CAUTION: Information in this manual is intended to be used by Taylor Authorized
Service Tech n ician s only.
Note: Contin u ing research results in steady improvements; therefore, information
in this manual is subject to change without notice.
E April, 2004 Taylor
All rights reserved.
057888-S
Model C602Table of Contents
Section 1:Introduction
SSafety
SRefrigerant
SSpecifications
SInstallation Instructions
Model C602
1
Introduction
Safety
______________________________
We at Taylor Company, are committed to
manufacturing safe operating and serviceable
equipment. The many built-in safety features that
are part of all Taylor equipment are aimed at
protecting operators and trained service technicians
alike.
This manual is intended exclusively for Taylor
Company authorized service personnel.
Stationary appliances which are not
equipped with a power cord and a plug or other
device to disconnect the appliance from the power
source must have an all-pole disconnecting device
with a contact gap of at least 3 mm installed in the
external installation.
Thismachinemustbeplacedonalevel
surface. Failure to comply may result in personal
injury or equipment damage.
DO NOT installthemachineinanarea
where a water jet could be used to clean or rinse the
freezer. Failure to follow this instruction may result in
serious electrical shock.
DO NOT remove the door, beater, scraper
blades, drive shaft or air/mix pump unless all control
switches are in the OFF position. Failure to follow
this instruction may result in severe personal injury
from hazardous moving parts.
Refrigerant
______________________________
Taylor Company uses R404A refrigerant. This
refrigerant is generally considered non-toxic and
non-flammable; however, any gas under pressure is
potentially hazardous.
NEVER fill any refrigerant cylinder
completely with liquid. Filling the cylinder to
approximately 80% will allow for normal expansion.
Refrigerant liquid sprayed onto the skin may
cause serious damage to tissue. Keep eyes and skin
protected. If refrigerant burns should occur, flush
immediately with cold water. If burns are severe,
apply ice packs and contact a physician
immediately.
The Taylor Company reminds technicians to be
cautious of government laws regarding
refrigerant recovery, recycling, and reclaiming
systems. If you have any questions regarding
these laws, please contact the factory Service
Department.
WARNING: R404A refrigerant used in conjunction
with polyolester oils is extremely moisture
absorbent. When opening a refrigeration system, the
maximum time the system is open must not exceed
15 minutes. Cap all open tubing to prevent humid air
or water from being absorbed by the oil.
This machine is designed to operate indoors, under
normal ambient temperatures of 70°-75°F
(21°-24°C). The machine has successfully
performed in high ambient temperatures of 104°F
(40°C) at reduced capacities.
NOISE LEVEL: Airborne noise emission does not
exceed 78 dB(A) when measured at a distance of
1.0 meter from the surface of the machine and at a
height of 1.6 meters from the floor.
The refrigeration compressor(s) on this machine are
warranted for the term indicated on the warranty
card accompanying this machine. However, due to
the Montreal Protocol and the U.S. Clean Air Act
Amendments of 1990, many new refrigerants are
being tested and developed; thus seeking their way
into the service industry. Some of these new
refrigerants are being advertised as drop-in
replacements for numerous applications. It should
be noted that, in the event of ordinary service to this
machine’s refrigeration system, only the refrigerant
specified on the affixed data label should be used.
The unauthorized use of alternate refrigerants will
void your compressor warranty. It will be the owners’
responsibility to make this fact known to any
technicians they employ.
It should be noted, that Taylor does not warrant the
refrigerant used in its equipment. For example, if the
refrigerant is lost during the course of ordinary
service to this machine, Taylor has no obligation to
either supply or provide its replacement either at
billable or unbillable terms. Taylor does have the
obligation to recommend a suitable replacement if
the original refrigerant is banned, obsoleted, or no
longer available during the five year warranty of the
compressor.
The Taylor Company will continue to monitor the
industry and test new alternates as they are being
developed. Should a new alternate prove, through
our testing, that it would be accepted as a drop-in
replacement, then the above disclaimer would
become null and void. To find out the current status
of an alternate refrigerant as it relates to your
compressor, call the local Taylor Distributor or the
Taylor Factory. Be prepared to provide the
model/serial number of the unit in question.
Refrigerant: R404A (BTU’s may vary depending on
compressor used.)
Main Compressor:
Air Cooled Units:
Shake: 54 oz (1,531 g) of R404A
Soft Serve: 46 oz (1,304 g) of R404A
Water Cooled Units:
Shake: 48 oz (1,361 g) of R404A
Soft Serve: 32 oz (907 g) of R404A
Note: Specifications are subject to change. Check
the data label for proper charging specifications.
Electrical
Standard is 208/230-60-3; however, other electrical
characteristics are available. Each unit requires
electrical service - Three Phase Maximum Fuse
Size: 40 A, Minimum Wire Ampacity: 36 A
Note: McDonald’s specifies Hubbell A460P9 plug
for 208-230/60-3 equipment.
Air Cooled
Clearance: A minimum of 3” (76 mm) is required
around all sides. Install the deflector provided to
prevent recirculation of warm air. Minimum air
clearances must be met to assure adequate air flow
for optimum performance.
Net: 815 lbs. (369.7 kgs)
Crated: 1046 lbs. (474.5 kgs)
Volume: 66.5 cu ft (1.88 cu m)
Introduction
Figure 1
4
Model C602
Installation Instructions
Thismachinemustbeplacedonalevel
surface. Failure to comply may result in personal
injury or equipment damage.
Beater Rotation
REMEMBER TO DISCONNECT ALL
POWER TO THE FREEZER! Failure to follow this
instruction may result in electrocution.
DO NOT installthemachineinanarea
where a water jet could be used to clean or rinse the
freezer. Failure to follow this instruction may result in
serious electrical shock.
Disconnect Switch
Stationary appliances which are not
equipped with a power cord and a plug or other
device to disconnect the appliance from the power
source must have an all-pole disconnecting device
with a contact gap of at least 3 mm installed in the
external installation.
Air Cooled Units
These units require a minimum of 3” (76 mm) of air
clearance around all sides. Install the deflector
provided to prevent recirculation of warm air.
Minimum air clearances must be met to assure
adequate air flow for optimum performance.
Gear Alignment and Rear Shell Bearing
1.Make certain the drive shaft can easily slide in
and out of the female socket on the gear unit.
2.If a drive shaft is binding, the gear unit could be
out of alignment (loose). Check the bolts on the
gear unit to be sure they are tight.
3.Inspect the rear shell bearing for tightness. Be
sure the locking tab has been folded over to
prevent the nut from loosening.
