Schneider Electric MTZ2, MTZ3 User Manual

MasterPactMTZ2/MTZ3

DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3
IEC Circuit Breakers and Switch-Disconnectors from 800 to 6300 A User Guide
DOCA0101EN-04
www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical character­istics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.
You agree not to reproduce, other than for your own personal, noncommercial use, all or part of this document on any medium whatsoever without permission of Schneider Electric, given in writing. You also agree not to establish any hypertext links to this document or its content. Schneider Electric does not grant any right or license for the personal and noncommercial use of the document or its content, except for a non-exclusive license to consult it on an "as is" basis, at your own risk. All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to help ensure compliance with documented system data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2020 Schneider Electric. All rights reserved.
2 DOCA0101EN-04 07/2020

Table of Contents

Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 1 MasterPact MTZ2/MTZ3 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
MasterPact MTZ2/MTZ3 Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fixed Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Drawout Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Device Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MicroLogic X Control Unit: Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Go2SE Landing Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating Conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 2 MasterPact MTZ2/MTZ3 Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . 33
2.1 Device Operating Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating the Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Opening the Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Closing the Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Resetting the Circuit Breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Engaging the ERMS Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Drawout Device Racking Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Drawout MasterPact MTZ2/MTZ3 Device Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Disconnecting the Drawout Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the Drawout Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing the Drawout Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installing the Drawout Device in the Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Device Locking Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Locking the Pushbuttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Locking the Device in Open Position with Padlocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Locking the Device in Open Position with Keylocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chassis Locking in Disconnected Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chassis Locking in Any Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Locking the Safety Shutters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.4 Device Interlocking Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mismatch Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VPEC Door Interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VPOC Open-door Racking Interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IPA Cable-type Door Interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mechanical Interlocking for Transfer Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DAE Automatic Spring-Discharge Interlock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IBPO Racking Interlock Between Racking Handle and Opening Pushbutton . . . . . . . . . . . .
Chapter 3 MasterPact MTZ Critical Cases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Finding the Cause of a Trip or an Alarm in Critical Cases. . . . . . . . . . . . . . . . . . . . . . . . . . .
Resetting the Circuit Breaker After a Trip Due to an Electrical Fault . . . . . . . . . . . . . . . . . .
Resetting the Circuit Breaker After a Trip Due to an Incident Detected by the MicroLogic X
Self-tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnosing Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnosing Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10 12 16 23 26 29 31
34 35 39 44 47 50 51 53 60 61 65 68 71 74 77 78 80 82 84 88 90 93 94 96
99 102 103 105 105
108 111
114 116 124
DOCA0101EN-04 07/2020 3
Chapter 4 MasterPact MTZ Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Introduction to Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Inspection and MicroLogic X Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Communication Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Final Checks and Reporting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MasterPact MTZ Test Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
128 130 132 135 136 137
Chapter 5 MasterPact MTZ Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Introduction to Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting: Chassis Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting: Unexpected Tripping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting: Mechanical Control Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting: Electrical Control Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting: Control Operations from EcoStruxure Power Device App . . . . . . . . . . . . .
Troubleshooting: Control Operations from IO Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting: Control Operations from EcoStruxure Power Commission Software . . . . .
Troubleshooting: Control Operations from IFE/EIFE Webpages . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting: Control Operations from Communication Network. . . . . . . . . . . . . . . . . . .
Troubleshooting: Control Operations from FDM128 Display . . . . . . . . . . . . . . . . . . . . . . . . .
142 144 145 146 147 149 151 152 154 156 158
Chapter 6 Schneider Electric Green Premium™ Ecolabel . . . . . . . . . . . . . . . . . . . . . . 159
Schneider Electric Green Premium™ Ecolabel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
159
4 DOCA0101EN-04 07/2020

