WIKA LH-10 User Manual [en, de, es, fr]

0 (0)

 

Operating instructions

 

 

Betriebsanleitung

 

 

Mode d'emploi

 

 

Manual de instrucciones

 

 

 

Submersible pressure transmitter, model LH-10

GB

 

 

Pegelsonde, Typ LH-10

D

 

 

Transmetteur de pression immergeable, type LH-10

F

 

 

 

Sonda de pozo, modelo LH-10

E

Submersible pressure transmitter, model LH-10

GB

 

Operating instructions model LH-10

Page

3

- 16

 

 

 

 

 

 

D

Betriebsanleitung Typ LH-10

Seite

17

- 30

 

 

 

 

 

 

Mode d'emploi type LH-10

Page

31

- 44

F

 

 

 

 

 

 

E

Manual de instrucciones modelo LH-10

Página

45

- 58

© 2013 WIKA Alexander Wiegand SE & Co. KG All rights reserved. / Alle Rechte vorbehalten.

WIKA® is a registered trademark in various countries. WIKA® ist eine geschützte Marke in verschiedenen Ländern.

Prior to starting any work, read the operating instructions! Keep for later use!

Vor Beginn aller Arbeiten Betriebsanleitung lesen!

Zum späteren Gebrauch aufbewahren!

Lire le mode d'emploi avant de commencer toute opération ! A conserver pour une utilisation ultérieure !

¡Leer el manual de instrucciones antes de comenzar cualquier trabajo! ¡Guardar el manual para una eventual consulta!

14075011.01 08/2013 GB/D/F/E

2

WIKA operating instructions submersible pressure transmitter, model LH-10

14075011.01 08/2013 GB/D/F/E

Contents

Contents

GB

1.

General information

4

2.

Safety

5

3.

Specifications

8

4.

Design and function

9

5.

Transport, packaging and storage

10

6.

Commissioning, operation

11

7.

Maintenance and cleaning

13

8.

Faults

13

9.

Dismounting, return and disposal

14

Appendix 1: EC Declaration of conformity model LH-10

16

Declarations of conformity can be found online at www.wika.com.

WIKA operating instructions submersible pressure transmitter, model LH-10

3

1.General information

1.General information

■■ The submersible pressure transmitter described in the operating instructions has been designed and manufactured using state-of-the-art technology. All components are subject to stringent quality and environmental criteria during

GB production.Our management systems are certified to ISO 9001 and ISO 14001.

■■ These operating instructions contain important information on handling the instrument. Working safely requires that all safety instructions and work instructions are observed.

■■ Observe the relevant local accident prevention regulations and general safety regulations for the instrument's range of use.

■■ The operating instructions are part of the product and must be kept in the immediate vicinity of the instrument and readily accessible to skilled personnel at any time.

■■ Skilled personnel must have carefully read and understood the operating instructions prior to beginning any work.

■■ The manufacturer's liability is void in the case of any damage caused by using the product contrary to its intended use, non-compliance with these operating instructions, assignment of insufficiently qualified skilled personnel or unauthorised modifications to the instrument.

■■ The general terms and conditions contained in the sales documentation shall apply.

■■ Subject to technical modifications.

■■ Further information:

 

 

 

- Internet address:

www.wika.de / www.wika.com

- Relevant data sheet:

PE 81.09

+49

9372 132-8976

- Application consultant:

Tel.:

 

Fax:

+49

9372 132-8008976

 

support-tronic@wika.de

14075011.01 08/2013 GB/D/F/E

4

WIKA operating instructions submersible pressure transmitter, model LH-10

1. General information / 2. Safety

Explanation of symbols

 

WARNING!

 

... indicates a potentially dangerous situation that can result in serious injury or death, if not avoided.

GB

CAUTION!

... indicates a potentially dangerous situation that can result in light injuries or damage to equipment or the

 

environment, if not avoided.

 

Information

 

...points out useful tips, recommendations and information for efficient and trouble-free operation.

 

WARNING!

 

... indicates a potentially dangerous situation that can result in burns, caused by hot surfaces or liquids, if

 

not avoided.

 

14075011.01 08/2013 GB/D/F/E

2. Safety

WARNING!

Before installation, commissioning and operation, ensure that the appropriate submersible pressure transmitter has been selected in terms of measuring range, design and specific measuring conditions.

Non-observance can result in serious injury and/or damage to the equipment.

Further important safety instructions can be found in the individual chapters of these operating instructions.

2.1 Intended use

The submersible pressure transmitter is used to convert hydrostatic pressure into an electrical signal.

The instrument has been designed and built solely for the intended use described here, and may only be used accordingly.

