual contains information for two models of the PV100S 100 kW GridTied Photovoltaic Inverter. One model is designed to operate with a 208 Vac utility
input, and the other model is designed to operate with a 480 Vac utility input.
•The model PV100S-208 100kW Grid-Tied Photovoltaic Inverter
(208 Vac input) will be referred to as the PV100S-208 when it is being
referenced individually.
•The model PV100S-480 100kW Grid-Tied Photovoltaic Inverter
(480 Vac input) will be referred to as the PV100S-480 when it is being
referenced individually.
•When both models are being referenced together, they will be referred to as the
PV100S.
These notes describe things which are important for you to know, but not as
iv152379 Rev C
Abbreviations and Acronyms
ANSIAmerican National Standards Institute
CCU2Converter Control Unit 2
CFMCubic Feet per Minute
CWClockwise
DSPDigital Signal Processor
FPGAField Programmable Gate Array
GUIGraphical User Interface
IEEEInstitute of Electrical and Electronics Engineers
IGBTInsulated Gate Bipolar Transistor
IPMIntelligent Power Module
kcmil1000 circular mils
LANLocal Area Network
About This Manual
LCDLiquid Crystal Display
NFPANational Fire Protection Association
PBXPrivate Branch Exchange
PSLPhase-Shift Loop
POTSPlain Old Telephone Service
PVPhotovoltaic
UFCUUniversal Frontpanel Control Unit
Related Information
You can find more information about Xantrex Technology Inc. as well as its
products and services at www.xantrex.com.
152379 Rev Cv
vi
Important Safety Instructions
SAVE THESE INSTRUCTIONS - DO NOT DISCARD
This manual contains important safety instructions for the PV100S that must be
followed during installation and maintenance procedures.
WARNING: Shock Hazard
Read and keep this Operation and Maintenance Manual for future reference.
Before installing PV100S (either model), read all instructions, cautionary markings, and
all other appropriate sections of this manual. Failure to adhere to these warnings could
result in severe shock or possible death. Exercise extreme caution at all times to prevent
accidents.
WARNING: Shock Hazard
The PV100S enclosures contain exposed high voltage conductors. The enclosure doors
should remain closed with the latches tightened, except during maintenance or testing.
These servicing instructions are for use by qualified personnel who meet all local and state
code requirements for licensing and training for the installation of Electrical Power
Systems with AC and DC voltage to 600 volts. To reduce the risk of electric shock, do not
perform any servicing other than that specified in the installation instructions unless you
are qualified to do so. Do not open the cabinet doors if extreme moisture is present (rain or
heavy dew).
WARNING: Lethal Voltage
In order to remove all sources of voltage from the PV100S, the incoming power must be
de-energized at the source. This may be done at the main utility circuit breaker and by
opening the AC Disconnect and the DC Disconnect Switches on the PV100S. Review the
system configuration to determine all of the possible sources of energy. In addition, allow
5 minutes for the DC bus capacitors, located on the ceiling of the cabinet, to discharge
after removing power.
152379 Rev Cvii
Safety
General Safety Precautions
1. When installing the PV100S use only components recommended or sold by
Xantrex. Doing otherwise may result in a risk of fire, electric shock, injury to
persons, and will void the warranty.
2. Do not attempt to operate the PV100S if it has been dropped, or received more
than cosmetic damage during transport or shipping. If the PV100S is
damaged, or suspected to be damaged, see the Warranty section of this
manual.
3. To reduce the risk of electrical shock, lock-out and tag the PV100S before
attempting any maintenance, service, or cleaning.
Personal Safety
Follow these instructions to ensure your safety while working with the PV100S.
Safety Equipment
Authorized service personnel must be equipped with standard safety equipment
including the following:
•Safety glasses
•Ear protection
•Steel-toed safety boots
•Safety hard hats
•Padlocks and tags
•Appropriate meter to verify that the circuits are de-energized
(600 Vac and DC rated, minimum)
Check local safety regulations for other requirements.
Wiring Requirements
1. All wiring methods and materials shall be in accordance with the National
Electrical Code ANSI/NFPA 70. When sizing conductors and conduits
interfacing to the PV100S, both shall be in accordance with the National
Electric Code ANSI/NFPA 70, as well as all state and local code
requirements.
2. Use copper conductors only with insulation rated for 90 °C.
3. The PV100S has a three-phase output. It is marked with this symbol:
4. The AC power conductor wiring interfacing with the AC terminals in the
Transformer Enclosure are located at T6-X1, T6-X2, and T6-X3. These
terminals should be tightened to a torque value of 420 in-lbs (47.5 Nm) for
model PV100S-208 and model PV100S-480. Conductors terminated to these
terminals must use a crimp-on type ring terminal or compression-type lug.
viii152379 Rev C
Safety
The terminals are one bolt per pole. See the PV100S 100 kW Grid-tied
Photovoltaic Inverter Planning and Installation Manual for the location of
these terminals.
5. The AC power conductor wiring interfacing with the AC terminals in the
Main Inverter Enclosure are located at TB4-A, TB4-B, and TB4- C. These
terminals are to be tightened to a torque value of 275 in-lbs (31.1 Nm) for
model PV100S-208 and model PV100S-480. The terminals will accept a
conductor size of 350 kcmil. See Figure 5-1 on page 5–4 for the location of
these terminals.
6. The AC power conductor wiring interfacing with the AC terminals in the
AC Interface Enclosure are located at S1-2T1, S1-4T2, and S1-6T3. These
terminals should be tightened to a torque value of 310 in-lbs (35.0 Nm) for
model PV100S-208 and to a torque value of 115 in-lbs (13.0 Nm) for model
PV100S-480. See Figure 5-2 on page 5–4 for the location of these terminals.
Also see the cautionary note in the PV100S 100 kW Grid-tied Photovoltaic
Inverter Planning and Installation Manual regarding hardware length.
7. The AC neutral conductor from the utility is terminated in the AC Interface
Enclosure at the TB6-Neutral terminal. This terminal requires the use of a
crimp-on type ring terminal or compression-type lug and should be tightened
to a torque value of 228 in-lbs (25.7 Nm) for model PV100S-208 and model
PV100S-480. See Figure 5-2 on page 5–4 for the location of these terminals.
8. The DC power conductor wiring interfacing with the DC terminals at TB3-1,
TB3-2, and TB3-3 are to be tightened to a torque value of 500 in-lbs
(56.5 Nm) for model PV100S-208 and model PV100S-480. These terminals
will accept a conductor size of 500 kcmil. Keep these cables together as much
as possible and ensure that all cables pass through the same knockout and
conduit fittings, thus allowing any inductive currents to cancel. See Figure 5-3
on page 5–5 for the location of these terminals.
9. This product is intended to be installed as part of a permanently grounded
electrical system per the National Electric Code ANSI/NFPA 70. A copper
ground rod must be installed within three feet of the PV100S enclosure. This
is the single point earth ground for the inverter system. The single point
ground for the system is to be made at the AC ground bus bar (TB2) in the AC
Interface Enclosure. This terminal requires the use of a crimp on type ring
terminal or compression-type lug and should be tightened to a torque value of
420 in-lbs (47.5 Nm) for model PV100S-208 and model PV100S-480.
10. The equipment grounds on the PV100S are marked with this symbol:
11. AC overcurrent protection for the utility interconnect (Grid-tie) must be
provided by the installers as part of the PV100S installation.
CAUTION: Fire Hazard
In accordance with the National Electrical Code, ANSI/NFPA 70, connect only to a circuit
provided with 400 amperes maximum branch circuit overcurrent protection for model
PV100S-208 and only to a circuit provided with 200 amperes maximum branch circuit
overcurrent protection for model PV100S-480.
152379 Rev Cix
Safety
Operational Safety Procedures
Never work alone when servicing this equipment. A team of two is required until
the equipment is properly de-energized, locked-out and tagged, and verified deenergized with a meter.
Thoroughly inspect the equipment prior to energizing. Verify that no tools or
equipment have inadvertently been left behind.
Lockout and Tag
Safety requirements mandate that this equipment not be serviced while energized.
Power sources for the PV100S must be locked-out and tagged prior to servicing.
Each energy source should have a padlock and tag installed on each energy source
prior to servicing.
WARNING: Shock Hazard
Review the system schematic for the installation to verify that all available energy sources
are de-energized. DC bus voltage may also be present. Be sure to wait the full 5 minutes to
allow the capacitors to discharge completely.
The PV100S can be energized from both the AC source and the DC source. To
ensure that the inverter is de-energized prior to servicing, lockout and tag the
PV100S using the following procedure.
1. Open, lockout, and tag the incoming power at the utility main circuit breaker.
2. Open, lockout, and tag the AC Disconnect Switch (S1) on AC interface
assembly.See Figure 1-8 on page 1–12 for the location of the AC Disconnect
Switch.
3. Open, lockout, and tag the DC Disconnect Switch (S2) on DC interface
assembly. See Figure 1-8 on page 1–12 for the location of the DC Disconnect
Switch.
4. Using a confirmed, accurate meter, verify all power to the inverter is deenergized. A confirmed, accurate meter must be verified on a known voltage
before use. Ensure that all incoming energy sources are de-energized by
checking the following locations.
a) Inverter Terminals: TB4-A, TB4-B, TB4-C (Phase A, B, C)
See Figure 5-1 on page 5–4.
b) Utility Terminals: Top of S1-2T1, S1-4T2, S1-6T3
See Figure 5-2 on page 5–4.
c) PV Terminals: Bottom of TB3-1, TB3-2, TB3-3 (PV+, PV-, GND)
See Figure 5-3 on page 5–5.
x152379 Rev C
De-Energize/Isolation Procedure
The following procedure should be followed to de-energize the PV100S for
maintenance.
WARNING
The terminals of the DC input may be energized if the PV arrays are energized. In
addition, allow 5 minutes for all capacitors within the main enclosure to discharge after
disconnecting the PV100S from AC and DC sources.
To isolate the PV100S:
Safety
1. Turn the O
2. Open the DC Interface Disconnect Switch.
3. Open the AC Interface Disconnect Switch.
4. Open the utility connection circuit breaker.
5. Install lockout devices on the utility connection circuit breaker and DC
Disconnect Switch.
N/OFF switch to the OFF position.
Interconnection Standards Compliance
The PV100S has been tested and listed by Underwriters Laboratories to be in
compliance with UL 1741 Static Inverters And Charge Controllers For Use In
Photovoltaic Power Systems, as well as IEEE-929-2000 Recommended Practice
For Utility Interface of Photovoltaic (PV) Systems.
IEEE-929-2000 provides guidance regarding equipment and functions necessary
to ensure compatible operation of photovoltaic systems which are connected in
parallel with the electric utility.
UL1741 is the standard applied by Underwriters Laboratory to the PV100S to
verify it meets the recommendations of IEEE-929-2000.
Refer to both documents for details of these recommendations and test
procedures.
Chapter 1, “Introduction” contains information about the features and
functions of the PV100S 100 kW Grid-Tied Photovoltaic Inverter.
Introduction
Operation Features
The PV100S 100 kW Grid-Tied Photovoltaic Inverter is a UL 1741 listed, utility
interactive, three-phase power conversion system for grid-connected photovoltaic
arrays with a power rating of 100 kW. Designed to be easy to install and operate,
the PV100S automates start-up, shutdown, and fault detection scenarios. With
user-definable power tracking that matches the inverter to the array and adjustable
delay periods, users are able to customize startup and shutdown sequences.
Multiple PV100S inverters are easily paralleled for larger power installations.
The PV100S power conversion system consists of a pulse-width modulated
(PWM) inverter, switch gear for isolation and protection of the connected AC and
DC power sources, and a custom Wye/Wye isolation transformer. Housed in a
rugged NEMA-3R rated, powder-coated steel enclosure, the PV100S incorporates
sophisticated Intellimod
the main power switching devices. An advanced, field-proven, Maximum Peak
Power Tracker (MPPT) integrated within the PV100S control firmware ensures
the optimum power throughput for harvesting energy from the photovoltaic array.
The advanced design of the PV100S includes an EMI output filter and the main
AC contactor located electrically on the utility side of the isolation transformer.
The location of the main AC contactor, and the ability to de-energize the isolation
transformer during times of non-operation, greatly reduces the night-time tare
losses consumed by an idle isolation transformer. An integrated soft-start circuit
precludes nuisance utility-tie circuit breaker trips as the result of isolation
transformer inrush current.
(IPM) Insulated Gate Bipolar Transistors (IGBT’s) as
Additionally, the PV100S integrated controller contains self-protection features
including over and under voltage and frequency safeguards. An integral
anti-island protection scheme prevents the inverter from feeding power to the grid
in the event of a utility outage.
The PV100S includes a local user interface comprised of an O
keypad, and 4-line, 80 character LCD display. A user-friendly Graphic User
Interface (GUI) provides a remote interface for operator interrogation of PV100S
system status, control, metering/data logging and protective functions within the
PV100S. The status, control, and logging features are also supported by the data
modem (included) and can be accessed remotely.
Fixed Unity Power Factor Operation
The Xantrex PV Series of grid-tied inverters maintains unity power factor during
operation. The control software constantly senses utility voltage, and constructs
the output current waveform to match the utility voltage. The PV line of inverters
is not capable of operation without the presence of normal utility voltage, nor is it
capable of varying the output power factor off unity.