Safety Information

Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation, and has received safety training to recognize and avoid the hazards involved.
DOCA0101EN-04 07/2020 5
SAFETY NOTICE
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See
NFPA 70E, CSA Z462, NOM 029-STPS or local equivalent.
This equipment must only be installed and serviced by qualified electrical personnel.Turn off all power supplying this equipment before working on or inside this equipment.Always use a properly rated voltage sensing device to confirm power is off.Replace all devices, doors, and covers before turning on power to this equipment.Beware of potential hazards, and carefully inspect the work area for tools and objects that may have
been left inside the equipment.
Failure to follow these instructions will result in death or serious injury.
CYBERSECURITY SAFETY NOTICE
POTENTIAL COMPROMISE OF SYSTEM AVAILABILITY, INTEGRITY, AND CONFIDENTIALITY
Change default passwords at first use to help prevent unauthorized access to device settings,
controls, and information.
Disable unused ports/services and default accounts to help minimize pathways for malicious
attackers.
Place networked devices behind multiple layers of cyber defenses (such as firewalls, network
segmentation, and network intrusion detection and protection).
Use cybersecurity best practices (for example, least privilege, separation of duties) to help prevent
unauthorized exposure, loss, modification of data and logs, or interruption of services.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
DANGER
WARNING
6 DOCA0101EN-04 07/2020
At a Glance
Document Scope
Validity Note
Online Information

About the Book

The aim of this guide is to provide users, installers, and maintenance personnel with technical information needed to operate MasterPact™ MTZ2/MTZ3 circuit breakers and switch-disconnectors, in compliance with the IEC standards.
This guide applies to MasterPact MTZ2/MTZ3 circuit breakers and switch-disconnectors.
This guide applies to MicroLogic™ X control units:
With firmware version 004.000.000 or greaterWith hardware version 001.000.000 or greater
NOTE: This guide also applies to MicroLogic™ Xi control units. A MicroLogic Xi control unit is a MicroLogic X control unit without Bluetooth low energy (BLE) communication. The specific features of the MicroLogic Xi control units are described in the appendix in
MasterPact MTZ - MicroLogic X Control Unit - User Guide
.
DOCA0102EN
The information contained in this guide is likely to be updated at any time. Schneider Electric strongly recommends that you have the most recent and up-to-date version available on
www.se.com/ww/en/download
.
The technical characteristics of the devices described in this guide also appear online. To access the information online, go to the Schneider Electric home page at
www.se.com
.
Related Documents
Title of Documentation Reference Number
MasterPact MTZ - MicroLogic X Control Unit - User Guide DOCA0102EN
MasterPact MTZ - Modbus Communication Guide DOCA0105EN
MasterPact MTZ - IEC 61850 Communication Guide DOCA0162EN
MasterPact MTZ - IEC Circuit Breakers and Switch-Disconnectors - Maintenance Guide
MasterPact MTZ Catalogue LVPED216026EN
MasterPact MTZ2/MTZ3 - Fixed IEC Circuit Breaker or Switch-Disconnector ­Instruction Sheet
MasterPact MTZ2/MTZ3 - Drawout IEC Circuit Breaker or Switch-Disconnector ­Instruction Sheet
Enerlin'X IO - Input/Output Application Module for One IEC Circuit Breaker - User Guide
Enerlin'X IFE - Ethernet Switchboard Server - User Guide DOCA0084EN
Enerlin'X IFE - Ethernet Interface for One IEC Circuit Breaker - User Guide DOCA0142EN
Enerlin'X EIFE - Embedded Ethernet Interface for One MasterPact MTZ Drawout Circuit Breaker - User Guide
Enerlin’X FDM128 - Ethernet Display for Eight Devices - User Guide DOCA0037EN
ULP System for MasterPact and ComPact (IEC Standard) - User Guide DOCA0093EN
DOCA0099EN
NVE35469
NVE35470
DOCA0055EN
DOCA0106EN
You can download these technical publications and other technical information from our website at https://www.se.com/ww/en/download/ .
Trademark Notice
All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
DOCA0101EN-04 07/2020 7
8 DOCA0101EN-04 07/2020
MasterPact MTZ2/MTZ3 MasterPact MTZ2/MTZ3 Description DOCA0101EN-04 07/2020

MasterPactMTZ2/MTZ3 Description

Chapter 1
MasterPact MTZ2/MTZ3 Description
What Is in This Chapter?
This chapter contains the following topics:
MasterPact MTZ2/MTZ3 Range 10
Fixed Device 12
Drawout Device 16
Device Identification 23
MicroLogic X Control Unit: Description 26
Go2SE Landing Page 29
Operating Conditions 31
Topic Page
DOCA0101EN-04 07/2020 9
MasterPact MTZ2/MTZ3 Description

