Electronic differential pressure switch with display, model A2G-45
|
|
|
|
|
|
|
|
|
|
|
|
GB |
|
Operating instructions model A2G-45 |
Page |
3-13 |
|
|
|
|
|
|
|
D |
Betriebsanleitung Typ A2G-45 |
Seite |
15-25 |
||
|
|
|
|
|
|
F |
Mode d'emploi type A2G-45 |
Page |
27-37 |
||
|
|
|
|
|
|
E |
Manual de instrucciones modelo A2G-45 |
Página |
39-49 |
||
|
|
|
|
|
|
Manuale d'uso modello A2G-45 |
Pagina |
51-61 |
|||
I |
© 2012 WIKA Alexander Wiegand SE & Co. KG All rights reserved. / Alle Rechte vorbehalten.
WIKA® is a registered trademark in various countries. WIKA® ist eine geschützte Marke in verschiedenen Ländern.
Prior to starting any work, read the operating instructions! Keep for later use!
Vor Beginn aller Arbeiten Betriebsanleitung lesen! Zum späteren Gebrauch aufbewahren!
Lire le mode d‘emploi avant de commencer toute opération ! A conserver pour une utilisation ultérieure !
¡Leer el manual de instrucciones antes de comenzar cualquier trabajo! ¡Guardar el manual para una eventual consulta!
Prima di iniziare ad utilizzare lo strumento, leggere il manuale d‘uso! Conservare per future consultazioni!
40389228.01 09/2012 GB/D/F/E/I
2 |
WIKA operating instructions air2guide model A2G-45 |
Contents
Contents
|
|
|
|
1. |
General information |
4 |
GB |
|
|||
2. |
Safety |
5 |
|
3. |
Specifications |
6 |
|
4. |
Design and function |
7 |
|
5. |
Transport, packaging and storage |
8 |
|
6. |
Commissioning, operation |
9 |
|
7. |
Maintenance and cleaning |
13 |
|
8. |
Disposal |
13 |
|
40389228.01 09/2012 GB/D/F/E/I
WIKA operating instructions air2guide model A2G-45 |
3 |
1.General information
1.General information
|
■■ |
The electronic differential pressure switch with display described |
|
|
|
in the operating instructions has been designed and manufactured |
|
|
|
using state-of-the-art technology. All components are subject to |
|
GB |
|
||
|
stringent quality and environmental criteria during production. Our |
||
|
|
management systems are certified to ISO 9001 and ISO 14001. |
|
|
■■ |
These operating instructions contain important information on |
|
|
|
handling the instrument. Working safely requires that all safety |
|
|
|
instructions and work instructions are observed. |
|
|
■■ |
Observe the relevant local accident prevention regulations and |
|
|
|
general safety regulations for the instrument's range of use. |
|
|
■■ |
The operating instructions are part of the product and must be kept |
|
|
|
in the immediate vicinity of the instrument and readily accessible to |
|
|
|
skilled personnel at any time. |
|
|
■■ |
Skilled personnel must have carefully read and understood the |
|
|
|
operating instructions prior to beginning any work. |
|
|
■■ |
The manufacturer's liability is void in the case of any damage caused |
|
|
|
by using the product contrary to its intended use, non-compliance |
|
|
|
with these operating instructions, assignment of insufficiently quali- |
|
|
|
fied skilled personnel or unauthorised modifications to the instru- |
|
|
|
ment. |
|
|
■■ |
The general terms and conditions contained in the sales documenta- |
|
|
|
tion shall apply. |
|
|
■■ |
Subject to technical modifications. |
|
|
■■ |
Further information: |
www.wika.de / www.wika.com |
|
|
- Internet address: |
|
|
|
|
www.air2guide.com |
|
|
- relevant data sheet: SP 69.08 |
40389228.01 09/2012 GB/D/F/E/I
4 |
WIKA operating instructions air2guide model A2G-45 |
40389228.01 09/2012 GB/D/F/E/I
1.General information / 2.Safety
Explanation of symbols
WARNING!
... indicates a potentially dangerous situation that can result in serious injury or death, if not avoided.
GB
Information
... points out useful tips, recommendations and information for efficient and trouble-free operation.
2.Safety
WARNING!
Before installation, commissioning and operation, ensure that the appropriate differential pressure switch has been selected in terms of measuring range, design and specific measuring conditions.
Non-observance can result in serious injury and/or damage to the equipment.