N/OFF switch,
1–2152379 Rev C
Peak Power Tracking
An advanced, field-proven, Maximum Peak Power Tracker (MPPT) algorithm
integrated within the PV100S control software ensures the optimum power
throughput for harvesting energy from the photovoltaic array. The peak power
voltage point of a PV array can vary, primarily depending upon solar irradiance
and surface temperature of the PV panels. This peak power voltage point is
somewhat volatile, and can easily move along the I-V curve of the PV array every
few seconds. The MPPT algorithm allows the PV100S to constantly seek the
optimum voltage and current operating points of the PV array, and maintain the
maximum peak PV output power.
Accessible via the UFCU, there are five user settable parameters that control the
behavior of the maximum peak power tracker within the PV100S. As show in
Figure 1-1 on page 1–4, user settable parameters include:
•PPT V Ref (ID# 37),
•I PPT Max (ID#42),
•PPT Enable (ID# 44),
•PPT Rate (ID# 45), and
•PPT V Step (ID# 46).
Operation Features
Upon entering the Power Tracking mode, it takes approximately 20 seconds for
the PV100S to ramp the PV voltage to the “PPT V Ref” set point regardless of the
actual PV voltage.
With the “PPT Enable” set to “0” (power tracker disabled), the PV100S will
regulate the DC Bus at the “PPT V Ref” set point. Regulating the DC bus means
drawing more or less current out of the PV array to maintain this desired voltage.
With the “PPT Enable” set to “1” (power tracker enabled), followed by the
expiration of the “PPT Rate” (MPPT decision frequency), the MPPT will reduce
the reference voltage by an amount equal to the “PPT V Step” value.
At this point the MPPT will compare the amount of AC output power produced to
the previous amount of AC power produced by the PV100S. If the output power
has increased, the next change made (after “PPT Rate” has again expired) to the
reference voltage, will be in the same direction.
Conversely, if the power comparison proves undesirable, the power tracker will
reverse the direction of the change to the “PPT_V Step”. The MPPT algorithm
within the PV100S will then continue this ongoing process of “stepping and
comparing” in order to seek the maximum power throughput from the PV array.
The changes made by the MPPT to the reference voltage are restricted to ± 20% of
“PPT V Ref” and by the maximum and minimum PV input voltage (600 and
300 volts respectively). Also, the MPPT will not attempt to produce power greater
than that allowed by the “I PPT Max” set point. If available PV power is above the
maximum allowable power level of the PV100S, the MPPT will increase voltage
as needed to maintain output power below rated maximum.
152379 Rev C1–3
Introduction
Optimization of the PV100S MPPT will result in an increase in energy production.
The user is encouraged to study the PV array’s I-V curves and to adjust the MPPT
user settable parameters accordingly.
Figure 1-1
Maximum Peak Power Tracking
Utility Voltage/Frequency Fault Automatic Reset
In the event of a utility voltage or frequency excursion outside of preset limits, the
PV100S will stop operation and display a fault at the operator interface. Once the
utility voltage has stabilized within acceptable limits for a period of at least
5 minutes, the PV100S will automatically clear the fault and resume normal
operation. Voltage and frequency fault setpoints are detailed later in this section.
1–4152379 Rev C
Safety Features
Anti-Island Protection
A condition referred to as "Islanding" occurs when a distributed generation source
(such as the PV100S Grid-tied Photovoltaic Inverter) continues to energize a
portion of the utility grid after the utility experiences an interruption in service.
This type of condition may compromise personnel safety, restoration of service,
and equipment reliability.
The PV100S employs a method for detecting the islanding condition using a
Phase-Shift-Loop (PSL). This method is implemented in the CCU2 to prevent
islanding of the PV100S. The CCU2 continuously makes minor adjustments to
the power factor phase angle above and below unity. In the event of a utility
interruption or outage, these adjustments destabilize the feedback between the
inverter and the remaining load, resulting in an over/under frequency or voltage
condition.
Upon detection of such a condition, the PV100S then performs an immediate
orderly shutdown and opens both the main AC and DC contactors. The fault
condition will remain latched until the utility voltage and frequency have returned
to normal for at least 5 minutes.
This method has been extensively tested and proven to exceed the requirements of
IEEE-929 (Recommended Practices for Utility Interface of Photovoltaic [PV]
Systems) and UL-1741 (Static Inverters and Converters for use in Independent
Power Systems).
Safety Features
PV Ground Fault Detection
The PV100S is equipped with a ground fault detection circuit by means of a
Hall-effect current transducer (CT3). This circuit is active when the PV array is
properly grounded. In the event of a ground fault exceeding 10 amps DC, the
PV100S will execute an immediate orderly shutdown, open both the main AC and
DC contactors, and report a ground fault on the LCD of the UFCU. The PV100S
will remain faulted until the ground fault is remedied and the advisory is cleared at
the operator interface.
For additional information, seeChapter 4, “Troubleshooting”.
DC Over-voltage Detection
In the event of DC voltage greater than 600 Vdc, the PV100S will execute an
orderly shutdown and will report a fault to the operator interface. If DC voltage
remains greater than 600 Vdc, the PV100S may be irreparably damaged.
See Chapter 4, “Troubleshooting” for further information on this fault condition.
152379 Rev C1–5
Introduction
Physical Characteristics
The PV100S comes in two modules comprised of six enclosures to house the
electronics described above. The first module includes the Main Inverter
Enclosure, Inductor Enclosure, DC Interface Enclosure, and Communications
Enclosure. The second module includes the Transformer Enclosure and AC
Interface Enclosure.
These components are identified in Figure 1-2.
Power Electronics Matrix
Communications
Enclosure
AC Interface
Enclosure
Figure 1-2
Transformer
Enclosure
PV100S Major Components
THIS UNIT EMPLOYS FIELD AD J U STABLE VOL T AGE AND
FREQUENC Y SETPOINT S AND TIME DELAYS. THEY ARE
FACTORY SET IN COMPLIANCE WITH UL1741 AND MAY
ONLY BE CHANGED BY TRAINED SERVICE TECHNICIANS
WITH APPR OVAL BY BOTH TH E LOCAL UTILITY AND
EQUIPMEN T OWNER.
REFER TO T H E OPERATOR’S
MANUAL FOR FURTHER DETAI L.
TYPE 3R
U
®
L
61CN
LISTED UTILITY IN TERACTIVE PHASE INVERTER
Max. system DC
DC
Voltage 6 00V
Max. operating
DC
current 319A
Range of oper.
Volts. 330-480V
DC
Max. array abort
circuit current
DC
480A
Nominal output
voltage 208V
DC
Maximum utilit y
feedback current
DC
178A
Max. continuous
output current
DC
278A
Maximum operating ambient 50 °C
MODEL NUMBER:
PV100S-208
SERIAL NUMBER:
XXXX
L-152462 Rev A
Mfg - Arl
Max. input
AC
current 3A
Oper. Volt. Range
AC
183-229 L-L
Oper. Freq. range
AC
59.3 - 60.5
Normal output frequency
60 Hz
AC
Max. output
overcurrent
AC
protection
400A
Maximum output
fault current
AC
323 A
Max continuous
AC
output power
100 kVA
MANUFACTURED
04
MAY
SEP
JAN
FEB
JUN
05
OCT
06
APR
JUL
NOV
07
MAR
AUG
DEC
987F1
^
^
F2654
F3MENU
32
.
-10
F4ENTER
0
I
WARNING:
This is a class A product.
In a domestic environment this
product may cause radio
interferences, in which case, the user
may be required to take adequat e measures.
Main Inverter
Enclosure
Inductor
Enclosure
PV
DISCONNECT
WARNING
RISK OF ELECTRICAL SHOCK
DO NOT REMOVE COVER,
NO USER SERVICEABLE
PARTS INSIDE,
STORED ENERGY IN CAPACITOR.
ALLOW AT LEAST 5 MINUTES
AFTER DISCONNECTING ALL
SOURCES OF SUPPLY.
REFER SERVICING TO QUALIFIED SERVICE
PERSONNEL.
BOTH AC AND DC VOLTRAGE SOURCES ARE
TERMINAED
INSIDE THIS EQUIPMENT.
EACH CIRCUIT MUST BE
INDIVIDUAL DISCONNECTED
BEFORE SERVICING.
WHEN THE PHOTOVOLTAIC ARRAY
IS EXPOSED TO LIGHT,
IT SUPPLIES A DC VOLTAGE
TO THIS EQUIPMENT.
DC Interface
Enclosure
1–6152379 Rev C
Main Inverter Enclosure
The PV100S Main Inverter Enclosure is NEMA-3R rated and contains the power
distribution panel, the converter control unit (CCU2), and power electronics
matrix. Also found within the Main Inverter Enclosure are some of the system
protection devices (such as the sense and control power fuses).
Power Distribution Panel
This panel contains many of the Electromechanical, protective, and control power
components necessary to support the operation of the PV100S.
Converter Control Unit (CCU2)
The CCU2 is a Digital Signal Processor (DSP) based control board that performs
numerous control and diagnostic functions associated with PV100S operation. Its
most significant tasks are control of PV100S electromechanical components and
power electronics converters, signal conditioning for high voltage signal inputs
and communication with the Universal Front Panel Control Unit, and system
sensors. The CCU2 also contains the necessary DC power supplies to support its
operation.
Physical Characteristics
Power Electronics Matrix
The power electronics converter is located at the top of the PV100S main inverter
enclosure. The matrix is comprised of six switching transistors (IGBT’s),
transistor gate drive electronics, a laminated power bus, DC capacitor bank, and
an aluminum extrusion heatsink with a cooling fan. The fan is located above the
matrix heatsink.
The PV array is tied logically to the matrix DC bus within the DC interface
enclosure. The embedded CCU2 control unit manages the transfer of power
between the DC bus and the utility grid.
Inductor Enclosure
The Inductor Enclosure is NEMA-3R rated. It contains the necessary filter
components to ensure the PV100S line current meets IEEE-519 (1992, standard
Practices and REquirements for Harmonic Control in Electrical Power Systems)
and UL 1741 (2001, Static Inverters and Converters for use in Independent Power
Systems) harmonic distortion requirements. Mounted on the right side of the
lower enclosure is an inductor fan to allow cooling of the line filter components
within. This enclosure also serves as the mounting base for the PV100S main
enclosure.
152379 Rev C1–7
Introduction
DC Interface Enclosure
The DC Interface Enclosure is NEMA-3R rated. The DC interface serves as the
connection interface between the PV array and the PV100S. This enclosure is
where the DC Disconnect Switch and DC contactor reside.
CAUTION: Equipment Damage
The fuses within the PV100S are intended for protecting the PV100S control circuitry
only. They are not intended to provide protection for the PV array or external cabling.
DC Disconnect Switch
DC Interface Enclosure
Figure 1-3
DC Interface Enclosure
Transformer Enclosure
The Transformer Enclosure is NEMA-3R rated. The main isolation transformer
inside electrically isolates the PV100S from the utility power. Voltage-sensing
circuit wiring and soft-start circuit pass through the Transformer Enclosure from
the AC Interface Enclosure to the Main Inverter Enclosure.
AC Interface Enclosure
The AC Interface Enclosure is NEMA-3R rated. The AC interface serves as the
connection between the utility and the isolation transformer. This enclosure is
where the AC line fuses and AC disconnect switch reside. Also included in the
AC Interface Enclosure are the main AC contactor and transformer soft-start
circuit.
1–8152379 Rev C
AC Interface Enclosure
Physical Characteristics
AC Disconnect
Figure 1-4
AC Interface Enclosure and Transformer Enclosure
Communications Enclosure
The Communications Enclosure is NEMA-4 rated. It contains the hardware to
enable a personal computer to connect to the unit, either directly or remotely.
Hardware could include a POTS Connect Kit, a Wireless Connect Kit, or an
Ethernet LAN kit, or a Direct Connect Kit.
Switch
Transformer Enclosure
Communications Enclosure
Communications Enclosure
Figure 1-5
PC Connections in the Communications Enclosure
RS232/FO
Converter
MultiTech 56K
Modem
SA2 Surge
Arrestor
POTS connection option shown.
Enlargement
152379 Rev C1–9
Introduction
Operator Interface Controls
Operator interface controls are located on the front door of the main inverter
enclosure. These controls include an ON/OFF Switch, 4-line LCD display and
keypad called the Universal Frontpanel Control Unit (UFCU). Additionally there
is an AC and DC Disconnect on the AC Interface Enclosure and the DC Interface
Enclosure Doors.
Communication
Enclosure
AC Disconnect
Switch
Figure 1-6
AC Interface Enclosure
(AC Side View)
PV100S Operator Interface Components
Display
Universal
Frontpanel
Control
(UFCP)
ON/OFF
Switch
Main Enclosure Door Interlock Switch
LCD
DC Disconnect
Switch
DC Interface
Enclosure
Main Inverter Enclosure
(Front View)
The front door of the PV100Smain enclosure is equipped with an interlock switch
to preclude operation while the front door is open. Opening the door of the main
inverter enclosure will initiate an immediate controlled shutdown of the PV100S
and opens both the main AC and DC contactors. The main AC and DC contactors
cannot be closed unless the door’s interlock is in the engaged position. The
PV100S is prevented from being restarted until the door is again closed and the
switch is in the engaged position.