MasterPact MTZ2/MTZ3 Range

Description
The MasterPact MTZ2/MTZ3 range of circuit breakers and switch-disconnectors offers current ratings from 800 A to 6,300 A, for AC power systems up to 1,150 Vac.
The MasterPact MTZ2/MTZ3 range is available in the following frame sizes:
MasterPact MTZ2 for current ratings from 800 A to 4,000 AMasterPact MTZ3 for current ratings from 4,000 A to 6,300 A
Each frame size is available in the following power systems:
3-pole (3P)4-pole (4P)
Devices are available in the following installation types:
Fixed-mounted devicesDrawout devices
Convention
In this guide, the term
Circuit Breakers
The following performance levels are available:
N1: standard short-circuit level (42 kA) with total selectivityH1: high short-circuit level (66 kA) with total selectivityH2: very high short-circuit level (100 kA) with very high selectivity (85 kA)H2V: very high short-circuit level (100 kA) with very high selectivity (100 kA) (Rated operational voltage
Ue limited to 440 Vac)
H3: extremely high short-circuit level (150 kA) with high selectivity (66 kA)L1: extremely high short-circuit level (150 kA) with strong current limitation and significant selectivity
(30 kA)
NOTE: The values above correspond to a 440 Vac network, for higher voltage levels the values can be different. Refer to
MasterPact MTZ device
covers circuit breakers and switch-disconnectors.
LVPED216026EN MasterPact MTZ Catalogue
.
Switch-Disconnectors
10
Circuit breakers are fitted with a MicroLogic X control unit.
For full information about available circuit breaker models, frame sizes, interrupting ratings, sensor ratings, and control units, refer to
LVPED216026EN MasterPact MTZ Catalogue
.
The following performance levels are available:
NA: Icw = 42 kA/1sHA: Icw = 66 kA/1sHF: Icw = 85 kA/1sHH: Icw = 100 kA/1s
For information about available switch-disconnector models and frame sizes, refer to
MasterPact MTZ Catalogue
.
LVPED216026EN
DOCA0101EN-04 07/2020
Neutral Position on 4P Devices
On 4P circuit breakers:
For MasterPact MTZ2 N1, H3, L1, H10, the neutral position is on the left side as standard.For MasterPact MTZ2 H1, H2, and H2V, the neutral position is on the left side as standard. A version
with neutral position on the right side is available when ordering.
For MasterPact MTZ3 H1, H2, the neutral position is on the left side as standard. A version with neutral
position on the right side is available when ordering.
On 4P switch-disconnectors:
For MasterPact MTZ2 NA, HA, HF, the neutral position can be switched from the left side to the right
side using the label provided.
For MasterPact MTZ2 HH, the neutral position is on the left side as standard. A version with neutral
position on the right side is available when ordering.
For MasterPact MTZ3 HA, the neutral position is on the left side as standard.
MasterPact MTZ2/MTZ3 Description
DOCA0101EN-04 07/2020 11
MasterPact MTZ2/MTZ3 Description

