Schneider Electric MP131-24T, MP131-24F, MP131-24MP Specification Sheet

MP131-24T,-24F, -24MP
7
3
Actuators for Floating and Proportional Control
Product Description
MP131 actuators are used together with automatically bal­anced combination valve type SmartX PIBCV for 1/2” to 1-¼”. Typical applications are temperature control and permanent automatic balancing on terminal units (fan-coils, chilled ceil­ings, air-handling units).
Specifications
Part Numbers MP131-24T
Power supply Power consumption
running standby
24 Vac +10 –15 %
MP131-24F
MP131-24MP
1, 24MP: 1.5 VA
0, 24MP: 0.4 W
Features
• Gap detection at stem up position
• 3 point version
• Force switch-off at stem down position prevents overload of actuator and valve
• No tools required for mounting
• Maintenance-free lifetime
• Low-noise operation
4.67
5.15
Specification Sheet
2.08
Frequency 50/60 Hz 24MP:
Control input Y Control output X (V)
Close off force MP131-24T MP131-24F MP131-24MP
Stroke MP131-24T MP131-24F MP131-24MP
Speed MP131-24T MP131-24F MP131-24MP
Relative humidity max. 80 % Max. medium temperature 240 °F (120 °C) Ambient temperature 0…131 °F (0…55 °C) Storage and transport
temperature Protection class IP42 Weight .66 lbs (0.3 kg) Agency Listings Underwriters Laboratory (E489326)
cULus LISTED per UL60730 and CSA
E60730. European Community com-
pliance per EMC directive (2014/30/
EU) and LVD directive (2014/35/EU).
Australian/New Zealand community
V 010 (2-10) Ri = 200 kΩ
mA 020 (4-20) Ri = 500 Ω
010 Ro (min) = 38 kΩ
130 N
5 mm
12 s/mm 24 s/mm
-40…158 °F (–40…70 °C)
compliance as Electric Actuators,
RCM mark.
3.56
2.89
Mounting and Installation
The actuator should be mounted with the valve stem in either horizontal position or pointing upwards. The actuator is fixed to the valve body by means of a ribbed nut which requires no tools for mounting. The ribbed nut should be tightened by hand.
1. Check the valve neck. The actuator should be in stem up position (factory setting) and mounted securely on the valve body.
2. Wire the actuator according to the wiring diagram.
3. Stem movement is indicated by the Position Indicator (a small pin riding in a channel as shown in (1) below).