Note: If the gear unit is out of alignment, refer to
the General Service Manual.
Beater rotation = CLOCKWISE (when viewed from
the front of the machine).
Note: This machine is equipped with an interlock
circuit that prevents beater motor operation when
the freezer door is not installed.
1.Remove the side panels.
2.Place the power switch in the ON position.
3.Select the WASH key on the control panel. This
activates the beater motor only.
CAUTION: Hazardous moving
components! Keep your hands clear when
operating the machine with the panels
removed. Failure to follow this instruction may
result in severe personal injury from hazardous
moving parts.
4.Check the rotation of the drive coupling located
on the output shaft of the gear reducer. The
coupling should be turning CLOCKWISE as
viewed from the front of the machine.
5.Press the WASH key again to stop the beater
motor.
If rotation is not correct, exchange any two incoming
power lines at the freezer main terminal box only
(splice box).
REMEMBER TO DISCONNECT ALL
POWER TO THE FREEZER! Failure to follow this
instruction may result in electrocution.
Model C602
5
Introduction
Pump Motor Rotation
1.Remove the air/mix pump assembly.
2.Connect power to the freezer and place the
power switch in the ON position.
3.Press the PUMP key on the control panel. This
will activate the pump motor only.
4.Observe the pump ball crank. It should be
rotating counterclockwise.
Electrical Connections
Each freezer requires one power supply. Check the
data label on the freezer for fuse, circuit ampacity
and electrical specifications. Refer to the wiring
diagram, provided inside the control box, for proper
power connections.
In the United States, this equipment is intended to
be installed in accordance with the National
Electrical Code (NEC), ANSI/NFPA 70-1987. The
purpose of the NEC code is the practical
safeguarding of persons and property from hazards
arising from the use of electricity. This code contains
provisions considered necessary for safety.
Compliance therewith and proper maintenance will
result in an installation essentially free from hazard!
If rotation is not correct, refer to the wiring diagram
on the pump motor and re-wire accordingly.
REMEMBER TO DISCONNECT ALL
POWER TO THE FREEZER! Failure to follow this
instruction may result in electrocution.
In all other areas of the world, equipment should be
installed in accordance with the existing local codes.
Please contact your local authorities.
Stationary appliances which are not equipped with a
power cord and a plug or other device to disconnect
the appliance from the power source must have an
all-pole disconnecting device with a contact gap of at
least 3 mm installed in the external installation.
Introduction
6
Model C602
Section 2:
Systems, Controls and Operations
SRunning Specifications
SRefrigeration System Schematic
SControl Panel Functions
SFreezer Lock-Out
SHeat Treatment Cycle
SHeat Treatment Graph
STimers
SAdjustable Draw Handle
SBeater Stir Cycles
SGlycol System
Model C602
SGlycol Path
SSetting Viscosity
SPortion Control (Shake)
SControl Overview
SElectrical System Modes of Operation Chart
SElectrical System - L1 Power Path
SShake Draw Sequence Chart
SSyrup Delivery
SSyrup Calibration
SShake Draw Mechanism Alignment
7
Systems, Controls and Operations
Running Specifications
Pressures/Temperatures
The following are the Taylor Company
recommended settings for various components in
the Model C602. (See page 9 for the Refrigeration
System Schematic.)
Expansion Valve
Soft Serve
Air Cooled: 20 - 22 psi. (138 - 152 kPa)
Water Cooled: 20 - 22 psi. (138 - 152 kPa)
for a normal product of 16_ -18_F. (-8.8_to -7.7_C).
Shake
Air Cooled: 38 - 39 psi. (262 - 269 kPa)
Water Cooled: 38 - 39 psi. (262 - 269 kPa
for a normal product of 24_ -26_F. (-4_C).
Note: Triple Thick Shake product temperature is
22_-24_F. (-5_C).
Low Side (Suction)
Suction pressure equals expansion valve setting.
High Side (Discharge)
High side pressure varies for air cooled units,
depending on the ambient temperature.
Ambient TemperatureNormal Operating Head
Pressures
FCPSI
70_21.1_240 - 270
(1,655 - 1,862 kPa)
80_26.7_270 - 300
(1,862 - 2,069 kPa)
90_32.2_300 - 340
(2,069 - 2,344 kPa)
100_37.8_340 - 380
(2,344 - 2,620 kPa)
Water Valve
Expansion Valve Adjustment
Connect your refrigerant gauge to the low side
access valve. Turn the access valve
counter-clockwise to open the valve.
Adjust the pressure higher or lower by turning the
expansion valve adjustment screw. Clockwise turns
will raise the pressure and counterclockwise will
lower the pressure.
Note: Make expansion valve adjustments with mix
in the freezing cylinder and the freezer in the AUTO
mode. Be sure to allow adequate time for the
pressure to stabilize.
Turn the access valve clockwise to close the valve.
Install and securely tighten the access valve caps
and the expansion valve cap.
On a water cooled unit, the water valve should be
set to maintain a compressor head pressure of 255
psi. (1,758 kPa).
Water Valve Adjustment
Note: Make this adjustment with mix in the cylinder
and the freezer in the AUTO mode. Be sure to allow
adequate time for pressure to stabilize.
Connect your refrigerant gauge to the high side
access valve. Turn the access valve counterclockwise to open the valve. Turning the adjustment
stem on the water valve clockwise will lower the
pressure.
Turn the access valve clockwise to close the valve.
Install and securely tighten the access valve caps.
Systems, Controls and Operations
8
Model C602
Refrigeration System Schematic
Model C602
Figure 2
9
Systems, Controls and Operations
Control Panel Functions
Figure 3
ITEM
1Keypad-ShakeUsed for selecting operating functions on the shake side of the machine.
2Display-Vacuum
3Keypad-Menu (Entry/Exit)Used to select the Manager or Service Menu or to exit the Menu Display.
4Keypad-Soft ServeUsed for selecting operating functions on the soft serve side of the
5Standby-Soft ServeIndicates when the soft serve side is in the Standby mode.
6Standby-ShakeIndicates when the shake side is in the Standby mode.
7Keypad-Topping HeaterUsed to activate the topping rail heaters.
8Display-LED Dual (Brush
9Keypad-Flavor SelectUsed for selecting the desired shake flavor to be dispensed. Also used
10Switch-PowerWhen placed in the ON position, allows control panel operation.