Fixed Device

Fixed Device Description
The following image shows the standard version of the fixed device (no optional accessories).
A Mounting side plate B Carrying grip C Arc chute D Blue fault-trip reset button E Opening pushbutton F Closing pushbutton G Spring charging handle H Terminal blocks for standard accessories I Front cover J VBP pushbutton locking cover (optional) K Rating plate L Spring charged and ready-to-close indicator M Main-contact position indicator N Window to read the (optional) CDM mechanical
operation counter O Control unit P Control unit transparent cover
Fixed Device Accessories Description
The following image shows the accessories available for the fixed device.
A Additional support brackets for mounting on a
backplate B ULP port module C Terminal blocks for optional accessories D Four OF indication contacts (optional) E Four OF indication contacts (delivered as
standard) F KMT grounding kit G MCH gear motor H CDM mechanical operation counter Z1, Z2 See following images
12
DOCA0101EN-04 07/2020
The following images zoom in on the accessories for the fixed device:
MasterPact MTZ2/MTZ3 Description
I Standard SDE1 fault-trip indication contact J Optional SDE2 fault-trip indication contact or RES electrical
remote reset K Microswitch L M2C programmable contacts or ESM ERMS switch module M Isolation module
N MN undervoltage release or MX2 opening voltage release O MX1 opening voltage release P PF ready-to-close contact Q XF closing voltage release R BPFE electrical closing pushbutton S VCPO OFF-position locking by padlocks T VSPO OFF-position locking by keylocks
DOCA0101EN-04 07/2020 13
MasterPact MTZ2/MTZ3 Description
Fixed Device Terminal Block Description
Terminal block supplied as standard on the circuit breaker
Terminal block for optional accessories on the circuit breaker
14
DOCA0101EN-04 07/2020
Assignment of Terminal Blocks
The following table describes the assignment and the availability of the terminal blocks for circuit breakers and switch-disconnectors for fixed devices:
Standard terminal blocks and the associated accessories are delivered with the device.Optional terminal blocks are delivered with the device only if the associated optional accessories are
installed in the device.
N/A indicates that the terminal blocks and the associated optional accessories are not compatible with
the device.
MasterPact MTZ2/MTZ3 Description
Block Marking Description Circuit
breaker
A COM Terminal block for the external power supply
of the MicroLogic X control unit or ULP port module
UC1 Zone selective interlocking (ZSI),
rectangular sensor for earth-leakage protection, or MDGF module input
UC2 Neutral external sensor, rectangular sensor
for earth-leakage protection, or MDGF module input
SDE2/RES SDE2 additional fault-trip indication contact
or RES electrical remote reset
UC4 External voltage connector Optional N/A
UC3 External voltage connector Optional N/A
M2C/ESM M2C programmable contacts or ESM ERMS
switch module
SDE1 SDE1 fault-trip indication contact Standard N/A on MasterPact MTZ NA,
B MN/MX2 MN undervoltage release
or MX2 opening voltage release
MX1 MX1 opening voltage release Optional Optional
XF XF closing voltage release Optional Optional
PF PF ready-to-close contact Optional Optional
MCH MCH gear motor Optional Optional
C OF21–OF24 4 OF indication contacts Optional Optional
OF11–OF14 4 OF indication contacts Optional Optional
OF1–OF4 4 OF indication contacts Standard Standard
Standard
Optional
Standard N/A
Standard N/A
Optional N/A on MasterPact MTZ NA,
Optional N/A
Optional Optional
Switch-disconnector
N/A
N/A
HA, HA10 Optional on MasterPact MTZ2 HF, HH
N/A
HA, HA10 Standard on MasterPact MTZ2 HF, HH
DOCA0101EN-04 07/2020 15
MasterPact MTZ2/MTZ3 Description