Further important safety instructions can be found in the individual chapters of these operating instructions.
2.1 Intended use
This electronic differential pressure switch is used for monitoring the differential pressure of air and other non-inflammable and non-aggres- sive gases.And also for controlling air as well for monitoring of air filters, blowers in ventilation ducts, control of air and fire shutters, for overpressure monitoring in clean rooms and laboratories.
The instrument has been designed and built solely for the intended use described here, and may only be used accordingly.
The manufacturer shall not be liable for claims of any type based on operation contrary to the intended use.
WIKA operating instructions air2guide model A2G-45 |
5 |
2.Safety / 3.Specifications
2.2 Personnel qualification
WARNING!
Risk of injury should qualification be insufficient!
GB Improper handling can result in considerable injury and damage to equipment.
■■ The activities described in these operating instructions may only be carried out by skilled personnel who have the qualifications described below.
Skilled personnel
Skilled personnel are understood to be personnel who, based on their technical training, knowledge of measurement and control technology and on their experience and knowledge of country-specific regulations, current standards and directives, are capable of carrying out the work described and independently recognising potential hazards.
Explanation of symbols
CE, Communauté Européenne
Instruments bearing this mark comply with the relevant
European directives.
3.Specifications
Process connection
Connecting nozzle (copper alloy), for hoses with inner diameter 4 or 6 mm
Measuring element
Piezo measuring cell
Case/cover
Plastic (ABS)/plastic (PC)
40389228.01 09/2012 GB/D/F/E/I
6 |
WIKA operating instructions air2guide model A2G-45 |
3.Specifications
Electrical connection
Cable gland M16 and M20, screw terminals max. 1.5 mm²
Output signal |
|
0 … 10 V, 2-wire, load resistance min. 1 kOhm |
GB |
|
Voltage supply
AC 24 V ±10 % or DC 21 ... 35 V
Long-term stability
≤±8 Pa
≤±1 Pa with automatic zero adjustment (option)
Dimensions in mm
GB/D/F/E/I |
Weight |
|
|
150 g |
|
||
Ingress protection |
|
||
09/2012 |
|
||
IP 54 per EN 60529 / lEC 529 |
|
||
For further specifications seeWIKA data sheet SP 69.08 and the order |
|
||
40389228.01 |
|
||
documentation. |
|
||
WIKA operating instructions air2guide model A2G-45 |
7 |
||
|
4.Design and function / 5.Transport, packaging ...
4.Design and function
4.1 Description
Design
GB CE conformity:
2004/108/EC electromagnetic compatibility
2002/95/EC RoHS (restriction of the use of certain hazardous substances in electrical and electronic equipment)
Accuracy class
1.5 %
Measuring ranges
■■ Variant 1: -500 ... +500 Pa (-100 .. +100 Pa, -250 ... +250 Pa, -300 ... +300 Pa to be set via jumper) or
■■ Variant 2: 0 ... 2,500 Pa (0 ... +100 Pa, 0 ... +250 Pa, 0 ... +1,000 Pa to be set via jumper)
Pressure limitation
Maximum pressure: 25 kPa
Permissible temperature
Ambient: -20 … +70 °C
Operation: -10 … +50 °C
(-5 … +50 °C with automatic zero adjustment)
4.2 Scope of delivery
Cross-check scope of delivery with delivery note.
5.Transport, packaging and storage
5.1 Transport
Check the differential pressure switch for any damage that may have been caused by transport. Obvious damage must be reported immediately.
40389228.01 09/2012 GB/D/F/E/I
8 |
WIKA operating instructions air2guide model A2G-45 |
40389228.01 09/2012 GB/D/F/E/I
6.Commissioning, operation
5.2 Packaging
Do not remove packaging until just before mounting.
Keep the packaging as it will provide optimum protection during transport (e.g. change in installation site, sending for repair).
|
|
|
|
5.3 Storage |
GB |
||
|
|||
Permissible conditions at the place of storage |
|
||
Storage temperature: -20 ... +70 °C |
|
||
Protect the instruments from moisture and dust. |
|
||
|
|
|
|
6.Commissioning, operation |
|
||
Installation |
|
||
■■ |
When connecting the instrument, the process lines must be free of |
|
|
|
pressure. |
|
|
■■ |
Observe the suitability of the instrument for the media to be |
|
|
|
measured |
|
|
■■ |
Observe maximum pressures |
|
Electrical connection
The instruments are designed to operate with safety extra-low voltage
(SELV).When wiring up the instruments, the technical specifications for those instruments should be followed. In the case of a sensor with transmitter, as a rule, the transmitter should be operated in the middle of the measuring range, since deviations can occur at the range limits.
