SERVICE
Model AMB 955
Version 8528 955 10000 Page
Whirlpool Europe
Customer Services
AMB 955
Service Manual
Air Conditioning
Split
AMB 955
Technical data 2
Spare part list 3
Exploded view 4
Circuit and Wiring diagram 5
This documentation is only intended for qualified technicians who are aware of the respective safety regulations.
Date: 08.11.2004 (Mod. 01) Subject to modification
Document-No.: 4812 731 19882
28.06.2004 / Page 2 AMB 955 Whirlpool Europe
Doc. No: 4812 731 19882 8528 955 10000 Customer Service
SERVICE
Technical data
Operation type
Cooling / Heating
Dimensions
Indoor-unit
Height 270 mm
Width 890 mm
Depth 168 mm
Outdoor-unit
Height 530 mm
Width 755 mm
Depth 252 mm
Weight
Indoor-unit 14 kg / net
Outdoor-unit 43 kg / net
Compressor
Type Toshiba, PA 150 X 1C - 4 FZ
Refrigerant
Type R 410 a
Quantity 1270 g
Cooling Capacity
3516 Watt
12000 BTU/h
Heating Capacity
3956 Watt
13500 BTU/h
Airflow / Evaporator Airvolume
520 m3 /h
Electrical connection
Voltage 220 - 240 V
Frequency 50 Hz
Power Supply
Cooling
Input 1160 W
5.4 A
Heating
Input 1230 W
5.7 A
Dehumidifying Capacity
1.5 l/h
Working temp. range
Indoor + 18.0 / + 32.0˚C
Outdoor - 5.0 / + 43.0˚C
Noise level
Indoor-unit 30 - 37 dB
Outdoor-unit 52 dB