Drawout Device

Definition
A drawout device is composed of the moving part (also called the device) and the fixed part (or chassis).
Drawout Device Moving Part Description
The following image shows the standard version of the moving part of a drawout device (no optional accessories).
A Carrying grip B Arc chute C Blue fault-trip reset button D Opening pushbutton E Closing pushbutton F Spring charging handle G Terminal block connectors H Front cover I VBP pushbutton locking cover (optional) J Rating plate K Spring charged and ready-to-close indicator L Main-contact position indicator M Window to consult the (optional) CDM
mechanical operation counter N Control unit O Control unit transparent cover
16
DOCA0101EN-04 07/2020
Drawout Device Accessories Description
The following image shows the accessories available for the moving part of a drawout device.
MasterPact MTZ2/MTZ3 Description
A VDC mismatch protection B Terminal block connectors for optional
accessories
C Terminal block connectors for standard
accessories
D Optional block of four OF indication contacts
or EF combined connected/closed contacts
E Four OF indication contacts (delivered as
standard) F KMT grounding kit G MCH gear motor H CDM mechanical operation counter Z1, Z2 See following images
DOCA0101EN-04 07/2020 17
MasterPact MTZ2/MTZ3 Description
The following images zoom in on the accessories for the moving part of a drawout device.
I Standard SDE1 fault-trip indication contact J Optional SDE2 fault-trip indication contact or RES electrical
remote reset K Microswitch L IBPO interlock between racking handle and opening pushbutton M M2C programmable contacts or ESM ERMS switch module N Isolation module
O MN undervoltage release or MX2 opening voltage release P MX1 opening voltage release Q PF ready-to-close contact R XF closing voltage release S BPFE electrical closing pushbutton T VCPO OFF-position locking by padlocks U VSPO OFF-position locking by keylocks
18
DOCA0101EN-04 07/2020
Chassis Description
MasterPact MTZ2/MTZ3 Description
The following image shows the standard version of the chassis (no optional accessories).
A Carrying grip B ULP port module C Terminal blocks supplied as standard D Terminal block identification plate E Top safety shutter F Bottom safety shutter G Rail release tab H Drawout grip I Extension rail J Racking handle storage space
DOCA0101EN-04 07/2020 19
K Racking handle L Moving part position indicator M Racking handle socket N Position release button O Chassis locking by padlocks P Latch for switching chassis locking from disconnected position to
any position (connected, test, disconnected)
Q Shutter locking block
MasterPact MTZ2/MTZ3 Description
Chassis Accessories Description
The following image shows the accessories available for the chassis.
A VDC mismatch protection B Drawout device position contacts C Optional terminal block D Cord between ULP port module and EIFE interface E EIFE embedded Ethernet interface F Circuit breaker auxiliary terminal shield
G VPOC open-door racking interlock H VIVC shutter position indication and locking I IBPO interlock between racking handle and opening pushbutton J VSPD chassis locking by keylocks K VPEC door interlock
20
DOCA0101EN-04 07/2020
Chassis Terminal Block Description
MasterPact MTZ2/MTZ3 Description
Terminal block supplied as standard on the chassis
Optional terminal block on the chassis
(1) Supplied as standard with chassis for MasterPact MTZ2/MTZ3 circuit breakers only (2) Supplied as standard with 3P chassis only
DOCA0101EN-04 07/2020 21
MasterPact MTZ2/MTZ3 Description
Assignment of Terminal Blocks
The following table describes the assignment and the availability of the terminal blocks for circuit breakers and switch-disconnectors for drawout devices:
Standard terminal blocks are delivered on the chassis, even if the associated optional accessories are
not installed in the device.
Optional terminal blocks are delivered on the chassis only if the associated optional accessories are
installed in the device.
N/A indicates that the terminal blocks and the associated optional accessories are not compatible with
the device.
Block Marking Description Circuit breaker Switch-disconnector
A CD1–CD3
CE4–CE6
B COM ULP port module Standard N/A
UC1 Zone selective interlocking (ZSI), rectangular
UC2 Neutral external sensor, rectangular sensor
SDE2/RES SDE2 additional fault-trip indication contact
UC4 External voltage connector Optional N/A
UC3 External voltage connector Standard on
3 CD disconnected position contacts or 3 CE connected position contacts
sensor for earth-leakage protection, or MDGF module input
for earth-leakage protection, or MDGF module input
or RES electrical remote reset
Optional Optional
Standard Standard
Standard Standard
Optional N/A on MasterPact MTZ
NA, HA, HA10 Optional on MasterPact MTZ2 HF, HH N/A
Standard on 3P switch-
3P circuit
disconnectors
breakers
Optional on 4P circuit breakers
M2C/ESM M2C programmable contacts
Optional N/A
or ESM ERMS switch module
SDE1 SDE1 fault-trip indication contact Standard Standard
CE1–CE3 CT4–CT6
C MN/MX2 MN undervoltage release
3 CE connected position contacts or 3 CT test position contacts
Optional Optional
Standard Standard
or MX2 opening voltage release
MX1 MX1 opening voltage release Standard Standard
XF XF closing voltage release Standard Standard
PF PF ready-to-close contact Standard Standard
MCH MCH gear motor Standard Standard
(1)
D
OF11–OF24 EF11–EF24
8 OF indication contacts or 8 EF combined connected/closed position
Optional Optional
auxiliary contacts
OF1–OF4 4 OF indication contacts Standard Standard
Optional Optional
Optional N/A
(2)
D
CT1–CT3 CD4–CD6 CE7–CE9
OF11–OF22 EF11–EF22
3 CT test position contacts or 3 CD disconnected position contacts or 3 CE connected position contacts
6 OF indication contacts or 6 EF combined connected/closed position auxiliary contacts
OF1–OF4 4 OF indication contacts Standard Standard
EIFE EIFE embedded Ethernet interface Optional N/A
(1) Without EIFE interface (2) With EIFE interface
N/A on 4P switch­disconnectors
22
DOCA0101EN-04 07/2020

