WIKA A2G-55 User Manual [en, de, es, fr, it]

4 (1)

Operating instructions

Betriebsanleitung

Mode d'emploi

Manual de instrucciones

Instruzioni per l'uso

ECO differential pressure transmitter model A2G-55

 

 

 

GB

 

 

 

ECO-Differenzdrucktransmitter Typ A2G-55

D

 

 

 

Transmetteur de pression différentielle ECO, type A2G-55

F

 

 

 

Transmisor de presión diferencial ECO modelo A2G-55

E

Trasmettitore di pressione differenziale ECO modello A2G-55 I

ECO differential pressure transmitter air2guide E, model A2G-55

 

 

 

 

 

GB

Operating instructions model A2G-55

Page

 

3 - 8

 

 

 

 

D

Betriebsanleitung Typ A2G-55

Seite

9 - 14

 

 

 

 

 

F

Mode d'emploi type A2G-55

Page

15

- 20

 

 

 

 

E

Manual de instrucciones modelo A2G-55

Página 21

- 26

 

 

 

 

I

Instruzioni per l'uso modello A2G-55

Pagina 27

- 32

2

40317650.01 09/2010 GB/D/F/E/I

WIKA operating instructions air2guide model A2G-55

Contents

Contents

 

 

 

 

1.

General information

4

GB

 

2.

Safety

4

 

3.

Description

4

 

4.

Specifications and intended use

5

 

5.

Installation

6

 

6.

Commissioning / Electrical connections

6

 

7.

Storage

7

 

8.

Maintenance and cleaning

7

 

9.

Repairs

7

 

10.

Disposal

7

 

11.

Dimensions

8

 

40317650.01 09/2010 GB/D/F/E/I

Warning!

This symbol warns you against actions that can cause injury to people or damage to the instrument.

WIKA operating instructions air2guide model A2G-55

3

1.General information / 2.Safety / 3.Description

1.General information

Please keep these operating instructions in a place where they will be easily accessible and visible to all users.The information contained in

GB these installation and operating instructions has been compiled with care and is, to the best of our knowledge, accurate and correct.For additional information relating to your specific application please refer to:

■■ Official website at www.air2guide.com

■■ The appropriate data sheet

2.Safety

WARNING!

Electrical devices may only be installed and mounted by a qualified electrician.

The modules may not be used in connection with devices that directly or indirectly affect human health or safety or that could endanger humans, animals or material assets.

■■ Serious injuries and/or damage can occur should the appropriate regulations not be observed.

■■ Only qualified personnel, who are familiar with the relevant countryspecific regulations, should install and commission this ECO differential pressure transmitter.

3.Description

These operating instructions apply to the following model:

ECO differential pressure transmitter model A2G-55, data sheet SP 69.05

4

WIKA operating instructions air2guide model A2G-55

40317650.01 09/2010 GB/D/F/E/I

40317650.01 09/2010 GB/D/F/E/I

4.Specifications and intended use

4.Specifications and intended use

Accuracy

Linearisation error: ±1.0 % FS

Measuring accuracy at 0 … +50 °C: ±3.0 % FS at -10 … +50 °C: ±5.0 % FS

Typical overall error: ±2.0 % FS

Measuring ranges

0 … 250 Pa, 0 … 500 Pa, 0 … 750 Pa, 0 … 1000 Pa,

0 … 1250 Pa, 0 … 2500 Pa, 0 … 3750 Pa, 0 … 5000 Pa

Maximum pressure

0 … 250 to 0 … 750 Pa: 5 kPa 0 … 1000 to 0 … 5000 Pa: 5 x FS

Burst pressure

0 … 250 to 0 … 750 Pa: 10 kPa 0 … 1000 to 0 … 5000 Pa: 10 x FS

Operating temperature

Storage: -20 … +85 °C

Operation: -10 … +50 °C

Ingress protection

IP 65 per EN 60529 / lEC 529

Standards

CE conformity:

89/336/EEC Electromagnetic Compatibility

2002/95/EG RoHS (restriction of the use of certain hazardous substances in electrical and electronic equipment)

WIKA operating instructions air2guide model A2G-55

GB

5

5.Installation / 6.Commissioning / Electrical connections

5.Installation

■■ Protect measuring instruments from contamination, high temperature changes and vibrations

GB ■■ In order to avoid any additional heating, the instruments must not be exposed to direct solar irradiation while in operation.

■■ The differential pressure transmitter must be screw-fitted on a suitable vertical surface.The instrument has to be mounted horizontally using the enclosed mounting screws.

6.Commissioning / Electrical connections

Output signal

DC 0 … 10V, 3-wire optionally 4 … 20 mA, 2-wire

Supply voltage

DC 13 ...32V

Electrical connection

PG-gland M16

Screw terminals max.1.5 mm²

Connection diagram

Output signal DC 0 … 10V, 3-wire

Uv Out Gnd

Uv Out Gnd

Legend

Pin 1: Power supply (+)

Pin 2: Output signal

Pin 3: Ground

Output signal 4 … 20 mA, 2-wire

Loop

Legend

Pin 1: Loop +

Pin 3: Loop -

6

WIKA operating instructions air2guide model A2G-55

40317650.01 09/2010 GB/D/F/E/I

7.Storage / 8.Maintenance and cleaning ...10.Disposal

7.Storage

■■ To protect the differential pressure transmitters from mechanical damage keep them in the original packaging until installation.