WIKA operating instructions submersible pressure transmitter, model LH-10

5

2. Safety

The technical specifications contained in these operating instructions must be observed.Improper handling or operation of the pressure transmitter outside of its technical specifications requires the instrument to be taken out of service immediately and inspected by an authorised WIKA service engineer.

GB The manufacturer shall not be liable for claims of any type based on operation contrary to the intended use.

2.2 Personnel qualification

WARNING!

Risk of injury should qualification be insufficient!

Improper handling can result in considerable injury and damage to equipment.

The activities described in these operating instructions may only be carried out by skilled personnel who have the qualifications described below.

Skilled personnel

Skilled personnel are understood to be personnel who, based on their technical training, knowledge of measurement and control technology and on their experience and knowledge of country-specific regulations, current standards and directives, are capable of carrying out the work described and independently recognising potential hazards.

Special operating conditions require further appropriate knowledge, e.g. of aggressive media.

2.3 Special hazards

WARNING!

For hazardous media such as acetylene, flammable or toxic gases and liquids, etc., in addition to all standard regulations, the appropriate existing codes or regulations must also be followed.

WARNING!

Residual media in the dismounted instrument can result in a risk to persons, the environment and equipment.

Take sufficient precautionary measures.

Do not use this instrument in safety or emergency stop devices. Incorrect use of the instrument can result in injury.

14075011.01 08/2013 GB/D/F/E

6

WIKA operating instructions submersible pressure transmitter, model LH-10

2.Safety

2.4Labelling, safety marks

Product label

Model

see explanation of symbols

Measuring range

Output signal Pin assignment Power supply

S# serial number P# product number

If the serial number becomes illegible due to mechanical damage or overpainting, traceability will no longer be possible.

Explanation of symbols

CE, Communauté Européenne

Instruments bearing this mark comply with the relevant European directives.

CSA, Canadian Standard Association®

The instrument has been inspected and certified by CSA International.Instruments bearing this mark comply with the applicable Canadian standards on safety (including explosion protection).

14075011.01 08/2013 GB/D/F/E

GB

WIKA operating instructions submersible pressure transmitter, model LH-10

7

3.Specifications

3.Specifications

 

Measuring ranges

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GB

 

Relative pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

bar

Measuring range

...0

0.1

...0

0.16

...0

0.25

...0

0.4

...0

0.6

...0

1

...0

1.6

 

 

 

Overpressure limit

1

 

1.5

 

2

 

2

 

3

 

5

 

8

 

 

 

 

Burst pressure

2

 

2

 

2.4

 

2.4

 

4

 

6

 

10

 

 

 

 

Measuring range

0 ...

2.5

0 ...

4

0 ...

6

0 ...

10

0 ...

16

0 ...

25

 

 

 

 

 

Overpressure limit

8

 

10

 

10

 

10

 

16

 

25

 

 

 

 

 

 

Burst pressure

10

 

10

 

10

 

10

 

16

 

25

 

 

 

 

 

inWC

Measuring range

0 ...

50

0 ...

100

0 ...

150

0 ...

250

 

 

 

 

 

 

 

 

 

Overpressure limit

750

 

750

 

750

1,100

 

 

 

 

 

 

 

 

 

Burst pressure

950

 

950

 

950

1,600

 

 

 

 

 

 

 

 

psi

Measuring range

0 ...

5

0 ...

10

0 ...

15

0 ...

25

0 ...

50

0 ...

100

0 ...

150

 

 

 

Overpressure limit

30

 

45

 

70

 

120

 

150

 

150

 

150

 

 

 

 

Burst pressure

35

 

60

 

90

 

180

 

150

 

150

 

150

 

 

 

 

Measuring range

0 ...

160

0 ...

200

0 ...

300

 

 

 

 

 

 

 

 

 

 

 

Overpressure limit

160

 

200

 

300

 

 

 

 

 

 

 

 

 

 

 

Burst pressure

160

 

200

 

300

 

 

 

 

 

 

 

 

 

 

mH2O

Measuring range

0 ...

1

0 ...

1.6

0 ...

2.5

0 ...

4

0 ...

6

0 ...

10

0 ...

16

 

 

 

Overpressure limit

10

 

15

 

20

 

20

 

30

 

50

 

80

 

 

 

 

Burst pressure

20

 

20

 

24

 

24

 

40

 

60

 

100

 

 

 

 

Measuring range

0 ...

25

0 ...

40

0 ..

60

0 ...

100

0 ...

160

0 ...