Device Identification

Identification
The MasterPact MTZ2/MTZ3 device can be identified in the following ways:
Rating plate on deviceQR code located:
Identification labels on the device and on the chassis
MasterPact MTZ2/MTZ3 Description
On the front face of the control unit of the circuit breakerOn the front face of the switch-disconnector
A Product identification label B Product checked label C Accessory voltages label D Rating plate E QR code to access product information
DOCA0101EN-04 07/2020 23
MasterPact MTZ2/MTZ3 Description
Product Identification Label
Legend Description Explanation
A Product code The product code is a line of code representing the complete
B Schneider Electric internal
C Description of device The description of the device, specifies the following characteristics:
D Certification logos The logos of the mandatory certifications of the device.
E Device serial number The device serial number is coded PPYYWWDXXXX, where:
configuration of a MasterPact circuit breaker or switch-disconnector. It is automatically generated for each MasterPact device after completing the configuration using the Product Selector configuration tool. The product code appears on the invoice and on the delivery documents as well as on the MasterPact device and packaging labels. The product code can be entered in the Product Selector configuration tool, which generates the complete configuration of the MasterPact device.
identification numbers
RangeRatingPerformance levelNumber of polesControl unit type
PP: Plant codeYY: Year of manufactureWW: Week of manufactureD: Day of the week of manufacture (Monday = 1)XXXX: The production number of the product on the day. Ranges from
0001 to 9999
For example, PP162330064 is the sixty fourth device manufactured at plant PP on Wednesday, June 8, 2016.
Product Checked Label
Legend Description Explanation
F Device serial number See explanation in preceding table.
G Device test date code The device test date code is coded PPYYWWD HH:MM, where:
Accessory Voltages Label
The accessory voltages label gives the voltage of the accessories which are installed in the device and which need to be connected to a power supply.
PP: plant codeYY: year of testWW: week of testD: day of the week of test (Monday = 1)HH:MM: the time of test in hours and minutes
24
DOCA0101EN-04 07/2020
Rating Plate
MasterPact MTZ2/MTZ3 Description
The rating plate with the device information is located on the front cover of the device.
Circuit breaker rating plate Switch-disconnector rating plate
QR Code
A Device size and rated current x 100 A B Ui: rated insulation voltage C Ue: rated operational voltage D Frequency E Type of device: circuit breaker or switch-disconnector,
suitable for insulation F Ics: rated service short-circuit breaking capacity G Icw: rated short-time withstand current H Standards I Performance level
J Uimp: rated impulse withstand voltage K Icu: rated ultimate short-circuit breaking capacity L Selectivity category as per IEC 60947-2 M Place for sticker with IP address of the optional EIFE
interface N Icm: rated short-circuit making capacity O Ith: conventional free air thermal current P Ie: rated operational current Q Information related to switch-disconnectors used as
unprotected circuit breakers
When the QR code on the front face of a MasterPact MTZ device is scanned with a smartphone running a QR code reader and connected to the Internet, the Go2SE landing page is displayed
(see page 29)
. The
landing page displays some information about the device and a list of menus.
DOCA0101EN-04 07/2020 25
MasterPact MTZ2/MTZ3 Description