11Keypad-Calibrate MenuUsed to access the Calibrate Menu containing options for calibrating the
12Indicator Light-Mix LowIlluminates when the mix hopper has a low supply of mix and should be
13Indicator Light-Mix OutIlluminates when the mix hopper has an insufficient supply of mix to
DESCRIPTIONFUNCTION
Fluorescent Menu (VFD)
Clean Countdown)
Screen which displays menu options and notifies operator if a fault is
detected.
machine.
Displays the number of days before brush cleaning is required.
for opening and closing the draw valve when cleaning, sanitizing, and
priming the shake side.
syrup dispensing rate or priming and flushing the syrup lines.
refilled as soon as possible.
operate the freezer. The Auto mode will be locked out and the machine
will be placed in the Standby mode.
Systems, Controls and Operations
10
Model C602
Symbol Definitions
To better communicate in the International arena,
the words on many of our operator keys have been
replaced by symbols to indicate their functions. Your
Taylor equipment is designed with these
International symbols.
The following chart identifies the symbol definitions.
=CALIBRATE
= MENU DISPLAY
=AUTO
= HEAT CYCLE
= WASH
=MIXPUMP
= STANDBY (SHAKE)
= STANDBY (SOFT SERVE)
= FLAVOR SELECTION
Power Switch
When placed in the ON position, the power switch
allows control panel operation.
Vacuum Fluorescent Display
The vacuum fluorescent display (VFD) is located on
the front control panel. During normal operation the
display is blank. The display is used to show menu
options and notifies the operator if a fault is
detected. On International models, the display will
indicate the temperature of the mix in each hopper.
Indicator Lights
=MIXLOW
= MIX OUT
= TOPPING HEATER-LEFT
= TOPPING HEATER-RIGHT
Model C602
MIX LOW - When the MIX LOW symbolis
illuminated, the mix hopper has a low supply of mix
and should be refilled as soon as possible.
MIX OUT - When the MIX OUT
illuminated, the mix hopper has been almost
completely exhausted and has an insufficient supply
of mix to operate the freezer. At this time, the AUTO
mode is locked out and the freezer will be placed in
the STANDBY mode. To initiate the refrigeration
system, add mix to the mix hopper and touch the
AUTO symbol
begin operation.
11
. The freezer will automatically
Systems, Controls and Operations
symbol is
Heat Mode Symbol
When the HEAT MODE symbolis illuminated,
the freezer is in the process of a heat cycle. The
heat mode symbol may be selected to start a heat
cycle following a freezer soft lock condition.
For some International models, the heat symbol can
be selected to manually start a heat cycle at any
time.
The SAFETY TIMEOUT screen will be displayed
with the alarm on, for 60 seconds or until any control
symbol is selected.
After the safety timeout has been completed and the
power switch is OFF, the following screen is
displayed. (See Figure 6.)
Brush Clean Countdown - Displays the number of
days before the next brush cleaning is required.
When the display has counted down to “1”, the
machine must be disassembled and brush cleaned
within 24 hours.
Power Up
When the machine is powered the control system
will initialize to perform a system check. The screen
will display “INITIALIZING”. There will be four types
of data the system will check: LANGUAGE,
SYSTEM DATA, CONFIG DATA, and LOCKOUT
DATA.
During the INITIALIZING... LANGUAGE screen, the
alarm will be on. If the system detects corrupt data
during INITIALIZING, the following display will alert
the operator that the control settings may have been
changed (See Figure 4.)
SERVICE REQ’D
NVRAM FAULT
RESET TO DEFAULTS
< PRESS TO CLEAR
POWER SWITCH OFF
=-=-=-=-=-=-=-
UNIT CLEANED
Figure 6
Power Switch ON
When the power switch is placed in the ON position,
the control panel touch keys become operative. The
VFD will be either blank or indicate that the unit has
been cleaned. (See Figure 7.)
UNIT CLEANED
Figure 7
Figure 4
Once the system has initialized, the number of days
remaining before the next required brush cleaning is
indicated on the control panel and the SAFETY
TIMEOUT screen is displayed with the alarm turned
on. (See Figure 5.)
SAFETY TIMEOUT
ANY KEY ABORTS
Figure 5
Systems, Controls and Operations
Display for International Models Only:
Some International models will continuously display
the temperature of each mix hopper when the power
switch is in the ON position. (See Figure 8.)
HOPPERS21.021.1
UNIT CLEANED
Figure 8
12
Model C602
Heat Cycle
The HEAT symbolson the control panel are
illuminated throughout the heat treatment cycle. Two
warning messages will be displayed on the screen.
“DO NOT DRAW” will be displayed when the mix
temperature is below 130°F (54.4°C). (See
Figure 9.)
L:DO NOT DRAW
R:DO NOT DRAW
Figure 9
When the temperature of the mix is above 130°F
(54.4°C) the screen will display a message
indicating that HOT PRODUCT is in the machine.
(See Figure 10.)
L:HOT PRODUCT
R:HOT PRODUCT
Figure 10
DO NOT attempt to draw product or
disassemble the unit during the HEAT cycle. The
product is hot and under extreme pressure.
In the HEAT cycle, the mix temperature in the
hoppers and freezing cylinders must be raised to
151°F (66.1°C) within 90 minutes.
When the heating phase is complete, the freezer
goes into the holding phase of the cycle. The holding
phase will keep the temperature above 151°F
(66.1°C) for a minimum of 30 minutes.
The final phase of the heat treatment cycle is the
cooling phase. The freezer must cool the mix below
41°F (5°C) within two hours.
When the entire heat cycle has been completed, the
HEAT symbols
machine will enter the STANDBY mode (STANDBY
symbols
placed in AUTO or left in STANDBY.
andilluminate). The machine can be
will no longer be illuminated. The
Model C602
13
Systems, Controls and Operations
Freezer Lock-Out
Heat Cycle Failure Messages
To comply with health codes, heat treatment system
freezers must complete a heat treatment cycle
daily, and must be disassembled and brush cleaned
a minimum of every 14 days. Brush cleaning is the
normal disassembly and cleaning procedure found in
the Operator Manual. Failure to follow these
guidelines will cause the control to lock the freezer
out of the AUTO mode.
Always comply with local guidelines for the
maximum number of days allowed between brush
clean cycles. (See the Manager/Service Menu for
setting the Brush Clean interval, on page 21.)
If the Heat Treatment Cycle fails, the VFD will
display a failure message and return the freezer to
the STANDBY mode. A “lock” is defined as a special
STANDBY mode of operation which does not allow
the machine to operate in the AUTO mode.