■■ Storage temperature range:-20 ...+85 °C GB ■■ Protect pressure measuring instruments from moisture and dust.

8.Maintenance and cleaning

Clean the instruments with a moist cloth (soap water).

9.Repairs

Repairs must only be carried out by the manufacturer or appropriately qualified personnel.For further specifications seeWIKA data sheet

SP 69.05.

10.Disposal

Incorrect disposal can put the environment at risk.

Dispose of instrument components and packaging materials in an environmentally compatible way and in accordance with the countryspecific waste disposal regulations.

40317650.01 09/2010 GB/D/F/E/I

WIKA operating instructions air2guide model A2G-55

7

WIKA A2G-55 User Manual

12.Dimensions in mm

12.Dimensions in mm

GB

8

40317650.01 09/2010 GB/D/F/E/I

WIKA operating instructions air2guide model A2G-55

Inhalt

Inhalt

1.

Allgemeines

10

 

2.

Sicherheit

10

D

 

3.

Beschreibung

10

 

4.

Technische Daten und bestimmungsgemäße

11

 

 

Verwendung

 

 

5.

Installation

12

 

6.

Inbetriebnahme / Elektrische Anschlüsse

12

 

7.

Lagerung

13

 

8.

Wartung und Reinigung

13

 

9.

Reparaturen

13

 

10.

Entsorgung

13

 

11.

Abmessungen

14

 

40317650.01 09/2010 GB/D/F/E/I

Warnung!

Dieses Symbol warnt Sie vor Handlungen, die Schäden an Personen oder am Gerät verursachen können.

WIKA Betriebsanleitung air2guide Typ A2G-55

9

1.Allgemeines / 2.Sicherheitshinweise / 3.Beschreibung

1.Allgemeines

Bewahren Sie die Betriebsanleitung an einem für alle Benutzer zugänglichen Ort auf.Die nachfolgenden Einbauund Betriebshinweise haben wir nach bestemWissen und Gewissen zusammengestellt.Sollten Sie Hinweise für Ihre spezielle Anwendung vermissen, können Sie weitere

DInformationen finden:

■■ Über unsere Homepage www.air2guide.com

■■ Die Bezeichnung des zugehörenden Datenblattes

2.Sicherheit

WARNUNG!

Einbau und Montage elektrischer Geräte dürfen nur durch eine Elektrofachkraft erfolgen.

Die Module dürfen nicht inVerbindung mit Geräten benutzt werden, die direkt oder indirekt menschlichen, gesundheitsoder lebenssichernden Zwecken dienen oder durch deren Betrieb Gefahren für Menschen,Tiere oder Sachwerte entstehen können.

■■ Bei Nichtbeachten der entsprechendenVorschriften können Körperverletzungen und/oder Sachschäden auftreten.

■■ Montieren und nehmen Sie den ECO-Differenzdrucktransmitter nur in Betrieb, wenn Sie mit den zutreffenden landesspezifischen Richtlinien vertraut sind und die entsprechende Qualifikation besitzen.

3.Beschreibung

Diese Betriebsanleitung ist gültig für denTyp:

ECO-Differenzdrucktransmitter

Typ A2G-55, Datenblatt SP 69.05

10

WIKA Betriebsanleitung air2guide Typ A2G-55

40317650.01 09/2010 GB/D/F/E/I

4.Technische Daten und bestimmungsgemäße Verwendung

40317650.01 09/2010 GB/D/F/E/I

4.Technische Daten und bestimmungsgemäße Verwendung

Genauigkeit

±1,0 % FS

 

Linearitätsfehler:

±3,0 % FS

Messgenauigkeit

bei 0 … +50 °C:

 

bei -10 … +50 °C:

±5,0 % FS

Typischer Gesamtfehler: ±2,0 % FS

 

D

Messbereiche

 

0

… 250 Pa, 0 … 500 Pa, 0 … 750 Pa, 0 … 1000 Pa,

 

0

… 1250 Pa, 0 … 2500 Pa, 0 … 3750 Pa, 0 … 5000 Pa

 

Maximaler Druck

0 … 250 bis 0 … 750 Pa: 5 kPa 0 … 1000 bis 0 … 5000 Pa: 5 x FS

Berstdruck

0 … 250 bis 0 … 750 Pa: 10 kPa 0 … 1000 bis 0 … 5000 Pa: 10 x FS

Zulässige Temperatur

Lagerung:

-20 … +85 °C

Betrieb:

-10 … +50 °C

Schutzart

IP 65 nach EN 60529 / lEC 529

Normen und Standards

CE-Konformität:

89/336/EWG ElektromagnetischeVerträglichkeit

2002/95/EG RoHS (Beschränkung derVerwendung bestimmter gefährlicher Stoffe in Elektround Elektronikgeräten)

WIKA Betriebsanleitung air2guide Typ A2G-55

11