Whirlpool 3397612 User Manual

IMPORTANT:
Thin Twin Washer »Dryer - 240 Voit
Installation Instructions
Read and save
these instructions
IMPORTANT: Installer: Leave Installation Instructions
Homeowner: Keep Installation Instructions
for future reference.
Save Installation Instructions for local
electrical inspector's use.

Before yott start...

Check location where washer/dryer will be installed. Proper Installation is your responsibility. The washer/dryer must not
be installed or stored in an area where it will be exposed to water and/or weather. Make sure you have everything necessary for correct installation.
Location: Should be large enough
to fully open dryer door to 90°. See Panel G for "Recessed and closet installation instructions" and "Product dimensions."
Grounded electrical outlet is
required. See "Electrical requirements."
Standpipe drain system:
Needs q two-inch diameter standpipe with minimum carry-away capacity of
17 gallons per minute. Top of
standpipe must be at least 28 inches high and no higher
than 48 inches from floor.
Floor drain system requires
a siphon break. Part No. 285320, available from your authorized parts distributor.
Awarning
Check code requirements: Some codes limit or
Do Not permit installation of clothes dryers in garages, closets, mobile homes and sleeping quarters. Contact your local building inspector.
Check utilities: Proper water and
electrical supply connections must be available.
Hot and cold water faucets:
Must be within 4 feet of the back of the washer/dryer and provide water pressure of 5-100 PSI.
Level floor:
1-inch maximum
slope under entire
washer/dryer.
'Support: Floor must be
sturdy enough to support washer/dryer weight, with water and clothes, of 375 pounds.
Do Not store or operate washer/dryer below 32° F (some water may remain in washer). Proper operation of dryer cycles requires temperatures above 45°F. See Use & Care Guide for “Winterizing” information.
Water heater: Set to deliver 140°F
water to the washer.
Laundry tub drain system: Needs a
20-gallon laundry tub, Top of tub must be at least 28 inches high and no higher than 48 inches from floor.
If a longer drain hose is needed, drain hose (Part No. 388423) and hose extension kit (Part No. 285442) are available from your authorized parts distributor.
Dryer may be exhausted from the rear or left or right side. Exhausting
through the side requires Pqrt No.
279823. See "Exhaust requirements," Panels C and D.
Four-inch metal exhaust duct is required.
SEE RECESSED AREA INSTRUCTIONS ON PANEL G.
Important: Observe all governing codes and
ordinances.
Electrical Shock Hazard
It is the customer’s responsibility:
To contact a qualified electrical installer.
To assure that the electrical installation is adequate.
Failure to do so could result in death
or serious injury.
Fire Hazard
For your safety, the information in this manual must be followed to minimize the risk of fire or explosion or to prevent property damage, personal injury or loss of life.
— Do Not store or use gasoline or
other flammable vapors and liquids in the vicinity of this or any other appliance.
— Never install washer/dryer up
against draperies or curtains or on carpet.
— Keep any and all items from
falling or collecting behind the
washer/dryer.
— Replace all access panels before
operating washer/dryer.
Failure to follow these instructions could result in a fire.

Tools and materials needed for installation:

utility knife
1/4" socket wrench
or nut driver
Panel A
slip-joint pliers that open to
1-1/2" minimum