It is required that the PV100Smain enclosure door must be locked during normal
operation. The door interlock switch does NOT remove all hazardous voltages
from inside the inverter. Before attempting to service the PV100S, follow the
de-energize Lockout and Tag procedure on
1–10152379 Rev C
page 5–3.
On/Off Switch
Operator Interface Controls
WARNING: Shock Hazard
Disengaging the main enclosure door interlock switch does NOT remove all hazardous
voltages from inside the inverter. Before attempting to service the PV100S, follow the
de-energize Lockout and Tag procedure on page 5–3.
The PV100Sincorporates a maintained position ON/OFF switch located on the
front door of the main enclosure. Under normal conditions, the
the O
N position. Turning the switch to the OFF position will initiate an immediate
ON/OFFswitch is in
controlled shutdown of the PV100Sand open both the main AC and DC
contactors within the unit. The main AC and DC contactors cannot be closed
unless the switch is in the
restarted until the O
ON position. The PV100Sis prevented from being
N/OFFswitch is turned back to the ONposition.
WARNING: Shock Hazard
Turning the ON/OFF switch to the OFF position does NOT remove all hazardous voltages
from inside the inverter. Before attempting to service the PV100S, follow the de-energize
Lockout and Tag procedure on page 5–3.
Figure 1-7
152379 Rev C1–11
On/Off Switch
Introduction
AC and DC Disconnect Switches
Both AC and DC interface enclosures are equipped with lockout hasps for
personnel safety. The enclosure doors should not be opened while the PV100Sis
operating.
The switch handles and shafts provide a door interlock for both the AC and DC
interface enclosures. The doors cannot be opened when the switch is in the
position.
The DC Disconnect switch is equipped with an auxiliary contact block which
enables the switch to be used as a load break DC disconnect. In the event the DC
Disconnect switch is opened while the PV100Sis processing power from the PV
array, the early-break contact block will signal the CCU2 (Converter Control
Unit 2) to stop processing power prior to opening the DC Disconnect switch.
Additionally, opening the DC Disconnect switch will cause the PV100S to
execute an immediate orderly shutdown, open both the main AC and DC
contactors, and report a PV disconnect fault on the LCD of the UFCU.
ON
DC Disconnect
Switch
AC Disconnect
Switch
AC Interface Enclosure
Figure 1-8
AC and DC Disconnect Switches
Communication Features
The PV100S provides two types of information to the user:
•system status and/or fault information, and
•data logging information.
System status and fault information can be accessed using the Universal Front
Panel Control Unit (UFCU) or a personal computer using the Xantrex Solar
Graphic User Interface (GUI) software. Data logging requires the use of a PC
using the GUI software.
DC Interface Enclosure
1–12152379 Rev C
System Status and Fault Reporting
Basic system status and all fault conditions rising from within the PV100Sare
reported to the UFCU. The unit stores the time and details of all faults in
non-volatile memory. The 4-line LCD will display a hexadecimal value and a
brief text description of the fault.
This information can also be accessed using a personal computer using the GUI
software either directly or remotely.
Types of status information include:
•Current Operating State or Goal State
•Fault Code (if applicable)
•Inverter State
•Line Voltage and Current
•Inverter Matrix Temperature
•Inverter Power
•PV State
•PV Voltage and Current
•PV Power
•Grid Frequency
•Peak Power Tracker Enabled
Communication Features
Data Logging
The inverter stores data values and software metrics for debugging. These values
are stored within the CCU2 controller board in non-volatile memory. Data logging
requires the use of a PC connection using the Xantrex Solar Graphic User
Interface (GUI) software.
The Data logging features include:
•Operational Values
•Internal Metrics
•Data Log Acquisition
•Graphic Data Analysis
•Fault Log Acquisition
•Software Upgrade
•Accumulated Values
•Configurable Parameters
For details on using this feature, consult the GUI Help program.
152379 Rev C1–13
Introduction
Communication Methods
The PV100S communicates system status information to the user using the
following methods.
•The Front Panel Control Unit (UFCU) Display
•PC Connection (Direct or Remote) - Xantrex Solar Graphic User Interface
(GUI) Software required. Communication with a PC requires the selection of
one of the following options.
•Remote Connection -- This method has three options available. One of
these options will be field-installed prior to commissioning.
•POTS Connection
•Wireless Connection
•Ethernet LAN Connection
•Direct Connection -- This method is most commonly used by field
technicians for commissioning and troubleshooting purposes.
Important:
to support a PC connection. (i.e., making arrangements for an analog phone line, data line,
wireless service or local area network.)
The customer is responsible for providing the appropriate support service
Universal Front Panel Control Unit (UFCU)
The UFCU keypad is located on the front of the Main Inverter Enclosure to
manipulate and view system operation and status.
The keypad is comprised of 20 touch-sensitive keys that provide a means to
navigate through the menus and alter user-changeable settings.
Communications
Enclosure
LCD Display
Universal Front Panel
Control Unit (UFCU)
Figure 1-9
LCD Display and UFCU Location
See “UFCU Keypad Operation and LCD Display” on page 2–6 for details.
1–14152379 Rev C
PC Connection Methods
Personal computers can be used to access the system status and programming
features of the PV100S. A computer can be connected either directly or remotely.
1. Remote Connect - uses one of the three kits below.
•POTS Kit - uses a MultiTech® 56K Modem, RS232/Fiber Optic
•Wireless Kit - uses a GSM Wireless Modem.
•Ethernet LAN Kit - uses a data communication device to enable the unit
2. Direct Connect - This method is used for troubleshooting. It uses a
RS232/Fiber Optic Converter (configured for a PC), a DB25-to-DB25 gender
changer, and a DB25-to-DB9 Serial Cable.
Software is included to provide a graphic user interface that relates important
system information. This software is called Xantrex Solar Graphic Interface
(GUI). See “Minimum System Requirements” on page 2–26 for minimum system
requirements.
Communication Methods
Converter (configured for ethernet) and SA2 Surge Arrestor.
to connect to a local area network.
Communications
Enclosure
Communications Enclosure
Enlargement
RS232/FO Converter
MultiTech 56K Modem
SA2 Surge Arrestor
POTS connection option shown.
Figure 1-10
152379 Rev C1–15
PC Connections in the Communications Enclosure
Introduction
POTS Access
Figure 1-11 illustrates the PV100S connected remotely to a personal computer.
Figure 1-11
POTS Access
Wireless Access
Figure 1-12 illustrates the PV100S connected remotely to a personal computer
using a wireless network.
Figure 1-12
1–16152379 Rev C
Wireless Access
Ethernet LAN Access
Communication Methods
The PV100S can be remotely accessed through a local area network.
Figure 1-13
Direct Access
Figure 1-14
Ethernet LAN Access
Figure 1-14 illustrates the PV100S connected directly to a personal computer.
Direct Access
152379 Rev C1–17
Introduction
GUI Software Features
Read-only MenuThe GUI software provides access to the following “Read-only Menu”
information. See Table 2-2, “Read Menu Descriptions” on page 2–11 for a
specific list of available parameters.
•Operational Values
•Internal Metrics
Write-MenuThe GUI software provides control of the following system parameters. These
parameters are in the Write Menu.
•User-Configurable Parameters. See Table 2-5, “Write Menu Parameters” on
page 2–16 for a specific list of available parameters.
Data LoggingThe GUI software provides the following data collection/reports (data logging).
These features are not available through the Universal Front Panel Control Unit
(UFCU).
•Operational Values - The present operational values (such as PV voltage and
current, grid network voltage and frequency, or inverter current and power)
can be read remotely.
•Internal Metrics - The inverter also maintains internal software metrics for
remote review by Xantrex field service or engineering.
•Data Log Acquisition - The inverter maintains a data log in non-volatile
memory for up to 30 days, after which the oldest data is overwritten. The GUI
reads this data and updates a local file that can be imported to a spreadsheet.
•Graphic Data Analysis - Graphical charts of any operational values from the
data log of an inverter can be displayed remotely.
•Fault Log Acquisition - The inverter maintains a log of faults (description,
time and date). This can be viewed remotely. The fault log is stored in the
inverter’s non-volatile memory, and is also read by the GUI and stored at its
computer in a text file.
•Software Upgrade - The system software of the inverter can be upgraded
remotely through the GUI software running on a Windows computer. The
GUI reads the file containing the upgrade from Xantrex Technology, and then
sends it to the inverter. The software upgrade method employs high-speed
streaming with error detection and correction to allow error-free transmission
of data even over a noise-ridden telephone connection.
•Accumulated Values - The inverter tracks power production statistics, such as
total energy sold, operating hours, power production hours, peak power and
energy, energy by month, and energy by the hour. Accumulated values are
stored in the inverter’s non-volatile memory, and are also read by the GUI and
stored at its computer in a text file.
•Configurable Parameters - The configuration parameters controlling the
inverter’s operation can be viewed and changed from a remote GUI.
See Table 2-3 on page 2–14 for a list of the Data Logging parameters available.
1–18152379 Rev C
2
Operation
Chapter 2, “Operation” contains information on the basic operation of
the PV100S 100 kW Grid-Tied Photovoltaic Inverter.
Operation
Description of System Operation
Overview
The PV100Sis a fully automated grid-interactive photovoltaic inverter. System
startup, system shutdown, PV power tracking, and fault detection scenarios are all
governed and monitored by the CCU2 controller within the PV100S. Manual
interaction or control of the inverter is necessary only in the event of a system
fault. Additionally, the following conditions govern operation of the PV100S.
•Stable utility AC voltage and frequency as specified in Table A-3 must be
present for all states of operation.
•PV voltage as specified in Table A-3 must be present.
•With the exception of the Matrix Test state, the
front door of the PV100S main inverter enclosure, must be switched to the
position for all operating states.
•The door of the main inverter enclosure must be closed with the door
interlock switch in the engaged position.
•Both the AC and DC Disconnect switches must be in the ON or closed
position.
•Fault conditions must not be present.
ON/OFF switch, located on the
ON
Faults
Fault states are automatic from any state of operation. In the event of a fault
condition, the PV100S will immediately stop processing power and execute an
immediate orderly shutdown, open both the main AC and DC contactors, and
remain in a faulted state until the fault is remedied and cleared (manually or
automatically).
Most faults are latching, and only those faults associated with grid disturbances
are auto-clearing and thus enable the PV100S to restart after a 5 minute delay
period. All fault conditions arising from within the PV100Sare reported to the
UFCU (Universal Frontpanel Control Unit). The 4-line LCD on the UFCU will
display a hexadecimal value (fault code) and a brief text description of the fault.
Once the cause of the fault has been identified and corrected, and it is determined
to be safe to proceed, PV100S faults may be cleared from the UFCU keypad or
via the remote GUI.
See “Clearing Faults Manually” on page 4–3 for instructions on this procedure.
2–2152379 Rev C
System State: Key Disable
Inverter State: Standby
PV State: Sleep
POWER UP
INITIALIZING
PV contactor opened.
Inverter matrix off.
Grid contactor open.
Green LED on. Red off.
DISABLE
PV contactor open.
Inverter matrix off.
Grid contactor open.
Enable Key
Description of System Operation
KEY
Inverter matrix off. Line contactor open
System State: Shutdown
Inverter State: Standby
PV State: Sleep
PV Voltage > 440V
(PV V START)
System State: Shutdown
Inverter State: Standby
PV State: Wake Up
Grid Contactor K1 Close
System State: Shutdown
Inverter State: Main Settling
PV State: Wake Up
Inverter Matrix On
System State: Power Tracking
Inverter State: On Line
PV State: On Line
SLEEP
for at least 10
seconds
WAKE UP
for 5.0 min.
(PV T START)
K1 Settle
for .5 seconds
ON LINE
PV Voltage >
PV Voltage <
PV Voltage < 440V (PV V Start)
PV Voltage <
PV Power < 1.0kW (PV P STOP)
PV Power > 1.0kW (PV P STOP)
300V
Close K2
50V (300V - 250V
300V (Min. Oper.)
margin)
TEST
for 5.0 min.
(PV T STOP)
PV Contactor Closed
PV Contactor Open
PV Voltage <
5 minutes elapsed
300V (Min. Oper.)
Retrun to SleepState
Return to Sleep State
System State: Power Tracking
Inverter State: On Line
PV State: Sleep Test
FAULT
Fault from any State Fault Cleared
PV contact o r opened.
Inverter matrix off.
Grid contactor open.
Red LED on. Green off.
Bold
- constant value
Italic- User settable.
Figure 2-1
Underline
Operating States Flow Chart
- Default value.
152379 Rev C2–3
Operation
Operating States
A state machine implemented within the CCU2 control software governs the
operation of the PV100S with clearly defined transitions between its operating
states. There are five steady-state operating states and numerous intermediate
transition states.
•Power Tracking
•Transition
•Shutdown
•Fault
•Manual Current
•Matrix Test
•Automatic Sleep Test
Power Tracking
This is the standard operating state of the PV100S. The PV100S maximum power
tracker will demand maximum power from the PV array, given sufficient PV
irradiance.
Trans ition
The user should be aware of the following conditions governing PV100S state
transitions:
•Qualified utility voltage must be present for all states of operation.
