tekmar 081 User Manual

081_D
Three Outdoor Sensor Module 081
Accessories
01/13
The tekmar Three Outdoor Sensor Module 081 includes three 10 kΩ thermistors which provide an accurate measurement of the outdoor temperature. Each sensor has two separate terminals for wiring. The 081 is designed to be installed in a tekmar Outdoor Sensor 070 enclosure. This allows for four separate sensors to be combined into a single enclosure that is mounted on the exterior of the building.
Installation
STEP ONE
The Three Outdoor Sensor Module 081 is designed to mount in the Outdoor Sensor 070 enclosure as shown in the diagram.
• Remove the screw from the center of the Outdoor Sensor 070 and pull the front cover off the encloser.
• The 081 is mounted into the Outdoor Sensor 070 enclosure. Using the two screws provided, fasten the module in the top left hand corner of the 070’s enclosure as indicated in the diagram.
MOUNTING THE MODULE
Mounting location for Three Outdoor Sensor Module 081
1Os2
Os
Sensor is built into the enclosure
Outdoor Sensor 070 Enclosure
A Watts Water Technologies Company
1 of 4 © 2013 081_D - 01/13
STEP TWO
• Connect 18 AWG or similar wire to the two terminals (S1 and S1) provided on the module and run the wires from the module to the control. Do not run the wires parallel to telephone or power cables. If the sensor wires are located in an area with strong sources of electromagnetic interference (EMI), shielded cable or twisted pair should be used or the wires can be run in a grounded metal conduit. If using shielded cable, the shield wire should be connected to the Com terminal on the control and not to earth ground.
• Follow the sensor testing instructions on the bottom of this brochure and connect the wires to the control.
• Repeat the above steps for the second (S2 and S2) and third (S3 and S3) sensors.
• Replace the front cover of the Outdoor Sensor 070 enclosure.
WIRING AND TESTING THE SENSOR
Sensor Testing Instructions
A good quality test meter capable of measuring up to 5,000 k (1 k = 1000) is required to measure the sensor resistance. In addition to this, the actual temperature must be measured with either a good quality digital thermometer, or if a thermometer is not available, a second sensor can be placed alongside the one to be tested and the readings compared.
First measure the temperature using the thermometer and then measure the resistance of the sensor at the control. The wires from the sensor must not be connected to the control while the test is performed. Using the chart on the following page, estimate the temperature measured by the sensor. The sensor and thermometer readings should be close. If the test meter reads a very high resistance, there may be a broken wire, a poor wiring connection or a defective sensor. If the resistance is very low, the wiring may be shorted, there may be moisture in the sensor or the sensor may be defective. To test for a defective sensor, measure the resistance directly at the sensor location.
Do not apply voltage to a sensor at any time as damage to the sensor may result.
A Watts Water Technologies Company
2 of 4
© 2013 081_D - 01/13
Loading...
+ 2 hidden pages