There are two types of freezer lock conditions that
can occur: Hard Lock or Soft Lock. A Hard Lock
requires the machine be disassembled and brush
cleaned. A Soft Lock can be corrected by either
disassembling and brush cleaning the machine, or
by starting another heat treatment cycle.
Selecting the WASH symbol
following screen. (See Figure 12.)
FREEZER LOCKED
Figure 12
2.There has been a thermistor failure (freezing
cylinder, hopper, or glycol) during the heat
treatment process. (See Figure 13.)
SYSTEM FAULT
FREEZER LOCKED
SERVICE REQ’D
<PRESS TO CLEAR
Figure 13
Selecting the CALIBRATE symbol
which thermistor caused the Hard Lock. (See
Figure 14.)
L: HOPPER THERM BAD
will display the
will indicate
Hard Lock: There are two causes of a hard lock
failure:
1.The brush clean timer has elapsed (maximum
setting of 14 days). (See Figure 11.)
If the machine has hard locked and an attempt is
made to enter AUTO, the machine will enter the
STANDBY mode and display the following message.
(See Figure 15.)
FREEZER LOCKED
Figure 15
14
Model C602
To restore the message that identified the reason for
the hard lock, turn the power switch OFF for five
seconds and then return the power switch to the ON
position. The original message with the reason for
the Hard Lock will be displayed. The FAULT
DESCRIPTION can also be found in the Manager or
Service Menu (See page 22.)
The FREEZER LOCKED message will remain on
the display until the brush clean requirements are
fulfilled. The freezer must be disassembled in order
to activate the five minute timer on the display
screen. Once the timer counts down to zero, the
lockout is cleared.
Reasons For Soft Lock
Following are the variable messages for soft lock
failures that appear on the second line of the screen.
Power Switch Off
This soft lock will occur if the power switch is in the
OFF position and greater than 24 hours have
passed since the start of the 14 day timer, or the
start of the last successful Heat Treatment Cycle.
Soft Lock: If a heat treatment cycle has not been
initiated within the last 24 hours, a soft lock failure
will occur. A soft lock allows the operator to correct
the cause of the soft lock. The operator has the
option of either starting another heat cycle or brush
cleaning the machine. When a soft lock occurs, the
machine will go into the STANDBY mode. The
following message is displayed on the screen. The
reason for the soft lock is indicated on the second
line. (See Figure 16.)
HEAT TREAT FAILURE
REASON
HEAT FOR HEAT CYCLE
WASH TO BRUSH CLEAN
Figure 16
If the reason for the soft lock has been corrected,
selecting the HEAT symbol
immediately. Selecting the WASH symbol
the above message is displayed will hard lock the
machine and brush cleaning will be necessary.
initiates a Heat Cycle
when
Mix Out
This soft lock will occur if one or both sides has a
mix out condition and greater than 24 hours have
passed since the start of the 14 day timer or the
start of the last successful Heat Treatment Cycle.
Auto or Standby Off
This soft lock will occur if one or both sides is in the
OFF mode and greater than 24 hours have passed
since the start of the 14 day timer or the start of the
last successful Heat Treatment Cycle.
No Heat Cycle Tried
No Heat Treatment Cycle was performed in the 24
hours after the start of the 14 day timer, or the start
of the last successful Heat Treatment Cycle. (AUTO
HEAT TIME was advanced,a power loss was
experienced at the time the cycle was to occur, or a
heat cycle failure not due to a thermistor failure.)
Model C602
15
Systems, Controls and Operations
If the following screen appears, a soft lock has
occurred during the heat treatment cycle.
(See Figure 17.)
HEAT TREAT FAILURE
FREEZER LOCKED
HEAT FOR HEAT CYCLE
WASH TO BRUSH CLEAN
Figure 17
A soft lock can also occur any time during operation
when the hopper or freezing cylinder temperature
rises above 59°F (15°C), or the temperature rises
and remains above 41°F(5°C) for more than four
hours. If a PRODUCT OVER TEMPERATURE
condition occurs during operation, the following
screen will appear. (See Figure 18.)
PRODUCT OVER TEMP
HEAT FOR HEAT CYCLE
WASH TO BRUSH CLEAN
If the WASH symbolis selected to clear the
lockout by brush cleaning the machine, the
FREEZER LOCKED message will remain on the
display until the brush clean requirements are
fulfilled. The freezer must be disassembled in order
to activate the five minute timer on the display
screen. Once the timer counts down to zero, the
lockout is cleared. (See Figure 20.)
FREEZER LOCKED
Figure 20
To restore the message that identified the reason for
the soft lock, turn the power switch OFF for five
seconds, and then return the power switch to the
ON position. The original message with the reason
for the soft lock will be displayed. (See Figure 21.)
Figure 18
When one of these messages appears, automatic
freezer operation cannot take place until the freezer
is disassembled and brush cleaned, or has
completed a heat treatment cycle. Select the HEAT
symbol
symbol
machine.
Once the freezer is unlocked by starting a heat
treatment cycle the HEAT symbol
and the following message will be displayed on the
screen. (See Figure 19.)
to start a heat cycle, or select the WASH
to disassemble and brush clean the
will illuminate
L: DO NOT DRAW
R: DO NOT DRAW
Figure 19
HEAT TREAT FAILURE
REASON
HEAT FOR HEAT CYCLE
WASH TO BRUSH CLEAN
Figure 21
The FAULT DESCRIPTION can also be found in the
Manager and Service Menus. (See page 22.)
Note: A record of Heat Cycle Data and Lock Out
History can be found in the Manager and Service
Menus. (See page 23.)
Systems, Controls and Operations
16
Model C602
Service Menu
______________________________
The Service Menu option allows a trained service
technician to access and modify critical operating
parameters for the machine. All the menu screens
found in the Manager’s Menu are also included in
the Service Menu. To access the menu, touch the
center of the CONE symbol.
13117
Figure 22
illuminated and are non-functional when a menu
screen is displayed. The control keys for both sides
are only functional when the CURRENT
CONDITIONS screen is displayed.
Entering Access Cod e
With the ACCESS CODE screen on the display use
the AUTO
to set the first code number in the cursor position.
When the correct number is selected, touch the
CALIBRATION symbol
next number position.
The access code for the Service Menu is 5231.
The access code for the Operator Menu is 8309.
(See Figure 23.)
or OPTIONAL FLAVORsymbols
to move the cursor to the
ENTER ACCESS CODE
5231
_
The shake AUTO symbol
FLAVOR symbol
be illuminated when the ACCESS CODE screen is
displayed.