•Fault states are automatic from any state of operation. A fault will cause the
PV100S to immediately stop processing all power. The fault condition will be
reported to the operator interface LCD.
•Most PV100S faults are latching and must be cleared at the operator interface
keypad before transitioning to another operating state.
•The
The intermediate transition states provide an orderly progression from one
operating state to the next. The user has the ability to manually transition the
PV100S between operating states via the operator interface keypad or remotely
using the GUI software. Manual transitions are initiated by entering a “Goal
State”, where the goal state is the desired operating state. Given all applicable
system parameters are within acceptable limits, and the request is valid within the
state machine, the PV100S will initiate the proper sequence of operations
necessary to progress to the requested goal state. Refer to Figure 2-1 on page 2–3
for an illustration of valid state transitions.
ON/OFF switch, located on the front door of the PV100S, must be in the
ON position for all operating states except Matrix Test, in which case it must
be in the
OFF position.
2–4152379 Rev C
Shutdown
Fault
Manual Current
Operating States
The line interface controller is idle. The CCU2 monitors the status of the PV array
and utility grid, waiting in standby until the PV array is available to produce
power to the grid.
The PV100S has encountered a fault condition. When this happens, regardless of
the PV100S state of operation, the PV100S will stop processing all power and
execute an orderly system shutdown. A description of the fault and fault code will
appear on the operator interface LCD. The Fault state may be cleared from the
keypad once the cause of the fault has been corrected. See Chapter 4,
“Troubleshooting” for a complete description of all fault codes.
This operating state is provided to evaluate the existing PV array V-I
characteristics. The PV controller regulates a constant amount of PV current as
commanded by the user from the operator interface keypad, up to the PV current
limit of the PV100S. If the user commands more PV current than is available, the
DC bus voltage will drop below the minimum bus voltage level and the PV100S
will enter Shutdown mode.
Matrix Test
This operating state is provided to verify proper operation of the matrix and
associated control electronics. There is no power transfer between the PV and
utility in this mode. The
PV100S to enter this state.
Automatic Sleep Test
Toward the end of every solar day, the PV100S automatically determines when to
stop producing power dependent upon the output power of the inverter. As the net
output power of the PV100S nears zero, a timer is started to allow the inverter to
ride through any brief irradiance reductions.
ON/OFF switch must be in the OFF position for the
152379 Rev C2–5
Operation
Operator Interface
The purpose of the operator interface is to provide a means of communicating
critical operational information to and from the unit. This communication occurs
between the operator and the UFCU Keypad and LCD display or between the
operator and a personal computer running the Xantrex Solar GUI software.
UFCU Keypad Operation and LCD Display
The UFCU keypad is located on the front of the Main Inverter Enclosure to
manipulate and view system operation and status.
The keypad is comprised of 20 touch-sensitive, peizio electric keys that provide a
means to navigate through the menus and alter user-changeable settings.
•Four function keys are available.
•F1 - While in the R
In the W
RITE Menu, it jumps to set “Goal:”.
•F2 - While in the R
While in the W
•F3 - While in the R
While in the W
•F4 - While in the W
function key confirms the change in goal state.
•Two Navigation keys are available.
•\/ or /\ moves forward or backward within the menu structure. Upon
reaching the end of the menu, it will roll-over to the beginning of the
same menu.
•Ten numeric keys (0 through 9), two symbol keys (“.” and “-”), and an
NTER” key are available for entering user-settable parameters.
“E
•The “M
ENU” key allows you to enter the password-protected Write
parameters.
EAD Menu, this key is used to clear faults.
EAD Menu, this key jumps to display “INV A Volts”.
RITE Menu, this key jumps to display “Max AC Volts %”.
The Universal Front Panel Control Unit (UFCU) and LCD
LCD Display
UFCU Keypad
LCD Display - Initialization Screen
Any time AC power is applied to the unit, the LCD display will cycle through the
following displays while the system initializes. Once it’s done with this process,
the standard display will appear.
The Standard Display provides the following information:
•First Line - System Status (ID 1)
•Second Line - Inverter Status (ID 4)
•Third Line - PV Status (ID 13)
•Fourth Line - Goal State (ID 2)
152379 Rev C2–7
Operation
Menu Structure
The operator interface consists of three levels:
•R
EADMenu - operation information provided to the user from the PV100S.
The Read Menu consists of all operational values, the date and time. These
can be viewed any time the PV100S has control power.
•W
RITEMenu - operational parameters provided to the PV100S from the user.
The Write Menu consists of a goal state sub-menu, and all system
configurable parameters. The Write Menu is password protected and may
only be changed by trained service technicians. In particular are parameters
relating to utility protection setpoints.
•Data Logging - the collection of specific parameters values over a period of
time. The data logging feature is only available if using the GUI. However,
the user does have the ability to view a snapshot of specific data using the
“Read by ID” feature. See Table 2-3 on page 2–14 and Table 2-4 on
page 2–14.
Universal Front Panel Control Unit (UFCU) and (if used) at the computer running
the GUI monitoring program. Making changes to the parameters within the Write
Menu is done with the UFCU keypad or the GUI software program and requires a
password.
Important:
the factory to the limits mandated by UL 1741. Any changes to these setpoints should be
agreed upon by the local utility and the equipment owner.
Specific grid-interface parameters within the WRITE Menu have been set in
Upon system powerup, the operator interface LCD will display the system
operating state on the first line. The inverter’s state of operation will be reported
on the second line. The PV Array’s state of operation will be reported on the third
line. The Goal target will be reported on the fourth line.
Important:
the standard display if there is no input for more than 2 minutes.
While in the WRITE Menu, the operator interface display will reset itself to
Standard Display
Password
READ Menu
Enter Goal State
RITE Menu
W
Figure 2-4
2–8152379 Rev C
Operator Interface Menu Diagram
Set Date/Time
Change
Parameters
READ Menu
The READ Menu includes the following information:
•Current Operating State or Goal State
•Fault Code (if applicable)
•Inverter State
•Line Voltage and Current
•Inverter Matrix Temperature
•Inverter Power
•PV State
•PV Voltage and Current
•PV Power
•Grid Frequency
•Peak Power Tracker Enabled
Table 2-1 shows how the third and fourth line of the LCD will change as the
operator continues scrolling through the Menu. Table 2-2 on page 2–11 provides
a detailed description of R
EAD Menu operational values that are displayed on the
LCD.
To Display Any Operational Value in the READ Menu
From the Standard Display, use the /\ or \/ keys on the operator interface keypad
to scroll through the R
display the appropriate information. See Table 2-1.
•The \/ key will scroll downward through the menu.
•The /\ key will scroll upward through the menu.
EAD Menu. The fourth line of the display will change to
Operator Interface
Table 2-1
Read Menu ValueFourth Line of the LCD
Software Version (not shown)CCU Vx.xx FP V.x.x
Date/Time (not shown) Feb-14-2005 10:01:55
Read by ID#Value by ID#
Inverter A-B VoltINV A Volts:
Inverter B-C VoltINV B Volts:
Inverter C-A VoltINV C Volts:
Inverter A-B CurrentINV A Amps:
Inverter B-C CurrentINV B Amps:
Inverter C-A CurrentINV C Amps:
P V Vol ta geP V Vol ts :
PV CurrentPV Amps:
PV PowerPV kW:
Grid FrequencyGrid Freq:
PV PPT EnablePV PPT:
Ground CurrentGround I:
Accumulated PowerKWH:
Scrolling through the Read Menu Parameters
Upon reaching the end of the menu, it will go back to the beginning of the menu.
System: PWR Tracking
Inv: Online
Hit ENTER or "." "-"
Value by ID#
3. Press the \/ button again.
4. Text on Fourth line displays
the Date and Time.
5. Press the \/ again.
6. Third and Fourth line
displays the “Read by ID”
feature.
7. Either enter a Read
parameter ID number to
jump to the specified
parameter or press the \/
again continue scrolling
through the Read Menu.
The fourth line will continue
to change as described in
Table 2-1.
System: PWR Tracking
Inv: Online
Hit ENTER or "." "-"
Value by ID#
where * can be any one of the states
listed in the description for this
parameter.
Ground Current
Displays as:
Ground I:
kW Accumulated
Displays as:
kWH:
PV Power16kW
Grid Frequency17Hz
Indication as to whether the PPT is enabled or disabled.
Off (0)
On (1)
18N/A
Ground Current19N/A
kW Accumulated 20N/A
2–12152379 Rev C
READ-by-ID
Operator Interface
The Read-by-ID feature supports the ability of the user to view any Read or Write
parameter available within the menu structure. It also provides a means to view
data logging and accumulated values information. See Table 2-2 for a list of the
Read Menu parameters. See Table 2-3 for a list of data logging menu parameters.
See Table 2-4 for a list of accumulated values parameters.
To use the Read-by-ID Feature:
1. From the Standard Display, press the \/ key three times to scroll downward
through the menu to the Read-by-ID Menu item. Stop when the 3rd and 4th
line of the display change as shown in Figure 2-6.
2. Press <E
NTER> to enter the Read-by-ID feature.
3. Use the keypad to enter the ID number of the Data Log Configuration or
Accumulated Value ID number and press <E
EAD Menu items and their ID numbers.
R
NTER>. See Table 2-2 for a list of
a) Press the “.” button to move upward in the Menu structure.
b) Press the “-” to move backward in the menu structure. These keys only
function in the Read-by-ID feature.
System: Shutdown
Inv: Standby
Hit ENTER or "." "-"
Value by ID#
Use the keypad to enter the desired
ID number and press <
The display will change as shown and will
show the requested value.
where:
xxx = any Menu ID
xxx = operational value of Menu ID
ENTER>.
Press <ENTER> when this
screen appears to access the
Read-by-ID feature.
System: Shutdown
Inv: Standby
Hit ENTER or "." "-"
Read ID# xxx: xxx
Use the “.” and “-” buttons to scroll backward
and forward within the Read-by-ID menu.
Figure 2-6
Read-by-ID Feature
152379 Rev C2–13
Operation
Table 2-3 provides a list of the Data Logging Menu parameters.
Table 2-3
ID#Usage
300Data Log Daily Rate in Minutes
301ID# of 1st parameter to be logged
302ID# of 2nd parameter to be logged
303ID# of 3rd parameter to be logged
304 through 390ID#s of the 4th through the 90th parameter to be logged.
391Not available
392Data Log Nightly Rate in Minutes
393First Daytime Hour
394First Night-time Hour
395Size of Data Log in Words
396Words per record
397Count of parameters per record
398Offset from Data Log or next log record
299Address of the Data Log
Data Logging Menu
Table 2-4 provides a list of the Accumulated Values Menu parameters.
Table 2-4
ID#Usage
600Accumulated Operating Hours on actual day
601Accumulated Operating Hours in actual week
602Accumulated Operating Hours in actual month
603Accumulated Operating Hours in actual year
604Accumulated Operating Hours since Commissioning
605Accumulated Sell Mode Hours on Actual Day
606Accumulated Sell Mode Hours in actual week
607Accumulated Sell Mode Hours in actual month
608Accumulated Sell Mode Hours in actual year
609Accumulated Sell Mode Hours since Commissioning
610-619Not available
620Accumulated Power Sold Hours on actual day
621Accumulated Power Sold Hours in actual week
622Accumulated Power Sold Hours in actual month
623Accumulated Power Sold Hours in actual year
624Accumulated Power Sold Hours since Commissioning
625Accumulated Power Sold Hours since last reset
626-629Not available
630Peak Power monitored today
Accumulated Values Menu
2–14152379 Rev C
Operator Interface
WRITE Menu
Table 2-4
ID#Usage
631Peak Power monitored this week
632Peak Power monitored this month
633Peak Power monitored this year
634Peak Power monitored since Commissioning
635-639Not available
640Peak Power Sold for a day
641Peak Power Sold for a week
642Peak Power Sold for a month
643Peak Power Sold for a year
Important:
the factory to the limits mandated by UL 1741. Any changes to these setpoints should be
agreed upon by the local utility and the equipment owner.
Accumulated Values Menu
Specific grid-interface parameters within the WRITE Menu have been set in
The WRITE Menu includes the following parameters:
•Ground Current Max
•PPT Voltage Reference
•PV Voltage Start
•PV Time (Start and Stop)
•PV Power Stop
•PPT Current Max %
•Manual Current %
•PPT Enable
•PPT Update Rate and Voltage Step
Important:
by authorized personnel.
Table 2-5 provides a detailed description of W
WRITE parameters require a password to access and should only be changed
RITE parameters that are displayed
on the LCD.
152379 Rev C2–15
Operation
Changing and Displaying WRITE Menu Parameter Values
Follow the procedure below to change WRITE Menu parameters.
To c ha ng e W
RITE Menu parameters:
1. From the standard display or anywhere in the R
the W
RITE menu parameters by pressing the <MENU> key. This will ask for a
password.
2. Enter the password <5><9><4> and press the <E
a) If the wrong password is entered, the display will again prompt the user
for the password.
b) If a mistake is made while keying in the password, the /\ or \/ keys may be
used as a backspace key.
3. Once within the Write Menu, the first item is the “Set Goal State”. Use the /\
or \/ key on the operator interface keypad to scroll through the W
parameters.
a) To change the displayed parameter, press the <E
b) Enter the desired value and press <E
the acceptable range for the parameter, the original value will remain.
c) To leave the W
<M
ENU> button once and the standard display will reappear on the LCD.
