SILENT
KNIGHT
®
by Honeywell
SKE-V70 Module Installation
Instructions
The SKE-V70 converts the speaker circuit
voltage from 25 Vrms to 70.7 Vrms. The
following describe how to install and wire the
SKE-V70.
Mounting
Follow these steps to install the SKE-V70
module into the main control panel cabinet:
1. Unlock and open the cabinet door.
2. Remove the two cover plate retaining
screws, then open the control panel cover
plate. See Figure 1.
SKE-V70
Cabinet
Mounting
Screws
Figure 2: Main Control Board Mounting Location
5. Connect wiring as described in Section .
Zone Splitter
Access Plate
Control Panel
Cover Plate
Retaining Screws
Figure 1: View of Cabinet With Cover Plate in Place
Note: The control panel cover plate can be remove by removing
the Hinge screw.
Control Panel
Cover Plate
Hinge Screw
3. Run all wire needed to install the system at
this time.
4. Mount the module into the cabinet as shown
in Figure 2.
Wiring Connections
Each SKE-V70 supplies one NAC (Notification
Appliance Circuit) for speaker connection. The
speaker circuit can be supervised and wired
Class B (Style Y) or Class A (Style Z). The
speaker circuit is capable of 50 watts of power
70.7 Vrms (using the SKE-V70 Module).
Note: When the SKE-V70 Module is installed, all speaker
wiring must be separated by a minimum of 1/4” from the
low voltage wiring, and must exit the cabinet through its
own opening.
P/N 151305
SKE-V70 Module Installation Instructions
Connecting the SKE-V70 to the
Main Control Panel
Connect the SKE-V70 to the main control panel
using the supplied wire harness. See Figure 3.
Note: Speaker outputs of the SKE-450 must not be used with the
SKE-V70 because supervision will not be provided at the
SKE-450.
Figure 3: Wire Harness Connection From the Main
Control to the SKE-V70
Connecting the SKE-V70 to the
SKE-ZN4 or -ZN6
15 k
Ω EOL
UL Listed
Model 7630
Supervised
Power Limited
Figure 4: Class B (Style Y) Speaker Configuration
Class A (Style Z)
Figure 5 illustrates how to wire speakers to the
SKE-V70 using Class A (Style Z) wiring.
Supervised
Power Limited
If the optional SKE-ZN4 or -ZN6 zone splitter is
used in the system connect the wire harnesses as
described below.
Note: Speaker outputs of the SKE-450 and SKE-V70 must not
be used when using either the SKE-ZN4 or SKE-ZN6 in
combination with the SKE-V70 because supervision will
not be provided at the SKE-450 and the SKE-V70.
1. Connect one harness from the main control
to the SKE-V70 connector marked “FROM
CONTROL”. See Figure 3.
2. Connect the other harness from the SKEV70 connector marked “TO SPLITTER” to
the connector on the SKE-ZN4 or -ZN6 as
shown in Figure 3.
Class B (Style Y)
Figure 4 illustrates how to wire speakers to the
SKE-V70 using Class B (Style Y) supervision.
Figure 5: Class A (Style Z) Speaker Configuration
Electrical Specifications
Ground Fault Impedance To Any Terminal: 0 Ω
Standby Input Power: 27.4 VDC @ 10 mA
Alarm Input Power: 27.4 VDC @ 70 mA
SILENT
KNIGH
®
by Honeywell
Maple Grove, MN 55369-4927
763-493-6455 or 800-328-0103
2
© 2005 Silent Knight PN 151305 Rev B
7550 Meridian Circle
Fax: 763-493-6475
www.silentknight.com