In the Menu program, the shake side AUTO symbol
, OPTIONAL FLAVOR symbol, and
CALIBRATION symbol
keys.
AUTO
and used to scroll upward in text displays
OPTIONAL FLAVOR
above the cursor and used to scroll downward in text
displays.
CALIBRATION
the right and is used to select menu options.
Note: You will not be able to dispense shakes while
accessing the Service Menu options, except when
the CURRENT CONDITIONS screen is displayed.
- increases the value above the cursor
and the CONE symbolwill
- advances the cursor position to
, the OPTIONAL
will function as menu
- decreases the value
Figure 23
Continue to enter the proper access code numbers
until all four numbers are displayed, and then touch
the CALIBRATION symbol
list will display on the screen, provided the correct
access code is entered.
If an incorrect number is entered for the access
code, the display will exit the Menu program when
the CALIBRATION symbol
Figure 24.)
. The Service Menu
is selected. (See
13118
The soft serve side will continue operation in the
mode it was in when the Menu was selected.
However, the soft serve side control keys will not be
Model C602
17
Figure 24
Systems, Controls and Operations
Service Menu Options
Touch the AUTO symbolor OPTIONAL FLAVOR
symbol
Select a Menu option by aligning the option with the
arrow on the left side of the screen, and then touch
the CALIBRATION symbol
program by selecting EXIT FROM MENU or touch
the CONE symbol
The following menu options are listed in the Service
Menu:
to move up or down through the Menu.
. Exit the Menu
.
EXIT FROM MENU
Selecting “EXIT FROM MENU” will exit the Menu
and the return the control panel symbols to normal
operation.
VERIFY CALIBRATION
The VERIFY CALIBRATION option is used to verify
that the amount of syrup dispensed is within the
proper specification. (See Figure 25.)
VERIFY CALIBRATION
Select a flavor
<- Press to clear
Note: Options “EXIT FROM MENU” through
“CURRENT CONDITIONS” can also be accessed
through the Manager’s Menu.
EXIT FROM MENU
VERIFY CALIBRATION
RESET DRAW COUNTER
SET CLOCK
AUTO HEAT TIME
AUTO START TIME
STANDBY MODE
BRUSH CLEAN CYCLE
MIX LEVEL AUDIBLE
FAULT DESCRIPTION
LOCKOUT HISTORY
HEAT CYCLE SUMMARY
HEAT CYCLE DATA
SYSTEM INFORMATION
CURRENT CONDITIONS
TEMPERATURE SCALE
STANDBY TEMPERATURE
HOPPER TEMPERATURE
GLYCOL TEMPERATURE
VISCOSITY SETTING
COMPRESSOR CYCLE TIME
COMPRESSOR ON DELAY
BEATER OFF DELAY
MIXPUMPOFFDELAY
WHITESPOT ADJUST
CAL SYRUP TIME
DRAW SAFETY TIME
EDIT UNIT ID
CALIBRATE PROXIMITY SWITCH
SELECT LANGUAGE
ABORT HEAT CYCLE
SYRUP MOTOR SETUP
Figure 25
Remove the syrup valve from the dispensing door.
With the line fully primed with syrup, position the
syrup valve over the small chamber side of the
divided syrup cup, and then select the
corresponding favor selection. Syrup will flow into
the cup for 5 seconds (7 seconds for Triple Thick
Shake Syrup) and then automatically stop flowing.
Place the cup on a flat surface and check the
amount of syrup dispensed. If the level is not within
the correct specification, the flavor will need to be
recalibrated.
It is recommended to verify the calibration of each
syrup flavor and note any flavors that need to be
recalibrated before exiting the Menu to access the
CALIBRATION Menu.
Select the CALIBRATION symbol
VERIFY CALIBRATION screen and return to the
Menu list.
RESET DRAW COUNTER
The SERVING COUNTER screen is used to check
or reset the number of servings dispensed from the
machine. The SERVING COUNTER will
automatically reset to zero when the machine is
brush cleaned. (See Figure 26.)
SERVINGS COUNTER
LEFTRIGHT
00
> Next
Figure 26
to exit the
Systems, Controls and Operations
18
Model C602
Reset the SERVING COUNTER by selecting the
CALIBRATION symbol
screen. Select the AUTO symbol
to advance to the next
to move the
arrow (>) to YES and select the CALIBRATION
symbol
. The servings counter will reset to zero
and exit back to the Menu. (See Figure 27.)
Change the time by touching the AUTO
OPTIONAL FLAVOR symbol
with the cursor
or
under the hour position. Move the cursor to the
minutes by selecting the CALIBRATION symbol
Once the correct minutes are entered, select the
CALIBRATION symbol
to advance the cursor to
the month. (See Figure 30.)
.
RESET DRAW COUNTER
Yes
>No
Figure 27
SET CLOCK
The SET CLOCK option allows the manager or
service technician to adjust the control clock date
and time. The date and time may only be changed
after the freezer has been manually cleaned but
before it has been placed in the AUTO or STANDBY
mode. The following message will be displayed if the
SET CLOCK option is selected when the machine is
not in a brush clean state. (See Figure 28.)
SET CLOCK
08:0004/02/2004
NO CHANGES ALLOWED
>Press Any Key
SET CLOCK
08:0004/02/2004
__
>Exit
Figure 30
Enter the correct month, day, and year. Then select
the CALIBRATION symbol
to advance to the
DAYLIGHT SAVING TIME screen. (See Figure 31.)
DAYLIGHT SAVING TIME
ENABLED
>Enable
Disable
Figure 31
The Daylight Saving Time feature, when enabled,
will automatically adjust the control clock for daylight
saving time. To Disable the Daylight Saving Time
feature, select the AUTO symbol
to move the
arrow to Disable. Then touch the CALIBRATION
symbol
to save the new setting.
Figure 28
To change the date or time, select the SET CLOCK
option in the menu. Touch the AUTO symbol
to
advance the arrow from Exit to Change, and then
touch the CALIBRATION symbol
to select the
Change option. (See Figure 29.)
SET CLOCK
08:0004/02/2004
Change
>Exit
Figure 29
Model C602
AUTO HEAT TIME
The AUTO HEAT TIME screen allows the manager
or service technician to set the time of day in which
the heat treatment cycle will start. (See Figure 32.)
AUTO HEAT TIME
00:00
Change
>Exit
Figure 32
Note: Do not advance the Auto Heat Time setting
except on the day the unit is brush cleaned.
Increasing the time between heat cycles will cause
the machine to soft lock if the start of the cycle does
19
Systems, Controls and Operations
not begin within 24 hours from the start of the
previous heat treatment cycle.