MicroLogic X Control Unit: Description

Introduction
The MicroLogic X control unit includes:
LEDs to monitor the status of the circuit breakerA local Human Machine Interface comprising a graphic display with colored backlight, contextual
buttons, and dedicated buttons
LEDs to monitor the cause of trips and alarms
Control Unit Description
A Ready LED B Service LED C ERMS LED D Graphic display screen E NFC wireless communication zone F Home button G Three contextual buttons H Escape button ESC I Bluetooth LED J Bluetooth activation button K Test button for ground-fault and earth-leakage
protection (MicroLogic 6.0 X and 7.0 X) L Test/Reset button for trip cause LEDs and alarms M Mini USB port under rubber cover N Overload and trip cause LEDs O Cover for internal battery P VPS voltage power supply module (optional) Q VPS LED to indicate that the VPS module is
supplying the control unit R QR code to access product information S Control unit identification number T Control unit type U Sensor plug with the rated current of the circuit
breaker V Plastic cover
Status LEDs
LED Description
Ready The Ready LED blinks slowly when the standard protection functions of the control unit are
operational.
The service LED alerts the user to the health state of the circuit breaker.
Orange LED: medium severity detected alarm that requires non-urgent maintenance action.Red LED: high severity detected alarm that requires immediate maintenance action.
ERMS The ERMS (Energy Reduction Maintenance Setting) LED has the following statuses:
Blue LED: ERMS engagedOff LED: ERMS disengaged
Display Screen with Contextual Buttons and Dedicated Buttons
The local HMI screen and buttons are used to:
Navigate the menu structure.Display monitored values.Access and edit configuration settings.
26
DOCA0101EN-04 07/2020
NFC Communication Zone
The NFC communication zone is used to establish an NFC connection between a smartphone running the EcoStruxure Power Device app and the MicroLogic X control unit. When the connection is established, the circuit breaker operating data is automatically uploaded to the smartphone.
Bluetooth Activation Button and LED
The Bluetooth activation button is used to establish a Bluetooth low energy connection between a smartphone running the EcoStruxure Power Device app and the MicroLogic X control unit. When the connection is established, the circuit breaker can be monitored and controlled from the smartphone.
When the Bluetooth LED is blinking, it indicates that the MicroLogic X control unit is in communication with a Bluetooth device.
Test Button
The test button is used to test the ground-fault protection for MicroLogic 6.0 X and the earth-leakage protection for MicroLogic 7.0 X.
Overload and Trip Cause LEDs
The indications of the four trip cause LEDs depend on the type of MicroLogic X control unit.
LEDs Description
MasterPact MTZ2/MTZ3 Description
MicroLogic 2.0 X, 5.0 X, 6.0 X, 7.0 X: Overload pre-alarm, the load exceeds 90%
and is lower than 105% of the Ir setting of the long-time protection.
o
MicroLogic 2.0 X, 5.0 X, 6.0 X, 7.0 X: Overload alarm, the load exceeds 105% of
the Ir setting of the long-time protection.
MicroLogic 2.0 X, 5.0 X, 6.0 X, 7.0 X: Trip due to long-time protection.
MicroLogic 2.0 X: Trip due to instantaneous protection.MicroLogic 5.0 X, 6.0 X, 7.0 X: Trip due to short-time protection or instantaneous
protection.
MicroLogic 2.0 X, 5.0 X: Not applicable.MicroLogic 6.0 X: Trip due to ground-fault protection.MicroLogic 7.0 X: Trip due to earth-leakage protection.
MicroLogic 2.0 X, 5.0 X, 6.0 X, 7.0 X: Trip due to optional protections.
MicroLogic 2.0 X, 5.0 X, 6.0 X, 7.0 X: MicroLogic control unit invalid result detected
during self test.
NOTE: If the MicroLogic X control unit is not powered, the trip cause LEDs go off after 4 hours. After this period, press the Test/Reset button to light them again.
DOCA0101EN-04 07/2020 27
MasterPact MTZ2/MTZ3 Description
Test/Reset Button
The Test/Reset button performs the following functions:
Test of the internal battery or check LED functionality: press and hold the Test/Reset button for less than
3 seconds, the four trip cause LEDs switch off for one second. One of the following results:
The four trip cause LEDs switch on for two seconds: the battery is OK.The four trip cause LEDs flash sequentially for two seconds: the battery is near the end of its life.
Replace the battery.
The four trip cause LEDs do not light: replace the battery.
NOTE: This test must be carried out immediately after the replacement of the internal battery to check the correct functioning of the new battery. It can then be carried out at any time in the life of the internal battery.
Reset of the latched events: press and hold the Test/Reset button for more than 3 seconds to reset the
latched events. The trip cause LEDs and the service LED switch off.
Mini USB Port
Remove the rubber cover of the mini USB port to connect the following devices:
A Mobile Power Pack to supply power to the MicroLogic X control unit.A smartphone running the EcoStruxure Power Device app through USB OTG connection.A PC running EcoStruxure Power Commission software.
NOTE: The MicroLogic X control unit does not support USB keys. Even if a USB key is connected using an adapter, data is not transferred.
QR Code
When the QR code on the front face of a MicroLogic X control unit is scanned with a smartphone running a QR code reader and connected to the Internet, the Go2SE landing page is displayed landing page displays some information about the device and a list of menus.
Control Unit Identification Number
The identification number is made up as follows:
The serial number of the MicroLogic X control unit in the format FFFFFFYYWWDLXXXXThe commercial reference of the control unit in the format LV8•••••
Use the identification number to register your MicroLogic X control unit through mySchneider app, the customer care mobile application.
Registering your MicroLogic X control unit enables you to keep your records up to date and enables traceability.
Control Unit Type
This code indicates the type of MicroLogic control unit:
The number (for example, 6.0) defines the types of protection provided by the control unit.The letter (X) identifies the range of the control unit.
Internal Battery
The internal battery powers the trip cause LEDs and the main diagnostic functions in the absence of any other power supply.
(seepage29)
. The
VPS Voltage Power Supply Module
The VPS module provides an internal voltage supply to the MicroLogic X control unit.
The VPS module is optional for MicroLogic 2.0 X, 5.0 X, and 6.0 X. It is installed as standard on MicroLogic 7.0 X.
Sensor Plug
The protection ranges depend on the rated current In, defined by the sensor plug present below the MicroLogic X control unit.
28
DOCA0101EN-04 07/2020

