ARGUS light-sensitive switches with/
without switching delay
Operating instructions
MTN544819, MTN544894, MTN544829
Connections, displays and operating
elements
If you want to lead the cable into the housing from below
rather than above:
4 Swap over the lead-in guides (A/B).
A
B
B
For your safety
DANG ER
¼
Risk of fatal injury from electrical current.
All work carried out on the unit may only be performed by skilled electricians. Obser ve the regulations valid in the country of use.
Light-sensitive switch introduction
The ARGUS light-sensitive switch with or without switching delay can be connected to:
– ohmic loads (incandescent lamps, 230 V halogen
lamps)
– inductive loads (NV halogen lamps with wound
transformer)
– capacitive loads (electronic transformer)
As soon as the external brightness fails to reach a value
which you set (twilight threshold), the light-sensitive
switch will switch on the connected load. When the external brightness increases again and exceeds the twilight threshold, the load is switched off again.
The light-sensitive switches MTN544894 and
MTN544819 also have a switching delay function which
means that the load is only switched if the twilight threshold is exceeded or not reached for a longer period of time. The light-sensitive switch therefore only reacts at
dusk or dawn and not e.g. during the day due to temporary cloud cover or at night due to the light cast from a
headlamp.
A Opening for light sensor
B Setting disk for twilight threshold
C Connecting terminals
D Light sensor
E Openings for fixing
F Lead-in guides for connecting cable
G Switching delay On/Off (only MTN544894,
MTN544819)
Selecting the installation site
– If possible, install the device on the north- or eastfa-
cing wall of the building.
– If possible, install the device under roof overhangs or
similar covering.
– If possible, the connection cable should be inserted
into the device from below. If the connecting cable enters into the device from above, particularly good insulation must be ensured.
– Install the load to be switched (lighting) in such a way
that the light from it does not fall on the light sensor.
Otherwise, the sensor will not be able to calculate the
ambient brightness correctly (optical feedback).
Light-sensitive switch installation
1 Open the housing by unscrewing the two screws at
the front. Pull out the light-sensitive switch.
The condensation water opening on the underside of the
housing must be opened. Exception: If operated in
rooms subject to a large amount of dust, it must remain
closed.
2 Push open the condensation water opening A
(view from rear) from the inside to the outside and
break out the wall.
A
When switching inductive loads such as transfor-
|
mers, relays, contactors or fluorescent lamps,
spikes occur which could lead to the load being
switched on again ("maintained light effect").
Switch a capacitor parallel to the inductive load in
order to reduce these spikes.
5 Wiring the light-sensitive switch for the desired ap-
plication:
– Light-sensitive switch with On/Off switch (optional)
L
N
NL
– Light-sensitive switch with On/Off switch (optional)
and two-way switch for toggling between manual
and automatic operation.
L
N
NL
6 Insert the light-sensitive switch into th e housing and
screw the housing together.
Setting light-sensitve switch
Turning the switching delay on
3 Fasten the housing to the wall through the openings
using suitable fixing material (e.g. dowels and
screws). The "TOP" marking should be at the top.
1 Turn the adjuster completely to the position “ON“
(as far as possible to the left).
Turning the switching delay off
1 Turn the adjuster completely to the position “OFF“
(as far as possible to the right).
Setting the twilight treshold
1 Slowly turn the setting disk at dawn or dusk, thus
closing the opening of the light sensor, until the load
switches on or off.
V5448-565-00 04/08
Technical data
Nominal voltage: AC 230 V, 50 Hz
Max. switching
current: 10 A, AC 230 V, cosϕ = 0.6
Nominal power
Incandescent
lamps: AC 230 V, max. 2300 W
Halogen lamps: AC 230 V, max. 2000 W
Capacitive load: max 140 µF
Connecting terminals: for 2.5 mm
External diameter
of a cable: max. 14 mm
Adjustment range/
switch threshold: 3 -2000 Lux, adjustable
Relay: µ contact
Switching delay
(MTN544894,
MTN544819): Switching on: approx. 40 s
Switching off: approx. 100 s
Type of protection: IP 54
Dimensions: approx. 97x80x47 mm (HxWxD)
2
rigid conductors
Schneider Electric Industries SAS
If you have technical questions, please contact the Customer Care Center in your country.
www.schneider-electric.com
This product must be installed, connected and used in
compliance with prevailing standards and/or installation
regulations. As standards, specifications and designs
develop from time to time, always ask for confirmation of
the information given in this publication.
V5448-565-00 04/08