■■ The ambient temperature of the transmitter electronics should be kept constant.
■■ Current/voltage spikes from switching the power supply on or off must be prevented by the customer.
Current consumption
35 mA + switch (7 mA each) + instrument with automatic zero adjustment (20 mA)
0 … 10 V output (10 mA), max. 80 mA
WIKA operating instructions air2guide model A2G-45 |
9 |
6.Commissioning, operation
Connection diagram
Relay 1 (standard)
Power supply AC 24 V
Output signal 0 ... 10 V
GB
Relay 2 (option)
If the voltages being switched via the relays are not in accordance with SELV, then the power supply and signal/control cables of the relays should be installed so that they are separated. A separate cable entry is available for both.
Commissioning
A prerequisite for the commissioning is a proper installation of all electrical supply, control and measuring lines and of the pressure connection lines.
■■ Before commissioning, the leak tightness of the pressure connection lines must be checked.
Buttons for setting the individual functions
Key Function
MENU
BACK
OK
To access the menu, press the "MENU" button for approx. 3 seconds.
To exit the menu, press the "BACK" button.
To open an individual menu point, and to accept the changes, press the "OK" button.
These buttons enable you to scroll within the menu.
40389228.01 09/2012 GB/D/F/E/I
10 |
WIKA operating instructions air2guide model A2G-45 |
6.Commissioning, operation
Menu selection and initialisation instructions for installation
1. Pressure units selectable: Pa, kPa, mmH2O, inchWC, mbar
GB
2. Measuring ranges selectable, see page 3.Specifications
3. Response time selectable: 0.5 ... 10 s
4. Zero point adjustment and span calibration
Calibration of the upper point
Reset the span setting
5. Set point (between min. and max. pressure)
6. Hysteresis (0 ... 5 % of measuring range)
40389228.01 09/2012 GB/D/F/E/I
WIKA operating instructions air2guide model A2G-45 |
11 |
6.Commissioning, operation
Zero point adjustment
|
|
Attention! |
|
|
Connect the voltage supply one hour before making the |
|
|
zero point adjustment. |
GB |
|
|
|
|
|
|
■■ |
Remove both hoses from the pressure connections and . |
|
■■ |
Press both the "up" and "down" buttons simultaneously, or select |
|
|
"Zero" in the setting menu: |
|
|
the green LED switches off and "Zero" is shown in the display. |
|
■■ |
Wait until the green LED switches back on, then reconnect the and |
|
|
pressure connections. |
In normal operation, we recommend that a zero point adjustment is carried out every 12 months.
Span calibration
Attention!
Connect the voltage supply one hour before making the span calibration.
A reference pressure measuring instrument is needed for the span setting.
The span should not be set without pressure being present. If the span is set with either no test pressure, or too-low a pressure, the instrument will lose its accuracy and no longer give correct measured values.
If this should occur, select the menu point "Span" and then select "Reset", in order to reset the span setting.
40389228.01 09/2012 GB/D/F/E/I
12 |
WIKA operating instructions air2guide model A2G-45 |
6.Commissioning, operation ...8.Disposal
Set the span in the following sequence: |
|
|
1. Carry out a zero point calibration |
|
|
2. Connect the pressure connections |
|
|
3. Select "Span" in the menu and then select "Adjust" |
|
|
GB |
||
4. Using both the "up" and "down" arrow buttons, set the relevant value |
||
for the display or the 0 … 10 V output, so that it matches the reference |
|
|
pressure instrument's value |
|
|
5.Confirm the setting by pressing the "OK" button |
|
Pout
10 V
Influence of the span setting on the measured values
Pressure
7.Maintenance and cleaning
The differntial pressure switches are maintenance-free and offer long service life provided they are handled and operated properly.
Clean the instruments with a moist cloth (soap water).
Repairs must only be carried out by the manufacturer or appropriately qualified skilled personnel.
40389228.01 09/2012 GB/D/F/E/I
8.Disposal
Incorrect disposal can put the environment at risk.
Dispose of instrument components and packaging materials in an environmentally compatible way and in accordance with the countryspecific waste disposal regulations.