Electrical requirements

Awarning
V
Electrical Shock Hazard
Electrical ground is required on this
washer/dryer. Do Not ground to a gas pipe. Do Not modify the power supply cord
plug. If it will not fit the outlet, have a proper outlet installed by a qualified electrician.
Use a new 30-ampere power supply cord kit. Do Not reuse an old power supply cord. Possible electrical shock
or fire hazard could occur if old power supply cord is used.
Do Not have a fuse in the neutral or grounding circuit. A fuse in the neutral or grounding circuit could result in an electrical shock.
Do Not use an extension cord with
this washer/dryer. Check with a qualified electrician if
you are not sure washer/dryer is properly grounded.
Failure to follow these instructions could result in death or serious injury.
If codes permit and a separate grounding wire is used, it is recommended that a qualified electrician determine that the
grounding path is adequate.
A four-wire or three-wire, single-phase,
120/240-volt, 60-Hz, AC-only electrical
supply (or four-wire or three-wire,
120/208-volt, if specified on the model/serial rating plate) is required on a separate, 30-ampere circuit, fused on both sides of the line. A time-delay fuse or circuit breaker is recommended. The model/serial rating plate is located in
the door well behind the dryer door on the front of the opening.
It is the personal responsibility and obligation of the customer to contact a qualified electrician to assure that the
electrical installation is adequate and in conformance with the National Electrical Code, ANSI/NFPA 70 — latest edition*, and all local codes and ordinances.
Copies of the standards listed above may be obtained from;
' National Fire Protection Association
Batterymarch Park
Quincy, Massachusetts 02269
Power supply cord
Local codes may permit the use of a U.L­listed, 120/240-volt minimum, 30-ampere, dryer power supply cord kit (pigtail).
Power supply cord should be Type SRD or SRDT and be at least four feet long. The wires that connect to the dryer must end with ring terminals or spade terminals with upturned ends. A 3/4", U.L.-listed strain relief must be installed where the power supply cord connects to the dryer (see Figures 1 and 2).
spade terminals with upturned ends
3/4" U.L.-listed strain relief
grounding prong
Four-wire power supply cord
NEMA 14-30P
Figure 1
spade terminals with upturned ends
This blade connected to this conductor. ■
3/4" U.L.-liste strain relief
Three-wire power supply cord
NEMA 10-30P
Figure 2
(white or center)
NEUTRAL
(white)
ring terminals
ring terminals
NEUTRAL
For use where local codes permit use of
flexible power supply cord.
four-wire
receptacle(14-30R)
Figure 3
Four-wire installation is recommended (required for mobile homes): The power
/oJJScm
fhree-wire
receptacle(10-30R)
Figure 4
supply cord must hove four. No,-10 copper wires and match a four-wire recepfacle of NEMA Type 14-30R (see Figure 3). The fourth wire (grounding conductor) must be identified with a green cover and the neutral conductor by a white cover.
Three-wire installation (if a four-wire system is not available): The power
supply cord must have three, No.-lO copper wires to match a three-wire receptacle cf NEMA Type 10-30R (see Figure 4).
Direct wire
The washer/dryer can be connected directly to fused disconnect or circuit breaker box with four-wire or fhree-wire flexible armored or non-metallic sheathed copper cable (with grounding wire). Do Not use two-wire with bare grounding wire. All current-carrying wires must be insulated.
A conduit connector must be installed at junction box. USE ONLY 10-GAUGE SOLID COPPER WIRE. DO NOT USE ALUMINUM WIRE. Allow four feet of slack in the line so dryer can be moved if servicing is ever necessary.
A.
Four-wire connection...
POWER SUPPLY CORD
neufral (whife or confer)
power supply cord grounding wire (green)
Infernal cabinef-. grounding connector conne
1. Disconnect the power supply.
2. Remove terminal block cover.
3. Install copper, four-wire power supply cord through strain relief,
4. Remove the appliance harness grounding wire (green with yellow stripes) from the internal grounding connector and fasten under center, silver-colored terminal block
screw.
5. Connect the grounding wire (green) of the copper, four-wire
power suppiy cord to the internal
grounding connector.
6. Connect the neutral wire (white) of the power supply cord to the center, silver-colored termindl screw of the terminal block, Connect the other wires to the outer terminals.
Tighten screws firmly.
7. Tighten strain relief screws.
8. Replace the terminal block cover.
confer silvor-colorod forminal block screw
Figure 5
appliance harness
rounding wire
(green wirh
yellow sfripes)
.exfernal
cabinef­grounding
ptor
B.
Three-wire connection.
Where local codes permit
connecting cabinet-arounding
conductor to the neutral wire:
K>wrat SUPPLY CORD
cenfer silver-colored terminal block screw
neutral (white or center)
Internal cabinet grounding
connector
1. Disconnect the power supply.
2. Remove terminal block cover.
3. Install copper three-wire power supply cord through strain relief.
4. Connect the neutral wire (white or center) of the power supply cord to the center, silver-colored terminal screw of the terminal block. Connect the other wires to the outer terminals. Tighten screws firmly.
5. Tighten sfrain relief screws.
6. Replace the terminal block cover.
Where local codes permit
connecting cabinet-arounding
conductor to the neutral wire of the power supply cable:
appliance harness grounding wire rareen with yellow sfripes)
Figure 8
external cabinet grounding connector
Electrical connection

^WARNING

'if
Electrical Shock Hazard Check that wiring you are using matches colors shown in illustrations and specified in instruction steps. If
wiring does Not match, it is your
responsibility to have a qualified
electrician install the correct wiring.
Failure to install the correct wiring
could result in death or serious injury.
This washer/dryer Is manufactured with the neutral terminal connected to the cabinet.
Panel B
DIRECT WIRE
1. Disconnect the power supply.
2. Remove terminal block cover.
3. Strip 5 inches of oufer covering from end of cable. Leave bare grounding wire at 5 inches. Cut 1-1/2 inches from 3 remaining insulated wires. Strip insulation back 1 inch (see Figure 6).
' U.L.-lisfed
sfrain relief
10-gauge, 3-wire
with ■■ wire
Direct wire preparation
Figure 6
U-shaped
hook
r
Figure 7
4. Install copper, four-wire power supply cable through strain relief.
5. Remove the appliance harness grounding wire (green with yellow
stripes) from the internal grounding connector and fasten under center, silver-colored terminal block screw.
6. Slide the hook end of the grounding wire (bare) of the four-wire power supply cable under the internal grounding connector screw. Squeeze hook end of wire together. Tighten screw.
7. Connect the neutral wire (white) of
the power supply cable to the center, silver-colored termindl screw of the terminal block using the same
method. Connect the other wires to
the outer terminals. Tighten screws firmly.
8. Tighten strain relief screws.
9. Replace the terminal block cover.
Shape the end of each wire into a "U" shaped hook (see Figure 7). The bare grounding wire must be 4-1 /2" long after
forming the hook.
'Stripped of
insulation
bare grounding
wire
DIRECT WIRE
1. Disconnect the power supply.
Awarning
Electrical Shock Hazard
Do Not use two-wire with a bare grounding wire. All current-carrying
wires must be insulated.
Failure to install the correct wiring
could result in death or serious injury.
2. Remove terminal block cover.
3. Strip 3-1 /2 inches of outer covering from end of cable. If using three­wire cable with grounding wire, cut the bare wire even with outer covering. Strip 1 inch of insulation from the end of each insulated wire (see Figure 9).
Bare wire cut short. Wire is not
3/4" U.L.-listed strain relief
to
disconnect box
lO-gauge. 3-wire or, 10-gauge, 3-wire with
grounding wire (Romex)
Direct wire preparation
U-shaped hook
r
Figure 10
used. Dryer is grounded
through direct wire cable.
Figure 9
Shape the end of each wire into a "U" shaped hook (see Figure 10).
NEUTRAL
wires stripped of Insulation
Loading...
+ 6 hidden pages