Table 2-5
ParameterDescriptionIDUnits
Write Menu Parameters
RITE Menu and return to the READ Menu, press the
EAD Menu, you may access
NTER> button.
RITEMenu
NTER> button.
NTER>. If the value entered is outside
Default
Value
Maximum
Value
Minimum
Value
Set Goal State
Displays as:
Hit ENTER to set
Goal:
Set Date
Displays as:
042805
Set Time:
Displays as:
163000
Maximum Grid
Vo lt ag e
Displays as:
Max AC Volts %:
Commands a Goal State.
The date is entered
month-day-year (mmddyy):
April 28, 2005 is entered
042805.
The time is entered in military
hours-minutes-seconds
(i.e., 24-hour clock): 4:30 pm is
entered
163000.
This parameter sets the trigger
point value for “AC voltage High”
(0013) fault. If the grid voltage is
over this parameter’s value, the
fault is triggered. The upper limit
of this parameter is restricted by
UL requirements.
32Percentage
of
Nominal
voltage
110110105
2–16152379 Rev C
Operator Interface
Table 2-5
Write Menu Parameters
ParameterDescriptionIDUnits
Minimum Grid
Vo lt ag e
Displays as:
Min AC Volts%:
This parameter sets the trigger
point value for “AC voltage low”
(0012) fault. If the grid voltage is
below this parameter’s value, the
fault is triggered. The lower limit
33Percentage
of
Nominal
voltage
of this parameter is restricted by
UL requirements.
Maximum Grid
Frequency
This parameter sets the trigger
point value for “AC frequency
34Hertz60.560.559.5
high” (0011) fault. If the grid
Displays as:
Max AC Freq:
frequency is over this parameter’s
value, the fault is triggered. The
upper limit of this parameter is
restricted by UL requirements.
Minimum Grid
Frequency
This parameter sets the trigger
point value for “AC frequency
35Hertz59.559.560.5
low” (0010) fault. If the grid
Displays as:
Min AC Freq:
frequency is below this
parameter’s value, the fault is
triggered. The lower limit of this
parameter is restricted by UL
requirements.
Default
Value
Maximum
Value
Minimum
Value
889588
Maximum Ground
Fault Current
Displays as:
Max Gnd Flt I:
Peak Power Tracker
Reference Voltage
Displays as:
PPT V Ref:
PV Wakeup Voltage
Displays as:
PV V Start:
This parameter sets the trigger
point value for “Ground Over
Current” (0033) fault. Once the
current through the ground cable
is greater than the value of this
parameter, the fault is triggered.
This is the initial PV voltage the
inverter is going to try to keep as it
goes into on line mode. If the
power tracker is off, the inverter
will draw current from the PV
array to maintain this reference
voltage. If the power tracker is on,
this is the reference voltage from
which the inverter start exploring
voltages that produce more power.
This is the trigger point that
transitions the inverter from PV
Sleep state to PV Wake Up state.
When the PV voltage reaches the
value of this parameter the
inverter transitions into PV Wake
Up mode.
36Amps10201
37Volts400600300
38Volts440600300
152379 Rev C2–17
Operation
Table 2-5
Write Menu Parameters
ParameterDescriptionIDUnits
Time Delay for PV
Wake up
Time delay to transition from PV
wake up state to PV On-line state.
39Seconds30012000
Once the inverter is in PV Wake
Displays as:
PV T Start:
Up mode, it waits for the amount
of time determine by this
parameter before transitioning into
PV on-line mode. During this time
the inverter checks that the PV
voltage is no less than the PV
wake voltage, otherwise it goes
into PV Sleep mode.
Time delay for PV
Sleep Test
This is the amount of time the
inverter will be in Sleep Test mode
40Seconds30012000
if the output power continues to be
Displays as:
PV T Stop:
below “PV P Stop”. The inverter
will exit Sleep Test mode towards
on-line mode is the power is over
“PV P Stop” or towards Shutdown
mode is the “PV T Stop” timer
expires.
Default
Value
Maximum
Value
Minimum
Value
PV Output Power to
Enter Sleep Test
Mode
Displays as:
PV P Stop:
Power Tracker
Maximum Output
Power
Displays as:
I PPT Max:
Manual Current
Output
Displays as:
I Manual:
This is the output power trigger
point for the inverter to transition
into sleep test mode. When the
output power is below the value of
this parameter the inverter enters
sleep test mode.
This parameter sets the percentage
of maximum rated power the
inverter will produce when in
power tracker mode. For example,
a 100 Kw system with this
parameter set to 50 will not
attempt to produce more than 50
Kw.
This parameter sets the percentage
of maximum out current the
inverter will attempt to produce
while in manual current mode.
41KW110.00.1
42Percentage
1001100
of
maximum
output
power.
43Percentage
251100
of
maximum
output
current.
2–18152379 Rev C
Operator Interface
Table 2-5
Write Menu Parameters
ParameterDescriptionIDUnits
Enable Peak Power
Tracker
This parameter switches on and
off the Power Tracker function.
440 = Off
1 = On
When the Power Tracker is on, the
Displays as:
PPT Enable:
inverter will regulate the bus
voltage to optimize output power.
When the Power Tracker is off, the
inverter will regulate the bus
voltage to maintain it at “PPT V
Ref” volts.
Power Tracker Rate
This parameter sets the rate at
45Seconds0.510.00.1
which the Power Tracker function
Displays as:
PPT Rate:
makes changes to the voltage
reference point as it tries to find
the optimal position. For example,
if the value of this parameter is
0.5, then every half a second the
power tracker will increase or
decrease the voltage reference
point to check if more power can
be produced at the new level.
Default
Value
Maximum
Value
Minimum
Value
110
Power Tracker Step
Displays as:
PPT V Step:
This parameter sets the size of the
change the Power Tracker will
make to the voltage reference
point as it tries to find the optimal
position. For example, if the value
of this parameter is set to 1, the
Power Tracker will increase or
decrease the voltage reference
point by one volt at a speed of
“PPT Rate” to check if more
power can be produced at the new
level.
46Volts110.00.1
152379 Rev C2–19
Operation
Commanding Goal State Changes
To change the Goal State:
1. From the standard display press the <M
a password. The LCD will change the third line of the display to “
Hit ENTER” and fourth line of the display to “Password:”.
2. Enter the password <5><9><4> and press the <E
The LCD will change the third line of the display to “
and fourth line of the display to “
3. Press <E
NTER> again. The Goal State menu will show on the LCD display.
ENU> key. This will prompt the user for
Type and
NTER> button.
Hit ENTER to set”
Goal:”.
4. Scroll through the goal state menu with the /\ or \/ keys until the desired goal
state is displayed on the fourth line of the display.
5. Press <E
following text on the third line: “
NTER>. The LCD will then prompt the user by displaying the
Press F4 to Confirm”.
6. Press <F4> and the PV100S will transition to this goal state. If the goal state
requested violates the conditions of the state machine, the PV100S will
remain in the previous state of operation.
SHUTDOWN
Manual
Inverter =
Disabled
FAULT
Automatic
MATRIX
TEST
Inverter =
Idle
TRACKING
Figure 2-7
POWER
Inverter =
PV Power
State Transition Diagram
Manual
MANUAL
CURRENT
Inverter =
PV Current
2–20152379 Rev C
Setting the Date and Time
Follow the procedure below to change the date and time.
To change the Date and Time:
1. From the standard display, press the <M
for the password. The LCD will change the third and fourth lines of the LCD
display as follows:
“
Type and Hit ENTER”
Password:”.
“
2. Enter the password <5><9><4> and press the <E
3. Scroll down with the \/ key until date or time parameters are reached.
a) If you’re changing the date, the third and fourth lines of the LCD will
display as follows:
“
“
b) If you’re changing the time, the third and fourth lines of the LCD will
display as follows:
“
“
Operator Interface
ENU> key. This will prompt the user
NTER> button.
Type and hit ENTER”
Set Date: MMDDYY”
Type and hit ENTER”
Set Time: HHMMSS”
4. Press <E
NTER>. Enter the proper date or time in a six digit format. For
example:
a) The date is entered month-day-year (mmddyy):
April 28, 2005 is entered
042805 <ENTER>.
b) The time is entered in military hours-minutes-seconds
(i.e., 24-hour clock): 4:30 pm is entered
163000 <ENTER>.
If a mistake is made while entering the date or time, the /\ and \/ keys may be
used as a backspace key. Any two-digit year “YY” may be entered for the
date, but regardless of the keyed entry, the maximum Month/Day “MMDD”
that the UFCU will accept is a “1231” or Dec. 31st. The maximum allowable
time entry the UFCU will accept is “235959”.
5. Once the entry is accepted, the third and fourth lines of the LCD display will
revert back to the following:
a) If you’re changing the date, the third and fourth lines of the LCD will
display as follows:
“
Hit ENTER to set”
Set Date:”
“
b) If you’re changing the time, the third and fourth lines of the LCD will
display as follows:
“
Hit ENTER to set”
Set Time:”
“
6. Pressing the <M
ENU> key will return the user to the standard display.
152379 Rev C2–21
Operation
Manual State Transitions
State conditions can also be transitioned manually. Refer to “Commanding Goal
State Changes” on page 2–20 for instructions on commanding PV100S goal states
for manual transitions.
Shutdown → Matrix Test → Shutdown
1. Turn the ON/OFF switch to the OFF position.
2. Command the PV100S to the Matrix Test.
3. After completing the Matrix Test, command the PV100S to Shutdown.
If the O
N/OFF switch is turned to ON while the PV100S is in the Matrix Test state,
the PV100S will transition to Shutdown.
Power Tracking → Manual Current → Power Tracking or Shutdown
1. Verify the PV manual current parameter (I Manual %) is set to the desired
percent of rated.
2. Command the PV100S to Manual Current mode from the operator interface
keypad. While in the manual current mode, the user may change the PV
manual current parameter. However, the user may demand greater current
than the capacity of the PV array. If this causes the PV voltage to drop below
the minimum operating voltage (300 Vdc), the PV100S will transition to
Shutdown.
3. To exit the Manual Current mode, the user must manually command the
PV100S to Power Tracking.
Automatic State Transitions
State conditions can also be transitioned automatically. Refer to “Commanding
Goal State Changes” on page 2–20 for instructions on commanding PV100S goal
states.
Shutdown → Power Tracking → Shutdown
1. The ON/OFF switch must be turned to the ON position.
2. Once the PV voltage exceeds the PV voltage start set point (
PV100S will start a wake-up timer (
PV T Start).
PV V Start) the
a) If the PV voltage remains above the PV start voltage set point for the
duration of the wake-up timer, the PV100S will transition to Power
Tracking.
b) If the PV power drops below the PV power stop set point, (
the PV100S will start a PV sleep timer (
PV T Stop).
PV P Stop)
c) If the PV voltage and power remain below their respective setpoints for
the duration of the sleep timer, the PV100S will transition to Shutdown.
2–22152379 Rev C
Any State → Fault
Auto-restart Feature
If the PV100S encounters a fault, regardless of operating state, it will transition to
the Fault state. The PV100S will remain in this state until the fault condition has
been remedied and cleared. The Fault Code number will appear on the first line of
the LCD. A description of the fault will show on the second line. The third line of
the LCD will read “
F1 to Clear Fault?”. The fourth line shows the goal state.
Fault: 0070
INTERLOCK ACTIVATED
F1 to Clear Fault
Goal: PWR Tracking
LCD Display showing
Fault Code
UFCU Keypad
Figure 2-8
To clear the fault:
1. See Table 4-1, “Fault Codes” on page 4–4 for a complete listing of Fault
Codes and possible remedies. Correct the fault condition if possible and
attempt to clear the fault by pressing “F1”.
2. The ability to clear the fault can only be done from the R
occurs while accessing the W
to the Read Menu, and “
the LCD display.
Auto-restart Feature
In the event of a utility voltage or frequency excursion outside of those specified
inTable A-3 on page A–3, thePV100S will automatically transition to a Fault
condition. Once the Utility recovers for a period of five minutes, the PV100S will
automatically clear the fault, then resume normal operation.
LCD showing Fault Code
EAD Menu. If a fault
RITE Menu, pressing <MENU> once will return
F1 to Clear Fault” will appear on the third line of
152379 Rev C2–23
Operation
Energize Procedure (Startup)
To start up the PV100S:
1. Remove any lockout devices from the utility connection circuit breaker and
PV disconnect switch.
2. Close the utility connection circuit breaker.
3. Close the AC Disconnect Switch.
4. Close the DC Disconnect Switch.
5. Turn the O
After a 15 second initialization period, the PV100S will automatically transition
to ‘Waking Up’, given the PV voltage is greater than the PV V Start set point.
N/OFF switch to the ON position.
De-Energize/Isolation Procedure (Shutdown)
The following procedure should be followed to de-energize the PV100S for
maintenance.
WARNING
The terminals of the DC input may be energized if the PV arrays are energized. In
addition, allow 5 minutes for all capacitors within the main enclosure to discharge after
disconnecting the PV100S from AC and DC sources.