To set the AUTO HEAT TIME select the AUTO
symbol
select the CALIBRATION symbol
to move the arrow to Change. Then
. The screen
will display the time with the cursor under the hour
position. (See Figure 33.)
AUTO HEAT TIME
00:00
__
Figure 33
Select the AUTO symbol
FLAVOR symbol
to increase or decrease the
or the OPTIONAL
hour to the desired setting. Then move the cursor to
the minutes position by selecting the CALIBRATION
symbol
select the CALIBRATION symbol
. Adjust the setting for minutes, then
to save the
setting and return to the AUTO HEAT TIME screen.
Select the CALIBRATION symbol
to exit the
screen and return to the Menu.
Enable the AUTO START TIME by selecting the
AUTO symbol
Select the CALIBRATION symbol
to move the arrow up to Enable.
to advance to
the next screen. (See Figure 35.)
AUTO START TIME
00:00
Change
>Exit
Figure 35
Program the AUTO START TIME by selecting the
AUTO symbol
Select the CALIBRATION symbol
to move the arrow to Change.
to advance to
the next screen. (See Figure 36.)
AUTO START TIME
00:00
__
AUTO START TIME
The AUTO START TIME option allows the manager
or service technician to set the time of day at which
the machine automatically enters the AUTO mode
from the STANDBY mode. The machine must be in
the STANDBY mode without a freezer lock condition
in order to AUTO start at the programmable time.
The AUTO START TIME can be disabled and will
require starting the AUTO mode manually. (See
Figure 34.)
AUTO START TIME
DISABLED
Enable
>Disable
Figure 34
Figure 36
Program the AUTO START TIME by increasing
(AUTO symbol
FLAVOR symbol
cursor. Select the CALIBRATION symbol
) or decreasing (OPTIONAL
) the hour setting above the
to
advance the cursor and program the minutes
setting.
Select the CALIBRATION symbol
to return to the
previous screen with the new time setting displayed.
Select the CALIBRATION symbol
to exit the
screen and return to the Menu.
Systems, Controls and Operations
20
Model C602
STANDBY MODE
The Standby option is used only on models which
have the control panel Standby keys disabled.
The STANDBY option is used to manually place the
left or right side in the standby mode during long, no
draw periods. Select the STANDBY screen from the
Menu. Select the AUTO symbol
to move the
arrow up to the left (shake) or right (soft serve) side.
Select the CALIBRATION symbol
to activate
Standby for the selected side.
Repeat the steps to activate Standby on the
remaining side. (See Figure 37.)
STANDBY MODE
LEFT
RIGHT
>Exit
symbol
the CALIBRATION symbol
to increase the number of days. Select
to save the setting
and exit back to the Menu. The number of days
displayed on the brush clean counter will change to
the new setting. (See Figure 39.)
BRUSH CLEAN CYCLE
TIME14 DAYS
Figure 39
Always comply with local guidelines on the number
of days allowed between brush clean cycles.
Figure 37
Discontinue Standby operation for either side by
exiting the Menu and select the AUTO mode.
BRUSH CLEAN CYCLE
The BRUSH CLEAN CYCLE option allows the
manager or service technician to select the
maximum number of days between brush cleaning
the machine. The brush clean cycle may only be
changed after the freezer has been manually
cleaned but before it has been placed in the AUTO
or STANDBY mode.
The following message will be displayed if the
BRUSH CLEAN CYCLE option is selected when the
machine is not in a brush clean state.
(See Figure 38.)
BRUSH CLEAN CYCLE
TIME14 DAYS
NO CHANGES ALLOWED
Press Any Key
Figure 38
Change the number of days between brush clean
intervals by selecting the AUTO symbol
to
decrease the days or the OPTIONAL FLAVOR
MIX LEVEL AUDIBLE
The MIX LEVEL AUDIBLE option, when enabled,
will alert the operator with an audible tone when
there is mix low or mix out condition. The following
screen is displayed upon selecting this option. (See
Figure 40.)
MIX LEVEL AUDIBLE
ENABLED
>Enable
Disable
Figure 40
Disable the audible tone feature by selecting the
OPTIONAL FLAVOR symbol
to move the arrow
to DISABLE. Select the CALIBRATION symbol
to save the new setting and return to the Menu. The
control panel icons for Mix Low and Mix Out will
illuminate as the mix level drops in the hopper but
the audible tone will be disabled.
Model C602
21
Systems, Controls and Operations
FAULT DESCRIPTION
LOCKOUT HISTORY
The FAULT DESCRIPTION display will indicate if
there is a fault with the freezer and the side of the
freezer where the fault occurred. When no faults are
detected the following screen will be displayed. (See
Figure 41.)
FAULT DESCRIPTION
L: NO FAULT FOUND
R: NO FAULT FOUND
Figure 41
Select the CALIBRATION symbol
to display the
next fault found or return to the Menu if no other
faults exist. Selecting the CALIBRATION symbol
any time faults are displayed will clear the faults if
corrected, upon returning to the Menu screen.
Listed below are the variable messages which will
appear, along with an explanation for the corrective
action.
NO FAULT FOUND - There was no fault found in
the freezer. Nothing will appear on the screen after
this variable message appears.
The LOCKOUT HISTORY screen displays a history
of the last 40 soft locks, hard locks, brush clean
dates, or aborted heat cycles. Page numbers are
indicated in the upper right hand corner. Page 1
always contains the most recent failure. (See
Figure 42.)
LOCKOUT HISTORY2
00/00/0000:00
REASON
>Exit
Figure 42
The second line of the screen displays the date and
time a failure occurs. The third line indicates the
reason for a failure, or will indicate if a successful
brush cleaning has occurred. Some failures occur
with multiple reasons. When this occurs, a page will
be generated for each reason.
Select the AUTO symbol
symbol
to advance forward or backward to view
or OPTIONAL FLAVOR
each screen. Listed below are the variable
messages that may appear.
BEATER OVERLOAD - Press the beater reset
button firmly for the side of the freezer with the fault.
HPCO COMPRESSOR - Place the power switch in
the OFF position. Wait 5 minutes for the machine to
cool. Place the power switch in the ON position and
restarteachsideinAUTO.
HOPPER THERMISTOR BAD - Place the power
switch in the OFF position. Replace the bad probe.
BARREL THERMISTOR BAD - Place the power
switch in the OFF position. Replace the bad probe.
GLYCOL THERMISTOR BAD - Place the power
switch in the OFF position. Replace the bad probe.