250

 

 

 

 

 

Overpressure limit

80

 

100

 

100

100

 

160

 

250

 

 

 

 

 

 

Burst pressure

100

 

100

 

100

100

 

160

 

250

 

 

 

When choosing the FEP cable, measuring ranges up to and including 0 ...10 bar, 0 ... 150 psi and 0 ... 100 mH2O are available.

The given measuring ranges are also available in mbar, kPa and MPa.

14075011.01 08/2013 GB/D/F/E

8

WIKA operating instructions submersible pressure transmitter, model LH-10

3.Specifications / 4.Design and function

Output signals

 

 

Signal type

Signal

Current (2-wire)

4 ... 20 mA

Current (3-wire)

0 ... 20 mA

Voltage (3-wire)

DC 0

... 5 V

 

DC 0

... 10 V

 

DC 0.5 ... 2.5 V

Power supply

The power supply depends on the selected output signal.

■■ 4 ... 20 mA:

DC 10 ... 30 V

■■ 0 ... 20 mA:

DC 10 ... 30 V

■■ DC 0

... 5 V:

DC 10 ... 30 V

■■ DC 0

... 10 V:

DC 14 ... 30 V

■■ DC 0.5 ... 2.5 V:

DC 5 ... 30 V (suitable for battery

 

 

operation)

Ingress protection (per IEC 60529)

IP 68

Permissible temperature ranges

■■ Fluid

- PUR cable:

-10 ... +50 °C

GB

- FEP cable:

-10 ... +85 °C

 

■■ Ambient:

-10 ... +50 °C

 

■■ Storage:

-30 ... +80 °C

 

Submersion depths

 

■■ Submersible pressure

up to 100 m

transmitter with FEP cable:

■■ Submersible pressure

up to 300 m

transmitter with PUR cable:

CE conformity

EMC directive 2004/108/EC, EN 61326 emission (group 1, class B) and immunity (industrial application)

For special model numbers, e.g.LH-10000, please note the specifications stated on the delivery note.

For further specifications seeWIKA data sheet PE 81.09 and the order documentation.

14075011.01 08/2013 GB/D/F/E

4.Design and function

4.1Description

The prevailing pressure is measured at the sensor element through the deformation of a diaphragm. By supplying power, this deformation of the diaphragm is converted into an electrical signal. The output signal from the pressure transmitter is amplified and proportional to the prevailing pressure.

4.2 Scope of delivery

Cross-check scope of delivery with delivery note.

WIKA operating instructions submersible pressure transmitter, model LH-10

9

5. Transport, packaging and storage

5.Transport, packaging and storage

5.1Transport

Check the submersible pressure transmitter for any damage that may have been caused by transport. GB Obvious damage must be reported immediately.

5.2 Packaging

Do not remove packaging until just before mounting.

Keep the packaging as it will provide optimum protection during transport (e.g. change in installation site, sending for repair).

5.3 Storage

Permissible conditions at the place of storage:

Storage temperature: -30 ... +80 °C

Mount the protection cap for storing the submersible pressure transmitter, so that the diaphragm will not be damaged.

Avoid exposure to the following factors:

■■ Direct sunlight or proximity to hot objects

■■ Mechanical vibration, mechanical shock (putting it down hard) ■■ Soot, vapour, dust and corrosive gases

■■ Humid or wet environment

■■ Potentially explosive environments, flammable atmospheres

Store the submersible pressure transmitter in its original packaging in a location that fulfils the conditions listed above.

If the original packaging is not available, pack and store the instrument as described below:

1.Wrap the instrument in an antistatic plastic film.

2.Place the instrument along with shock-absorbent material in the packaging.

3.If stored for a prolonged period of time (more than 30 days), place a bag containing a desiccant inside the packaging.

WARNING!

Before storing the instrument (following operation), remove any residual media. This is of particular importance if the medium is hazardous to health, e.g. caustic, toxic, carcinogenic, radioactive, etc.

14075011.01 08/2013 GB/D/F/E

10

WIKA operating instructions submersible pressure transmitter, model LH-10

6. Commissioning, operation

6. Commissioning, operation

WARNING!

GB

Observe the working conditions in accordance with chapter 3 “Specifications”.

CAUTION!

 

Prior to commissioning, the submersible pressure transmitter must be subjected to a visual inspection.

 

■■ Leaking fluid is indicative of damage.

 

■■ Only use the submersible pressure transmitter if it is in perfect condition with respect to safety.

 

6.1 Mechanical mounting

 

The protection cap protects the internal diaphragm from damage. Remove the protective cap if the medium is viscous

 

or contaminated.

 

Protection cap

Internal diaphragm

14075011.01 08/2013 GB/D/F/E

6.2 Electrical mounting

6.2.1 Connection assembly

■■ Use the submersible pressure transmitter with shielded cable and ground the shield on at least one end of the lead, if the lines are longer than 30 m or leave the building.