To isolate the PV100S:
1. Turn the
2. Open the DC interface disconnect switch.
3. Open the AC interface disconnect switch.
4. Open the utility connection circuit breaker.
5. Install lockout devices on the utility connection circuit breaker and DC
disconnect switch.
ON/OFF switch to the OFF position.
2–24152379 Rev C
Computer Communications with the PV100S
Computer Communications with the PV100S
The PV100S provides multiple options for communicating system status or data
logging through a personal computer using the Xantrex Solar Graphic User
Interface (GUI) software.
The Xantrex Solar Graphic User Interface (GUI) software is a Windows™-based
program that:
•displays system status,
•accesses inverter controls,
•accesses metering and data logging capabilities, and
•controls protective functions.
If multiple inverters are networked together, the software is capable of tracking up
to 50 inverters on the same network.
Determine which method will be used to communicate with the PV100S and
ensure the appropriate hardware is in place before proceeding with installing the
GUI. See the “PC Connection Methods” section of the PV100S 100 kW Grid-tied
Photovoltaic Inverter Planning and Installation Manual for instructions on
establishing the desired connection if this has not already been done.
Figure 2-9
152379 Rev C2–25
GUI Interface Main Menu Screen
Operation
Installing the Graphic User Interface (GUI) Software
The following section outlines the minimum system requirements for using the
GUI software and instructions for installing, configuring, and using the software.
Close all programs running on the computer before proceeding with the
installation.
Minimum System Requirements
The following lists the minimum requirements for using the Xantrex Solar
Graphic User Interface (GUI) Software.
•Personal Computer with a 486DX/66 MHz or higher processor; Pentium™ or
higher processor recommended.
•Microsoft Windows™ operating system (Win98 or later).
•50 MB of free hard disk space.
•64 MB of RAM (128 MB recommended)
•56K modem (minimum)
•If using a LAN to access the inverters, a LAN card will be required in the PC.
Starting the Software Setup Program
Select one of the following methods to install the software:
•Use Autorun (must be enabled on your CDROM drive).
•Manual Start (assumes that Autorun is not enabled on your CDROM drive).
•Use a Command prompt to initiate the installation program.
Important:
most current version.
Software levels shown in the following illustrations may not represent the
Starting the Setup Program Using Autorun
To install the software with Autorun enabled on your CDROM drive:
1. Insert the CD into your computer’s CDROM drive. If autorun has not been
disabled for the CDROM in your computer, the Model Specific Software
Installation window shown in Figure 2-11 will appear.
Starting Setup Manually
To start the program from the CD if Autorun is disabled on your computer:
1. Insert the XANTREX SOLAR INVERTER GUI – INSTALLATION CD
into your CDROM drive.
2. Open Windows Explorer (or Click My Computer) and navigate to the
CDROM drive to view the contents of the disk.
3. Double-click on the file GUI_Menu.exe icon. The splash screen shown in
Figure 2-11 will appear.
4. Proceed to the Model Specific Software Installation section on page 2–28 to
continue with the installation.
2–26152379 Rev C
Starting Setup From a Command Prompt
To start the program from a command prompt:
1. Insert the XANTREX SOLAR INVERTER GUI – INSTALLATION CD
into your CDROM drive.
2. Click on START and select “RUN”.
3. Enter the drive letter assigned to your CDROM and the name of the
installation program as shown in Figure 2-10.
Computer Communications with the PV100S
Figure 2-10
Important:
shown in Figure 2-10. Be sure to use the correct letter for your drive or the program will
not start.
4. Click O
Starting Setup from a Command Prompt
The drive letter assigned to your CDROM may be different from the one
K. The splash screen shown in Figure 2-11 will appear.
5. Proceed to the Model Specific Software Installation section on page 2–28 to
continue with the installation.
152379 Rev C2–27
Operation
Model Specific Software Installation
Once the Setup program has been started, installation of the GUI software can
continue.
To continue with the GUI software installation:
1. After the GUI Setup Splash Screen appears (Figure 2-11), click on the button
I
NSTALL PV100S GUI. The GUI Setup Welcome Window will appear next
(Figure 2-12).
Click here to start
the model specific
installation
Figure 2-11
Figure 2-12
2–28152379 Rev C
GUI Splash Screen
GUI Setup Welcome Window
Computer Communications with the PV100S
2. Click OK and the following window will appear:
Figure 2-13
GUI Setup Start Window
If the directory provided in this window is acceptable for the installation,
proceed to Step 4. If not, click on the C
HANGE DIRECTORY button and
provide a new name for the desired destination directory.
3. Click on the picture of the computer to continue with the installation.
The following window will appear:
Figure 2-14
152379 Rev C2–29
GUI Setup Program Group Window
Operation
4. Click CONTINUEto confirm the program group to be used.
The following setup progress indication window will appear.
Figure 2-15
GUI Setup Progress Indicator Window
5. When completed, you will see this:
Figure 2-16
GUI Setup Start Window
6. Click OK. The GUI is now installed on the computer.
2–30152379 Rev C
Running the GUI
Computer Communications with the PV100S
To run the GUI software program, log onto the computer and click the following
menu items in the order shown below.
1. Window’s S
2. P
3. X
4. X
Remote/LAN Connection
If no inverter is connected to the COM1 serial port of the computer, the following
screen will appear:
TART button
ROGRAMS
ANTREX_SOLAR
ANTREX SOLAR GUI
Figure 2-17
152379 Rev C2–31
GUI Interface Screen if Connected Remotely
Operation
Direct Connection
If the serial communication port of the inverter is connected to the COM1 serial
port of the computer, the following screen will appear.
Figure 2-18
2–32152379 Rev C
GUI Interface Screen if Connected Directly
GUI Configuration - Adding Inverters
Once the GUI has started, you will need to configure each Inverter icon to reflect
the appropriate operational parameters for each inverter that is connected to the
system. The software automatically defaults to one inverter. To program that
inverter accordingly, follow the directions provided below.
To configure the inverters in the GUI:
1. With the GUI Main Menu open, Right-click on the “Inverter 1” icon.
2. Click on the tabs to display each page and fill out the required information.
3. Fill out the Detail Information in the form shown in Figure 2-19.
Form Tab
Computer Communications with the PV100S
Fill out all the required
information on this
form.
Figure 2-19
Form Tab
Fill out all the required
information on this
form.
Detail Screen
4. Fill out the Contact Information in the form shown in Figure 2-20.
Figure 2-20
152379 Rev C2–33
Contact Screen
Operation
Form Tab
Fill out all the required
information on this
form.
Sub-menu
5. Fill out the Operational Configurations Information in the form shown in
Figure 2-21 through Figure 2-23. This section has four sub-menu pages to
cover the following parameters.
a) Fill out Operational Limits Information requested.
b) Click on the PV Sub-menu to continue.
Figure 2-21
Form Tab
Fill out all the required
information on this
form.
Figure 2-22
Operational Configuration Screen - Limits
Sub-menu
Operational Configuration Screen - PV
c) Fill out PV Information requested.
d) Click on the Power Tracker Sub-menu to continue.
2–34152379 Rev C
Form Tab
Fill out all the required
information on this
form.
Computer Communications with the PV100S
e) Fill out the Power Tracking Information requested.
f)Click on the Connections Form Tab to continue.
Figure 2-23
Form Tab
Fill out all the
required
information
on this form.
Sub-menus
Operational Configuration Screen - Power Tracker
6. Fill out the Connection - General Information in the form in Figure 2-24.
7. Click on the Telephone Fault Configuration sub-menu to continue.
Figure 2-24
Connection Configuration Screen - General
152379 Rev C2–35
Operation
Form Tab
Fill out all the
required information
on this form.
Sub-menus
8. Fill out the Connection - Telephone Fault Configuration Information in the
form shown in Figure 2-25.
9. Click on the Telephone Configuration sub-menu to continue.
Figure 2-25
Form Tab
Fill out all the
required
information on
this form.
10. Fill out the Connection - Telephone Configuration Information in the form
shown in Figure 2-26.
Click on the OK
button to save the
changes and
return to the GUI
Main Menu.
Sub-menus
Figure 2-26
Connection Configuration Screen - General
11. Once the information is complete, click the O
K button to accept the changes
and return to the GUI main menu.
2–36152379 Rev C
GUI Help
Computer Communications with the PV100S
The GUI software program has a built-in help program. Once the program is
started, click on the H
ELP menu item to start the Help program.
The Help interface is divided into the following sections.
•Getting Started - IMPORTANT: Read this first
•Setup - Tutorial for setting up the GUI and configuring an inverter
•Windows - Description of each window of the GUI
•Menu Commands - Description of each GUI Menu command
•How to... - How to perform various tasks, by topic
•Reference - Glossary and miscellaneous information
•Messages - Explanation of GUI popup messages
•Problems - Troubleshooting for problems
Figure 2-27
152379 Rev C2–37
GUI Help Topics
2–38
3
Commissioning
Chapter 3, “Commissioning” contains information on safely
commissioning the PV100S 100 kW Grid-Tied Photovoltaic Inverter.
Commissioning
Commissioning Procedure
This section provides the procedure necessary to safely and correctly commission
a PV100S inverter.
Important:
procedure.
It is important to record any issues encountered while following this
SummaryTo commission the PV100S:
1. Ensure the Verification Tests have been completed and have passed
successfully. See the PV100S 100 kW Grid-tied Photovoltaic Inverter
Planning and Installation Manual, Section 4.
2. Begin the PV100S Commissioning Procedure as described in detail further in
this section. The steps are summarized below.
a) Start the GUI and open the PV100S Commissioning Procedure file.
b) Record the Serial Number.
c) Verify AC and DC Voltages.
d) Inspect Lower Inductor Enclosure.
e) Apply Grid Voltage.
f)Check the Front Panel Display.
g) Establish communications with the GUI.
h) Confirm Operational Parameters (AC, DC and Power Tracker).
i)Verify Door Interlock Functions.
j)Perform the Matrix Test.
k) Operate Inverter.
3. Submit the Test report and warranty form to Xantrex See “PRODUCT
REGISTRATION” on page WA–3.
Starting the Commissioning Test File
1. Start the Xantrex Solar Graphical User Interface (GUI) program.
2. Verify that both the AC (S1) and DC (S2) Disconnect switches are open.
3. Verify the O
N/OFF switch (S3) is in the OFF position.
4. Once you finish these tasks, go back to the GUI and click on the check box to
indicate the task is complete. Go to the next step by clicking on the "N
button.
3–2152379 Rev B
ENERAL PROCEDURES” from the
EXT"
Serial Number
Verify AC Voltage
Starting the Commissioning Test File
1. Enter the information required by GUI in the white text boxes on the form that
appears next. The converter serial number is located on a label placed on the
lower-left front of the Main Inverter Enclosure door.
2. Once you finish recording the required information, click on the check box to
indicate the task is complete. Go to the next step by clicking on the "N
button.
1. Open the door of the AC Interface Enclosure and verify that the Grid AC
cables have been installed at S1-2T1, S1-4T2, S1-6T3, TB6-Neutral, and
TB2.
2. With a voltmeter, verify if AC Grid voltage is present at the bottom of S12T1, S1-4T2, S1-6T3 (480 Vac or 208 Vac). These fuses are located in the
AC Interface Enclosure.
a) If voltage is correct, verify phasing using a phase rotation meter. The
phase rotation should be clockwise “A, B, C”.
b) If the voltage is not present, contact the installer, site electrician or site
operator to supply grid voltage to the unit.
3. If grid voltage is not available to the unit, open the AC Disconnect Switch
(S1) and lock the AC Interface Enclosure. The Commissioning Test procedure
must cease at this point. Do not attempt to continue the test until each step can
be checked and verified.
a) If grid voltage is not available and the Commissioning Test must be
stopped, SAVE the Commissioning File. This file will be used once grid
voltage has been applied and verified.
4. Once you finish verifying AC voltages, go back to the GUI Commissioning
Procedure and click on the check box to indicate the task is complete. Go to
the next step by clicking on the "N
EXT" button.
EXT"
Verify DC Voltage
1. Open up the DC Interface Enclosure and verify that the PV DC cables have
been installed correctly.
2. With a voltmeter, verify if PV DC voltage is present at TB3.
3. Verify the correct polarity.
4. If the voltage is not present, contact the installer, site electrician or site
operator to supply PV voltage to the unit.
5. If PV DC voltage is not available to the unit, open the DC Disconnect Switch
(S2) and lock the DC Interface Enclosure. The Commissioning Test procedure
must cease at this point. Do not attempt to continue the test until each step can
be checked and verified.
152379 Rev B3–3
Commissioning
a) If PV voltage is not available and the Commissioning Test must be
stopped, SAVE the Commissioning File. This file will be used once PV
DC voltage has been applied and verified.
6. Once you finish verifying PV DC voltages, go back to the GUI
Commissioning Procedure and click on the check box to indicate that the task
is complete. Go to the next step by clicking on the "N
Inspect Inductor Enclosure
1. Remove the back and side access panels to the Inductor Enclosure and inspect
the connections.
2. Check for loose cables, rubbing, or interference.
3. Check the AC Sense Harness to make sure it is terminated and secured
properly and not touching the inductor L1.
4. Correct and record any defects.
5. Reinstall the Inductor Enclosure access panels removed above.
6. Once you finish inspecting the Inductor Enclosure, go back to the GUI
Commissioning Procedure and click on the check box to indicate the task is
complete. Go to the next step by clicking on the "N
EXT" button.