Faults Occurring While Entering a Heat Treatment
Cycle
POWER SWITCH OFF - The power switch is OFF.
AUTO OR STBY OFF - The control was not in
AUTO or STANDBY.
MIX OUT FAILURE - A mix out condition was
present.
NO HEAT CYCLE TRIED - The Auto Heat Time
was set to attempt a heat cycle more than 24 hours
after the last successful heat cycle.
Systems, Controls and Operations
22
Model C602
Faults Occurring While in Heat Mode
HEAT MODE FAILURE - The maximum allowable
heat mode time exceeded 90 minutes.
COOL MODE FAILURE - The maximum allowable
cool mode time exceeded 120 minutes.
TOTAL TIME FAILURE - The maximum allowable
total heat treatment time exceeded 4 hours.
BRUSH CLEAN TIMEOUT - The total days in
operation exceeded the brush clean cycle setting.
Faults Occurring While in AUTO Mode
(L/R) HPR>41F (5C) AFTER 4 HR -Themix
temperature in the left or right hopper was above
41°F(5°C) more than four hours.
(L/R) BRL>41F (5C) AFTER 4 HR -Themix
temperature in the left or right barrel was above
41°F(5°C) more than four hours.
(L/R) HPR>41F (5C) AFTER PF -Themix
temperature in the left or right hopper was above
41°F(5°C) more than four hours following a power
failure.
(L/R) BRL>41F (5C) AFTER PF -Themix
temperature in the left or right barrel was above
41°F(5°C) more than four hours following a power
failure.
(L/R) HPR>59F (15C) - The mix temperature in the
left or right hopper exceeded 59°F(15°C).
POWER SWITCH OFF - The power switch was
turned OFF during the heat cycle.
POWERFAILINH/C- A power failure occurred
during the heat treatment cycle.
(L/R) MIX LOW FAILURE - The mix level in the
(left/right) Hopper is too low for a successful heat
cycle.
(L/R) BEATER OVLD H/C - The overload tripped for
the (left/right) side beater motor.
(L/R) BRL THERM FAIL - The thermistor sensor for
the (left/right) side barrel failed.
(L/R) HOPPER THERM FAIL - The thermistor
sensor for the (left/right) side hopper failed.
(L/R) HPCO H/C - The (left/right) side high pressure
switch opened during the heat treatment cycle.
(L/R) BRL>59F (15C) - The mix temperature in the
left or right barrel exceeded 59°F(15°C).
HEAT CYCLE SUMMARY
The HEAT CYCLE SUMMARY screen displays the
hours since the last heat cycle, the hours since the
product temperature was above 150°F (65.6°C), and
the number of heat cycles completed since the last
brush clean date. (See Figure 43.)
HEAT CYCLE SUMMARY
HRS SINCE HC0
HRS SINCE 150.00
HRS SINCE BC0
Figure 43
HEAT CYCLE DATA
The HEAT CYCLE DATA screen contains a record
of up to 366 heat treatment cycles. The most recent
heat cycle data will be shown first. Each heat cycle
record or page has two screens. The first screen
displays the month and day of the heat cycle, the
start time and end time, and which side of the
machine underwent the heat treatment cycle; L for
Left side, R for Right side, and B for both sides. Line
3 displays the total time in each heat cycle phase.
Line 4 displays the glycol temperature at the
completion of the heat cycle and the page number.
Model C602
23
Systems, Controls and Operations
Select the AUTO symbol
to advance forward
through the data pages. Select the OPTIONAL
FLAVOR symbol
to reverse the page direction.
(See Figure 44.)
00/0000:0000:00B
HEAT OVER COOLRC
00:0000:0000:00*
TEMP AT END0.01
Figure 44
The second screen will have the same page number
and display the temperature recorded in each
hopper, barrel, and the temperature of the glycol
when the heat cycle was terminated. The left hopper
and barrel temperature is displayed on line 2 and the
right side temperatures on are line 3. The time in the
last phase of heat cycle, whether successful or
failed, is displayed on line 4.
Select the AUTO symbol
page or the OPTIONAL FLAVOR symbol
to advance to the next
to view
the previous page. (See Figure 45.)
HOPPER BARREL GLYCOL
000.0000.0000.0
000.0000.0
PHASE TIME: 00:001
Figure 45
Heat Cycle Failure codes will display on the first
screen on line 2 if a failure occurred.
(See Figure 46.)
HOPPER BARREL GLYCOL
000.0000.0000.0 HT
000.0000.0
PHASE TIME: 00:001
Figure 46
Listed below are variable failure code messages
which could appear on line 2.
HTHeat Time Too Long
Mix temperature did not rise above 151°F
(66.1°C) in less than 90 minutes.
CLCool Time Too Long
Mix temperature in the hopper and freezing
cylinder did not fall below 41°F(5°C) in less
than 120 minutes.
TTTotal Time Too Long
The heat treatment cycle must be completed
in no more than 4 hours.
MO Mix Out Condition
A mix out condition was detected at the start
or during the heat cycle.
MLMix Low Condition
The Heat Phase or Cool Phase time was
exceeded and a mix low condition was
present.
BOBeater Overload Condition
A beater overload occurred during the heat
cycle.
HOHigh Pressure Cut-Out Condition
A high pressure cut-out condition occurred
during the heat cycle.
PFPower Failure
A power failure caused the Heat Phase,
Cool Phase, or Total Cycle Time to exceed
the maximum allowed time. If a power failure
occurs, but the heat treatment cycle does
not fail, an asterisk(*) will appear on the third
line of the display.
PSPower Switch OFF
The power switch was placed into the OFF
position during the heat cycle.
THThermistor Switch OFF
A thermistor probe has failed.
RCRecord Cleared
Data has not been written to the page or
cleared due to corrupt data.
OPOperator Abort
Indicates the heat cycle was aborted in the
OPERATOR ABORT option in the service
menu.
PDProduct Door Not in Place
A product door is not in place or is loose.
Systems, Controls and Operations
24
Model C602
SYSTEM INFORMATION
The SYSTEM INFORMATION is displayed on three
separate screens. The first screen contains the
control and software version installed in the
machine. (See Figure 47.)
VISC00.0
HOPPER41.041.0
BARREL41.041.0
GLYCOL41.0
SOFTWARE VERSION
C602 CONTROL UVC3
VERSION 1.00
>Next
Figure 47
Select the CALIBRATION symbol
to advance to
the next system information screen containing the
software language version. (See Figure 27.)
