For on-off control of media temperature in ducts, tanks, liqui d
lines, etc.
SPECIFICATIONS
Setpoint Dial Range: Dial plate is marked as °F on one
side and °C on the other. See Table-2 for specific ranges.
Sensing Element: Liquid-filled copper.
Differential: See Table-2.
Dual Bulb Units: One bulb senses the controlled media;
the second bulb senses the outside air temperature. The
temperature of the controlled media increases as outside air
temperature decreases.
Ambient Temperature Limits:
Case,
Shipping -40 to 160°F (-40 to 71°C).
Operating -40 to 150°F (-40 to 65°C): except return
air bulb unit, -40 to 140°F (-40 to 60°C).
Bulb, See Table-2.
Electrical Switch: Snap action SPDT, one per stage.
Ratings, See Table-1.
Connections: Coded screw terminals.
Cover: All metal with 1/2" to 3/4" conduit openings.
Case Locations: NEMA Type 1 indoor only.
Mounting: Case can be mounted in any position. See
ACCESSORIES for bulb mounting kits (order separately).
Dimensions:
Case, 4-5/8" high x 2-1/4" wide x 2" deep (117 mm x 57
On the dual bulb units, indoor and outdoor bulbs are
determined by the ratio selected (see T able-2). Ratio refers to
the outdoor air temperature change compared to the water
temperature change. The dial setpoint is the water
temperature setpoint when the outdoor temperature is 70°F.
T o select ratio, it is necessary to know only: (1) outdoor design
temperature, (2) maximum water temperature at outdoor
design temperature, and (3) desired water temperature at
70°F outdoors. Use Table-3 to determine the required ratio
based on this information and set the dial per item (3).
Note: If a 1-1/2:1 ratio is selected, the extra di al sup p l ied
with the unit must be used.
Example: Select ratio for an installation with a -10°F design
temperature and estimated supply water temperature of 75°F
at 70°F outdoors and 125°F at -10°F outdoors. From Table-3,
-10°F for 1-1/2:1 ratio, note by interpolation (70°F to 123°F
with dial at 70°F, 80°F to 133°F with dial at 80°F) that water
temperature varies from 75°F to 128°F as outdoor
temperature drops from 70°F to -10°F.
For this application, the 1-1/2:1 ratio should be selected. The
extra dial supplied with the unit would be used, and the dial set
at 75°F.
PRE-INSTALLATION
Location
Locate the device allowing proper distance to the bulb
location. The case can be mounted in any position. Refer to
Figure-2 for case dimensions.
TC-4166
TC-4266
Only
Cut Hole in
Duct 2-1/4" W x
2-1/2" H for
Mounting in
Return Air
7/8"
13-64"
1-9/16"
Side
2"
Bottom
TC-4166
TC-4266
Only
7"
TC-4166
TC-4266
Only
3-5/8"
TC-4166
4-5/8"
1"
Hole for 1/2" Conduit
Knockout for 3/4" Conduit
1-5/64"
TC-4266
Only
1/2"
1/4"
2-1/4"
Back
5/16"
Inspection
Visually inspect the carton for damage. If damaged, notify the
appropriate carrier immediately. If undamaged, open the
carton and visually inspect the device for obvious defects.
Return damaged or defective products.
Required Installation Items
• Wiring diagram
• Tools (not provided):
Volt-ohm meter
Room temperature thermometer on °F or °C
Appropriate screwdriver(s) for cover, terminals and
mounting screws
Appropriate drill and drill bit for mounting screws
INSTALLATION
Caution:
1. Installer must be a qualified, experienced technician.
2. Disconnect power supply before installation to prevent
electrical shock and equipment damage.
3. Make all connections in accordance with the electrical
wiring diagrams, and in compliance with national and
local codes. Use copper conductors only.
4. Do not exceed ratings of the device.
5. Avoid locations where excessive moisture, corrosive
fumes or vibrations are present.
Figure-2 Case Dimensions.
Procedure for Remote Bulb Mounting
Air Bulb Models — Mounting in Return Air Duct
1. Remove cover and provide two holes for #10 round head
screws using the housing as the template or by using the
dimensions shown in Figure-2.
2. Partially insert the mounting screws in the screw holes.
Fit the housing over the screws, slide housing down on
the screws and tighten the screws.
Air Bulb Models —
Mounting Outside of Return Air Duct
1. Prepare duct for mounting by cutting hole and providing
mounting screw holes per Figure-2.