EXT" button.
Apply Grid Voltage
Front Panel Display
1. Verify all enclosure doors are closed and locked.
2. Close the AC Disconnect (S1) Switch. This will energize the control power
circuits.
3. Look, listen and smell for signs of defects.
4. Record any defects found.
5. Once you finish applying the grid voltage, go back to the GUI Commissioning
Procedure and click on the check box to indicate the task is complete. Go to
the next step by clicking on the "N
EXT" button.
1. Open then close the AC Disconnect Switch (S1) and look at the Front Panel. It
should show the Software Versions of the CCU and Front Panel. Record these
numbers. Then it should go into Initialization.
2. After about 20 seconds it will be in its “ready” mode. At this time the Fault
Code “0071 PV SWITCH OPEN” will be reported. Close the PV Disconnect
Switch (S2) and verify alarm 0071 clears by pressing the “F1” key on the
keypad of the UFCU. If additional alarms are present, refer to Table 4-1 on
page 4–4.
3. Once all faults are clear, the front panel should report Key Disable (“Switched
Off”) and show Inverter Status.
4. Using the \/ key, scroll down in the R
EAD Menu and verify that the Time and
Date are correct.
3–4152379 Rev B
5. If not, refer to the “Setting the Date and Time” on page 2–21.
6. Scroll thru the parameters and verify that they are present.
7. Once you finish checking the Front Panel Display, go back to the GUI
Commissioning procedure and click on the check box to indicate the task is
complete. Go to the next step by clicking on the "N
Establish Communications with the GUI
1. Verify that the appropriate hardware has been installed for the desired
communications connection–Remote or Direct Connect.
If not, refer to the “PC Connection Methods” section of the PV100S 100 kW
Grid-Tied Photovoltaic Inverter Planning and Installation Manual for
instructions.
2. Verify that the communications with the inverter is working and that you have
established a connection with the inverter through the GUI.
a) Verify the signal lights on the modem show activity. Once communica-
tions are established, close the connection.
b) While at the Inverter, create a fault. This could be done by opening the
DC Disconnect Switch (S2).
c) Verify the Inverter calls the End User and reports the fault. The fault
reporting from the inverter to the End User will take approximately 1
minute.
Starting the Commissioning Test File
EXT" button.
d) Repair the fault–close the DC Disconnect Switch (S2)–and have the End
User clear the alarm.
If communications is not working as expected, refer to the “General
Troubleshooting” on page 4–2 for help.
3. Once you verify that communication has been established and is working
properly, go back to the GUI Commissioning Procedure and click on the
check box to indicate the task is complete. Go to the next step by clicking on
the "N
EXT" button.
Confirm AC Operational Parameters
1. Verify the inverter’s AC limits.
2. Make any necessary changes.
3. Record these values.
4. Once you finish these tasks, go back to the GUI Commissioning Procedure
and click on the check box to indicate the task is complete. Go to the next step
by clicking on the "N
EXT" button.
152379 Rev B3–5
Commissioning
Confirm DC Operational Parameters
1. Verify the Inverters PV Settings.
2. Make any necessary changes.
3. Record these values.
4. Once you finish these tasks, go back to the GUI Commissioning Procedure
and click on the check box to indicate the task is complete. Go to the next step
by clicking on the "N
EXT" button.
Confirm Power Tracker Configuration Operational Parameters
1. Verify the inverter’s Power Tracker Configuration.
2. Make any necessary changes.
3. Record these values.
4. Once you finish these tasks, go back to the GUI Commissioning Procedure
and click on the check box to indicate the task is complete. Go to the next step
by clicking on the "N
EXT" button.
Verify Door Interlock Functions
Matrix Test
1. Open the front door of the Main Inverter Enclosure and verify a door interlock
fault is triggered (0070 “INTERLOCK ACTIVATED”).
2. Bypass the switch by pulling it out into the service position.
3. Clear the fault.
4. Once you finish these tasks, go back to the GUI Commissioning Procedure
and click on the check box to indicate the task is complete. Go to the next step
by clicking on the "N
1. Confirm that the ON/OFF Switch (S3) in the OFF position.
1. From the GUI or front panel, select Matrix test from the Goal State menu.
2. Verify the six yellow LEDs on the IGBT driver board are blinking. The
blinking yellow LEDs are an indication that the IGBT driver board is gating
correctly.
3. If any of the six yellow LEDs on the IGBT driver board are not blinking, refer
to the Matrix Gate Faults listed on page 4–8 of the “Troubleshooting” Section.
4. To stop the test, select Goal state from the GUI or Front Panel and choose
Shutdown.
5. Close the door and clear any alarms.
6. Once you finish the Matrix Test, go back to the GUI Commissioning
Procedure and click on the check box to indicate the task is complete. Go to
the next step by clicking on the "N
EXT" button.
EXT" button.
3–6152379 Rev B
Operate Inverter
Starting the Commissioning Test File
1. Make sure all doors are closed and locked.
2. Using the Front Panel or the GUI, set the I PPT Max percent to 25%.
3. Place the O
N/OFF Switch (S3) in the ON position. If the PV voltage is above
PV Start voltage threshold, followed by a 5-minute delay period, the PV
contactor (K2) will close, followed by the Main AC contactor (K1). The
inverter will begin to produce power up to 25% of rated power.
4. Look, listen and smell for any defects.
Important:
Interface Failed
between the Isolation Transformer (T6-X1, T6-X2, and T6-X3) and Main Inverter
Enclosure (TB4-A, TB4-B, and TB4-C) are incorrect. Open the AC Disconnect Switch
(S1) and the DC Disconnect Switch (S2). Place the ON/OFF Switch (S3) in the OFF
position. Once the System is isolated for maintenance, verify that these terminations are
correct. Upon verification that the terminations are correct, close the AC and DC
Disconnect switches and repeat the previous steps.
If the PV100S suddenly ceases operation, and faults with an "0014 Grid
", this could be an indication that the power conductor terminations
5. Make sure the Matrix fan is operating.
6. If everything is okay, increase the I PPT Max until you reach 100%.
7. Check all the operating data with the GUI or front panel. Record any
irregularities.
8. Let the inverter run.
9. Once you finish these steps, go back to the GUI Commissioning Procedure
and click on the check box to indicate the task is complete. Go to the next step
by clicking on the "N
EXT" button.
Completed Commissioning
1. Once you have successfully completed all the commissioning steps, save the
test report to a file.
2. Email the completed report to:
pvcommissioningreport@xantrex.com
3. Send or Fax a copy of the Product Registration Form (page WA–3) to
Xantrex. The address and Fax numbers are available on page WA–3.
Thank You for choosing Xantrex "The Smart Choice for Power".
152379 Rev B3–7
3–8
4
Troubleshooting
Chapter 4, “Troubleshooting” contains information and procedures
for troubleshooting the PV100S 100 kW Grid-Tied Photovoltaic
Inverter. It provides descriptions of common situations and errors that
may occur and provides possible solutions for resolving fault
conditions. It also provides instructions for clearing faults manually, if
required.
Troubleshooting
Faults and Fault Codes
Fault states are automatic from any state of operation. In the event of a fault
condition, the PV100S will immediately stop processing power and execute an
immediate orderly shutdown, open both the main AC and DC contactors, and
remain in a faulted state until the fault is remedied and cleared (manually or
automatically).
In the event of an alarm or fault condition, the PV100S will execute an immediate,
orderly shutdown and remain in a faulted state until the alarm or fault is remedied
and cleared (manually or automatically).
•Faults associated with a grid disturbance clear automatically. The PV100S
will automatically re-start after a 5-minute delay.
•All other faults must be cleared manually.
All fault conditions arising from within the PV100Sare reported to the UFCU
(Universal Frontpanel Control Unit). The 4-line LCD will display a hexadecimal
value (fault code) and a brief text description of the fault.
Most faults are latching and only those faults associated with grid disturbances are
auto-clearing and thus enable the PV100S to restart after a 5 minute delay period.
Once the cause of the fault has been identified and corrected, and it is determined
to be safe to proceed, PV100S faults may be manually cleared from the UFCU
keypad or using the remote GUI.
See “Clearing Faults Manually” on page 4–3 for instructions on this procedure.
General Troubleshooting
Respond to any PV100S alarm or fault as follows:
1. Note and document the alarm or fault code and brief text description.
2. Determine the source of the alarm or fault by referring to Table 4-1, “Fault
Codes” on page 4–4.
3. Rectify the alarm or fault condition and attempt to clear the fault from the
display. See “Clearing Faults Manually” on page 4–3 for instructions on this
procedure.
4. If the condition is sustained and cannot be corrected, again note and document
the fault code and description, and contact either your Distributor / Reseller,
or Xantrex Customer Service.
WARNING: Lethal Voltage
In order to remove all sources of voltage from the PV100S, the incoming power must be
de-energized at the source. This may be done at the Utility main circuit breaker, and by
opening the AC disconnect and the DC disconnect switches on the PV100S. Review the
system configuration to determine all of the possible sources of energy. In addition, allow
5 minutes for the DC bus capacitors, located on the ceiling of the cabinet, to discharge
after removing power.
4–2152379 Rev C
Clearing Faults Manually
Faults associated with a grid disturbance clear automatically. These faults include:
•0010 (AC Frequency Low),
•0011 (AC Frequency High),
•0012 AC Voltage Low), and
•0013 (AC Voltage High) only.
Once the AC voltage and frequency return to within the acceptable range, the
PV100S will clear the fault and automatically restart after a 5-minute delay. All
other faults associated with the PV100S must be circumvented and cleared
manually using the UFCU.The following procedure describes how to manually
clear a fault message from the LCD.
To clear the fault:
1. Determine the source of the fault using Table 4-1, “Fault Codes” on page 4–4.
Correct the fault condition.
2. Ensure the fault code and “
Clearing Faults Manually
Clear Fault?” message is displayed in the LCD.
a) If the “
Clear Fault?” message is not shown on the second line of the
LCD, scroll through the read parameter menu with the /\ or \/ keys until
the message appears.
3. To clear the fault, press <E
mode.
0071
PV SWITCH OPEN
F1 to Clear Fault?
Goal: PWR TRACKING
Figure 4-1
Important:
LCD showing Fault Code
If the fault does not clear, the fault condition has not been corrected.
NTER>. The PV100S will transition to Sleeping
LCD Display showing
Fault Code
UFCU Keypad
152379 Rev C4–3
Troubleshooting
Fault Code Descriptions
Table 4-1 provides a complete description of all the fault conditions that may
occur on the PV100S.
Table 4-1
Error
Code Fault Source(s)
0000No FaultsN/AN/AN/A
0010AC Frequency LowSThis fault indicates that the Utility
0011AC Frequency HighSThis fault indicates that the utility
Fault Codes
Fault Type
H=Hardware
S=Software
Fault DescriptionPossible Causes
•Utility grid frequency
grid frequency is below or fell below
the minimum allowed value of
59.3 Hz for greater than 6 cycles.
This fault is auto-clearing. Once the
Utility grid frequency has recovered
within the acceptable operating
range, the PV100S will qualify the
value and automatically clear this
fault and resume normal operation
after 5 minute delay period.
•Utility grid frequency
grid frequency is above or rose above
the maximum allowed value of
60.5Hz for greater than 6 cycles. This
fault is auto-clearing. Once the Utility
grid frequency has recovered within
the acceptable operating range, the
PV100S will qualify the value and
automatically clear this fault and
resume normal operation after
5 minute delay period.
fell below the allowable
limit
rose above the
allowable limit
0012AC Voltage LowSThis fault indicates that the utility
grid voltage is below or fell below the
minimum allowed value of 88% of
nominal Vac for greater than 2
seconds, or 50% of nominal VAC for
greater than 6 cycles. This fault is
auto-clearing. Once the utility grid
voltage has recovered within the
acceptable operating range, the
PV100S will qualify the value and
automatically clear this fault and
resume normal operation after
5 minute delay period.
4–4152379 Rev C
•Utility grid voltage fell
below the allowable
limit
•Fuses F3, F7, F8 or F9
blown
•P1001 on CCU2 is
loose or disconnected
Fault Code Descriptions
Table 4-1
Error
Code Fault Source(s)
Fault Codes
Fault Type
H=Hardware
S=Software
Fault DescriptionPossible Causes
0013AC Voltage HighSThis fault indicates that the utility
grid voltage is above or rose above
the maximum allowed value of 110%
of nominal Vac for greater than
2 seconds, or 137% of nominal Vac
for greater than 2 cycles. This fault is
auto-clearing. Once the Utility grid
voltage has recovered within the
acceptable operating range, the
PV100S will qualify the value and
automatically clear this fault and
resume normal operation after
5 minute delay period.
0014Grid Interface Failed SThis fault indicates that the PV100S
has detected an imbalance of AC
output power of 5 kW or greater
when compared to the DC input
power for more than 6 seconds. This
normally means that the connection
of the PV100S to the grid has failed.
•Utility grid voltage rose
above the allowable
limit
•K1 was opened while
the PV100S was
processing power
•K1 is inoperable
•K3 is inoperable
•SSR1 is inoperable
•TS1 is open
0015Grid DisconnectionSThis fault indicates that the PV100S
has detected a sudden AC voltage
increase of greater than 40% of the
nominal peak-to-peak value. This
normally is the result of a sudden
disconnection from the Utility grid
while the PV100S was processing
power.