WIKA operating instructions air2guide model A2G-45 |
13 |
GB
40389228.01 09/2012 GB/D/F/E/I
14 |
WIKA operating instructions air2guide model A2G-45 |
Inhalt
Inhalt
1. |
Allgemeines |
16 |
|
2. |
Sicherheit |
17 |
D |
|
|||
3. |
Technische Daten |
18 |
|
4. |
Aufbau und Funktion |
19 |
|
5. |
Transport, Verpackung und Lagerung |
20 |
|
6. |
Inbetriebnahme, Betrieb |
21 |
|
7. |
Wartung und Reinigung |
25 |
|
8. |
Entsorgung |
25 |
|
40389228.01 09/2012 GB/D/F/E/I
WIKA Betriebsanleitung air2guide Typ A2G-45 |
15 |
1.Allgemeines
1.Allgemeines
■■ Der in der Betriebsanleitung beschriebene elektronische Differenzdruckschalter mit Anzeige wird nach dem aktuellen Stand der Technik konstruiert und gefertigt. Alle Komponenten unterliegen während der Fertigung strengen Qualitätsund Umweltkriterien.
DUnsere Managementsysteme sind nach ISO 9001 und ISO 14001 zertifiziert.
■■ Diese Betriebsanleitung gibt wichtige Hinweise zum Umgang mit dem Gerät. Voraussetzung für sicheres Arbeiten ist die Einhaltung aller angegebenen Sicherheitshinweise und Handlungsanweisungen.
■■ Die für den Einsatzbereich des Gerätes geltenden örtlichen Unfallverhütungsvorschriften und allgemeinen Sicherheitsbestimmungen einhalten.
■■ Die Betriebsanleitung ist Produktbestandteil und muss in unmittelbarer Nähe des Gerätes für das Fachpersonal jederzeit zugänglich aufbewahrt werden.
■■ Das Fachpersonal muss die Betriebsanleitung vor Beginn aller Arbeiten sorgfältig durchgelesen und verstanden haben.
■■ Die Haftung des Herstellers erlischt bei Schäden durch bestimmungswidrige Verwendung, Nichtbeachten dieser Betriebsanleitung,
Einsatz ungenügend qualifizierten Fachpersonals sowie eigenmächtiger Veränderung am Gerät.
■■ Es gelten die allgemeinen Geschäftsbedingungen in den Verkaufsunterlagen.
■■ Technische Änderungen vorbehalten. ■■ Weitere Informationen:
- Internet-Adresse: |
www.wika.de / www.wika.com |
- zugehöriges Datenblatt: |
www.air2guide.com |
SP 69.08 |
40389228.01 09/2012 GB/D/F/E/I
16 |
WIKA Betriebsanleitung air2guide Typ A2G-45 |
40389228.01 09/2012 GB/D/F/E/I
1.Allgemeines / 2.Sicherheit
Symbolerklärung |
|
|
WARNUNG! |
|
|
… weist auf eine möglicherweise gefährliche Situation hin, |
|
|
die zum Tod oder zu schweren Verletzungen führen kann, |
|
|
wenn sie nicht gemieden wird. |
|
|
Information |
D |
|
… hebt nützliche Tipps und Empfehlungen sowie Infor- |
|
|
mationen für einen effizienten und störungsfreien Betrieb |
|
|
hervor. |
|
|
|
|
|
2.Sicherheit |
|
|
WARNUNG! |
|
|
Vor Montage, Inbetriebnahme und Betrieb sicherstellen, |
|
|
dass der richtige Differenzdruckschalter hinsichtlich |
|
|
Messbereich, Ausführung und spezifischen Messbedin- |
|
|
gungen ausgewählt wurde. |
|
|
Bei Nichtbeachten können schwere Körperverletzungen |
|
|
und/oder Sachschäden auftreten. |
|
|
Weitere wichtige Sicherheitshinweise befinden sich in den |
|
|
einzelnen Kapiteln dieser Betriebsanleitung. |
|
|
2.1 Bestimmungsgemäße Verwendung |
|
|
Dieser elektronische Differenzdruckschalter dient zur Überwachung |
|
|
des Differenzdruckes von Luft und anderen nicht brennbaren und nicht |
|
|
aggressiven Gasen sowie zur Überwachung von Luftfiltern, Gebläsen in |
|
|
Lüftungskanälen, Regelung von Luftund Brandschutzklappen und zur |
|
|
Überdrucküberwachung von Reinräumen und Labors. |
|
|
Das Gerät ist ausschließlich für den hier beschriebenen bestimmungs- |
|
|
gemäßen Verwendungszweck konzipiert und konstruiert und darf nur |
|
|
dementsprechend verwendet werden. |
|
|
Ansprüche jeglicher Art aufgrund von nicht bestimmungsgemäßer |
|
|
Verwendung sind ausgeschlossen. |
|
WIKA Betriebsanleitung air2guide Typ A2G-45 |
17 |
2.Sicherheit / 3.Technische Daten
2.2 Personalqualifikation
WARNUNG!