■■ When the shield of the cable is being connected, no potential differences should exist between the medium, the vessel and the ground connection of the junction box or the control cabinet.

■■ Make sure that no moisture enters at the cable end.

WIKA operating instructions submersible pressure transmitter, model LH-10

11

6. Commissioning, operation

 

6.2.2 Pin assignment

 

 

 

Cable outlet

2-wire

3-wire

GB

U+

brown

brown

U-

green

green

 

S+

-

white

 

Shield

grey

grey

6.2.3 Setting up a voltage supply

The power supply for the pressure transmitter must be made via an energy-limited electrical circuit in accordance with section 9.3 of UL/EN/IEC 61010-1, or an LPS to UL/EN/IEC 60950-1, or (for North America) class 2 in accordance with

UL1310/UL1585 (NEC or CEC). The power supply must be suitable for operation above 2,000 m should the pressure transmitter be used at this altitude.

■■ Power supply

The power supply depends on the selected output signal.

4 ... 20 mA:

DC 10 ... 30 V

0 ... 20 mA:

DC 10 ... 30 V

DC 0

... 5 V:

DC 10 ... 30 V

DC 0

... 10 V:

DC 14 ... 30 V

DC 0.5 ... 2.5 V: DC 5 ... 30 V (suitable for battery operation)

■■ Load in Ω

Current output (2-wire): ≤ (power supply - 10V) / 0.02 A - (cable length in m x 0.14 Ω) Current output (3-wire): ≤ (power supply - 3V) / 0.02 A - (cable length in m x 0.14 Ω)

Voltage output (3-wire): > 100 kΩ

6.3 Functional check

The output signal must be proportional to the prevailing pressure. If this is not the case, this may indicate a damaged diaphragm.In this case, see chapter 8 “Faults”.

14075011.01 08/2013 GB/D/F/E

12

WIKA operating instructions submersible pressure transmitter, model LH-10

7. Maintenance and cleaning

7.Maintenance and cleaning

7.1Maintenance

This submersible pressure transmitter is maintenance-free.

GB

Repairs must only be carried out by the manufacturer.

7.2 Cleaning

 

CAUTION!

 

■■ Prior to cleaning, switch off and disconnect the submersible pressure transmitter from the voltage

 

supply.

 

■■ Clean the instrument with a moist cloth.

 

■■ Wash or clean the dismounted instrument before returning it, in order to protect persons and the environ-

 

ment from exposure to residual media.

 

■■ Residual media in dismounted instruments can result in a risk to persons, the environment and

 

equipment.Take sufficient precautionary measures.

 

■■ Do not use any pointed or hard objects for cleaning, as they may damage the diaphragm of the process

 

connection.

 

For information on returning the instrument see chapter 9.2 “Return”.

8. Faults

14075011.01 08/2013 GB/D/F/E

In the event of any faults, first check whether the submersible pressure transmitter is mounted correctly, mechanically and electrically.

Faults

Causes

Measures

No output signal

Cable break

Check the continuity, and if necessary exchange

 

 

the cable

 

No/wrong power supply

Correct the power supply

No/wrong output signal

Wiring error

Rectify the wiring

WIKA operating instructions submersible pressure transmitter, model LH-10

13

8. Faults / 9. Dismounting, return and disposal

 

 

Faults

Causes

Measures

 

 

Signal span too small/drops

Mechanical overload caused by overpres-

Replace instrument; if it fails repeatedly, contact

 

 

 

sure

the manufacturer.

 

 

 

Diaphragm damaged, e.g. due to impacts,

Replace instrument; if it fails repeatedly, contact

GB

 

 

 

 

abrasive/aggressive medium; corrosion at

the manufacturer.

 

 

 

diaphragm; transmission medium missing

 

 

 

Signal span varies/inaccurate

Operating temperature too high/low

Operate the instrument in the permissible

 

 

 

 

temperature range

 

 

Deviating zero point signal

Operating temperature too high/low

Operate the instrument in the permissible

 

 

 

Diaphragm damaged, e.g. due to impacts,

temperature range

 

 

 

Replace instrument; if it fails repeatedly, contact

 

 

 

abrasive/aggressive medium; corrosion at

the manufacturer.

 

 

 

diaphragm; transmission medium missing

 

If complaint is unjustified, we will charge you the complaint processing fees.

CAUTION!

If faults cannot be eliminated by means of the measures listed above, shut down the submersible pressure transmitter immediately, and ensure that pressure is no longer present, and secure the instrument from being put back into operation inadvertently. In this case, contact the manufacturer. If a return is needed, please follow the instructions given in chapter 9.2 “Return”.