0016DC Contactor
Circuit
SThis fault indicates that upon entering
the Power Tracking State, the
PV100S has detected that the PV
voltage has remained above the PV
Start Voltage threshold even after
commanding the DC contactor to
close. This condition is indicative of a
DC contactor circuit failure.
0020PV Over-CurrentSThis fault indicates that the PV100S
has detected a DC current greater
than the maximum allowed value of
712 Adc.
•S1 was opened while
the PV100S was
processing power
•K2 is inoperable
•SSR2 is inoperable
•TS1 is open
•CT4 is inoperable
•CCU2 ±15 Vdc Power
Supply is defective
•P3 on CCU2 is loose or
disconnected
•PV system wiring short
152379 Rev C4–5
Troubleshooting
Table 4-1
Error
Code Fault Source(s)
Fault Codes
Fault Type
H=Hardware
S=Software
Fault DescriptionPossible Causes
0021PV Over-VoltageSThis fault indicates that the PV100S
has detected a DC input voltage of
greater than the maximum allowed
value of 600 Vdc.
0023Bus Voltage HighHThis fault indicates that the PV100S
has detected that the DC bus voltage
has exceeded the maximum allowed
value of 925 Vdc.
XX30Matrix Over Current SThis fault indicates that the PV100S
has detected that the AC current on
one or more phases of the inverter
output has exceeded the maximum
allowed value of 712 A
rms
.
The first two digits of the fault code
indicate the particular phase where
the over current occurred as follow:
•0130 - Matrix over current in
phase A
•0230 - Matrix over current in
phase B
•0430 - Matrix over current in
phase C
•PV system wiring short
•Lightning strike on PV
system wiring
•PV system wiring short
•Lightning strike on PV
system wiring
•CT1 or CT2 are
inoperable
•CCU2 ±15Vdc Power
Supply is defective
•P3 on CCU2 is loose or
disconnected
•AC system wiring short
If more than one phase faults
simultaneously, the two first digits
are added in hexadecimal form to
indicate an over current condition in
more than one phase, thus the error
code will contain the summation of
the faulted phases.
0033Ground Over
Current
SThis fault indicates that the PV100S
has detected that the ground fault
current has exceeded the maximum
allowed value. This maximum
allowed value for ground fault current
is a user-configurable setting with a
range of 1 to 20 Adc. The default
setting for this value is 10 Adc.
•CT3 is inoperable
•CCU2 ±15 Vdc Power
Supply is defective
•P3 on CCU2 is loose or
disconnected
•Ground -to-AC or
DC-to-System wiring
short
4–6152379 Rev C
Fault Code Descriptions
Table 4-1
Error
Code Fault Source(s)
0040Programming
0041State InvalidSThe state machine implemented
0042Serial EEPROM
Fault Codes
Software
Write Error
Fault Type
H=Hardware
S=Software
SThis code indicates that the PV100S
SThis fault indicates that the PV100S
Fault DescriptionPossible Causes
has detected that the system is in
Programming mode. This fault does
not indicate any malfunction with the
PV100S, but is merely an indication
that the system software is in the
process of being downloaded into the
EEPROMs of the CCU2.
within the CCU2 system software
governs the operation of the PV100S.
This fault indicates that the PV100S
has detected an unknown system
variable and has encountered an
invalid state.
has detected a serial EEPROM write
error. The CCU2 controller board
performs a verification check of data
written to ROM compared to what is
read back.
• Internal RAM error
• CPU error
•Internal ROM error
•CPU error
0043Serial EEPROM
Timeout
0044Bad NOVRAM
Memory
0045Interrupt 2 TimeoutSThis fault indicates that the PV100S
SThis fault indicates that the PV100S
has detected that when writing data to
the serial EEPROM, a confirmation
timer of 300mS has expired.
SThis fault indicates that the PV100S
has detected that one of the two nonvolatile memory banks on the CCU2
controller board has failed. The
CCU2 performs a series of tests to
confirm the validity of the
NOVRAM, and one of the two banks
has produced errors.
has detected that an interrupt 2
timeout has occurred. The CCU2
controller board performs a
conversion validation of analog-todigital data within the A to D
converters. If validation of the
conversion is not performed within
500mS, an interrupt 2 timeout fault
will occur.
•Internal ROM error
•CPU error
•Internal NOVRAM
error
•CPU error
•Internal A to D
converter error
•CPU error
152379 Rev C4–7
Troubleshooting
Table 4-1
Error
Code Fault Source(s)
Fault Codes
Fault Type
H=Hardware
S=Software
Fault DescriptionPossible Causes
0047Software TestSThis fault indicates that the PV100S
has detected that a software test fault
has occurred. This is a simulated fault
used for debugging purposes.
0048Bad MemorySThis fault indicates that the PV100S
has detected that the SRAM DIMM
on the CCU2 controller board has
failed. The CCU2 performs a series
of tests to confirm the validity of the
SRAM, and the memory module has
produced errors.
timing signals for gating the IGBT’s
via the IPM driver board and bidirectional fiber optic
communication. This fault indicates
that the PV100S has detected that an
IGBT gate drive fault has occurred.
An internal protection circuit within
the individual IPM devices of the
IGBT matrix also generates a gate
fault as the result of either short
circuit, over current, over
temperature, or an under voltage
condition.
•Internal SRAM error
•CPU error
•Fiber-optic harness is
loose or disconnected
•PS1 ±15 Vdc Power
Supply is defective
•P1 on IPM driver board
is loose or disconnected
•IPM internal error
condition
The first two digits of the fault code
indicate the particular IGBT that
reported the fault, as follows:
•0152 (A+)
•0252 (A–)
•0452 (B+)
•0852 (B–)
•1052 (C+)
•2052 (C–)
If more than one IGBT faults
simultaneously, the two first digits
are added in hexadecimal form to
indicate that the gate drive fault has
occurred in more than one phase, thus
the error code will contain the
summation of the faulted phases.
4–8152379 Rev C
Fault Code Descriptions
Table 4-1
Error
Code Fault Source(s)
Fault Codes
Fault Type
H=Hardware
S=Software
Fault DescriptionPossible Causes
XX62Matrix TemperatureSThis fault indicates that the PV100S
has detected that the temperature of
the IGBT matrix aluminum heatsink
has exceeded the maximum allowed
value of 95 °C.
0070Interlock ActivatedHThis fault indicates that the PV100S
has detected that the door of the Main
Inverter enclosure is open and the
door interlock switch is in the active
position. This fault is primarily for
personnel safety. Opening the door of
the Main Inverter enclosure while the
PV100S is processing power will
cause an immediate orderly shutdown
of the system.
•Fuses F15 or F16 blown
•External cooling fan
inoperable
•Air flow on heat sink
impeded due to
accumulation of debris
•Operation above rated
ambient temperature for
an extended period of
time
•Door is open and
interlock switch is
active
•Interlock switch is
inoperable
•P2 or P3 on CCU2 is
loose or disconnected
•CCU2 +/-15Vdc Power
Supply is defective
0071PV Switch OpenHThis fault indicates that the PV100S
has detected that the DC disconnect
switch (S2) is open and the auxiliary
switch is in the active position. This
fault is primarily for personnel safety.
Opening the DC disconnect switch
while the PV100S is processing
power will cause an immediate
orderly shutdown of the system.
0074Fused PV ContactorSThis fault indicates that the PV100S
has detected that upon system
shutdown, the DC bus voltage has
remained within 5% of the DC input
voltage for more than 10 seconds.
This condition is indicative of a fused
PV contactor (K2).
•DC disconnect switch is
open and auxiliary
switch is active
•Auxiliary switch is
inoperable
•P2 or P3 on CCU2 is
loose or disconnected
•CCU2 +/-15 Vdc Power
Supply is defective
•K2 is inoperable
•SSR2 is inoperable
152379 Rev C4–9
Troubleshooting
Table 4-1
Error
Code Fault Source(s)
Fault Codes
Fault Type
H=Hardware
S=Software
Fault DescriptionPossible Causes
0075Shutdown RemotelySThis fault indicates that the PV100S
has detected that the system was
commanded via the GUI to transition
to the Shutdown State. This fault is
not indicative of a failure or
malfunction, but primarily used to
disable the system remotely.
0082Matrix Not ONSThis fault indicates that the PV100S
has detected that the IGBT matrix
(FPGA) was not enabled after having
sent a command for it to turn on. The
CCU2 sends an acknowledge bit to
confirm the command is received.
This fault is primarily a watch-dog
between software and hardware to
ensure control of the IGBT matrix
(FPGA).
0083Matrix Not OFFSThis fault indicates that the PV100S
has detected that the IGBT matrix
(FPGA) was not disabled after having
sent a command for it to turn off. The
CCU2 sends an acknowledge bit to
confirm the command is received.
This fault is primarily a watch-dog
between software and hardware to
ensure control of the IGBT matrix
(FPGA).
•Remote Shutdown
command via the GUI
•Software acknowledge
bit not accepted
•FPGA inoperable
•Software acknowledge
bit not accepted
•FPGA inoperable
F000Shipping SoftwareSThis fault indicates that the PV100S
has detected that the CCU2 controller
board has shipping software installed.
This software is not operational
software. The correct system
software for the PV100S must be
downloaded into the CCU2 controller
board.
F100Software RestartedSThis fault indicates that the PV100S
has detected that the system software
has been re-booted. This is not a true
fault, and does not effect the
operation of the PV100S. It is
primarily used as a watchdog for
debugging purposes.
4–10152379 Rev C
Preventative
5
Maintenance
Chapter 5, “Preventative Maintenance” contains information and
procedures for performing preventative maintenance on the PV100S
100 kW Grid-Tied Photovoltaic Inverter.
Preventative Maintenance
Maintenance Safety
Prior to following any Maintenance Procedures, follow the System Shutdown and
Lock-out and Tag procedure.
Operational Safety Procedures
Never work alone when servicing this equipment. A team of two is required until
the equipment is properly de-energized, locked-out and tagged, and verified deenergized with a meter. Thoroughly inspect the equipment prior to energizing.
Verify that no tools or equipment have inadvertently been left behind.
WARNING: Shock Hazard
Review the system schematic for the installation to verify that all available energy sources
are de-energized. DC bus voltage may also be present. Be sure to wait the full 5 minutes to
allow the capacitors to discharge completely.
De-Energize/Isolation Procedure
The following procedure should be followed to de-energize the PV100S for
maintenance:
WARNING: Shock Hazard
The terminals of the DC input may be energized if the PV arrays are energized. In
addition, allow 5 minutes for all capacitors within the main enclosure to discharge after
disconnecting the PV100S from AC and DC sources.
To isolate the PV100S:
1. Turn the
2. Open the DC interface disconnect switch.
3. Open the AC interface disconnect switch.
4. Open the utility connection circuit breaker.
5. Install lockout devices on the utility connection circuit breaker and DC
disconnect switch.
ON/OFF switch to the OFF position.
5–2152379 Rev C
Lockout and Tag
Maintenance Safety
Safety requirements mandate that this equipment not be serviced while energized.
Power sources for the PV100S must be locked-out and tagged prior to servicing.
Each energy source should have a padlock and tag installed on each energy source
prior to servicing.
WARNING: Shock Hazard
Review the system schematic for the installation to verify that all available energy sources
are de-energized. DC bus voltage may also be present. Be sure to wait the full 5 minutes to
allow the capacitors to discharge completely.
The PV100S can be energized from both the AC source and the DC source. To
ensure that the inverter is de-energized prior to servicing, lock out and tag the
PV100S using the following procedure.
1. Open, lockout, and tag the incoming power at the utility main circuit breaker.
2. Open, lockout, and tag the AC Disconnect Switch (S1) on AC interface
assembly.See Figure 1-8 on page 1–12 for the location of the AC Disconnect
Switch.
3. Open, lockout, and tag the DC Disconnect Switch (S2) on DC interface
assembly. See Figure 1-8 on page 1–12 for the location of the DC Disconnect
Switch.
4. Using a confirmed, accurate meter, verify all power to the inverter is deenergized. A confirmed, accurate meter must be verified on a known voltage
before use. Ensure that all incoming energy sources are de-energized by
checking the following locations.
a) Inverter Terminals: TB4-A, TB4-B, TB4-C (Phase A, B, C)
See Figure 5-1 on page 5–4.
b) Utility Terminals: Top of S1-2T1, S1-4T2, S1-6T3
See Figure 5-2 on page 5–4.
c) PV Terminals: Bottom of TB3-1, TB3-2, TB3-3 (PV+, PV-, GND)
See Figure 5-3 on page 5–5.
152379 Rev C5–3
Preventative Maintenance
TB4-A
TB4-B
TB4-C
TB1 Ground Bar
Figure 5-1
TB6 -
Neutral
Inverter AC Terminal Locations in the Main Inverter Enclosure
Enlargement of Terminal Connectors
in the AC Interface Enclosure
S1-2T1
(A phase)
AC Interface Enclosure
S1-4T2
(B phase)
S1-6T3
(C phase)
Figure 5-2
Utility AC Terminal Connections in the AC Interface Enclosure
5–4152379 Rev C
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.