Go2SE Landing Page

Presentation
When the QR code on the front face of a MasterPact MTZ device is scanned with a smartphone running a QR code reader and connected to the Internet, the Go2SE landing page is displayed.
The landing page displays information about the device and a list of menus.
Landing Page Description
The landing page is accessible from Android and iOS smartphones. It displays the same list of menus with slight differences in presentation.
The following example shows the landing page displayed on an Android smartphone:
MasterPact MTZ2/MTZ3 Description
A Commercial reference of MicroLogic X control unit B Type of MicroLogic X control unit C Landing page menus. See the following menu descriptions
for details.
D Downloadable applications
Characteristics
Documentation
Selecting this menu gives access to a product datasheet with detailed information about the MicroLogic X control unit.
Selecting this menu gives access to a sub-menu with the following options:
Asset Life Cycle Documents: gives access to Safe Repository.
Safe Repository is a web service allowing documentation linked to assets to be consulted, stored, and shared in a Schneider Electric environment. Access to Safe Repository is restricted to authorized users. Safe Repository gives access to the bill of materials of the MasterPact MTZ circuit breaker.
Technical Guidance at Glance: gives access to the MasterPact MTZ technical publications, including:
MasterPact MTZ - MicroLogic X Control Unit - User Guide
MasterPact MTZ1 - Circuit Breakers and Switch-Disconnectors - User Guide
MasterPact MTZ2/MTZ3 - Circuit Breakers and Switch-Disconnectors - User Guide
All the instruction sheets for MasterPact MTZ devices and MicroLogic X control units
Product Documentation: gives access to the MicroLogic X technical publications
DOCA0101EN-04 07/2020 29
MasterPact MTZ2/MTZ3 Description
EcoStruxure Facility Expert App
Selecting this application gives access to the EcoStruxure Facility Expert mobile application that can be downloaded on Android and iOS smartphones. For smartphone compatibility, check on your application store.
EcoStruxure Facility Expert optimizes operations and maintenance, helping to ensure business continuity, and provides insights to service providers or facility managers.
EcoStruxure Facility Expert is a real-time collaborative technology available on mobile devices and PCs that enables managers and maintenance personnel to be connected with facilities and equipment. Information exchange between users is simple and fast.
The QR code on MasterPact MTZ devices enables managers and maintenance personnel to access the following automatic downloads:
MasterPact MTZ device identifier.Technical documentation.The maintenance plan for the MasterPact MTZ device.
EcoStruxure Facility Expert enables managers and maintenance personnel to access the maintenance plan for MasterPact MTZ devices.
EcoStruxure Facility Expert helps maintenance personnel to diagnose issues remotely and manage maintenance efficiently by:
Providing relevant information on critical assets.Sending immediate state of the equipment and detailed information helping for diagnostics.
EcoStruxure Power Device App
Selecting this application gives access to the EcoStruxure Power Device app that can be downloaded and installed on Android and iOS smartphones. For smartphone compatibility, check on your application store.
mySchneider App
Selecting this application gives access to the Schneider Electric customer care mobile application mySchneider app that can be downloaded on Android and iOS smartphones. For smartphone compatibility, check on your application store. The customer care application offers self-service instructions and easy access to expert support and information.
30
DOCA0101EN-04 07/2020
Loading...
+ 134 hidden pages