2. Fabricate a cover as shown in Figure-3.
3. Carefully roll bulbs toward back of unit and insert through
2-1/4" x 2-1/2" (57 mm x 64 mm) hole.
4. Remove cover and attach unit to duct with #10 screws.
5. Attach cover over 2-1/4" x 2-1/2" (57 mm x 64 mm) hole.
Table-4 Bulb Mounting Installation Hardware And Application Limitations.
Application Limitations
Part
Number
AT-201
AT-203
AT-206
a
Max. recommended fluid temperature is 350 F (177°C).
b
Requires AT-209.
b
b
Description
Copper
Bulb Well
Stainless Steel
Bulb Well
Copper
Bulb Well
Mounting
Fitting
3/4"
MNPT
1/2"
MNPT
Insertion Size
in. (mm)
1/2 (13) dia. O.D.
9-1/2 (241) long
1/2 (13) dia. O.D.
4-1/2 (114) long
at 250°F (121°C) Fluid Temperature
Max. Recommended
Velocity fps (m/s)
11 (3.3)250 (1728)
20 (6.1)500 (3448)
11 (3.3)250 (1728)8
WIRING
The thermostat has one 1/2" to 3/4" conduit opening in the
bottom of the housing. Terminal coding and switch action are
shown in Figures-9 and 10.
a
Max. Recommended
Static Press. psig (kPa)
Installation
per Figure
7
Figure-9 Terminal Coding and Switch Action.
Figure-10 Two Stage Switch Sequence.
TYPICAL APPLICATIONS
Figures-11 and 12 show typical heating and cooling
applications for single stage units. Figures-13 and 14 show
typical heating and cooling applications for two stage units.
Figure-11 Typical Heating Application for Single Stage Units.
Figure-12 Typical Cooling Application for Single Stage Units.
Figure-13 Typical Heating Application for Two Stage Units.
Figure-14 Typical Cooling Application for Two Stage Units.
CHECKOUT
After installing a thermostat, make an initial check of the
switching action. Verify the switch action by listening to the
switch contacts.
1. Turn the setpoint dial to a tempera ture above ambient. This
should cause the thermostat to switch, making orange to
brown.
2. Turn the setpoint dial setting down gradually. Orange to
brown must break, making orange to red.
3. Compare the differential of the device to the differential
shown on the performance charts by turning the dial. The
differential of the device is the difference in dial reading
between the make of orange to brown and the make of
orange to red on single switch units.
ADJUSTMENTS
To adjust interstage differential:
1. Disconnect power to unit.
2. Remove cover.
3. Turn adjustor to approximately desired position.
4. Check out by turning dial and noting dial readings where
switch contacts make.
5. After changing interstage differential, recalibrate. See
CALIBRATION.
CALIBRATION
1. With all power disconnected, soak bulb(s) for 10 minutes
at known temperature (must be 70°F for dual bulb).
2. Turn dial and note where switch contacts make.
3. Turn dial midway between click points.
4. Turn the calibration nut (located under dial) until the
temperature of the bulb is indicated on the dial (see
Figure-15).
Note: On two stage units follow above procedure. LO switch
is first stage on cooling applications. HI switch is first stage on
heating applications.
MAINTENANCE
Regular maintenance of the total system is needed to assure
sustained optimum performance. Thermostats should be
periodically inspected for dirt or blockage of air over the
elements.
Setpoint
Screwdriver adjustment. Scales dual marked °F on front and
°C on back. To change scale, remove spring retaining ring,
select scale and replace retaining ring.
Differential
The differential is adjustable by turning the adjustor located on
the side of the device (see Figure-15).
Calibration Nut
(Turn with 1/2"
open end wrench)
Incr. Spread
Differential Adjustment
Figure-15 Adjustments.
Single Stage: Each line represents approximately 3°F (2°C)
change.
Two Stage: Each notch represents approximately 2°F (1°C)
change between stages. (Differential per switch is fixed.)
REPAIR
Field repair is not recommended. Replace defective device.
On October 1st, 2009, TAC became the Buildings business of it s parent company Schneide r Electric. This document reflects th e visual identity of Schneider Ele ctric,
however there remains references to T AC as a corporate brand in th e body copy. As each document is updated, the body copy will be changed to reflect ap propriate
corporate brand changes.
Copyright 2009, Schneider Electric
All brand names, trademarks and registered
trademarks are the property of their respective
owners. Information contained within this
document is subject to change without notice.
F-18895-7
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.