Verletzungsgefahr bei unzureichender Qualifikation!
Unsachgemäßer Umgang kann zu erheblichen Personenund Sachschäden führen.
D ■■ Die in dieser Betriebsanleitung beschriebenen Tätigkeiten nur durch Fachpersonal nachfolgend beschriebener Qualifikation durchführen lassen.
Fachpersonal
Das Fachpersonal ist aufgrund seiner fachlichen Ausbildung, seiner Kenntnisse der Messund Regelungstechnik und seiner Erfahrungen sowie Kenntnis der landesspezifischenVorschriften, geltenden Normen und Richtlinien in der Lage, die beschriebenen Arbeiten auszuführen und mögliche Gefahren selbstständig zu erkennen.
Symbolerklärung
CE, Communauté Européenne
Geräte mit dieser Kennzeichnung stimmen überein mit den zutreffenden europäischen Richtlinien.
3.Technische Daten
Prozessanschluss
Anschlussstutzen (Kupferlegierung), für Schläuche mit Innendurchmesser 4 oder 6 mm
Messelement
Piezo-Messzelle
Gehäuse/Deckel
Kunststoff (ABS)/Kunststoff (PC)
40389228.01 09/2012 GB/D/F/E/I
18 |
WIKA Betriebsanleitung air2guide Typ A2G-45 |
3.Technische Daten
Elektrischer Anschluss
Kabelverschraubung M16 und M20, Schraubklemmen max. 1,5 mm²
Ausgangssignal
0 … 10 V, 2-Leiter, Lastwiderstand mind. 1 kOhm
Spannungsversorgung |
|
D |
|
AC 24 V ±10 % oder DC 21 ... 35 V |
|
Langzeitstabilität
≤±8 Pa
≤±1 Pa mit automatischer Nullpunktkorrektur (Option)
Abmessungen in mm
GB/D/F/E/I |
Gewicht |
|
|
150 g |
|
||
Schutzart |
|
||
09/2012 |
|
||
IP 54 nach EN 60529 / lEC 529 |
|
||
Weitere technische Daten siehe WIKA-Datenblatt SP 69.08 und |
|
||
40389228.01 |
|
||
Bestellunterlagen. |
|
||
WIKA Betriebsanleitung air2guide Typ A2G-45 |
19 |
||
|
4.Aufbau und Funktion / 5.Transport, Verpackung ...
4.Aufbau und Funktion
4.1 Beschreibung
Ausführung
CE-Konformität:
2004/108/EG Elektromagnetische Verträglichkeit
D2002/95/EG RoHS (Beschränkung der Verwendung bestimmter gefährlicher Stoffe in Elektround Elektronikgeräten)
Genauigkeitsklasse
1,5 %
Messbereiche
■■ Variante 1: -500 ... +500 Pa
(-100 ... +100 Pa, -250 ... +250 Pa, -300 ... +300 Pa über Jumper
einstellbar) oder
■■ Variante 2: 0 ... 2.500 Pa
(0 ... +100 Pa, 0 ... +250 Pa, 0 ... +1.000 Pa über Jumper einstellbar)
Druckbelastbarkeit
Maximaler Druck: 25 kPa
Zulässige Temperatur
Umgebung: -20 … +70 °C
Betrieb: |
-10 … +50 °C |
|
(-5 … +50 °C mit automatischer Nullpunktkorrektur) |
4.2 Lieferumfang
Lieferumfang mit dem Lieferschein abgleichen.
5.Transport, Verpackung und Lagerung
5.1 Transport
Differenzdruckschalter auf eventuell vorhandeneTransportschäden untersuchen.Offensichtliche Schäden unverzüglich mitteilen.
40389228.01 09/2012 GB/D/F/E/I
20 |
WIKA Betriebsanleitung air2guide Typ A2G-45 |