9. Dismounting, return and disposal

WARNING!

Residual media in the dismounted instrument can result in a risk to persons, the environment and equipment.Take sufficient precautionary measures.

9.1 Disassembly

WARNING!

Risk of burns!

Let the instrument cool down sufficiently before dismounting it!

During dismounting there is a risk of residual, dangerously hot media.

14075011.01 08/2013 GB/D/F/E

14

WIKA operating instructions submersible pressure transmitter, model LH-10

9. Dismounting, return and disposal

9.2 Return

 

WARNING!

 

Strictly observe the following when shipping the submersible pressure transmitter:

GB

All submersible pressure transmitters delivered to WIKA must be free from any kind of hazardous substances

(acids, bases, solutions, etc.).

 

When returning the instrument, use the original packaging or a suitable transport package.

 

To avoid damage:

1.Wrap the instrument in an antistatic plastic film.

2.Place the instrument along with shock-absorbent material in the packaging. Place shock-absorbent material evenly on all sides of the transport packaging.

3.If possible, place a bag containing a desiccant inside the packaging.

4.Label the shipment as carriage of a highly sensitive measuring instrument.

5.Mount the protection cap.

Information on returns can be found under the heading “Service”on our local website.

9.3 Disposal

Incorrect disposal can put the environment at risk.

Dispose of instrument components and packaging materials in an environmentally compatible way and in accordance with the country-specific waste disposal regulations.

14075011.01 08/2013 GB/D/F/E

WIKA operating instructions submersible pressure transmitter, model LH-10

15

WIKA LH-10 User Manual

Appendix 1: EC Declaration of conformity model LH-10

GB

14075011.01 08/2013 GB/D/F/E

16

WIKA operating instructions submersible pressure transmitter, model LH-10

Inhalt

Inhalt

14075011.01 08/2013 GB/D/F/E

D

1. Allgemeines

18

2. Sicherheit

19

3. Technische Daten

22

4. Aufbau und Funktion

23

5. Transport, Verpackung und Lagerung

24

6. Inbetriebnahme, Betrieb

25

7. Wartung und Reinigung

27

8. Störungen

27

9. Demontage, Rücksendung und Entsorgung

28

Anlage 1: EG-Konformitätserklärung Typ LH-10

30

Konformitätserklärungen finden Sie online unter www.wika.de.

WIKA Betriebsanleitung Pegelsonde, Typ LH-10

17

1. Allgemeines

1. Allgemeines

 

■■ Die in der Betriebsanleitung beschriebene Pegelsonde wird nach dem aktuellen Stand der Technik konstruiert und

 

gefertigt. Alle Komponenten unterliegen während der Fertigung strengen Qualitätsund Umweltkriterien. Unsere

 

Managementsysteme sind nach ISO 9001 und ISO 14001 zertifiziert.

 

■■ Diese Betriebsanleitung gibt wichtige Hinweise zum Umgang mit dem Gerät. Voraussetzung für sicheres Arbeiten ist

D

die Einhaltung aller angegebenen Sicherheitshinweise und Handlungsanweisungen.

 

■■ Die für den Einsatzbereich des Gerätes geltenden örtlichen Unfallverhütungsvorschriften und allgemeinen

 

Sicherheitsbestimmungen einhalten.

 

 

■■ Die Betriebsanleitung ist Produktbestandteil und muss in unmittelbarer Nähe des Gerätes für das Fachpersonal

 

jederzeit zugänglich aufbewahrt werden.

 

■■ Das Fachpersonal muss die Betriebsanleitung vor Beginn aller Arbeiten sorgfältig durchgelesen und verstanden

 

haben.

 

 

 

■■ Die Haftung des Herstellers erlischt bei Schäden durch bestimmungswidrige Verwendung, Nichtbeachten dieser

 

Betriebsanleitung, Einsatz ungenügend qualifizierten Fachpersonals sowie eigenmächtigerVeränderung am Gerät.

 

■■ Es gelten die allgemeinen Geschäftsbedingungen in den Verkaufsunterlagen.

 

■■ Technische Änderungen vorbehalten.

 

 

■■ Weitere Informationen:

 

 

 

- Internet-Adresse:

www.wika.de / www.wika.com

 

- zugehöriges Datenblatt:

PE 81.09

+49 9372 132-8976

 

- Anwendungsberater:

Tel.:

 

 

Fax:

+49 9372 132-8008976

support-tronic@wika.de

14075011.01 08/2013 GB/D/F/E

18

WIKA Betriebsanleitung Pegelsonde, Typ LH-10