Language
V1.11r00 English 515
>Next
Figure 48
Select the CALIBRATION symbol
to advance to
the third system information screen containing the
model bill of material and machine serial number.
Selecting the CALIBRATION symbol
again will
return to the Menu list. (See Figure 49)
Figure 50
CURRENT CONDITIONS is the only Menu screen
that will return the left and right side control panel
keys to normal operation. The Menu keys will not be
illuminated when this option is selected so shakes
can be dispensed and all panel touch keys are fully
functional. Use this screen when you wish to remain
in the Menu and dispense a shake. Exit the
CURRENT CONDITIONS screen and return to the
Menu by selecting the CALIBRATION symbol
.
Note: All screens from this point forward can only
be accessed through the service menu.
TEMPERATURE SCALE
The TEMPERATURE SCALE option allows the
service technician to choose the scale in which the
machine will display all temperatures. (See
Figure 51.)
B.O.M. C60233H000
S/NK0000000
>Next
Figure 49
CURRENT CONDITIONS
The CURRENT CONDITIONS screen provides the
viscosity readings for the product when the side is
running and hopper and barrel temperatures for both
sides of the machine. The left column displays the
readings for the shake side and the right column
displays the soft serve side readings. The bottom
line in the display indicates the current glycol
temperature. (See Figure 50.)
Model C602
TEMPERATURE SCALE
FAHRENHEIT
>Fahrenheit
Celsius
Figure 51
To change the scale setting, use the AUTO
symbol
or OPTIONAL FLAVOR symbolto
move the cursor along side of the desired
temperature scale then touch the CALIBRATION
symbol
to save the selection and return to the
service menu.
25
Systems, Controls and Operations
STANDBY TEMPERATURE
HOPPER TEMPERATURE
The STANDBY TEMPERATURE option allows the
service technician to adjust the freezing cylinder
temperature in the Standby mode. In Standby, the
machine will cycle the compressor (and beater) on if
the temperature of the product in the freezing
cylinder rises above the setpoint. The compressor
will cycle off when the temperature of the product in
the freezing cylinder drops 4°F(2.2°C) or more
below the set point. (See Figure 52.)
STANDBY TEMP
L CUT IN AT : 30.5
CURRENT: 30.5
>Next
Figure 52
Adjust the temperature setting using the AUTO
symbol
OPTIONAL FLAVOR symbol
to increase the temperature or
to decrease the
temperature. Save the setting by selecting the
CALIBRATION symbol
to advance to the next
screen for the right side freezing cylinder Standby
temperature setting. (See Figure 53.)
The HOPPER TEMPERATURE menu allows the
service technician to adjust the hopper temperature
by which the glycol pump and the left and right
glycol solenoids are controlled when the machine is
operating in AUTO or STANDBY modes.
Hopper cooling is activated when the mix
temperature rises above the set point temperature.
When the temperature drops 2°F(1°C) below the
set point the hopper cooling is discontinued. (See
Figure 54.)
HOPPER TEMP
L CUT IN AT : 39.0
CURRENT: 39.0
>Next
Figure 54
Adjust the temperature setting using the AUTO
symbol
OPTIONAL FLAVOR symbol
to increase the temperature or
to decrease the
temperature. Save the setting by selecting the
CALIBRATION symbol
to advance to the next
screen for the right side Hopper temperature setting.
(See Figure 55.)
STANDBY TEMP
R CUT IN AT : 30.5
CURRENT: 30.5
>Next
Figure 53
Select the CALIBRATION symbol
setting and return to the Service Menu.
to save the
HOPPER TEMP
R CUT IN AT : 39.0
CURRENT: 39.0
>Next
Figure 55
Select the CALIBRATION symbol
setting and return to the Service Menu.
to save the
Systems, Controls and Operations
26
Model C602
GLYCOL TEMPERATURE
VISCOSITY SETTING
The GLYCOL TEMPERATURE allows the Service
Technician to adjust the glycol temperature used to
control the glycol heater in the HEAT and HOLD
phases of the Heat Treatment Cycle.
When the glycol temperature falls 6°F(3.3°C) or
more below the set point, the glycol heater is
activated. When the glycol temperature rises above
the set point, the heater is de-activated. The factory
glycol temperature setting is 178°F(81°C). (See
Figure 56.)
GLYCOL TEMPS
HEATING : 178.0
CURRENT : 41.0
>Next
Figure 56
Adjust the temperature setting using the AUTO
symbol
OPTIONAL FLAVOR symbol
to increase the temperature or
to decrease the
temperature. Save the setting by selecting the
CALIBRATION symbol
to advance to the next
screen for the right Glycol temperature setting in the
HOLDING phase. (See Figure 57.)
GLYCOL TEMPS
HOLDING : 177.0
CURRENT : 41.0
>Next
The viscosity setting option allows the service
technician to adjust the viscosity at which the
compressor cycles off during the AUTO mode of
operation.
Select the AUTO symbol
to move the cursor up
to the left or right side viscosity setting. (See
Figure 58.)
VISCOSITY SETTING
LEFT
RIGHT
>Exit
Figure 58
Shake Viscosity Setting (Left):
Select the AUTO symbol
to increase the viscosity
setting or the OPTIONAL FLAVOR symbol
decrease the setting. (See Figure 59.)
VISCOSITY SETTING
LEFT = 4000HD
CURRENT =0
Figure 59
to
Figure 57
The GLYCOL HOLDING TEMPERATURE set point
controls the glycol heater in the HOLDING phase of
the Heat Treatment Cycle. When the glycol
temperature is 6°F(3.3°C) or more below the set
point, the glycol heater is activated. When the glycol
temperature rises above the set point, the heater is
de-activated. The factory setting for the glycol
holding temperature is 177°F(81°C).
Adjust the temperature setting using the AUTO
symbol
to increase the temperature or
OPTIONAL FLAVOR symbolto decrease the
temperature. Select the CALIBRATION symbol
to save the setting and return to the Service Menu.
Model C602
Note: A Hedlund (HD) is a Taylor factory defined
unit of measure representing the relative product
viscosity (thickness). Product in the shake machines
is normally set at a viscosity ranging from 4,000 to
7,500 HD’s to accomplish a neutral frozen product
temperature around 23° -26°F (-5 to -3.3°C).
While the beater motor is on, the current viscosity
indicated on the display is updated continually.
When the beater motor is off, this value is zero.
Select the CALIBRATION symbol
to save the
setting and return the Service Menu.
27
Systems, Controls and Operations
Loading...
+ 84 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.